Danfoss Erc 101 Instruction
Danfoss Erc 101 Instruction
Installation Display/operation
yy Insert the ERC 101 in to the cabinet Press BRIEFLY to defrost
yy Attach the clips to each side of the ^
Press the button
ERC 101 5 seconds to ON/OFF
Press UP/DOWN to
^ adjust setpoint
36.5 mm
^
28 mm
Output compressor 16 (16A) EN60730; 16 (16A) CQC; 71 mm
^ 30 mm
relay 16A (16A FLA/72A LRA) UL60730
LED display, 3 digits, decimal point and 47.25 mm Higher left button to exit
Display rear mounting
multi functionality icons, °C scale 78.25 mm 51.25 mm Lower left button to confirm
Operating
0 °C to 55 °C, 93% rH
conditions 2) Parameter name
Storage conditions -40 °C to 85 °C, 93% rH
Measurement range -40 °C to 85 °C ^ Scroll through the
^ parameters group
Front: IP65/Rear: water and dust protection
Protection corresponds to IP31, accessibility of connectors limit
rear part rating to IP00
Higher left button to exit
Pollution degree III 3) Parameter value
Environmental (can be mounted inside a refrigerated cabinet), Lower left button to confirm
non-condensing
Resistance to heat
Category D (UL94-V0)
& fire
EMC category Category I
IMPORTANT NOTE
Compressor relay: The inputs are not galvanic separated and are connected directly to
Operating cycles more than 175,000 at full load ((16A) 16A) the mains supply! For that reason, door-switches, sensors as well as the cables must fulfil the reinforced
insulation requirements.
R290/R600a: EN/IEC 60079-15:2005,
Glow wire according to EN/IEC 60335-1,
Approvals IEC/EN 60730, UL60730, NSF, CQC, GOST R 60730 Safety info
Note: These approvals are only valid when using the Risk of electrocution!
accessories listed in this document For mounting: do not connect mains power until the controller is correctly mounted.
For unmounting: disconnect the power supply before unmounting
Parameters
De- Assignments Assignments of inputs and outputs
Menu Parameters Cod Description Min Max Unit fault
Application to be controlled with Sensor
Setpoint Stp Setpoint -50 80 C 2 C. (nC=Not Connected, Sco= Temp control,
S2 Application S2A EuA= Evap temp, Con=Cond temp {condenser nC Con - nc
Thermostat tHE Thermostat settings cleaning})
Setpoint adjustment Relay output 1. compressor (CoP)
SPr Current setpoint adjustment value diF * SPr 0.0 1.0 - 0.0 DO1 configuration o1C CoP HeT - CoP
ratio 2. Heater HeT
Differential diF Thermostat differential 0.0 20.0 K 2.0 Password level1 PS1 Shop owner Most common parameters 0 999 - 0
Air temperature Service technician all parameters with read
tAD Air Temp Adjust 0.0 20.0 K 0
adjust Password level2 PS2 permission and possibility to change a 0 999 - 0
Alarm ALA Alarm setting number of parameters
High temperature Alarm is activated above this temperature Service Service
HAt -50.0 80.0 C 15.0
alarm (Celsius ) Voltage value uAC Current main power supply voltage 0 270 Vac -
Low temperature Alarm is activated below this temperature Thousands of cycles of compressor relay since
LAt -50.0 80.0 C -50.0 Relay 1 counter rL1 0 999 1000 -
alarm (Celsius ) manufacture
Compressor CoP Compressor Setting Interval counter int Compressor run time since last defrost 0 999 min -
Minimum time compressor must run 0-30 Defrost time counter dnt Duration of last defrost cycle [min] 0 999 min -
Min run time Crt 0 30 min 0
minutes
Firmware version Fir Danfoss software version number - - - -
Minimum time compressor must idle 0-30
Min Stop time CSt 0 30 min 0
minutes Hardware version HAr Danfoss hardware version number - - - -
Maximum time compressor must idle 0-480
Max OFF time Cot 0 480 min 0
minutes
Error run time Ert Compressor run time if temperature sensor is 0 60 min 0 Problem solving
not working (0-60 minutes )
Compressor stop time if temperature sensor is 0 Problem Probable cause Remedy
Error stop time ESt 60 min 0
not working (0-60 minutes )
Waiting for compressor delay timer Check CoP->CSt
Minimum cut-in When compressor is OFF: Compressor does not start
uLi 0 270 Vac 0 Line voltage to compressor too low or too high Check CoP->uLi, uLo, uHi
voltage lowest compressor start voltage (0-270 V)
Minimum cut-out When compressor is ON: E01: Sensor "S1" defective
uLo 0 270 Vac 0 E01 or E02 is shown on display Replace sensor
voltage lowest operation voltage (0-270 V) E02: Sensor "S2" defective
When compressor is ON: Display alternates between "Con" and Condenser temperature exceeds the Clean condenser,
Maximum voltage uHi 0 270 Vac 270
highest operation voltage (0-270 V) temperature temperature set in condenser settings menu Check Con->CAL, CbL
Delay in seconds between power ON & Display alternates between "Hi" and
Power ON delay Pod 0 300 Sec 180 Temperature too high Check ALA->HAt
compressor being activated temperature
Defrost dEF Defrost Setting Display alternates between "Lo" and Temperature too low Check ALA-> LAt
No: defrost function is disabled, temperature
Defrost type dFt no nat - nat
nat: OFF-cycle defrost (natural defrost)
Temp at which defrost stop
Terminating temp dtt 0 25 C 7
(evap temperature or cabinet temperature)
The minimum time in hours between the start 0
Def Min Interval dii 96 hours 6
of each defrost cycle
The maximum time in hours between the
Def Max Interval dAi 0 96 hours 7
start of each defrost cycle
The minimum duration of a defrost cycle
Def Min time dit 0 240 min 10
in minutes
The maximum duration of a defrost cycle
Def Max time dAt 0 480 min 30
in minutes
Condenser Con Condenser protection settings
Protection
Condenser Alarm If condenser sensor exceeds this temperature,
CAL 0 85 C 75
Limit alarm is activated
Condens er Block If this temperature is exceeded, compressor
CbL 0 85 C 85
Lim it will be stopped
Temperature at which compressor may start
Condenser OK limit CoL 0 85 C 60
after a stop due to exceeding CbL
Temperature below which the compressor is
Condenser Low Temp CLL -50 20 C -5
not allowed to start
Display diS Display setting
Lock-time After dLt Display lock time after defrost [0-60 min] 0 60 min 5
defrost
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifica-