Instruction Manual Fieldvue dvc2000 Digital Valve Controller Fisher en 135208
Instruction Manual Fieldvue dvc2000 Digital Valve Controller Fisher en 135208
Contents W8755
www.Fisher.com
DVC2000 Digital Valve Controller Instruction Manual
June 2017 D103176X012
2
Instruction Manual Introduction and Specifications
D103176X012 June 2017
Scope of Manual
This instruction manual is a supplement to the quick start guide that ships with every instrument. This instruction
manual includes specifications, detailed configuration and calibration using a Field Communicator, maintenance and
troubleshooting information and replacement part details.
Note
ValveLink software can also be used for detailed configuration and calibration, as well as performing diagnostic and performance
tests. For information on using ValveLink software with the instrument, refer to the appropriate user guide or help.
Do not install, operate, or maintain a DVC2000 digital valve controller without being fully trained and qualified in
valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions
and warnings. If you have any questions regarding these instructions, contact your Emerson sales office or Local
Business Partner before proceeding.
Instrument Description
The DVC2000 digital valve controller is a communicating, microprocessor-based current-to-pneumatic valve
positioner. It is designed to replace standard pneumatic and electro-pneumatic valve positioners.
In addition to the traditional function of converting an input current signal (4-20 mA) to a pneumatic output pressure,
the DVC2000 digital valve controller communicates via a local display panel and/or via the HART® protocol. An option
is available which provides isolated circuitry for two (2) integrated limit switches (for open/close valve indication) and a
valve position transmitter (for separate valve position feedback).
3
Introduction and Specifications Instruction Manual
June 2017 D103176X012
Terminology
Instrument Level— There are four (4) levels of functionality available: AC, HC, AD and PD.
AC—This level provides the capability to setup and calibrate the positioner through the LCD or the Field
Communicator.
HC—This level provides additional capability for advanced configuration of the positioner (such as travel limits/cutoffs,
custom characterization, and minimum open/closing time). Also, information is available through the HART protocol
for diagnostic alerts such as travel deviation, cycle count, and travel accumulation.
AD—This level provides advanced diagnostic capabilities for performance testing. When used with ValveLink software,
instrument health can be evaluated with tests such as Valve Signature, step response and dynamic error band. The
software program provides detailed analysis with graphics.
PD—This level provides automated, non-intrusive testing of the operating performance of the control valve assembly.
When used with ValveLink software, tests to isolate component degradation can be run on the valve assembly without
affecting the process.
Local Interface— The DVC2000 comes standard with a Liquid Crystal Display (LCD) and four (4) pushbuttons. The local
interface provides the capability to setup and calibrate the positioner and view basic diagnostic messages.
Magnet Assembly—This is the feedback component that is mounted directly to the valve stem. It supplies a magnetic
field that is sensed by the digital valve controller.
Options Board—The DVC2000 digital valve controller is available with two (2) limit switches and a valve position
transmitter. The options board includes the additional circuitry and terminations that are required to support these
output signals.
Pole Piece—Inserted into the DVC2000 housing and protruding through the back of the instrument is a two-pronged
fork that houses the magnetic sensor for position feedback.
Specifications
Specifications for the DVC2000 digital valve controller are shown in table 1‐1. Specifications for the Field
Communicator can be found in the User's Manual.
WARNING
This product is intended for a specific range of application specifications. Incorrect configuration of a positioning
instrument could result in the malfunction of the product, property damage, or personal injury.
4
Instruction Manual Introduction and Specifications
D103176X012 June 2017
5
Introduction and Specifications Instruction Manual
June 2017 D103176X012
6
Instruction Manual Introduction and Specifications
D103176X012 June 2017
Related Documents
Other documents containing information related to the DVC2000 digital valve controller include:
D INMETRO Hazardous Area Approvals for FIELDVUE DVC2000 Digital Valve Controller (D103780X012)
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) (D103263X012)
D HART Field Device Specification - Fisher FIELDVUE DVC2000 Digital Valve Controller (D103783X012)
D Using the HART Tri-Loopt HART-to-Analog Signal Converter with Fisher FIELDVUE Digital Valve Controllers
(D103267X012)
These documents are available from your Emerson sales office, Local Business Partner, or at Fisher.com.
7
Introduction and Specifications Instruction Manual
June 2017 D103176X012
Educational Services
For information on available courses for the DVC2000 digital valve controller, as well as a variety of other products,
contact:
8
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Detailed Setup
The DVC2000 digital valve controller has the capability to communicate via the HART protocol. This section describes
the advanced features that can be accessed with the Field Communicator. Table 2‐1 lists the default settings for a
standard factory configuration. Table 2‐2 provides the actuator information required to setup and calibrate the
instrument.
Setting Modes
Field Communicator Setup & Diag > Detailed Setup > Mode (1-2-1)
Instrument Mode
You can change the instrument mode by selecting Instrument Mode from the Mode menu, or press the Hot Key and
select Instrument Mode.
Instrument Mode allows you to either take the instrument Out Of Service or place it In Service. Taking the instrument
Out Of Service allows you to perform instrument calibration and also allows you to change setup variables that affect
control, provided the calibration/configuration protection is properly set. See Setting Protection.
Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In
Service or the instrument is restarted.
Control Mode
You can change the control mode by selecting Control Mode from the Mode menu, or press the Hot Key and select
Control Mode.
Control Mode lets you define where the instrument receives its set point. Follow the prompts on the Field
Communicator display to choose one of the following control modes: Analog or Digital.
Choose Analog if the instrument is to receive its set point over the 4-20 mA loop. Normally the instrument control
mode is Analog.
Choose Digital if the instrument is to receive its set point digitally, via the HART communications link.
A third mode, Test, is also displayed. Normally the instrument should not be in the Test mode. The Field
Communicator automatically switches to this mode whenever it needs to stroke the valve, for example during
9
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
calibration or stroke valve. However, if you abort from a procedure where the instrument is in the Test mode, it may
remain in this mode. To take the instrument out of the Test mode, select Control Mode then select either Analog or
Digital.
Burst Mode
Enabling burst mode provides continuous communication from the digital valve controller. Burst mode applies only to
the transmission of burst mode data (analog input, travel target, pressure, and travel) and does not affect the way
other data is accessed.
Access to information in the instrument is normally obtained through the poll/response of HART communication. The
Field Communicator or the control system may request any of the information that is normally available, even while
the instrument is in burst mode. Between each burst mode transmission sent by the instrument, a short pause allows
the Field Communicator or control system to initiate a request. The instrument receives the request, processes the
response message, and then continues “bursting” the burst mode data.
There are four burst mode commands. Command 3 is recommended for use with the RosemountR 333 HART
Tri-Loopt HART-to-analog signal converter. The other three are not used at this time.
10
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
11
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Setting Protection
Field Communicator Setup & Diag > Detailed Setup > Protection (1-2-2)
Some setup parameters may require changing the protection with the Field Communicator.
12
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Table 2‐3 lists configurable parameters in the instrument and the requirements for modifying these parameters, in
terms of instrument mode and protection.
Table 2‐3. Conditions for Modifying FIELDVUE DVC2000 Digital Valve Controller Parameters
In Service/ In Service/ Out of Service/ Out of Service/
Parameters
Config Protected Config Unprotected Config Protected Config Unprotected
Control Mode --- --- n n
Restart Ctrl Mode --- --- --- n
Burst Mode Enable n n n n
Burst Mode Command --- --- --- n
Protection n n n n
HART Tag --- n --- n
Message --- n --- n
Description --- n --- n
Date --- n --- n
Valve Serial Num --- n --- n
Inst Serial Num --- --- --- n
Polling Address --- --- --- n
Max Supply Pressure --- --- --- n
Zero Ctrl Signal --- --- --- n
Analog In Units --- --- --- n
Input Range High --- --- --- n
Input Range Low --- --- --- n
Pressure Units --- --- --- n
Temp Units n n n n
Tuning Set --- n --- n
Prop Gain --- n --- n
Velocity Gain --- n --- n
MLFB Gain --- n --- n
Input Char --- --- --- n
Define Custom Char --- --- --- n
Set Pt Filter Time --- --- --- n
Tvl Limit High --- --- --- n
Tvl Limit Low --- --- --- n
Tvl Cutoff High --- --- --- n
Tvl Cutoff Low --- --- --- n
Min Opening Time --- --- --- n
Min Closing Time --- --- --- n
Integral Gain --- n --- n
Integral Deadband --- n --- n
Tvl Hi/Lo Enab n n n n
Tvl HH/LL Enab n n n n
Tvl Alert Hi Pt n n n n
Tvl Alert Lo Pt n n n n
Tvl Alert HiHi Pt n n n n
Tvl Alert LoLo Pt n n n n
Tvl Alrt DB n n n n
Tvl Dev Alrt Enab n n n n
Tvl Dev Alrt Pt n n n n
Tvl Dev Time n n n n
Cycl Cnt Alrt Enab n n n n
Cycl Count Alrt Pt n n n n
Cycl Count DB n n n n
Cycl Count n n n n
Tvl Acum Alrt Enab n n n n
Tvl Acum Alrt Pt n n n n
Tvl Acum DB n n n n
Tvl Acum n n n n
n—indicates parameter may be modified for instrument mode and protection shown.
