0% found this document useful (0 votes)
46 views

Manual UFM NC V3

Servo Promess UFM NC V3 instruction manual

Uploaded by

Uga Gonzalez
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views

Manual UFM NC V3

Servo Promess UFM NC V3 instruction manual

Uploaded by

Uga Gonzalez
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 99

Manual

UFM
NC module
PROMESS

TABLE OF CONTENTS
1 Introduction................................................................................................................ 4
1.1 Contents of supply ..............................................................................................................................5
2 Correct usage ............................................................................................................ 7

3 Safety precautions .................................................................................................... 7


3.1 Risk analysis .......................................................................................................................................9
4 Software installation................................................................................................ 10

5 Program start ........................................................................................................... 11

7 Screen settings........................................................................................................ 12

8 Manual positioning .................................................................................................. 14

9 Programming ........................................................................................................... 15
9.1 Positioning ........................................................................................................................................16
9.2 Press to Force...................................................................................................................................17
9.3 Press to signal ..................................................................................................................................19
9.4 Delay time .........................................................................................................................................21
9.5 Calibration.........................................................................................................................................21
9.6 Variables ...........................................................................................................................................21
9.7 Conditional jump ...............................................................................................................................22
9.8 Motion Control...................................................................................................................................22
9.9 Program end .....................................................................................................................................23
9.10 Set outputs......................................................................................................................................24
9.11 Analog output..................................................................................................................................24
9.12 Set status ........................................................................................................................................25
9.13 Dialog window.................................................................................................................................25
10 Force - Distance - Development .......................................................................... 27
10.1 Register measuring values .............................................................................................................27
10.2 Monitoring .......................................................................................................................................27
10.3 Edit limit curves...............................................................................................................................29
11 Zoom graphics....................................................................................................... 29

12 Data......................................................................................................................... 30
12.1 Record measurement values..........................................................................................................30
12.1.1 Save measurement values as ASCII data...................................................................................31
12.1.2 Save measurement values via Profibus DP, CAN Open, Interbus - S . ......................................32
12.1.3 Save measurement values in database ......................................................................................32
12.1.4 Database maintenance................................................................................................................33
12.1.5 Database Structure ......................................................................................................................34
12.2 Call up saved measurement values................................................................................................36
13 Printing ................................................................................................................... 40
13.1 Printer settings ................................................................................................................................40
13.2 Printing graphics .............................................................................................................................41
13.3 Printing the CNC program ..............................................................................................................42
14 Service.................................................................................................................... 43
14.1 Program parameters .......................................................................................................................43
1
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul
PROMESS
14.1.1 Standard settings .........................................................................................................................43
14.1.2 Program settings..........................................................................................................................45
14.1.3 Analog Input.................................................................................................................................45
14.1.4 Program parameters ....................................................................................................................46
14.1.5 Graphics.......................................................................................................................................46
14.1.6 Profibus DB participant address ..................................................................................................47
14.1.7 CAN Open....................................................................................................................................47
14.1.8 Analog output...............................................................................................................................47
14.2 In / outputs ......................................................................................................................................49
14.3 Change station address..................................................................................................................49
14.4 Parameter NC module ....................................................................................................................50
14.4.1 Service Window Bus Systems ....................................................................................................51
14.4.2 Link Module Inputs / Outputs ......................................................................................................52
15 Register an NC module to the PC ........................................................................ 53
15.1 Register a new station ....................................................................................................................53
15.2 Switching Programs ........................................................................................................................54
16 Error messages ..................................................................................................... 55

17 Configuration ......................................................................................................... 56
17.1 Serial communication RS232/RS485 .............................................................................................56
17.1.1 Serial communication Ethernet module .......................................................................................57
17.2 General ...........................................................................................................................................58
17.2.1 Password protection ....................................................................................................................58
17.3 ASCII Data export ...........................................................................................................................59
17.4 Layout (Display Error Messages) ...................................................................................................59
18 Link Module............................................................................................................ 60
18.1 Functions Link Module ....................................................................................................................60
18.2 Configuration Link Module ..............................................................................................................62
18.2 Configuration Link Module ..............................................................................................................63
18.3 Link Module Sending and Loading of Programs.............................................................................63
18.4 Ethernet-Module .............................................................................................................................65
18.4.1 IP Address Ethernet module.......................................................................................................66
19 Technical appendix ............................................................................................... 68
19.1. General description and design .....................................................................................................68
19.1.2 Weights Mechanics......................................................................................................................69
19.2 Specifications and technical features .............................................................................................69
19.3 The drive .........................................................................................................................................69
19.4 Power amplifier ...............................................................................................................................70
19.5 Force measuring .............................................................................................................................72
19.6 Distance measuring ........................................................................................................................72
19.7 Electrical connections .....................................................................................................................73
19.8 SG pre-amplifier..............................................................................................................................74
19.9 Transducer calibration ....................................................................................................................75
19.10 Wheight of toools ..........................................................................................................................77
19.11 Integration of a holding break into the control ..............................................................................78
20 PLC Interface ......................................................................................................... 79
20.1 Reference motion after start-up ......................................................................................................79
20.2 Reference motion without a request ...............................................................................................80
20.3 Cycle start .......................................................................................................................................81
20.4 Emergency Stop during a motion ...................................................................................................81
20.5 Emergency Stop during standstill ...................................................................................................82
20.6 Cycle Stop.......................................................................................................................................83
20.7 Transfer of program number...........................................................................................................84

2
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
21 Lubrication advice ................................................................................................. 85
21.1 Gear box oil.....................................................................................................................................95
22 Software Update ................................................................................................... 96

• Index ...................................................................................................................... 98

3
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
1 Introduction

The UFM-NC-MODULE system is a powerful tool to rapidly setup, alter, optimize and adapt press and
positioning tasks.

