Ecu List Gems 2 3 0 Global Guide
Ecu List Gems 2 3 0 Global Guide
GEMS
Gen-set controller for Gas
application
SW version 2.3.0
Table of contents 2
1 Document information 3
2 Principle of ECU support 5
3 List of ECU 9
4 Notes 43
3 List of ECU 9
3.1 Altronic CD200XX and NGI1000 10
3.2 Altronic NGI 1000RC 12
3.3 GMF 14
3.4 Heinzmann Ariadne 16
3.5 Heinzmann Helenos 18
3.6 Heinzmann Kronos 19
3.7 Heinzmann Pandaros 20
3.8 Heinzmann Phlox 21
3.9 MWM ADEM A4 24
3.10 Powerlink 26
3.11 TPEM 27
3.12 Trijekt 33
3.13 Uninox 39
3.14 Varistep 1 41
3.15 Varistep 2 42
4 Notes 43
4.1 Software compatibility 43
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
By any of not used ExtValue1deflt - ExtValue4deflt setpoint. The value of an ExtValueXdeflt setpoint can
be used as a source for ECU control. It is recommended to use a source Logical 1 for a particular
ExtValueXreset (in LBI card).
There is a recommended way in DriveConfig software:
By math function ADD in PLC where first input is a required analog value (constant) and the second input
is value 0. The output of the function is a constant which can be used as a source for ECU control. In this
example is created constant = 2.
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name Modbus Address Modbus name
Syncing 10001 Syncing
InSync1 10002 InSync1
InSync2 10003 InSync2
Purging 10004 Purging
Trying 10005 Trying
Firing 10006 Firing
LockOut 10007 LockOut
Fired 10008 Fired
Cranking 10009 Cranking
Running 10010 Running
Wrong Disk 10011 Wrong Disk
GLeadSDGround 10012 GLead SD Grounded
RemotePresent 10013 Remote Present
GLeadSDLogged 10014 GLead SD Logged
RemoteSDLogged 10015 Remote SD Logged
Overspeed Sd 10016 OverSpeed SD Logged
WDG1 Reset 10017 WDG1 Reset
WDG2 Reset 10018 WDG2 Reset
CheckSumError 10019 CheckSumError
LowSuppVolt 10020 Low Supply Voltage
NoCharge 10021 NoCharge
OpenPrimary 10022 OpenPrimary
ShortPrimary 10023 ShortPrimary
OpenSecond 10024 Open Secondary
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name Modbus Address Modbus name
Syncing 10001 Syncing
InSync1 10002 In Sync1
InSync2 10003 In Sync2
Purging 10004 Purging
Trying 10005 Trying
Firing 10006 Firing
LockOut 10007 Lock Out
Fired 10008 Fired
Cranking 10009 Cranking
Running 10010 Running
Wrong Disk 10011 Wrong Disk
GLeadSDGround 10012 GLead SD Grounded
RemotePresent 10013 Remote Present
GLeadSDLogged 10014 GLead SD Logged
RemoteSDLogged 10015 Remote SD Logged
Overspeed Sd 10016 OverSpeed SD Logged
WDOG1 Reset 10017 WDOG1 Reset
WDOG2 Reset 10018 WDOG2 Reset
CheckSumError 10019 CheckSumError
LowSuppVolt 10020 Low Supply Voltage
NoCharge 10021 No Charge
OpenPrimary 10022 Open Primary
ShortPrimary 10023 Short Primary
OpenSecond 10024 Open Secondary
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
StatusOK - Overall Status OK
P-Zero - Zero Pressure Detection
FlowZero - Zero Flow Detection
NoFlow - Flow Not Reached
VlvPositionFlt - Valve Possition Error
T-ActuatorHi - High Actuator Temperature
T-ActuatorFlt - Actuator Temperature Fail
FGTFlt - FGT Fail
P-DiffFlt - Differential Pressure Fail
HiCurrCoilFlt - Coil Current Fail (High)
HiPositionFlt - Position Fail (High)
LowCurrCoilFlt - Coil Current Fail (Low)
FlowNotPlsb - Flow Not Plausible
LowPositionFlt - Position Fail (Low)
V-BatteryLow - Battery Voltage Error (Low)
FGTLowLimit - FGT Low Limit
P-DiffErrorLow - Differential Pressure Error (Low)
V-BatteryHi - Battery Voltage Error (High)