-Continued-
13
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Table 2‐3. Conditions for Modifying FIELDVUE DVC2000 Digital Valve Controller Parameters
In Service/ In Service/ Out of Service/ Out of Service/
Parameters
Config Protected Config Unprotected Config Protected Config Unprotected
Drive Alert Enable n n n n
Flash ROM Fail --- --- --- n
Ref Voltage Fail --- --- --- n
Drive Current Fail --- --- --- n
Critical NVM Fail --- --- --- n
Temp Sensor Fail --- --- --- n
Press Sensor Fail --- --- --- n
Tvl Sensor Fail --- --- --- n
n—indicates parameter may be modified for instrument mode and protection shown.
To change an instrument's protection, press the Hot key on the Field Communicator display window and select
Protection or select Protection from the Detailed Setup menu. Select the desired level of protection. Follow the prompts
on the Field Communicator display to set the protection level.
General Information
Field Communicator Setup & Diag > Detailed Setup > General (1-2-3)
Follow the prompts on the Field Communicator to enter or view information in the following fields:
D HART Tag—Enter an up to 8 character HART tag for the instrument. The HART tag is the easiest way to distinguish
between instruments in a multi-instrument environment. Use the HART tag to label instruments electronically
according to the requirements of your application. The tag you assign is automatically displayed when the Field
Communicator establishes contact with the digital valve controller at power-up.
D Message—Enter any message with up to 32 characters. Message provides the most specific user-defined means for
identifying individual instruments in multi-instrument environments.
D Descriptor—Enter a descriptor for the application with up to 16 characters. The descriptor provides a longer
user-defined electronic label to assist with more specific instrument identification than is available with the HART
tag.
D Date—Enter a date with the format MM/DD/YY. Date is a user-defined variable that provides a place to save the date
of the last revision of configuration or calibration information.
D Valve Serial Num—Enter the serial number for the valve in the application with up to 12 characters.
D Inst Serial Num—Enter the serial number on the instrument nameplate, up to 12 characters.
D Polling Address—If the digital valve controller is used in point-to-point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique
polling address. The Polling Address is set to a value between 0 and 15. To change the polling address the
instrument must be Out Of Service.
For the Field Communicator to be able to communicate with a device whose polling address is not 0, it must be
configured to automatically search for all or specific connected devices.
D LUI Language—Select the language to be displayed on the local user interface; English, French, German, Italian,
Spanish, Chinese and Japanese.
14
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Follow the prompts on the Field Communicator to define the following measured variables units and ranges:
D Analog In Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
D Input Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range
High, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
High corresponds to Travel Range Low. See figure 2‐1.
D Input Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
Low corresponds to Travel Range High. See figure 2‐1.
D Pressure Units—Defines the output and supply pressure units in either psi, bar, or kPa.
D LUI Pressure Units—Enter the pressure units displayed on the local user interface; psi, bar, or kPa.
D Temp Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the digital
valve controller's printed wiring board.
TRAVEL
RANGE
HIGH ZCS = OPEN
CALIBRATED TRAVEL, %
ZCS = CLOSED
THE SHAPE OF
THESE LINES DEPENDS ON
THE INPUT CHARACTERISTICS
TRAVEL LINEAR CHARACTERISTIC SHOWN
RANGE
LOW
ANALOG INPUT
INPUT RANGE INPUT RANGE
MA OR % OF 4-20 MA
LOW HIGH
NOTE:
ZCS = ZERO CONTROL SIGNAL
A6531-1
15
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Follow the prompts on the Field Communicator to edit or view information in the following fields:
D Max Supply Press—Enter the maximum supply pressure in psi, bar, or kPa, depending on what was selected for
pressure units.
Note
If the actual measured pressure exceeds this setting by 25%, the pressure measurement will not be displayed.
D Actuator Style—Enter the actuator style, spring and diaphragm, piston double-acting without spring, piston
single-acting with spring, or piston double-acting with spring.
D Zero Control Signal—Identifies whether the valve is fully open or fully closed when the input is 0%. If you are unsure
how to set this parameter, disconnect the current source to the instrument. The resulting valve travel is the Zero
Control Signal. (With direct acting digital valve controllers, disconnecting the current source is the same as setting
the output pressure to zero.)
Setting Response
Field Communicator Setup & Diag > Detailed Setup > Response Control (1-2-6)
Follow the prompts on the Field Communicator to configure the following response control parameters:
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
D Tuning Set—There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital
valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Table 2‐4 lists the proportional gain, velocity gain, and minor loop feedback gain values for preselected tuning sets.
16
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
D Damping Factor—If after selecting a tuning set the valve travel overshoot is excessive or unsatisfactory, the damping
factor allows you to either decrease damping to allow more overshoot, or increase damping to decrease the
overshoot.
D Expert Tuning Gains—With Expert Tuning, you can specify the proportional gain, velocity gain, and minor loop
feedback gain.
D Input Char—Defines the relationship between the travel target and ranged set point. Ranged set point is the input to
the characterization function. If the zero control signal equals closed, then a set point of 0% corresponds to a ranged
input of 0%. If the zero control signal equals open, a set point of 0% corresponds to a ranged input of 100%. Travel
target is the output from the characterization function.
You can select from the three fixed input characteristics shown in figure 2‐2 or you can select a custom
characteristic. Figure 2‐2 shows the relationship between the travel target and ranged set point for the fixed input
characteristics, assuming the Zero Control Signal is configured as closed.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel,
for a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before
modification, the custom characteristic is linear.
With input characterization you can modify the overall characteristic of the valve and instrument combination.
Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic
modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the
overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim
(i.e., the plug or cage).
D Custom Char Table—To define a custom input characteristic, select Custom Char Table. Select the point you wish to
define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for the
corresponding set point. When finished, select point 0 to return to the Response Control menu.
17
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Figure 2‐2. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Control Signal = Closed)
125 125
100 100
Travel Target, %
Travel Target, %
0 0
-25 -25
−25 0 Ranged Set Point, % 100 125 −25 0 Ranged Set Point, % 100 125
125
100
Travel Target, %
-25
−25 0 Ranged Set Point, % 100 125
D Setpt Filter Time—Time constant for the set point filter, in seconds. The set point filter slows the response of the
digital valve controller and is typically used with noisy or fast processes. The filter provides improved closed loop
process control. To disable the filter, set the time constant to 0 seconds.
Travel Limit Hi—Defines the high limit for the travel in percent (%) of ranged travel. It is the maximum allowable
travel (in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When
a Travel Limit High is set, the Travel Cutoff High is deactivated, since only one of these parameters can be active.
Travel Limit High is deactivated by setting it to 125.0%.
18
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Travel Limit Lo—Defines the low limit for the travel in percent (%) of ranged travel. It is the minimum allowable travel
(in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When a
Travel Limit Low is set, the Travel Cutoff Low is deactivated, since only one of these parameters can be active. Travel
Limit Low is deactivated by setting it to -25.0%.
Travel Cutoff Hi—Defines the high cutoff point for the travel in percent (%) of ranged travel. Above this cutoff, the
travel target is set to 123.0% of the ranged travel. When a Travel Cutoff High is set, the Travel Limit High is
deactivated, since only one of these parameters can be active. Travel Cutoff High is deactivated by setting it to
125.0%.
Travel Cutoff Lo—Defines the low cutoff point for the travel. Travel Cutoff Low can be used to ensure proper seat load
is applied to the valve. When below the travel cutoff low, the output is set to zero or to full supply pressure,
depending upon the zero control signal. A Travel Cutoff Low of 0.5% is recommended to help ensure maximum
shutoff seat loading.
When a Travel Cutoff Low is set, the Travel Limit Low is deactivated, since only one of these parameters can be
active. Travel Cutoff Low is deactivated by setting it to -25.0%.