The basic element is the electro-mechanical assembly unit from PROMESS, consisting of:

• assembly unit with motor, transducer and distance measuring device,


• motor power amplifier,
• NC module for NC control of the assembly program,
• programming and user software.

Several press units can be connected via a network and programmed


from a single programming device.

The following figure shows a block schematic:

UNIT UNIT UNIT UNIT


1 2 3 n

Servo Servo Servo Servo


amplifier amplifier amplifier amplifier

NC NC NC NC
Module Module Module Module

Programming PLC-control
unit

4
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

1.1 Contents of supply

Option
Mechanical unit
Mounting plate
AC – Servo motor

Press S.G.-amplifier
safety control
4
3

LV
NC
Module

1
2

Option
F
• PC
• Monitor
• Keyboard S

5
PC

• Electro-mechanical press unit,


• SG–amplifier in diecast aluminium housing (SG = Strain Gauge)
• Power module
• NC module
• PLC interface (basic function)

• Optional mounting plate for the installation of the control cabinet, including Emergency Stop
circuitry according to EN 4181, Stop Cat. Dimensions H * W * D = 773 * 492 * 300 mm (Units > 60
kN: H * W = 1896 * 499 mm)
• Connection cable, confectioned:
1. Connection cable motor – power amplifier (power cable), length 5 m
2. Connection cable motor – power unit (resolver), length 5 m
3. Connection cable SG amplifier – control unit, length 5 m
4. Connection cable proximity switch in OT – SG amplifier, length = 2 m
5. Interface cable (RS 485, RS232)

• Optional PC with monitor + keyboard

5
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
1.2. Transport

The units are supplied packaged in standard cases. The belt drive protection is not mounted to
facilitate the use of lifting equipment when unpacking the unit. Please follow the instructions below to
remove the unit:

Use a broad double belt, placed under the motor plate and around the mounting flange, to unload the
press unit.

ATTENTION:
Do not put any loads on the proximity and limit switches when attaching the lifting device!

There is also the possibility of using an eyebolt, attached to the thread of the ball screw, to unload the
press unit.

After the unit has been unloaded, inspect it for visible transport damages.

The press unit and related servo amplifier may only be installed in appropriate and suitable locations.
In particular, please observe all protection regulations. Should you require information concerning
requirements about the admissible locations, please contact the manufacturer.

After the installation of the press unit, please make sure you comply with the manufacturer's specific
measures before operation:

Mount the belt protection, prior to connecting the power cable.


Only use the power cables supplied.
Assemble the power amplifier with the supplied filters and choking coils according to the power
amplifier manual instructions.
Make sure all cables are correctly installed. Avoid laying power and data cables next to each other.

6
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

2 Correct usage

The press unit is designed and built for assembly operation tasks, e. g. for pressing in bearings,
absorbers and shafts or to press in and caulk seals.

Operations, other than the above, may not be performed on the machine.

The permissible loads are determined by the performance data of the unit and must not be exceeded
by any larger extent.
Avoid the following situations in particular:
Abrupt loads at high positioning velocities - “collisions”,
Forces under normal operations that exceed the nominal load by more than 110%,
Excessive loads through unpredicted operational conditions, exceeding the nominal load by 100%.

3 Safety precautions

The press unit may only be used to perform the operations it is intended for. The use in other
operations or for other purposes may lead to operator injuries and damages to the unit.

If you have acquired the unit as “components“ without the optional mounting plate, you are responsible
for the installation of the Emergency Stop chain according to EN 418 Cat. 1. PROMESS is not liable
for damages resulting from incorrect installation.

The power amplifier may only be connected and operated by competent personnel.

It is strictly forbidden to disconnect, bridge or remove any safety equipment!

The belt protection may only be removed once the unit is completely electrically disconnected from the
power amplifier.
If it is not possible to start the unit because of a technical disturbance or functional problem of the
protective equipment, then the faulty part or equipment must be repaired or exchanged.
It is strictly forbidden to operate the press unit without the proper function of the safety equipment,
e. g. through manipulation of the safety devices!

The press unit may only be operated by personnel who have been fully instructed in its proper
operation.

If problems occur during normal operation and they can not be resolved through known and
recommended strategies, specialist personnel from the responsible department must be informed.

7
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
The press unit must be completely disconnected from any electrical power supply before any service,
repair work or problem solving can start! Proceed as follows:
• Set main switch to “OFF“ position,
• If necessary, pull out the power plug.

IMPORTANT: The switch, in the “0” or “OFF” position, must be marked with a sign:

WARN ING !
UN IT UN DER MA IN TENANC E, R EPA IR OR
S E R VIC E - DO N OT SW ITCH ON!

If the unit has to be disassembled, you must first undo all electrical connections.