FGTHighLimit - FGT High Limit
P-DiffErrorHi - Differential Pressure Error (High)
FGPHighLimit - FGP High Limit
Watchdog - Watchdog
CanFlowDemFlt - Can Flow Demand Fail
TecjetSd - Tecjet Shutdown
GMFInternalFlt - GMF Internal Fault
Keyswitch - Keyswitch State
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
1,2,3,4,5,6,7,8
StopLamp 623 Red Stop Lamp
1,2,3,4,5,6,7,8
WarningLamp 624 Amber Warning Lamp
ProtectLamp 987 Protect Lamp
MalfunctLamp 1213 Malfunction Indicator Lamp
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
1,2,3,4,5,6,7,8
StopLamp 623 Red Stop Lamp
1,2,3,4,5,6,7,8
WarningLamp 624 Amber Warning Lamp
ProtectLamp 987 Protect Lamp
MalfunctLamp 1213 Malfunction Indicator Lamp
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
1,2,3,4,5,6,7,8
StopLamp 623 Red Stop Lamp
1,2,3,4,5,6,7,8
WarningLamp 624 Amber Warning Lamp
ProtectLamp 987 Protect Lamp
MalfunctLamp 1213 Malfunction Indicator Lamp
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
1,2,3,4,5,6,7,8
StopLamp 623 Red Stop Lamp
1,2,3,4,5,6,7,8
WarningLamp 624 Amber Warning Lamp
ProtectLamp 987 Protect Lamp
MalfunctLamp 1213 Malfunction Indicator Lamp
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
1,2,3,4,5,6,7,8
StopLamp 623 Red Stop Lamp
1,2,3,4,5,6,7,8
WarningLamp 624 Amber Warning Lamp
ProtectLamp 987 Protect Lamp
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
FuelShtoff1 632 Engine Fuel Shutoff 1 Control
FuelShtoff2 2807 Engine Fuel Shutoff 2 Control
PTO Enabled 3452 Enable Switch - Transmission input shaft PTO 1
ESDRequest 3607 Engine Emergency (Immediate) Shutdown Indication
*The parameter requires extended controller's support. Please refer controller's manual for further
information.
Available parameters
ECU analog outputs (controller's inputs)
Configuration Name SPN J1939 Name
ThrottleVlv1 51 Engine Throttle Valve 1 Position 1
1,2,3,4,5,6,7
P-Oil 100 Engine Oil Pressure
1,2,3,4,7
T-IntManifold 105 Engine Intake Manifold 1 Temperature
P-IntakeAir 106 Engine Intake Air Pressure
1,2,3,4,5,6,7
T-Coolant 110 Engine Coolant Temperature
T-Exhaust 173 Engine Exhaust Temperature
1,2,3,4,7
T-Oil 175 Engine Oil Temperature 1
1,2,3,4,5,6,7
EngineSpeed 190 Engine Speed
T-ExhPort 1 1137 Engine Exhaust Gas Port 1 Temperature
T-ExhPort 2 1138 Engine Exhaust Gas Port 2 Temperature
T-ExhPort 3 1139 Engine Exhaust Gas Port 3 Temperature
T-ExhPort 4 1140 Engine Exhaust Gas Port 4 Temperature
T-ExhPort 5 1141 Engine Exhaust Gas Port 5 Temperature
T-ExhPort 6 1142 Engine Exhaust Gas Port 6 Temperature
T-ExhPort 7 1143 Engine Exhaust Gas Port 7 Temperature
T-ExhPort 8 1144 Engine Exhaust Gas Port 8 Temperature
T-ExhPort 9 1145 Engine Exhaust Gas Port 9 Temperature
T-ExhPort10 1146 Engine Exhaust Gas Port 10 Temperature
T-ExhPort11 1147 Engine Exhaust Gas Port 11 Temperature
T-ExhPort12 1148 Engine Exhaust Gas Port 12 Temperature
T-ExhPort13 1149 Engine Exhaust Gas Port 13 Temperature
T-ExhPort14 1150 Engine Exhaust Gas Port 14 Temperature
T-ExhPort15 1151 Engine Exhaust Gas Port 15 Temperature
T-ExhPort16 1152 Engine Exhaust Gas Port 16 Temperature
T-ExhPort17 1153 Engine Exhaust Gas Port 17 Temperature
T-ExhPort18 1154 Engine Exhaust Gas Port 18 Temperature
T-ExhPort19 1155 Engine Exhaust Gas Port 19 Temperature
T-ExhPort20 1156 Engine Exhaust Gas Port 20 Temperature
P-FuelIntake 1390 Engine Fuel Valve 1 Intake Absolute Pressure
IgnitionTime1 1433 Engine Desired Ignition Timing 1