D Min Open/Close
Min Opening Time—Minimum Opening Time is configured in seconds and defines the minimum time for the travel to
increase the entire ranged travel. This rate is applied to any travel increases. A value of 0.0 seconds deactivates this
feature and allows the valve to stroke open as fast as possible. This parameter should be set to 0 in firmware 1, 2, 3,
and 4.
Min Closing Time—Minimum Closing Time is configured in seconds and defines the minimum time for the travel to
decrease the entire ranged travel. This rate is applied to any travel decreases. A value of 0.0 seconds deactivates this
feature and allows the valve to stroke closed as fast as possible. This parameter should be set to 0 in firmware 1, 2,
3, and 4.
D Integral Settings
Integral Gain—By setting this value to 0.0 the positioner integrator is disabled. Any other value will provide reset
action to improve static performance.
Integral Dead Zone—When the travel target and actual target deviate by less than this amount, the integrator is
automatically disabled. This prevents the positioner integrator from fighting with the process controller integrator
which may result in valve oscillation.
Setting Alerts
Field Communicator Setup & Diag > Detailed Setup > Alerts (1-2-7)
The following menus are available for configuring Alerts. Items on the menus may be changed with the instrument In
Service. Protection does not need to be removed (no need to set to None). Alerts are not processed when a Diagnostic
is in progress. Follow the prompts on the Field Communicator display to configure alerts.
Note
Alerts are not available with instrument level AC.
19
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
D Tvl Hi/Lo Enab—Yes or No. Travel Hi/Lo Enable activates checking of the ranged travel against the Travel Alert High
and Low Points. Travel Alert Hi is set if the ranged travel rises above the alert high point. Once the alert is set, the
ranged travel must fall below the alert high point by the Travel Alert Deadband before the alert is cleared. See figure
2‐3.
Travel Alert Lo is set if the ranged travel falls below the alert low point. Once the alert is set, the ranged travel must
rise above the alert low point by the Travel Alert Deadband before the alert is cleared. See figure 2‐3.
D Tvl HH/LL Enab—Yes or No. Travel HH/LL Enable activates checking of the ranged travel against the Travel Alert
High-High and Low-Low Points. Travel Alert Hi Hi is set if the ranged travel rises above the alert high-high point.
Once the alert is set, the ranged travel must fall below the alert high-high point by the Travel Alert Deadband before
the alert is cleared. See figure 2‐3.
Travel Alert Lo Lo is set if the ranged travel falls below the alert low-low point. Once the alert is set, the ranged travel
must rise above the alert low-low point by the Travel Alert Deadband before the alert is cleared. See figure 2‐3.
TRAVEL ALERT
DEADBAND
ALERT IS CLEARED
A6532
D Tvl Alert Hi Pt—Travel Alert High Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert High alert.
D Tvl Alert Lo Pt—Travel Alert Low Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Low alert.
D Tvl Alert Hi Hi Pt—Travel Alert High-High Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Hi Hi alert.
D Tvl Alert Lo Lo Pt—Travel Alert Low-Low Point is the value of the travel, in percent (%) of ranged travel, which, when
exceeded, sets the Travel Alert Lo Lo alert.
20
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
D Tvl Alrt DB—Travel Alert Deadband is the travel, in percent (%) of ranged travel, required to clear a travel alert, once it
has been set. The deadband applies to both Travel Alert Hi/Lo and Travel Alert Hi Hi/Lo Lo. See figure 2‐3.
Note
The Travel Alert Deadband applies to the Travel Deviation as well as Travel Alert Hi/Lo and Travel Alert Hi Hi/Lo Lo.
D Tvl Dev Alrt Enab—Yes or No. When enabled, checks the difference between the travel target and the actual travel. If
the difference exceeds the Travel Deviation Alert Point for more than the Travel Deviation Time, the Travel
Deviation Alert is set. It remains set until the difference between the travel target and the actual travel is less than
the Travel Deviation Alert Point minus the Travel Alert Deadband.
D Tvl Dev Alrt Pt—Travel Deviation Alert Point is the alert point for the difference, expressed in percent (%), between
the travel target and the actual travel. When the difference exceeds the alert point for more than the Travel
Deviation Time, the Travel Deviation Alert is set.
D Tvl Dev Time—Travel Deviation Time is the time, in seconds, that the travel deviation must exceed the Travel
Deviation Alert Point before the alert is set.
D Tvl Acum Alrt Enab—Yes or No. Travel Accumulator Alert Enable activates checking of the difference between the
Travel Accumulator value and the Travel Accumulator Alert Point. The Travel Accumulator Alert is set when the
Travel Accumulator value exceeds the Travel Accumulator Alert Point. It is cleared after you reset the Travel
Accumulator to a value less than the alert point.
D Tvl Accum Alrt Pt—Travel Accumulator Alert Point is the value of the Travel Accumulator, in percent (%) of ranged
travel, which, when exceeded, sets the Travel Accumulator Alert.
D Tvl Accum DB—Travel Accumulator Deadband is the area around the travel reference point, in percent (%) of ranged
travel, that was established at the last increment of the accumulator. This area must be exceeded before a change
in travel can be accumulated. See figure 2‐4.
D Tvl Accum—Travel Accumulator records the total change in travel, in percent (%) of ranged travel, since the
accumulator was last cleared. The value of the Travel Accumulator increments when the magnitude of the change
exceeds the Travel Accumulator Dead- band. See figure 2‐4. You can reset the Travel Accumulator by configuring it
to zero.
21
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
DEADBAND EXCEEDED,
NEW REFERENCE POINT
ESTABLISHED
D Cycl Cnt Alrt Enab—Yes or No. Cycle Counter Alert Enable activates checking of the difference between the Cycle
Counter and the Cycle Counter Alert point. The Cycle Counter Alert is set when the value exceeds the Cycle Counter
Alert point. It is cleared after you reset the Cycle Counter to a value less than the alert point.
D Cycl Cnt Alrt Pt—Cycle Counter Alert Point is the value of the Cycle Counter, in cycles, which, when exceeded, sets the
Cycle Counter Alert.
D Cycle Count DB—Cycle Counter Deadband is the area around the travel reference point, in percent (%) of ranged
travel, that was established at the last increment of the Cycle Counter. This area must be exceeded before a change
in travel direction can be counted as a cycle. See figure 2‐5.
POINT AT WHICH
CYCLE IS COUNTED.
DEADBAND REFERENCE POINT
A6533-1
DEADBAND (+/- 5%)
22
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
D Cycle Count—Cycle Counter records the number of times the travel changes direction. The change in direction must
occur after the deadband has been exceeded before it can be counted as a cycle. See figure 2‐5. You can reset the
Cycle Counter by configuring it as zero.
Other Alerts
Follow the prompts on the Field Communicator to configure Drive Alert Enable:
D Drive Alert Enab—Yes or No. Drive Alert Enable activates checking of the relationship between the Drive Signal and
the calibrated travel. If one of the following conditions exists for more than 20 seconds, the Drive Alert is set.
Alert Record
The alert record can store up to 20 alerts from any of the enabled alert groups: Valve Alerts, Failure Alerts, or
Miscellaneous Alerts. Starting from a cleared database, the first 20 alerts that become active will be stored in memory.
Follow the prompts on the Field Communicator to set or display the following:
D Display Record—Displays all recorded alerts and the date and time the alerts were recorded.
D Clear Record—Clears the alert record. To clear the alert record, all alerts in enabled groups must be inactive.
D Inst Date & Time—Permits setting the instrument clock. When alerts are stored in the alert record, the date and time
(obtained from the instrument clock) that they were stored is also stored in the record. The instrument clock uses a
24-hour format. Enter the date and time in the form: MM/DD/YYYY HH:MM:SS, where MM is two digits for the
month (1 through 12), DD is two digits for the day (1 through 31), and YYYY is four digits for the year (1980 through
2040), HH is two digits for the hour (00 to 23), MM is two digits for the minutes (00 to 59), and SS is two digits for
the seconds (00 through 59).
D Record Group Enab—Permits enabling one or more alert groups. Table 3‐2 lists the alerts included in each of the
groups. When any alert from an enabled group becomes active, active alerts in all enabled groups are stored.
23
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Upon shutdown, the instrument attempts to drive its output pressure to the zero current condition and no longer
executes its control function. In addition, the appropriate failure statuses are set. Once the problem that caused the
shutdown has been fixed, the instrument can be restarted by cycling the power or selecting Restart from the Mode
menu of the Field Communicator. Also see the Viewing Instrument Status section on page 35 for further details about
failures.