The PROMESS electro-mechanical press unit can harm the operator,


if used incorrectly. Please comply with the following directions:

1. Do NOT attempt to undertake any internal system configurations without prior


consultation with PROMESS,
2. Do NOT keep your hands in the working area,
3. The safety chain must be closed when operating the press unit,
4. Do NOT operate the unit in areas for which it was not designed,
5. Only authorised personnel may operate the press unit.

8
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

3.1 Risk analysis

Risk estimation

Frequency of exposure Accident probability

seldom often great small

Possible injuries 1 2 3 1 2 3 Countermeasures


A B C D E F
Category 1
Minor injuries,
crushing of the hand and
fingers
Category 2
Major injuries,
loss of fingers,
severe crushing of the hand
Category 3
Death
Severe crushing of the head

Dangers through mechanical malfunctions

Type of malfunction Possible Countermeasures


injuries
Guides: wear, blocking after being None
damaged
Thrust bearing: wear, damage None
Ball screw: wear, damage None

Broken drive belt: 1A 3F Category 1 and 10-fold safety level against rupture
2 under normal working conditions
No brake function after the belt is
ruptured
Cog-belt coupling loosened 1A 3F Category 1 and The couplings are self-retaining, loose
2 screws can only result in the coupling
loosening itself when the press unit is
exerted to extremely strong vibrations
or shocks.
Slippage of the cog-wheel on the None
axle, wrong positioning, force
exceeded
Transducer, destroyed through None
excessive load
Cable breakage, force transducer None
Cable breakage, limit switches None
Cable breakage, motor resolver None
Cable breakage, power cable None

9
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

4 Software installation

Place the disk or CD-ROM in the appropriate drive. Go to the Windows start button (bottom far left),
select 'Execute' and then type “Setup”. Follow the on-screen instructions to install the program.
Connect your PC with the press unit NC module via the serial interface RS 232 or RS 485
(a separate board is needed in your PC). If you connect via RS 485, you must bridge pins 4 and 9.

• Position of the NC module in the power amplifier

RS 485

Pin
1 0V
2 /TX
3 /RX
4 NC
5 NC
6 TX
7 RX
8 NC
9 0V

RS 232

Pin
1 Schirm
2 TXD
3 RXD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 NC

10
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

5 Program start

Start the program with the help of the icon installed.

During start up, the program scans the whole system to determine which modules are connected. This
scanning takes place provided the option "automatic" has been selected under “polling of the stations”
(new or substitute modules are always supplied with the station number 31 set). The station number
desired must be entered in parameter 20.29 of the Unidrive. For details on how to enter parameters,
please see the Unidrive manual, page 5-5 (parameterisation).
If you only want to establish a connection to a specific station, you should select “manual”.

Once a station has been detected, the following station window is opened:

The program stored in the NC module is automatically loaded and displayed.

If there are any communication problems, check the configuration of the interface first.

!!!
Before you start the unit for the first time, please check whether the calibration factor is
correct. To do this, open „program parameter“ in the menu „service“ and check under
„calibration“. You will find the right calibration factor in the „Proprietary Calibration
Certificate“, you have got with the UFM and on the mechanical unit.

11
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
6 Program window
The main window:

Histogram: On/Off

Meas. variable

Variable
Editor

Signal progress

Step list

Status
information

Status line

7 Screen settings

Various windows may be displayed on the screen. The windows can easily be opened, closed or
toggled, so that any combination is possible. The windows can be selected or de-selected via the
menu “View”.

12
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

• LEDs
The LEDs show the status of the I/Os of the PLC – interface (basic function):

The following conditions are displayed:

- Start reference positioning (I)


- Start (I)
- Confirmation (O)
- Ref. (Error / reference request) (O)
- NOK (O)
- OK (O)

• Pushbuttons NC module

The buttons are used to initiate the following functions:

- E-Stop: The program can only be resumed after a reference positioning.


- Stop: The program execution is interrupted. Resume with “Start”.
- Step: The next step in the program cycle is executed.
- Start: The complete program cycle is started.
- Ref..: A reference positioning is executed.

• Program pushbuttons

Send program to
Graphics, Open database
NC module
zoom out
New program Save Program Preset
Graphics,
zoom in

Open Print Add


Delete Graphics, Arrange stations
program step Get program
step full view
from NC module

13
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
• Analog inputs

The values for force, distance and the external analog signal are displayed here.

• Status line
Status of communication between the PC and NC module

113
Status
Error messages
Step counter

8 Manual positioning

You will find the item “Manual positioning” in the service menu.

Use this window to control the axis in manual mode.


Enter the values required for position, speed, acceleration and excessive load limit.

Jogging - press and hold down the respective button to move the axis in the
direction desired at the speed programmed. As soon as you let go of the
button the axis stops.

Continuous motion, the axis is positioned the equivalent distance you have
entered. The axis moves along the programmed distance. If the button is
released the press will stop. To continue moving along the distance, press the
button again.
14
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

9 Programming

To generate a new program, first select “New” from the drop down menu “File” or click on the
corresponding button in the toolbar.

Select the function required before you start generating your press program:

All functions for the generation can also be selected with the right mouse button, if you click in the step
list. With the help of the right mouse button, it is also possible to copy and paste program steps.