Available parameters
ECU binary outputs (controller's inputs)
Modbus
Configuration Name Modbus Name
Address
T604 CV 11002 T604 CV exhaust air sensor error
T404 CV 11003 T404 CV supply air 10 K too high
G987 CV 11004 G987 CV inlet flap limit stop opened
G988 CV 11005 G988 CV inlet flap limit stop closed
G350 CV 11006 G350 CV outlet flap limit stop opened
G351 CV 11007 G351 CV outlet flap limit stop closed
G555 CV 11008 G555 CV circulation flap limit stop opened
G354 CV 11009 G354 CV circulation flap limit stop closed
G885 MCC Warm 11010 G885 MCC control valve limit stop warm
G886 MCC Cold 11011 G886 MCC control valve limit stop cold
MCC340 11012 340 MCC Rec FC demanded
G880 HC 11016 G880 HC valve limit stop cold
G881 HC 11017 G881 HC valve limit stop warm
631 ECC Pump 11018 631 ECC pump demanded
HC Pump 11019 HC pump demanded
G890 EmCC Cold 11020 G890 EmCC valve limit stop cold
G891 EmCC Warm 11021 G891 EmCC valve limit stop warm
938 EmCC Pump 11022 938 EmCC pump demanded
CPH demanded 11023 CPH demanded
Power Lim Op 1 11024 Power limitation by mains operator level 1
Power Lim Op 2 11025 Power limitation by mains operator level 2
Power Lim Op 3 11026 Power limitation by mains operator level 3
Power Lim Op 4 11027 Power limitation by mains operator level 4
Aut Power Dem 11028 Automatic power demand active
GCB Closed 11029 GCB closed
MCB Closed 11030 MCB closed
GCB Release 11031 GCB release
Automatic 11032 Automatic
RP OverF 11033 Mains-dependent RP active in the event of overfrequency
CV Control 11034 CV control at standstill active
BlackStartRun 11035 Black start running
BlackStartPos 11037 Black start possible
StarterDem 11038 Starter demanded in
PrelubPumpIn 11039 Prelubrication pump demanded in
GCL A 1 11040 GCL A gas shut-off valve 1 demanded
GCL A 2 11041 GCL A gas shut-off valve 2 demanded
GCL A Leak 11052 GCL A leakage check demanded
FreshOilDem 11053 Fresh oil refill demanded
T207 ECC High 11054 T207 ECC engine inlet too high
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
ReadyStart - Ready to Start
DInEngEn - Dig. Input Engine Enable
DInTypOp - Dig. Input Type of Operation
DInOpPhase - Dig. Input Operation Phase
DinPlus - Dig. Input Plus
DInMinus - Dig. Input Minus
DInF1 - Dig. Input Function 1
DInF2 - Dig. Input Function 2
DInF3 - Dig. Input Function 3
DInF4 - Dig. Input Function 4
DInF5 - Dig. Input Function 5
DInF6 - Dig. Input Function 6
DInF7 - Dig. Input Function 7
DInF8 - Dig. Input Function 8
DOutIgnLoA - Dig. Output Ign. Low A
DOutIgnLoB - Dig. Output Ign. Low B
DOutIgnLoC - Dig. Output Ign. Low C
DOutIgnLoD - Dig. Output Ign. Low D
DOutIgnLoE - Dig. Output Ign. Low E
DOutIgnLoF - Dig. Output Ign. Low F
DOutIgnLoG - Dig. Output Ign. Low G
DOutIgnLoH - Dig. Output Ign. Low H
DOutIgnHiA - Dig. Output Ign. High A
DOutIgnHiB - Dig. Output Ign. High B
DOutIgnHiC - Dig. Output Ign. High C
DOutIgnHiD - Dig. Output Ign. High D
DOutIgnHiE - Dig. Output Ign. High E
DOutIgnHiF - Dig. Output Ign. High F
DOutIgnHiG - Dig. Output Ign. High G
DOutIgnHiH - Dig. Output Ign. High H
DOutSw1 - Dig. Output Switch 1
DOutSw2 - Dig. Output Switch 2
DOutSw3 - Dig. Output Switch 3
DOutSw4 - Dig. Output Switch 4
DOutSw5 - Dig. Output Switch 5
DOutSw6 - Dig. Output Switch 6
DOutSw7 - Dig. Output Switch 7
DOutSw8 - Dig. Output Switch 8
DOutSw9 - Dig. Output Switch 9
*The parameter requires extended controller's support. Please refer controller's manual for further
information.