Follow the prompts on the Field Communicator display to determine the self test shutdown criteria from the
following:
D Done—Select this if you are done modifying the self test shutdown criteria.
D Flash ROM Fail—When enabled, the instrument shuts down whenever there is a failure associated with flash ROM
(read only memory).
D Temp Comp Fail—When enabled, the instrument shuts down whenever this is a failure associated with Temperature
Compensation.
D Ref Voltage Fail—When enabled, the instrument shuts down whenever there is a failure associated with the internal
voltage reference.
D Drive Current Fail—When enabled, the instrument shuts down whenever the drive current does not read as expected.
D NVM Fail—When enabled, the instrument shuts down whenever there is a failure associated with NVM (non-volatile
memory).
D Temp Sensor Fail—When enabled, the instrument shuts down whenever there is a failure associated with the internal
temperature sensor.
D Press Sensor Fail—When enabled, the instrument shuts down whenever there is a failure associated with the pressure
sensor.
D Travel Sensor Fail—When enabled, the instrument shuts down whenever there is a failure associated with the travel
sensor.
24
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Transmitter/Switches
Field Communicator Setup & Diag > Detailed Setup > Transmitter/Switches (1-2-9)
Note
These menu items are only available on units that have the optional position transmitter / limit switch hardware installed.
If optional limit switches are being used, power must be applied to the switch circuits throughout the calibration routine. Failure to
power the switches may result in incorrect switch orientation.
Follow the prompts on the Field Communicator display to configure the following:
D Switch 1 Trip Point—Defines the threshold for the limit switch wired to terminals +41 and -42 in percent of calibrated
travel.
D Switch 1 Closed—Configures the action of the limit switch wired to terminals +41 and -42. Selecting ABOVE
configures the switch to be closed when the travel is above the trip point. Selecting BELOW configures the switch to
be closed when the travel is below the trip point. Selecting DISABLED removes the icons and status from the display.
D Switch 2 Trip Point—Defines the threshold for the limit switch wired to terminals +51 and -52 in percent of calibrated
travel.
D Switch 2 Closed—Configures the action of the limit switch wired to terminals +51 and -52. Selecting ABOVE travel is
above the trip point. Selecting BELOW configures the switch to be closed when the travel is below the trip point.
Selecting DISABLED removes the icons and status from the display.
Note
Switch #2 is only operational if power is applied to switch #1 also. Switch #2 cannot be used alone.
D Transmitter Action—This configures the relationship between the valve travel and the position transmitter output
signal. If you select CLOSED, the transmitter will send 4 mA when the valve is closed. If you select OPEN, the
transmitter will send 4 mA when the valve is open.
A switch is located on the options board to select the transmitter fail signal (high+ or low-). High+ will result in a
current output of > 22.5 mA upon transmitter failure. Low- will result in a current output of < 3.6 mA. Refer to
figure 2‐6 for location and switch selection.
25
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
TRANSMITTER SWITCH
FOR FAIL SIGNAL
+ HIGH (SHOWN) OR
- LOW
Tuning
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
Automatic
Field Communicator Calibrate > Calibrate > Auto Tuner (1-4-5)
The auto tuner is used to optimize digital valve controller tuning. It can be used on most sliding-stem and rotary
designs, including Fisher and other manufacturers' products. Moreover, because the auto tuner can detect internal
instabilities before they become apparent in the travel response, it can generally optimize tuning more effectively than
manual tuning.
Manual
If the auto tuner does not provide the desired responsiveness, you can manually tune the DVC2000. Refer to Setting
Response, page 16.
26
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Calibration
Field Communicator Calibrate > Calibrate (1-4)
WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.
Note
If optional limit switches are being used, power must be applied to the switch circuits throughout the calibration routine. Failure to
power the switches may result in incorrect switch orientation.
27
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
Note
Analog Input Calibration can also be peformed using the Local Operator Interface, as decribed in the procedure below.
Connect a variable current source to the instrument +11 and -12 terminals. From the home screen, press the DOWN
(B) arrow key five times and then press the RIGHT (") arrow key. Acknowledge the warning if you are sure that you
want to proceed.
1. Adjust the variable current source to 4 mA.
2. Press the RIGHT (") arrow key
3. Adjust the variable current source to 20 mA.
4. Press the RIGHT (") arrow key.
If you want to keep this calibration, select SAVE AND EXIT. If you exit without saving, the last saved configuration data
will be restored.
Adjusting the minor loop feedback bias is done around mid travel. The valve position is briefly moved back and forth
to determine the relay beam position at quiescence. Essentially, it establishes the zero point for the Minor Loop
Feedback circuit. The back and forth motion is performed to account for hysteresis.
28
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Adjusting the output bias aligns the travel set point with the actual travel by computing the drive signal required to
produce 0% error. This is done while the valve is at 50% travel, making very small adjustments.
2. Place the instrument In Service and verify that the travel properly tracks the current source.
D Analog Adjust
D Digital Adjust
Note
0% Travel = Valve Closed
100% Travel = Valve Open
1. Adjust the input current until the valve is near mid-travel. Press OK.
Note
In steps 2 through 4, the accuracy of the current source adjustment affects the position accuracy.
2. Adjust the current source until the valve is at 0% travel, then press OK.
3. Adjust the current source until the valve is at 100% travel, then press OK.
4. Adjust the current source until the valve is at 50% travel, then press OK.
5. Place the instrument In Service and verify that the travel properly tracks the current source.
Note
0% Travel = Valve Closed
100% Travel = Valve Open
29
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
1. From the adjustment menu, select the direction and size of change required to set the travel at 0%.
If another adjustment is required, repeat step 1. Otherwise, select Done and go to step 2.
2. From the adjustment menu, select the direction and size of change required to set the travel to 100%.
If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3.
3. From the adjustment menu, select the direction and size of change required to set the travel to 50%.
If another adjustment is required, repeat step 3. Otherwise, select Done and go to step 4.
4. Place the instrument In Service and verify that the travel properly tracks the current source.
Note
The pressure sensor is calibrated at the factory and should not require calibration.
30
Instruction Manual Detailed Setup and Calibration
D103176X012 June 2017
Note
The position transmitter is calibrated at the factory and should not require calibration.
Note
This procedure will not move the control valve. The instrument will simulate an output for calibration purposes only.
This procedure is only available on units that have the optional position transmitter / limit switch hardware installed.
The DVC2000 digital valve controller is shipped from the factory with the position transmitter already calibrated.
To calibrate the position transmitter, select Transmitter Calibration from the Calibrate menu. Connect a current meter
in series with the +31 and -32 terminals, and a voltage source (such as the DCS analog input channel). Follow the
prompts on the Field Communicator display to manipulate the output current read by the current meter to 4 mA, and
then to 20 mA.
31
Detailed Setup and Calibration Instruction Manual
June 2017 D103176X012
32
Instruction Manual Viewing Device Variables and Diagnostics
D103176X012 June 2017
Note
These variables are not available for instrument level AC.
Analog Input, Travel, Valve Set Point, Drive Signal and Output Pressure
The following variables are displayed on the Online menu:
Analog In shows the value of the instrument analog input in mA (milliamperes) or % (percent) of ranged input.
Travel shows the value of the DVC2000 digital valve controller travel in % (percent) of ranged travel. Travel always
represents how far the valve is open.
Drive Sgl shows the value of the instrument drive signal in % (percent) of maximum drive.
Pressure shows the value of the instrument output pressure in psi, bar, or kPa.
Note
These variables are not available for instrument level AC.
The Variables menu is available to view additional variables, such as the status of the auxiliary input, the instrument
internal temperature, cycle count, travel accumulation and device free time. If a value for a variable does not appear
on the display, select the variable and a detailed display of that variable with its value will appear. A variable's value
does not appear on the menu if the value becomes too large to fit in the allocated space on the display, or if the
variable requires special processing.
D Temp—The internal temperature of the instrument is displayed in either degrees Fahrenheit or Celsius.
D Cycl Count—Cycle Counter displays the number of times the valve travel has cycled. Only changes in direction of the
travel after the travel has exceeded the deadband are counted as a cycle. Once a new cycle has occurred, a new
deadband around the last travel is set. The value of the Cycle Counter can be reset from the Cycle Count Alert menu.
33
Viewing Device Variables and Diagnostics Instruction Manual
June 2017 D103176X012
D Tvl Accum—Travel Accumulator contains the total change in travel, in percent of ranged travel. The accumulator
only increments when travel exceeds the deadband. Then the greatest amount of change in one direction from the
original reference point (after the deadband has been exceeded) will be added to the Travel Accumulator. The value
of the Travel Accumulator can be reset from the Travel Accum Alert menu.