All generation functions can also be called up via the right mouse button if you click within the step list.
It is also possible, using the right mouse button, to copy and insert program steps.

Menu by clicking the right mouse button

Memory requirement of the individual program steps


see: Program parameter (Standard parameter) page
48

15
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
Saved programs can be reopened under “Open Program”.
If you want to delete a program, please click with the right mouse button on the chosen program and
on the menu that is opened then, on the function “Delete”.

9.1 Positioning

This function block is used to move the press ram to any position, both in absolute and relative mode.
The actual motion curve can be registered, but in addition also the force – distance – development can
be monitored (see monitoring). It is also possible to position according to any variable value. (Working
with variables, please refer to the chapter Variable).

Click the button “Positioning” in the drop-down menu Function.

The following window is opened:

Enter the values required in the following fields :

Current position

Current force

Current value of an
additional analogue sensor

• Position (positions may be reached in either relative or absolute mode).


• Speed
• Acceleration
• Brake ramp
• Overload limit (Please choose the input for overload)
• Signal source (Please choose the input for monitoring)
• Limit curve teach-in: A teach-in curve for this function is established, when the next teach-in
cycle is started. Existing limit curves are overwritten. The distance of the limit curves relative the
actual curve may be set in the service menu under configuration => control parameters =>
parameters in field, teach-in strategy.

16
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
• Cycle stop: Select this point, when you want to stop the cycle after having executed the active
function.

9.2 Press to Force

This function block is used to press to a given force, the distance may be expressed as absolute or
relative values. The actual motion curve can be registered, but in addition also the force – distance
development can be monitored (see monitoring).

Click the button “Press on block“ in the drop-down menu Function.

The following window is opened:

Current position

Kurrent force

Current value of an
additional analogue sensor

In the following fields enter the values needed:

• Force: the required switch off force can be entered directly or via a variable
• Pre-position: Up to this position, positioning is done at the speed value entered
(the position can be reached in relative or absolute mode),
• Speed: Speed up until the force level is reached,
• Acceleration: Positioning acceleration,
• Max. press-in position: This is the max. position of the press ram,

17
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
• Press-in speed (feed): Speed at the beginning of the force level. With increasing force, the speed
is reduced to 10 % of the press force entered. The change of speed is executed via a brake ramp
of 1000 mm/s2,

• Add limit force to the current force at pre-position: If this function is activiated, the switch-off
criterion from the force at reaching the pre-position plus the value entered under force is
determined. Up to the pre-position, the movement with the nominal load is monitored for collision.
• Signal source (Please choose the input for monitoring)

• Recording of values: The force-way-course is recorded for the movement. Enter the desired
number of reading points (maximum 200).
• Teach-in of limit curves: A teach-in curve for this function is established, when the next teach-in
cycle is started. Existing limit curves are overwritten. The distance of the limit curves relative to the
actual curve may be set in the service menu under configuration => control parameters =>
parameters in field, teach-in strategy,
• Cycle stop: Select this point, if you want to stop the cycle after having executed the active
function.

18
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

9.3 Press to signal

This function is very similar to the press on force block, however in this case you press to an external
signal that you can select from the signal source. You can select between an external analog signal of
a switch signal. If you want to set the switch signal via the bus, you can use the freely programmable
inputs 1 and 2.

If you do not set the switch signal via the bus, but as a 24 VDC signal, you must first select the option
“User I/O“ in the standard settings under “Program Parameter“. The reference input then becomes
input PLC 1 and the start input becomes input PLC 2. The start and reference run can then only be
executed via the bus system.

19
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
Once you have selected one of the switch signals, define the threshold or switching limit that should
trigger the movement end using the signal limits. (On = Stop, when level is "high", Off = Stop, when
level is "low")

Enter the pre-position, speed, acceleration and overload value for the force. Also define the maximum
position and the pressing speed.

• Extension

Use this extension to configure the monitoring and, if necessary, a control once the switch-off criteria
are reached.

• Hold signal
If you select this point, you can regulate the external input values; i.e. the module changes its
position so that the signal remains constant for the given time.

• Teach-in of limit curves: A teach-in curve for this function is established, when the next teach-in
cycle is started. Existing limit curves are overwritten. The distance of the limit curves relative the
actual curve may be set in the service menu under configuration => control parameters =>
parameters in field, teach-in strategy,

• Cycle stop: Select this point, if you want to stop the cycle after having executed the active
function

20
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
9.4 Delay time

Programming of delay times during the execution of the program cycle. The delay time is entered in
milliseconds.

9.5 Calibration

This function is used to calibrate the input of force or additional analog input values. Select the input
desired by using the arrow.

9.6 Variables

There are 12 variables available in the process. By the use of this function you can assign a numerical
value, or the value of an external sensor via the analog input, to a variable of your choice.
In addition, you can execute calculations by means of the variable.

21
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
9.7 Conditional jump

Use this function to program jumps in your program.

9.8 Motion Control

This component makes it possible to keep the force or any other connected signal constant over a
certain period of time. This means, the joining unit moves back and (or) forth within a range that has
to be determined, in order to eliminate the deviations from the control size. This process is also
monitored by a overload limit for the force, to avoid destruction of components.

• Control Size
First, select the size to be controlled. You can choose between the force input and the defined
virtual analog inputs under “Program Parameters / Analog Inputs”.

