InteliATS2 50

Automatic Transfer Switch


Controller

1 Front panel elements 2


2 Display screens 4
3 Browsing alarms 13
4 Login 15
5 Production mode 18
6 Information screen 20
7 Language selection 22
8 Display contrast adjustment 24

Copyright © 2022 ComAp a.s.


Written by Jan Liptak
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: [email protected], www.comap-control.com Operator Guide
1 Front panel elements

Image 1.1 Operator interface of InteliATS2 50

Control buttons
Position Picture Description
LEFT button. Use this button to move left or to change the mode. The button
can change the mode only if the main screen with the indicator of currently
selected mode is displayed.
Note: This button will not change the mode if the controller mode is forced
by one of binary inputs listed in the Reference Guide – "Operating modes"
chapter.
RIGHT button. Use this button to move right or to change the mode. The
button can change the mode only if the main screen with the indicator of
currently selected mode is displayed.
Note: This button will not change the mode if the controller mode is forced
by one of binary inputs listed in the Reference Guide – "Operating modes"
chapter.

HORN RESET button. Use this button to deactivate the horn output without
acknowledging the alarms.

FAULT RESET button. Use this button to acknowledge alarms and


deactivate the horn output. Inactive alarms will disappear immediately and
status of active alarms will be changed to "confirmed" so they will disappear
as soon as their reasons dismiss.

UP button. Use this button to move up or increase value.

InteliATS2 50 Operator Guide 2


PAGE button. Use this button to switch over display pages.

DOWN button. Use this button to move down or decrease value.

ENTER button. Use this button to finish editing a setpoint or moving right in
the history page.

START button. Works in MAN mode and in Mains-Gen application. Press


this button to initiate the start sequence of the engine.

STOP button. Works in MAN mode and in Mains-Gen application. Press this
button to initiate the stop sequence of the Source 2.

S2CB button. Works in MAN mode only. Press this button to open or close
the S2CB.

S1CB button. Works in MAN mode only. Press this button to open or close
the S1CB.

Indicators and others


Position Description
Source 1 status indicator. There are two states – Source 1 OK (indicator is green) and
Source 1 failure (indicator is red). Green LED is on, if Source 1 is present and within
limits. Red LED is activated when Source 1 failure occurs.
Source 2 status indicator. There are two states – Source 2 OK (indicator is green) and
Source 2 failure (indicator is red). Green LED is on if the Source 2 voltage and frequency
is present and within limits. Red LED is activated when Source 2 failure occurs.

Graphic B/W display, 132 × 64 px.

S1CB Status. Green LED is on if S1CB is closed. It is driven by S1CB CLOSE/OPEN


output or by S1CB feedback signal.
S2CB Status. Green LED is on if S2CB is closed. It is driven by S2CB CLOSE/OPEN
output or by S2CB feedback signal.

InteliATS2 50 Operator Guide 3


2 Display screens
The displayed information is structured into "pages" and "screens". Use the PAGE button to switch over the
pages.
The page Measurement consists of screens which display measured values such as voltages, current
etc.; computed values such as Source 2 power, statistic data and the alarm list on the last screen.
The page setpoints contains all setpoints organized to groups and also a special group for a user to log in.
The page History log shows the history log with the most recent record displayed first.

2.1 Main Screen

2.1.1 Symbols
Padlock – active when LBI ACCESS LOCK is active
R – active when there is active remote connection to controller
Exclamation mark – active when there is any alarm in alarm list

2.1.2 Optional
Value can be chosen via setpoints Main Screen Line 1 and Main Screen Line 2.

2.2 Measurement Screens

Note: Use the Up and Down buttons to move between measurement pages.

InteliATS2 50 Operator Guide 4


Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

InteliATS2 50 Operator Guide 5


Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

InteliATS2 50 Operator Guide 6


Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

InteliATS2 50 Operator Guide 7


Note: Use the Up and Down buttons to move between measurement pages.

Note: Available only with plug-in module.

Note: Use the Up and Down buttons to move between measurement pages.

Note: Use the Up and Down buttons to move between measurement pages.

Note: From all of these pages it is possible to switch seamlessly to the setpoint group page by pressing
Page button.

Note: There can be some additional screens and also some screens can be hidden. Screen’s visibility
depends on actual configuration (usage of extension or communication modules, ECU etc.).

InteliATS2 50 Operator Guide 8


2.3 Setpoint Screens

Note: From all measurement pages you can easily go to the setpoint group page by pressing the Page
button.

Note: Use Up and


Down button to
select required
setpoint group.

Note: Use the Enter button to enter selected setpoint group.

Note: Use Up and


Down button to
select required
setpoint.

Note: Use the Left and the Right button to select required setpoint.

Note: Use the Enter button to enter selected setpoint.

InteliATS2 50 Operator Guide 9


Note: Use Up and
Down button to set
required value of
selected setpoint.

Note: Use the Enter button to confirm adjusted value of setpoint.

Note: Use the Page button to discard changes, to set setpoint to previous value and to return to the list of
setpoints of selected group.