The Device Information menu is available to view information about the instrument.
Follow the prompts on the Field Communicator display to view information in the following fields:
D HART Univ Rev—HART Universal Revision is the revision number of the HART Universal Commands which are used as
the communications protocol for the instrument.
D Device Rev—Device Revision is the revision number of the software for communication between the Field
Communicator and the instrument.
D Firmware Rev—Firmware Revision is the revision number of the Fisher firmware in the instrument.
D Firmware Date—Firmware Date is the revision date of the firmware being used.
D Main Elec Rev—Main Electronics Revision is the revision number of the main electronics component.
D Sec Elec Rev—Secondary Electronics Revision is the revision number of the secondary electronics component.
D Sensor Serial Num—Sensor Serial Number is the serial number of the sensor
D Inst Level—Indicates the instrument level
AC—Auto Calibrate
HC—HART Communicating
AD—Advanced Diagnostics
PD—Performance Diagnostic
Table 3‐1 lists the functions available for each instrument level.
D Device ID—Each instrument has a unique Device Identifier. The device ID provides additional security to prevent this
instrument from accepting commands meant for other instruments.
34
Instruction Manual Viewing Device Variables and Diagnostics
D103176X012 June 2017
Note
Instrument Status is not available for instrument level AC.
The following describes the various displays for the Instrument Status menu.
D Done—Select this when you are done viewing the instrument status.
Note
Alerts are not available with instrument level AC.
D Valve Alerts—If a valve alert is active, it will appear when the Valve Alerts menu item is selected. If more than one
alert is active, they will appear on the display one at a time in the order listed below.
1. Alert Record has Entries
2. Alert Record is full
3. Instrument Time is Invalid
4. Tvl Accumulation Alert
5. Cycle Counter Alert
6. Non-critical NVM Alert
7. Power Starvation Alert
8. Drive Signal Alert
9. Tvl Lim/Cutoff Low
10. Tvl Lim/Cutoff High
11. Tvl Deviation Alrt
12. Tvl Alert Hi Hi
13. Tvl Alert Hi
14. Tvl Alert Lo Lo
15. Tvl Alert Lo
35
Viewing Device Variables and Diagnostics Instruction Manual
June 2017 D103176X012
D Failure Alerts—If a self-test failure has occurred, it will appear when the Failure Alerts menu item is selected. If there
are multiple failures, they will appear on the display one at a time in the order listed below.
1. Offline/Failed—This failure indicates a failure, enabled from the Self Test Shutdown menu, caused an instrument
shutdown. Press Enter to see which of the specific failures caused the Offline/Failed indication.
2. Travel Sensor Fail—This failure indicates the sensed travel is outside the range of -25.0 to 125.0% of calibrated
travel. If this failure is indicated, check the instrument mounting.
3. Pressure Sensor Fail—This failure indicates the actuator pressure is outside the range of -24.0 to 125.0% of the
calibrated pressure for more than 60 seconds. If this failure is indicated, check the instrument supply pressure. If
the failure persists, ensure the printed wiring board assembly is properly mounted onto the mounting frame, and
the pressure sensor O-rings are properly installed. If the failure does not clear after restarting the instrument,
replace the printed wiring board assembly.
4. Temperature Sensor Fail—This failure is indicated when the instrument temperature sensor fails, or the sensor
reading is outside of the range of -40 to 85°C (-40 to 185°F). The temperature reading is used internally for
temperature compensation of inputs. If this failure is indicated, restart the instrument and see if it clears. If it
does not clear, replace the printed wiring board assembly.
5. NVM Fail—This failure is indicated when the Non-Volatile Memory integrity test fails. Configuration data is stored
in NVM. If this failure is indicated, restart the instrument and see if it clears. If it does not clear, replace the
printed wiring board Assembly.
6. Drive Current Fail—This failure is indicated when the drive current does not read as expected. If this failure occurs,
check the connection between the I/P converter and the printed wiring board assembly. Try removing the I/P
converter and re-installing it. If the failure does not clear, replace the I/P converter or the printed wiring board
assembly.
7. Ref Voltage Fail—This failure is indicated whenever there is a failure associated with the internal voltage reference.
If this failure is indicated, restart the instrument and see if it clears. If it does not clear, replace the printed wiring
board assembly.
8. Flash ROM Fail—This failure indicates the Read Only Memory integrity test failed. If this failure is indicated, restart
the instrument and see if it clears. If it does not clear, replace the printed wiring board assembly.
D Alert Record—The instrument contains an alert record that can store up to 20 alerts from any of the enabled alert
groups: Valve Alerts or Failure Alerts. See the Advanced Setup section for information on enabling alert groups.
Table 3‐2 lists the alerts included in each of the groups. The alert record also includes the date and time (from the
instrument clock) the alerts occurred.
36
Instruction Manual Viewing Device Variables and Diagnostics
D103176X012 June 2017
D Operational Status—This menu item indicates the status of the Operational items listed below. The status of more
than one operational may be indicated. If more than one Operational status is set, they will appear on the display
one at a time in the order listed below.
1. Out of Service
2. Auto Calibration in Progress
3. Input Char Selected
4. Custom Char Selected
5. Diagnostic in Progress
6. Calibration in Progress
7. Set Point Filter Active
37
Viewing Device Variables and Diagnostics Instruction Manual
June 2017 D103176X012
38
Instruction Manual Maintenance and Troubleshooting
D103176X012 June 2017
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing
any maintenance procedures on the the DVC2000 digital valve controller:
D Always wear protective clothing, gloves, and eyewear when performing any maintenance procedures to avoid personal
injury or property damage.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the control valve.
D Use bypass valves or completely shut off the process to isolate the control valve from process pressure. Relieve process
pressure from both sides of the control valve.
D Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression so the actuator is not
applying force to the valve stem; this will allow for the safe removal of the stem connector.
CAUTION
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 1‐1 and may also impair operations and the intended function of the device.
Note
Stroke Valve is not available with instrument level AC.
Follow the prompts on the Field Communicator display to select from the following: Done, Ramp Open, Ramp Closed,
Ramp to Target, and Step to Target, and Stop.
39
Maintenance and Troubleshooting Instruction Manual
June 2017 D103176X012
D Done—Select this if you are done. All ramping is stopped when DONE is selected.
D Ramp Open—ramps the travel toward open at the rate of 1.0% per second of the ranged travel.
D Ramp Closed—ramps the travel toward closed at the rate of 1.0% per second of the ranged travel.
D Ramp to Target—ramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
Instrument Removal
1. Make sure that the valve is isolated from the process.
2. Remove the instrument cover (refer to figure 4‐1).
40
Instruction Manual Maintenance and Troubleshooting
D103176X012 June 2017
6. Remove the bolts connecting the DVC2000 housing to the mounting bracket.
Note
The magnet assembly may remain on the valve stem (or shaft).
When replacing the instrument, be sure to follow the mounting procedure outlined in the quick start guide
(D103203X012) that shipped with the digital valve controller. Once the instrument is mounted, perform the Quick
Setup routine outlined in the quick start guide. If changes need to be made to the default settings, use Detailed Setup
to make the appropriate modifications.
Component Replacement
When replacing any of the components of the DVC2000, the maintenance should be performed in an instrument shop
whenever possible. Make sure that the electrical wiring and pneumatic tubing is disconnected prior to disassembling
the instrument.
CAUTION
When replacing components, proper means of electrostatic discharge protection is required. Failure to use a grounding
strap, or other means of electrostatic discharge protection can result in damage to the electronics.
41
Maintenance and Troubleshooting Instruction Manual
June 2017 D103176X012
Note
After I/P converter replacement, calibrate the digital valve controller to maintain accuracy specifications.
Removal
1. Remove the main cover.
2. Remove three screws that hold the EMI shield and remove the shield (refer to figure 4‐1).
3. Remove the three screws holding the electronics board to the mounting frame.
4. Pull the main electronics straight off of the mounting frame. The board is electrically connected to an
interconnecting board with a rigid connector.
5. Remove the two screws holding the mounting frame to the instrument housing (refer to figure 4‐2 for location of
screws).
INTERCONNECT MANIFOLD
BOARD ASSEMBLY
INTERCONNECT
BOARD SCREW (1) PNEUMATIC
RELAY SCREWS (2)
I/P CONVERTER SCREW HOLES (4) MOUNTING FRAME SCREW HOLES (2)
(SCREWS NOT SHOWN) (SCREWS NOT SHOWN)
W9103
6. Pull the manifold assembly straight out. The interconnecting board is electrically connected to the termination
board with a rigid connector.