• Control Deviation
Here, you set, how the unit should react to deviations from the control size.

22
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

+ A positive control deviation leads to a forward movement of the spindle.


(Example: Control value = 200, actual value = 202 => move forward; actual value = 199 =>
move backward)
- A negative control deviation leads to a forward movement of the spindle.
(Example: Control value = 200, actual value = 202 => move backward; actual value = 199 =>
move forward)

• Control Speed
Enter the speed, by which the control deviation should be moved out.

• Acceleration
Enter the acceleration, by which the control deviation should be moved out.

• Overload
This force monitors the control process.

• Min. Control Position / Max. Control Position


Enter here the range, within which the control may be performed. The entry can be made absolute
or relative. Basis of the relative way is the position at the entry into the control component.

!!! If the permitted positioning range is exceeded, the part is declared NIO. The
program continues the cycle. No reference run is requested.

• Duration
Please enter here the time, for which the control process should be performed. The time starts
with the first reaching of the control value.

• Cycle Stop
Choose this option, if the cycle should be stopped after this function has been executed.

9.9 Program end

With this function you can define the end of your program cycle. Mandatory in program structures
using conditional jumps. This input is not necessary in simple cycles without conditional jumps. The
program returns to the first step and awaits a new Start after the last step has been executed.

23
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

9.10 Set outputs

Using Profibus DP you can set or reset 8 freely programmable outputs in the program process.

When program control is implemented via the Profibus, it is possible to define 2 standard inputs and
outputs as freely programmable outputs. Outputs or inputs 1 and 2 are then no longer available in the
Profibus.

The outputs can be set directly or linked with variables.

In the above example, output 2 is set when the value of variable 1 is greater than 200.

9.11 Analog output

It is possible, using this function, to output the value of a variable, the actual position, the actual force
or the actual analog input signal via the two analog outputs.

You must first define the analog output (see Chapter 14.1.8 Analog output)

24
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

9.12 Set status

With the help of these function you can influence the total status, if necassary. To characterize the
“manipulatet” status in the database, the bit 15 (16384) is set in the stored status

9.13 Dialog window

With the help of this function you can generate a user dialog.

The following inputs are possible:

• Acknowledge: Choose this if you only want to display a message, the user has to confirm.
The message can consist of max 30 characters.

• DB Ident Number: Input of the Ident number, to store to part in the database.

• DB User: Input of the username, to store in the database.


• Variable 1-12: Input of the value for a variable via the keyboard.

25
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

• Single execution: With this switch you decide whether the window is opened in every cycle,
or only once. When the switch is not set, the window pops up every cycle. When the switch is
set, the window pops up once, after loading a part program or homing. up every cycle.

• Cycle Stop: If you choose this switch, the unit has to be started again, when you have
finished the dialog.

When you run the cycle, the following window pops up:

!!! Every input has to be confirmed with „OK“ The cycle stops until you confirm the input,
or if you have chosen “Cycle stop” until cycle start is set again.

26
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

10 Force - Distance - Development

In order to register and monitor the force – distance – development of the press process, please
proceed as follows:

In the desired motion mode activate the following functions:

10.1 Register measuring values

All measuring values are registered for this motion if this option has been activated.
Under How many you should enter the number of supporting points. The points are evenly dispersed
over the entire distance. An “A“ is entered in the function list to earmark this step. The development for
this particular step is displayed in the graphics window in the form of a sub-window.

10.2 Monitoring
When this function is activated, the force-distance-development is monitored by means of limit curves.
The limit curves consist of a chain of connected straight lines.

27
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

Mouse coordinates

Support points

Upper limit curve

Actual curve

Lower limit curve

• Teach-in limit curve


When this function is selected, limit-curves are recorded of the actual curve after the next step.

The number of supporting points may be determined via the button “Parameters“

(Max. 20 supporting points).

The distance of the limit curve during the learning process from the actual curve can be defined
globally via the register card “Program parameter“ in the service menu for all programs.

28
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

10.3 Edit limit curves

Right-click in the graphics to edit the path of the force-distance curve. You can also open the menu
“Graphics“ and select one of the edit functions from the drop-down menu.

If you want to edit an existing support point you must first select the upper or lower limit curve. Then
click with the cursor on the point you want to edit. Press and hold down the left mouse button and pull
the point to the new position.

In a similar way, click on either the upper or lower limit curve if you want to add or delete support
points. Subsequently with the cursor on the point where you want to add a support point, click the left
mouse button. Press and hold down the left mouse button and pull the point to the position where you
want to insert a new point. Existing points in between will be deleted.

11 Zoom graphics

There are several options to zoom graphics:

• via the buttons

optimal view enlarge reduce

• via the menu “Graphics“ or right-clicking in the graphics window


Scaling to nominal values

Reduce curve view

Increase curve view

• by using the mouse


Press and keep the shift button pressed, then with the left mouse button pressed draw a rectangle
corresponding to the view required.

29
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
12 Data

12.1 Record measurement values

Use this function to record and monitor force measurement values or external signals at any position
required. In addition, the max value, min value or middle value between specific positions can be
determined. Up to a maximum of 4 measurement variables can be saved. It is also possible record a
variable relative to the end of a movement.