2.4 History Log

Note: From all measurement pages you can easily go to the setpoint group page by pressing the Page
button.

Note: From setpoint group page we can fluently go to the history log pages by pressing the Page button.

InteliATS2 50 Operator Guide 10


Note: Use the Up
and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

InteliATS2 50 Operator Guide 11


Note: Use the Up
and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

Note: Use the Up


and the Down
button to select
required alarm
reason.

Note: Use the Enter button to move to the next page of history log.

IMPORTANT: The records are numbered in reverse order, i.e. the latest (newest) record is "0" and
older records have "-1", "-2" etc.

InteliATS2 50 Operator Guide 12


3 Browsing alarms

Note: Use the Up button to move to alarm list from main measurement screen.

Active alarms are displayed as white text on black background. It means the alarm is still active, i.e. the
appropriate alarm conditions are still present.
Inactive alarms are displayed as black text on white background. It means the alarm is not active, i.e. the
appropriate alarm conditions are gone.
Unconfirmed alarms are displayed with an asterisk. This means the alarm is still not acknowledged
(confirmed).

3.1 User access management alarms


The controller comes to the customer with Production mode turned on, the default administrator password
installed and with no prefilled email address for password reset. For security purposes, the following user
access management alarms will appear. Detailed description of situation when the alarms are active is
provided below:
Wrn Production Mode is present in the alarm list any time the production mode is turned on. To turn off
the Production mode go to User management and uncheck the checkbox Production mode or go to
Production Mode display screen and select disable.
Wrn Default Password appears in alarm list when the default administrator password is set and
communication module is plugged in the controller. The purpose of alarm is to inform that the controller

InteliATS2 50 Operator Guide 13


might be or is connected to an untrusted interface and cybersecurity rules are not fulfilled because there is
default administrator password.
Wrn Password reset e-mail address is not set appears in alarm list when there is no email address set
and the administrator password is not the default one. The purpose of alarm is to inform that there is
possibility that the controller might not be accessible by administrator password due to a forgotten
password. The password reset procedure cannot be performed without a filled email address. To fill out
email address, the administrator password is required.

InteliATS2 50 Operator Guide 14


4 Login

Note: From all measurement pages you can easily go to the setpoint group page by pressing the Page
button.

Note: Use the Up


and the Down button
to select setpoint
group Login.

Note: Use the Enter button to enter setpoint group Login.

Note: Use the Up


and the Down Button
to select Login.

Note: Use the Enter button to enter Login.

InteliATS2 50 Operator Guide 15


UserID Edit

Note: Use the Up


and the Down Button
to change the digit.

Note: Use the Left and the Right buttons to move between digits.

Note: Use the Enter button to confirm the UserID or Page button to cancel entering Login.

PIN Edit

Note: Use the Up


and the Down Button
to change the digit.

Note: Use the Left and the Right buttons to move between digits.

Note: Use the Enter button to confirm the PIN and Login or the Page button to cancel entering the Login.

InteliATS2 50 Operator Guide 16


Note: In case that invalid UserID or PIN are entered, the controller shows Wrong Credentials screen. Use
the Enter button to enter Login again or the Page Button to go back to menu.

InteliATS2 50 Operator Guide 17


5 Production mode

Note: From all measurement pages you can fluently go to the setpoint group page by pressing the Page
button.

Note: Use the Enter button to enter setpoint group Login.

Note: Use the Up


and the Down Button
to select Production
Mode

Note: Use the Enter button to enter the Production Mode.

InteliATS2 50 Operator Guide 18


Note: Use the Up
and the Down Button
to change to
disabled

Note: Use the Enter button to disable the Production Mode.

Note: Once Disabled is confirmed by Enter button the option Enabled is no longer on the screen and
therefore it is not possible to enable Production mode by HMI display screen. Use InteliConfig to enable the
Production mode.

InteliATS2 50 Operator Guide 19


6 Information screen

+
Note: On Main measurement screen press the Enter and the Page button together. The Enter button has to
be pressed first.

Note: Use the Page button to move to the next page.

Note: Use the Page button to move to the next page.

InteliATS2 50 Operator Guide 20


Note: Use the Up button to move back to main measurement screen.

InteliATS2 50 Operator Guide 21


7 Language selection

+
Note: On Main measurement screen press the Enter and the Page button together. The Enter button has to
be pressed first.

Note: Use the Page button to move to the next page.

Note: Use the Page button to move to the next page.

InteliATS2 50 Operator Guide 22


Note: Use the Page button to move to the next page.

Note: Use the Up


and the Down
button to select
required language.

Note: Use the Enter button to confirm the selected language.

InteliATS2 50 Operator Guide 23


8 Display contrast adjustment

+ +
Note: On any measurement screen press the Enter Note: On any measurement screen press the Enter
and the Up button together for higher contrast. and the Down button together for lower contrast.

Note: After setting the contrast, no another action is needed.

InteliATS2 50 Operator Guide 24