7. Remove the interconnect board from the mounting frame.
8. Remove the four screws holding the I/P converter to the mounting frame (refer to figure 4‐2 for location of screws).
9. Pull the I/P converter straight out taking care to capture the two o-rings (one has a screen).
42
Instruction Manual Maintenance and Troubleshooting
D103176X012 June 2017
Assembly
When installing a new I/P converter, follow the reverse procedure as outlined above and recalibrate the instrument.
1. Install the I/P converter, making sure the screen O-ring is installed on the I/P supply port (the circular port on the
mounting frame), and that the two manifold O-rings are in place.
2. Install the interconnect board on the mounting frame. Do not tighten the self-tapping screw on on the interconnect
board at this time (see figure 4‐2).
3. Replace the manifold assembly.
4. Install the mounting frame to the housing, making sure that the O-rings (keys 45 and 51) are in place.
5. Install the main electronics to the mounting frame, making sure that the pressure sensor seal (key 16) is in place.
6. Tighten the self-tapping screw on the Interconnect Board.
7. Install the primary shield (key 37) with three screws.
8. Recalibrate the instrument and install the cover.
Note
After pneumatic relay replacement, calibrate the digital valve controller to maintain accuracy specifications.
Removal
1. Remove the main cover.
2. Remove three screws that hold the EMI shield and remove the shield (refer to figure 4‐1).
3. Remove the three screws holding the electronics board to the mounting frame.
4. Pull the main electronics straight off of the mounting frame. The board is electrically connected to an
interconnecting board with a rigid connector.
5. Remove the two screws holding the mounting frame to the instrument housing (refer to figure 4‐2).
6. Pull the mounting frame straight out. The interconnecting board is electrically connected to the termination board
with a rigid connector.
7. Remove the two screws holding the pneumatic relay to the mounting frame.
8. Pull the pneumatic relay straight out.
Assembly
When installing a new pneumatic relay, follow the reverse procedure as outlined above and recalibrate the instrument.
43
Maintenance and Troubleshooting Instruction Manual
June 2017 D103176X012
Troubleshooting
What is a healthy unit?
In order to troubleshoot the DVC2000 digital valve controller, it is critical to understand how a healthy unit is supposed
to behave. Below is a list of behaviors you should see if the instrument is performing well.
D No diagnostics messages
D No alerts or alarms
D Hall sensor within the valid range of travel on the magnet array
D Minimal overshoot
D Quick response
The supply pressure feeding the instrument must fall within the rated pressure range of the installed relay for proper
operation.
2. Check the instrument protection (LCD via pushbuttons and Configure/Calibrate via HART)
3. Check for local device diagnostic messages
44
Instruction Manual Maintenance and Troubleshooting
D103176X012 June 2017
45
Maintenance and Troubleshooting Instruction Manual
June 2017 D103176X012
1 KILOHM POTENTIOMETER
MILLIAMMETER
VOLTMETER
CIRCUIT
UNDER
TEST
A6192-1
46
Instruction Manual Maintenance and Troubleshooting
D103176X012 June 2017
If not, describe:
3. Measure the voltage across the “+11” and “-12” terminal box screws when the commanded current is 4.0 mA and
20.0 mA: V @ 4.0 mA V @ 20.0 mA.
(These values should be around 8.0 V @ 4.0 mA and 8.25 V @ 20 mA.)
4. Is the front panel LCD functional? Yes _________ No _________
5. Is it possible to communicate with the DVC2000 via the LUI pushbuttons? Yes _________ No _________
6. Are Travel, Input Signal, and Output Pressure in the LCD shown correctly? Yes _________ No _________
7. Is it possible to communicate via HART to the DVC2000? Yes _________ No _________
8. What is the Diagnostic Tier of the digital valve controller? AC ____ HC____ AD____ PD____
9. What is the firmware version of the DVC2000? _________________
10. What is the hardware version of the DVC2000? _________________
11. Is the digital valve controller's Instrument Mode “In Service”? Yes _________ No _________
12. Is the digital valve controller's Control Mode set to “Analog”? Yes _________ No _________
13. What are the following parameter readings?
47
Maintenance and Troubleshooting Instruction Manual
June 2017 D103176X012
Mounting
1. Actuator application: Sliding Stem? _______ Rotary? _______
2. What Make, Brand, Style, Size, etc. actuator is the DVC2000 mounted on? ________________________
3. What is the Mounting Kit part number? _________________________________________________________
4. If mounting kits are made by LBP/Customer, please provide pictures of installation.
5. If sliding stem:
Which Magnet Array? 25 mm (1 inch)_____ 50 mm (2 inch) _____ 110 mm (4-1/8 inch) _____
Does the Magnet Array move through marked areas? Yes _________ No _________
6. If Rotary: Is the actuator rotation 90_? Yes _________ No _________
48
Instruction Manual Parts
D103176X012 June 2017
Section 5 Parts5‐5‐
Parts Ordering
Whenever corresponding with your Emerson sales office or Local Business Partner about this equipment, always
mention the controller serial number. When ordering parts kits, refer to the 11-character part number of each
required kit as found in the following list.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Automation Solutions should
not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Automation
Solutions may void your warranty, might adversely affect the performance of the valve, and could cause personal injury
and property damage.
The DVC2000 digital valve controller is designed with all metric fasteners and threaded connections. However,
optional inch connections are available for the two conduit entrance points (1/2 NPT) and the supply/output
pneumatic ports (1/4 NPT). Even with this option, all other fasteners and threaded connections are metric.
49
Parts Instruction Manual
June 2017 D103176X012
Relay Assembly(2)
gaskets (qty 2) GE26550X012
APPLY LUBRICANT/SEALANT
NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED VIEW A
PIPE AWAY VENT
GE13174-F, SHEET 1 OF 3
51
Parts Instruction Manual
June 2017 D103176X012
APPLY LUBRICANT/SEALANT
NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE13174-F, SHEET 2 OF 3
52
Instruction Manual Parts
D103176X012 June 2017
SEE SEE
VIEW B VIEW B
VIEW B
APPLY LUBRICANT/SEALANT
NOTE:
1. APPLY LUBRICANT KEY 65 TO ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE13174-F, SHEET 3 OF 3
53
Parts Instruction Manual
June 2017 D103176X012
54
Instruction Manual Principle of Operation
D103176X012 June 2017
DVC2000 Operation
The DVC2000 digital valve controller uses a traditional 4-20 mA input signal and converts it into a pneumatic output
pressure that is delivered to the control valve actuator. Accurate control of the position of the valve is enabled by valve
stem position feedback. The way in which the DVC2000 accomplishes this is through a two-stage positioner design.
Refer to figure A‐1 for a block diagram of the positioner operation.
NON-CONTACT
POSITION FEEDBACK
OUTPUT
ACTUATOR
MAIN BOARD PRESSURE
TERMINATIONS ASSEMBLY SENSOR
& SINGLE ACTING
MINOR LOOP RELAY
INPUT SIGNAL POSITION FEEDBACK
SENSOR (POWER
(4-20 MA, 9 VOLTS) AMPLIFIER)
BOARD
TRAVEL = 66.8%
14.6 MA 0.29 BAR
I/P
PRESSURE
SIGNAL
I/P
CONVERTER
DRIVE (PRE- AIR SUPPLY
SIGNAL AMPLIFIER
A traditional 4-20 mA signal provides the set point and power to the instrument. At the same time, the HART protocol
provides instrument and process data through digital communications. The instrument receives this set point and
positions the valve where it needs to be.
D The input signal provides electrical power and the set point simultaneously. It is routed into the terminal board
through a twisted pair of wires. The terminal board contains the termination points for the loop signal (+11/-12). If
the options board is installed, an additional options board set includes additional terminals for the transmitter
output (+31/-32), switch #1 output (+41/-42), and switch #2 output (+51/-52).
D The input signal is then directed to the main electronics board assembly where the microprocessor runs a digital
control algorithm resulting in a drive signal to the I/P converter.
55
Principle of Operation Instruction Manual
June 2017 D103176X012
D The I/P converter assembly is connected to supply pressure and converts the drive signal into a pressure signal. The
I/P converter is the pre-amplifier stage in the two-stage positioner design. This component enables high static gain
for responsiveness to small changes in the input signal.