Select the variable and the required type of measurement value recording. Then define the required
position or start and end point of the measurement value recording. The measurement values can be
recorded as “absolute” or “relative”. If relative measurement value recording is selected, the reference
measurement is taken as the position the press module is located in when the function is called.

To record a value relative to the end of a movement, please choose “Behind position”. Enter the
distance as a positive relative number. When the end of the next movement is reached, the value will
be recorded relative to the postion of these step. If you choose “Behind position” you have to program
these step always just before the movement you want to gauge the value.

The recorded measurement variables can be monitored using upper and lower limit values. The “OK“
or “NOK“ evaluation occurs independently of any limit curve monitoring. In the “NOK” case, the display
of the measurement variable has an orange background.

30
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

The values are, if the step is monitored, saved together with the relevant limits from the limit curve.

You can transmit the values as follows:

• In an ASCII text file (the values are overwritten after every cycle)
• Via the fieldbus system (Profibus DP, CAN Open, Interbus - S)
• In the program-internal database

12.1.1 Save measurement values as ASCII data


To save the ASCII data, please activate the data export under "Configuration / file settings"

The data are saved in the selected directory under the following name:

Sn_Programname_Gn

Sn = Station number n
Gn = Measurement variable n

The file is structured as follows: Measurement


value

# SPosition EPosition APosition UL AValue LL


1 33.00mm 34.00mm 33.42mm 2300N 2178N
2100N

Start position End position Actual position Upper limit Lower limit
where the value
is recorded

31
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

12.1.2 Save measurement values via Profibus DP, CAN Open, Interbus - S .

The data within the Promess program are saved in Microsoft Access format and can be
edited/evaluated at any time with the Access program.

The values recorded using the function “Measure“ can also be transmitted as measurement variables
via the bus systems (for further details, see bus system manuals)

12.1.3 Save measurement values in database

The requirements for data storage are as follows:

Pentium class PC.


MS Access or DAO 3.5 / 3.6 driver installed (available from Promess).
Data storage facility to hold the database, or
LAN network installed with relevant server.
At least one press module actively connected with the PC.

To store measurement values in the database, you must activate data storage under the Service /
Program parameter in the register card “Data storage”.

Selection of data
path

32
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
The data path for the data to be stored can be set using the buttons. This gives you the choice of
saving the data locally or decentrally in a network (LAN). For decentralised data storage, the
connected PC must have the relevant network card. It can also be specified at this point whether each
station (if more than one present) should write to a central file or to an individual database. It must be
noted, however, that the data may be stored and distributed across the local hard drive and than one
must save several files. The database itself offers the opportunity of being used by many stations
simultaneously.

The measurement values are saved with the data, time, actual position, force value or signal value. If
the movement to the selected position is also monitored then the limit values are also written to the
database.

• The data volume to be transmitted or saved can be influenced by using the following switches:

• Save measurement values: The values recorded with the function “Measure“ are saved in
the database

• Save curves: The curves recorded with the function “Monitor“ are saved in the
database

• Always load curve from station: The transmission of the curves from the station
always occurs. The switch “Curves” determines whether
the curve is only displayed graphically or also saved in
the database.

• Only load curve from station in case of error: The curves are only transmitted from the
station if an “NOK” occurs

If the database is activated, the status data of the cycle are always saved.

Leave the window with “OK“

If a database is not present, the following message appears:

Reply with “OK“ to create a database.

12.1.4 Database maintenance

The size of the database is generally limited to 650 MByte. Further on you can limit the size by time
and by number of entrees. When a limit is reached, a new database is produced. The name is of the

33
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
database is extended by a counter. The data are always a stored in the datbase with the highest
number. Please enter a zero to stop a creating databases by time or number.

12.1.5 Database Structure

The database is divided into three tables:

1. Data
2. Curves
3. Measurement Values

The tables are linked by the cycle ID.

34
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

* Data type: 0 = X-value upper limit


1 = Y-value upper limit
2 = X-value lower limit
3 = Y-value lower limit
4 = X-value actual value
5 = Y-value actual value

** Status binary codes:

Bit 1 (1) = Overload


Bit 2 (2) = Reference Error
Bit 3 (4) = Force or signal too early (i.e. the switch-off force was exceeded during
the pre-positioning)
Bit 4 (8) = No force and/or signal within the set range
Bit 5 (16) = Emergency-off
Bit 6 (32) = Upper limit of the envelope curve exceeded
Bit 7 (64) = Lower limit of the envelope curve exceeded
Bit 8 (128) = Tracking error
Bit 9 (256) = Force transducer outside the permitted offset area

35
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
(This message means that the zero point of the force transducer was
shifted by more than 10%. This was probably caused by an overload.
The joining module cannot be loaded anymore to the nominal load.
Please perform an immediate re-calibration of the transducer).
Bit 10 (512) = Maximum travel range exceeded
Bit 11 (1024) = Not used
Bit 12 (2048) = AD converter has reached maximum value
Bit 13 (4096) = Start signal was cancelled during the movement
Bit 14 (8192) = Not used
Bit 15 (16283) = Not used
Bit 16 (32768) = Status manual set

12.2 Call up saved measurement values

To recall saved values, select “Data call” in the “File” menu or actuate the corresponding button.

Measurement
value
Database call up

Filter

Cycle data

The following database view is opened.