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
AT1IntGSPwr 3218 Aftertreatment 1 Intake Gas Sensor 1 Power In Range
AT1IntGSTmp 3219 Aftertreatment 1 Intake Gas Sensor 1 at Temperature
SCR IntakeNOx 3220 Aftertreatment 1 SCR Intake NOx 1 Reading Stable
AT1IntWROxygen 3221 Aftertreatment 1 Intake Wide-Range Percent Oxygen 1 Reading Stable
AT1IntGSHeater 3223 Aftertreatment 1 Intake Gas Sensor 1 Heater Control
AT1OutGS1Pwr 3228 Aftertreatment 1 Outlet Gas Sensor 1 Power In Range
AT1OutGS1Tmp 3229 Aftertreatment 1 Outlet Gas Sensor 1 at Temperature
AT1OutNOxRead 3230 Aftertreatment 1 Outlet NOx 1 Reading Stable
AT1OutWROxygen 3231 Aftertreatment 1 Outlet Wide-Range Percent Oxygen 1 Reading Stable
AT1OutGS1Heat 3233 Aftertreatment 1 Outlet Gas Sensor 1 Heater Control
AT2IntGSPwr 3257 Aftertreatment 2 Intake Gas Sensor 1 Power In Range
AT2IntGSTmp 3258 Aftertreatment 2 Intake Gas Sensor 1 at Temperature
SCR2IntakeNOx 3259 Aftertreatment 2 SCR Intake NOx 1 Reading Stable
AT2IntWROxygen 3260 Aftertreatment 2 Intake Wide-Range Percent Oxygen 1 Reading Stable
AT2IntGSHeater 3262 Aftertreatment 2 Intake Gas Sensor 1 Heater Control
AT2OutGS1Pwr 3267 Aftertreatment 2 Outlet Gas Sensor 1 Power In Range
AT2OutGS1Tmp 3268 Aftertreatment 2 Outlet Gas Sensor 1 at Temperature
AT2OutNOxRead 3269 Aftertreatment 2 Outlet NOx 1 Reading Stable
AT2OutWROxy1 3270 Aftertreatment 2 Outlet Wide-Range Percent Oxygen 1 Reading Stable
AT2OutGS1Heat 3272 Aftertreatment 2 Outlet Gas Sensor 1 Heater Control
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
Offline - Offline
Mode - Error
Man/Auto - Manual / Auto Mode
StepError - Step Error
Timeout - Time out error
LowPwr - Low power error
OverTemp - Over temperature error
OverCurr - Over Current Error
OpenPosition - Open position
ClosePosition - Close position
Available parameters
ECU binary outputs (controller's inputs)
Configuration Name SPN J1939 Name
Offline - Offline
Mode - Error
Man/Auto - Manual / Auto Mode
StepError - Step Error
Timeout - Time out error
LowPwr - Low power error
OverTemp - Over temperature error
OverCurr - Over Current Error
OpenPosition - Open position
ClosePosition - Close position