D The I/P output is sent to the pneumatic relay assembly. The relay is also connected to supply pressure and amplifies
the small pressure signal from the I/P converter into a larger pneumatic output signal used by the actuator. The
pneumatic relay is the power amplifier stage in the two-stage positioner design. This component enables superior
dynamic performance with minimal steady-state air consumption.
D A sensor on the printed wiring board measures the motion of the small valve inside the pneumatic relay. This
measurement is used for minor loop feedback to the control algorithm resulting in stable, robust tuning.
D The change in relay output pressure to the actuator causes the valve to move.
D Valve position is sensed through the non-contact, linkage-less feedback sensor. There are no moving linkages and
the DVC2000 is physically separated from the valve stem through the use of a magnetic Hall effect sensor. A
magnetic array is mounted to the valve stem and the sensor is embedded in the DVC2000 housing. The sensor is
electrically connected to the printed wiring board to provide a travel feedback signal used in the control algorithm.
56
Instruction Manual Local Interface Flow Chart/Menu Trees
D103176X012 June 2017
57
Local Interface Flow Chart/Menu Trees Instruction Manual
June 2017 D103176X012
TRAVEL = 66.8%
1 14.6 MA 0.92 BAR SHUTDOWN TRAVEL CHECK CHECK CHECK I/P
Y
Y
Y
QUICK SETUP
Y
FINDING 0% ... FINDING 100% ... FINDING 0% ... FINDING 50% ...
Y
PRESS FOR 3 SEC
Y
AUTO
FINDING 100% ... FINDING 0% ...
Y
FINDING 50% ...
Y
B
3
Y
Y
Y
MANUAL FINDING 50% ...
100% TRAVEL 0% TRAVEL
AUTOTUNING 1
Y
COMPLETE
VALVE WILL MOVE
AUTO
AUTOTUNING IN
Y
Y
USE MANUAL TUNING
TUNING
Y
4 TUNING AUTOMATIC
Y
MANUAL
Y
TUNING
Y
1
Y
Y
Y
ZERO CTL SIGNAL PRESSURE UNITS INPUT RANGE INPUT RANGE CHARACTERISTIC
5 DETAILED SETUP
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
8
Y
ANALOG OR DIGITAL
MANUAL
58
Instruction Manual Local Interface Flow Chart/Menu Trees
D103176X012 June 2017
1
Y
Y
Y
Y
BOARD SWITCH 2 = CLOSED TUNING = C OFF
OFF
ON
QUICK SETUP 1
Y
COMPLETE
+
INVERT DISPLAY 180
CALIBRATION 1 Note: Hold + for 3 to 10 seconds
Y
COMPLETE
Y
CALIBRATION 1
FAILED
+
CANCEL
SAVE AND EXIT? (TAKES YOU TO THE HOME SCREEN)
Y
+ + +
LANGUAGE SELECTION
Note: Hold + + +
for 3 to 10 seconds
Y
Y
PRESS PRESS FOR 3 SEC
Y
TRANSMITTER SWITCH1 SWITCH1 CLOSED SWITCH2 SWITCH2 CLOSED
Y
Y
Y
Y
Y
Y
Y
Only when transmitter / limit Only when transmitter / limit switch hardware is installed
switch hardware is installed.
59
Local Interface Flow Chart/Menu Trees Instruction Manual
June 2017 D103176X012
60
Instruction Manual Local Interface Flow Chart/Menu Trees
D103176X012 June 2017
1 2 3 4 5 6
61
Local Interface Flow Chart/Menu Trees Instruction Manual
June 2017 D103176X012
62
Instruction Manual Local Interface Flow Chart/Menu Trees
D103176X012 June 2017
1‐1‐1
Auto Setup
1‐1‐1‐4
1
2
Setup Wizard
Auto Calib Travel Tuning B
1‐1
Basic Setup 3 Auto Tuner 1 Tuning Set
4 Tuning 2 Damping Factor 1‐1‐1‐4‐3
1 Auto Setup
3 Expert Tuning Gains Expert Tuning Gains
2 Manual Setup Manual Setup
1‐1‐2 1 Prop Gain
1 Instrument Mode 1‐1‐2‐2 2 Vel Gain
2 Press and Actuator Press and Actuator 3 MLFB Gain
3 Tuning and Calib 1 Pressure Units
2 LUI Pressure Units
3 Max Supply Press C
4 Zero Control Signal
1‐1‐2‐3
Tuning and Calib
1 Tuning Set
2 Damping Factor 1‐1‐2‐3‐3
3 Expert Tuning Gains Expert Tuning Gains
4 Tvl Cutoff Lo
5 Auto Calib Travel 1 Prop Gain
2 Vel Gain
1‐2‐1 3 MLFB Gain
General
1 1‐2 D
Setup Detailed Setup 1 HART Tag
2 Message
1 Basic Setup 1 General 3 Descriptor
2 Detailed Setup 2 Measured Var 4 Date
3 Calibrate 3 Response Control 5 Valve Serial Num
4 Transmitter/Switches 1 6 Inst Serial Num
7 Polling Address
1‐3 8 LUI Language
Calibrate 1‐2‐2
1 Analog In Calib Measured Var
1‐2‐3‐3
Online 2 Auto Calib Travel 1 Analog Input Units Expert Tuning Gains E
3 Manual Calib Travel 2 Input Range Hi
1 Setup 4 Transmitter Calib 1 1 Prop Gain
2 3 Input Range Lo 2 Vel Gain
2 Display Display 4 Pressure Units 3 MLFB Gain
2‐1 5 LUI Pressure Units
1 Device Information Device Information
2 DD Revision 1‐2‐3 1‐2‐3‐5
1 HART Univ Rev Response Control Travel Cutoffs
2 Device Rev 1 Travel Cutoff Hi
Field Communicator 1 Tuning Set
3 Firmware Rev 2 Damping Factor 2 Travel Cutoff Lo
1 Offline 4 Firmware Date
1 3 Expert Tuning Gains
5 Main Elec Rev
2 Online
6 Sec Elec Rev
4 Input Char F
3 Utility 5 Travel Cutoffs 1‐2‐3‐6
7 Sensor Serial Num 6 Integral Settings Integral Settings
8 Inst Level
9 Device Id 1‐2‐4 1 Enab Int Control
Transmitters / Switches 1 2 Integral Gain
1 Switch 1 Trip Point 3 Integral Dead Zone
2 Switch 1 Closed
3 Switch 2 Trip Point
4 Switch 2 Closed
5 Transmitter Action
Note: G
1 Available only if the instrument has a transmitter
and limit switches installed.
1 2 3 4 5 6
63
Local Interface Flow Chart/Menu Trees Instruction Manual
June 2017 D103176X012
64
Instruction Manual Glossary
D103176X012 June 2017
Glossary
Alert Point Calibration Location
An adjustable value that, when exceeded, Where the instrument was last calibrated; either
activates an alert. in the factory or in the field.
Configuration
Algorithm Stored instructions and operating parameters for
A set of logical steps to solve a problem or a FIELDVUE Instrument.
accomplish a task. A computer program contains
one or more algorithms.
Control Loop
An arrangement of physical and electronic
Alphanumeric components for process control. The electronic
components of the loop continuously measure
Consisting of letters and numbers.
one or more aspects of the process, then alter
those aspects as necessary to achieve a desired
process condition. A simple control loop
Analog Input Units measures only one variable. More sophisticated
Units in which the analog input is displayed and control loops measure many variables and
maintained in the instrument. maintain specified relationships among those
variables.
65
Glossary Instruction Manual
June 2017 D103176X012
Controller Deviation
A device that operates automatically to regulate a Usually, the difference between set point and
controlled variable. process variable. More generally, any departure
from a desired or expected value or pattern.
Current‐to‐Pressure (I/P) Converter
An electronic component or device that converts Device ID
a milliamp signal to a proportional pneumatic Unique identifier embedded in the instrument at
pressure output signal. the factory.
66
Instruction Manual Glossary
D103176X012 June 2017
Input Characteristic
Feedback Signal The relationship between the ranged travel and
Indicates to the instrument the actual position of ranged input. Possible values include: linear,
the valve. The travel sensor provides the feedback equal percentage, and quick opening.
signal to the instrument printed wiring board
assembly.
Input Current
Firmware Revision The current signal from the control system that
The revision number of the instrument firmware. serves as the analog input to the instrument. See
Firmware is a program that is entered into the also Input Signal.
instrument at time of manufacture and cannot be
changed by the user.
Input Range
Free Time The analog input signal range that corresponds to
Percent of time that the microprocessor is idle. A the travel range.
typical value is 25%. The actual value depends on
the number of functions in the instrument that
are enabled and on the amount of
communication currently in progress. Input Signal
The current signal from the control system. The
input signal can be displayed in milliamperes or in
Full Ranged Travel percent of ranged input.