Values from
the function
“Measure”

The data from all connected stations are stored in the sequence of their occurrence in time. The
window that displays the measurement values only opens if you have used the function “Measure“ in
your program. To update the values, actuate the “Cycle data“ button. Use the “Measure“ button to
show all values that have been collected using the “Measure” function.

To navigate within the database, you can either use the scroll bars on the side and at the bottom, or
use the navigator buttons (arrow keys) at the bottom of the PC screen.
Cycle data
Previous record Next record
36
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

Jump to end of database.


Jump to start of
database

• Database filters

To display a reduced amount of data from a station or program you must define filters.

To define a database filter, use the button in the top symbol bar or in the footer bar. In the new
window, you can set filters to specific values in specific columns.

You can filter according to the following criteria:

- Counter
- Cycle ID
- Program ID
- Program name
- Stations ID
- Station
- Date
- Time
- Status
- Identifier
- User

37
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
- NOK
- OK
- Force or signal too early
- No force or signal not reached
- Upper limit broken
- Lower limit broken
- Overload

The filters can be linked with “and” or “or” conditions.

Example:

You want to define the NOK components for a specific program (test2.ppg).

First define the following filter with the program name.

Activate the condition with the “Add” button.

In order to filter with the NOK component of the program test2, select the link “and“ and enter the
condition “NOK = 1“. (You could also filter using “OK = 0 „. 1 stands for the condition “True“, while 0
stands for the condition “Not true“)

Add the condition and then apply the filter. All the NOK components in program test2 are displayed.

38
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

• Show curves

By activating the appropriate control button, the database view also displays the curves and status
information.

39
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

13 Printing

The following print options can be selected:

• Curves report: Printout of graphic with status messages for the displayed step
• Program listing: CNC program
• Stations window: Screenshot

13.1 Printer settings

This menu item for configuring your printer can be reached from the file menu.

40
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

13.2 Printing graphics

The graphic of the currently displayed curve, together with the status of the press operation, are
available using the function “Report“ in the file menu.

41
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

13.3 Printing the CNC program

Use the button “Print“ or the file menu item “Print“ to print out the CNC program.

42
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

14 Service

14.1 Program parameters

The program parameters are retrieved via the menu "Service".

14.1.1 Standard settings

Manual Motion

The standard values for manual mode can be set here.

You can also decide whether inputs/outputs 1 and 2 should be used as standard inputs or as freely
definable inputs/outputs. This selection is only useful if the module is controlled via the Profibus. Inputs
and outputs 1 and 2 are then no longer available in Profibus.

Input "Start Reference run" = Freely prog. input I1


Input "Cycle Start" = Freely prog. input I2
Output "OK" = Freely prog. output O1
Output "NOK" = Freely prog. output O2

43
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

You have different options to save the program in the NC module:

1. In the non-volatile storage (fixed-digit storage: The programs remain stored after the power is
switched off. Storage size: 154 Words).

2. In the volatile storage: The programs are lost after the power is switched off and have to be
reloaded from the PC or the link module after system is switched back on (storage size: 722
words).

Required storage of the individual program steps:

Command No. Of Controlled


Words Words
• Positioning 7 1*
• Press to Force 8 1*
• Delay Period 2
• Program End 1
• Variable 2
• Conditional Jump 2
• Taring 1
• Joining on Signal 9 1*
• Measuring
Individual Value on Actual 1 2
Position
Individual Value on 2 2
Position X
Min, Max, Mean Value 3 2
• Output 2
• Input 2
• Analog Output 2
• Status 1

* every point of the upper / lower envelope curve needs one additional word

• Ethernet module text


To describe a station, please enter the text here. This text is shown in the respective station window.

Ethernet module text

44
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

14.1.2 Program settings

Use this register card to set the press unit nominal values for position, acceleration, speed and force.
You can also determine the number of decimal places to display force, distance and additional analog
input values.

14.1.3 Analog Input

In this register card you can define additional virtual analog inputs, which you can use in the function
„Join upon Signal“ and in the „control component“. You can choose between external analog input 1,
external analog input 2, the power input, an incremental transducer and the engine power. You can

45
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
set the physical interface via analog type. Enter also the nominal value and, if necessary, the offset of
your analog source.

14.1.4 Program parameters

On the register card "Program parameters" you enter the offset value of the actual force during teach-
in. The data entry is expressed as a percentage of the nominal load.

• Expansion parameter

This is used to compensate for the expansion of the press frame caused by the force produced during
the positioning process. Input is based on the nominal load. The value is stored related to the active
part program, so you can store different values for different part programs. The compensation is linear.

14.1.5 Graphics

In this menu you can set the colors of the various curves that are going to be displayed.

46
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
14.1.6 Profibus DB participant address

Enter the address you wish to assign to the station.

• Exchange data words


Data word 1 on the Profibus is exchanged with data word 3.

14.1.7 CAN Open

Enter the participant address and the timeout time for the bus.

Select the required baud rate.

• Exchange data words


Use this switch to exchange data word 1 transmitted to the bus with data word 3.

14.1.8 Analog output

47
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
The system has two analog outputs that can be used to output the following values:

• Variables 1 - 4
• Position
• Force
• Analog input

Define the nominal value or the physical output for the respective outputs. Assign these using the
function "Analog output", see Chapter 9.11 Analog output.