Current, in mA, that corresponds with the point
where ranged travel is maximum, i.e., limited by
the mechanical travel stops.
Instrument Level
Determines the functions available for the
Gain instrument. See table 3‐1.
The ratio of output change to input change.
67
Glossary Instruction Manual
June 2017 D103176X012
68
Instruction Manual Glossary
D103176X012 June 2017
Primary Master
Masters are communicating devices. A primary
master is a communicating device permanently Set Point Filter Time
wired to a field instrument. Typically, a The time constant, in seconds, for the first‐order
HART‐compatible control system or a computer input filter.
running ValveLink Software is the primary master.
In contrast, a secondary master is not often
permanently wired to a field instrument. The 375
Field Communicator or a computer running Software
ValveLink Software communicating through a Microprocessor or computer programs and
HART modem could be considered a secondary routines that reside in alterable memory (usually
master. RAM), as opposed to firmware, which consists of
programs and routines that are programmed into
Note: If one type of master takes an instrument
memory (usually ROM) when the instrument is
Out Of Service, the same type must put it In
manufactured. Software can be manipulated
Service. For example, if a device set up as a
during normal operation, firmware cannot.
primary master takes an instrument Out Of
Service, a device set up as a primary master must
be used to place the instrument In Service.
Stroking Time
Quick Opening The time, in seconds, required to move the valve
A valve flow characteristic where most of the from its fully open position to fully closed, or vice
change in flow rate takes place for small amounts versa.
of stem travel from the closed position. The flow
characteristic curve is basically linear through the
first 40 percent of stem travel. One of the input
characteristics available for a FIELDVUE
Instrument. See also, Equal Percentage and Temperature Sensor
Linear. A device within the FIELDVUE instrument that
measures the instrument's internal temperature.
Random Access Memory (RAM)
A type of semiconductor memory that is normally
used by the microprocessor during normal
operation that permits rapid retrieval and storage Travel
of programs and data. See also Read Only Movement of the valve stem or shaft which
Memory (ROM) and Non‐Volatile Memory (NVM). changes the amount the valve is open or closed.
Rate
Amount of change in output proportional to the
rate of change in input. Travel Accumulator
The capability of a FIELDVUE instrument to record
total change in travel. The value of the Travel
Read‐Only Memory (ROM) Accumulator increments when the magnitude of
A memory in which information is stored at the the change exceeds the Travel Accumulator
time of instrument manufacture. You can Deadband. To reset the Travel Accumulator, set it
examine but not change ROM contents. to zero.
69
Glossary Instruction Manual
June 2017 D103176X012
70
Instruction Manual Glossary
D103176X012 June 2017
71
Glossary Instruction Manual
June 2017 D103176X012
72
Instruction Manual Index
D103176X012 June 2017
Index
A Analog Input Units, 15
ATEX, Hazardous Area Classification, 5
AC (Auto Calibrate), 4, 34 Auto Calibrate (AC), 4, 34
Actuator and Valve Information, 16 Auto Calibrate Travel, 28
Actuator Information, for Setup, 12
auto tuner, 26
AD (Advanced Diagnostics), 4, 34
Advanced Diagnostics (AD), 4, 34
Air Capacity, 5 B
Air Consumption, 5 Basic Setup and Calibration, using the Local Operator
Airset option, 6 Interface, 3
Alert Record, 23, 36 Burst Mode, 10
Clearing, 23 Commands, 10
Displaying, 23 Enabling, 10
Enabling Alert Groups, 23
Inst Date & Time, 23
Alert Record has Entries, 35 C
Alert Record is full, 35 Calibration
Alerts, 19 Analog Input, 27
Alert Record, 36 using the Field Communicator, 27
Enabling via Local Interface, 28
Cycle Counter, 22 Auto Calibrate Travel, 28
Drive Signal, 23 Manual Calibrate Travel, 29
Travel Accumulator, 21 Output Pressure Sensor, 30
Travel Alerts Position Transmitter, 31
High and Low, 20 Pressure Sensor, 30
High High and Low Low, 20 Certifications
Travel Deviation, 21 CUTR, Russia, Kazakhstan, Belarus, and Armenia, 6
Setting, 19 INMETRO, Brazil, 6
Cycle Counter, 22 KGS, South Korea, 6
Other Alerts, 23 NEPSI, China, 6
Travel Alerts, 20 PESO CCOE, India, 6
High, High-High, Low and Low-Low, 20
Travel Accumulation, 21 Clear Record, 23
Travel Deviation, 21 Command 3, 10
Valve Alerts, 35
Component Replacement, 41
Analog Calibration Adjust, 29
Config & Calib, 12
Analog Input
Calibration, 27 Connections
Display Value, 33 Electrical, 3
Range Hi, 15 Pneumatic, 3
Range Lo, 15 specifications, 6
73
Index Instruction Manual
June 2017 D103176X012
Cycle Counter
Displaying Value, 33
F
Enabling Alert, 22 Factory Default Settings, Detailed Setup Parameters,
Resetting, 23 11
Cycle Counter Alert, 22, 35 Failure Alerts, 36
Cycle Counter Alert Enable, 22 Drive Current Fail, 36
Flash ROM Fail, 36
Cycle Counter Alert Point, 22 NVM Fail, 36
Cycle Counter Deadband, 22 Offline/Failed, 36
Pressure Sensor Fail, 36
Ref Voltage Fail, 36
Temperature Sensor Fail, 36
D Travel Sensor Fail, 36
Fast Key Sequences, Field Communicator, 57
Damping Factor, Tuning, 17
Firmware Date, 34
Date, 14
Firmware Revision, 34
Declaration of SEP, 6 Flash ROM Failure, 24, 36
Descriptor, 14 FM, Hazardous Area Classification, 5
Detailed Setup, 9
Detailed Setup Parameters, Factory Default, 11
G
Device ID, 34
General Information, 14
Device Information, 34
Device Revision, 34
Digital Calibration Adjust, 29 H
Display Record, 23 HART Communicating (HC), 4, 34
Drive Alert Enable, 23 HART Tag, 14
Drive Current Failure, 24, 36 HART Universal Revision, 34
Drive Signal, 23, 55 Hazardous Area Classifications
Displaying Value, 33 ATEX, 5
Enabling Alert, 23 CSA, 5
FM, 5
Drive Signal Alert, 35 IECEx, 5
HC (HART Communicating), 4, 34
E
Educational Services, 8
I
Electrical Classification, 5 I/P Converter
Electrical Housing, 6 Assembly, 43
Removal, 42
Hazardous Area, 5
Replacing, 41
Electrical Connections, 3 IEC 60534-6-1 mounting standards, 5
Electrical Housing Classification, 6 IEC 60534-6-2 mounting standards, 5
Electromagnetic Compatibility, 5 IEC 61326-1 (First Edition), 5
EMC Summary Results, Immunity, 7 IECEx, Hazardous Area Classification, 5
Expert Tuning, Gains, 17 Independent Linearity, 5
74
Instruction Manual Index
D103176X012 June 2017
Installation, 3 Message, 14
K
O
KGS, South Korea, Certification, 6
Offline/Failed, 36
Operational Status, 37
L Options, 6
Limit Switches, 6 Options Board, 4
OFF State, 6 Output Pressure Sensor, Calibration, 30
ON State, 6
Supply Voltage, 6 Output Signal, 5
Action, 5
Local Interface, 4 Maximum Span, 5
Local Interface Flow Chart, 58 Minimum Span, 5
LUI Language, 14 Overcurrent Protection, 5
75
Index Instruction Manual
June 2017 D103176X012
R
T
Record Group Enab, 23
Ref Voltage Failure, 36 Temperature, Internal, Displaying Value, 33
Limit, Reference Accuracy, 6 Temperature Compensation Failure, 24
Reference Voltage Failure, 24 Temperature Limits, 5
Related Documents, 7 Temperature Sensor Failure, 24, 36
relay pressure range, 44 Temperature Units, 15
76
Instruction Manual Index
D103176X012 June 2017
77
Index Instruction Manual
June 2017 D103176X012
78
Instruction Manual Digital Valve Controller
D103176X012 June 2017
79
DVC2000 Digital Valve Controller Instruction Manual
June 2017 D103176X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, Tri-Loop, Rosemount are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson
Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a registered
trademark of FieldComm Group. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
80
E 2004, 2017 Fisher Controls International LLC. All rights reserved.