48
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

14.2 In / outputs

Use this menu to check the digital inputs and outputs as well as the analog inputs.

14.3 Change station address

If you do not know the station address of the connected unit, you can search for it using the buttons “?
31-1“. Once you have entered the new station address, you can implement changes using the button
“Change station address from n to m“.

49
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

14.4 Parameter NC module

Once the press module is successfully installed, we recommend that the parameter sets of the unit be
backed up. To do this, open the item “Unidrive parameter” in the service menu, then click on the
button “NC->Host“ in the new window to load the NC module values onto the PC.

Then back up the values on floppy disk. Use the “Host->NC“ button to send saved values to the NC
module after the power unit is changed. It is possible to load parameter sets for download to the NC
module using the “Import“ button.

50
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

14.4.1 Service Window Bus Systems

Use this window to check the entered bits or the output bits that are transmitted via the Profibus.
Depending on the levels selected by the PLC, either I/O or variable information is displayed. For
further information regarding the Profibus module, please refer to the Profibus manual.

I/O level

Variable level

51
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

14.4.2 Link Module Inputs / Outputs

Here, you can have the condition of the inputs and/or outputs of the link module displayed. If you want
to set an output, please click on the button.

52
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

15 Register an NC module to the PC

When started, the program scans to determine which modules are connected. This scanning takes
place provided the option “Automatic" has been selected under “Polling of the stations“. (New or
substitute modules are always supplied with station number 31). If you only want to establish a
communication with a single station, you should select “Manual“ in stead of “Automatic".

When a station has been detected, the following station window is opened:

The program stored in the NC module is automatically loaded and displayed.

No communication?

Proceed to configure the communication via the menu option “Configuration" in the menu “File“
(please refer to Chapter 13 "Configuration")

• Select the COM-port number of the interface you are using (baud rate = 19200 Baud)

• Polling error: Check if you have selected the proper COM-port.

15.1 Register a new station


!!! This is only active, if you use the RS232 or RS485. Using the Ethernet module you have to register
the module under „configuration“ (17.1.1 and 18.4.1)

Open this point in the menu “File“


Select the station number you want to open, or select “Auto Poll".

53
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

15.2 Switching Programs

The programs in the NC-module can be switched manually via the PC or via the PLC. If you use the
PC, please open the program, which you would like to send to the NC-module and confirm it in the
following window with „Yes“.

If you want to switch programs via the PLC, you first have to enter the programs in an allocation table,
because the program call via the PLC can only be performed binary code figures.

Program Pre-selection
You can reach the allocation table via the file menu. Select the menu item „Program Pre-selection“, or
the respective button on the task bar.

The allocation is executed by a „double click“ in the column Program Name. Choose the desired
program in the Explorer window that pops up.

For the process for the program change via the PLC see Chapter 20.7 Transfer of program number,
and/or in the description of the used bus system.

54
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
16 Error messages

The following error messages may be displayed in a message window:

• Overload
• Emergency stop
• Reference switch defective

The following coded errors can be displayed in the status bar:

• U = Overload
• R = Reference error
• F = Force or signal too early (i.e. the switch-off force was exceeded during the pre-positioning)
• N = No force or signal within the set path window
• E = Emergency Stop
• UL = Upper limit of generating curve exceeded
• LL = Lower limit of generating curve exceeded
• FE = Contouring error
• T = Force transducer outside permissible offset range.
(This message means that the zero point of the force transducer is displaced by more than 10%.
This is probably due to an overload. The press module can no longer be loaded up to the nominal
load. The transducer should be recalibrated immediately)

These messages will also be output via any connected bus systems or the Link-Module.

55
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

17 Configuration

17.1 Serial communication RS232/RS485

You can set the COM-port and baud rate used on your PC here.

• Polling of the stations

You can also determine whether the stations connected should be automatically registered to the PC
during the program start or if you want to carry out the registration manually. Enter the numbers of the
stations, which will be automatically registered, in the corresponding fields in the registry card.

The following Baud rates are available:


• RS 232 19200 Baud
• RS 485 max. 38400
• Link Module 115kBaud

56
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

17.1.1 Serial communication Ethernet module

Please choose Ethernet for communication.

The connected Ethernet modules are shown, by clicking on the „Find” button. Active modules are
marked by the green LED. Modules which have been connected are still shown, but marked as
inactive. You can choose the stations you want to connect. Only chosen modules are polled by the
software. If you want to delete a station please enter zero as IP address.

The station text is entered in program parameter in the service menu. (chapter 14.1.1)

57
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

17.2 General

Select the language for the UFM software here.

In addition, you can also specify the start settings of the window and the password settings.

17.2.1 Password protection

The following program functions can be password protected:

• Edit program
• Load, save program
• Quit program
• Start movement (reference move, start , step, manual moving)

Call up the password settings in the file menu using “Configuration”. Select the register card “General“.

Default delivery password is “Bach”

Under validity period, enter the period in minutes for which the protected functions are enabled after
the password is entered. Once this period is expired, the password must be entered again.

58
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

17.3 ASCII Data export

• File settings
Data path for ASCII data export

Define the file path of the ASCII data export via the RS232 in the register card “File settings” using the
“File/Configuration” menu. If a warning before the overwriting of data, you have to activate the
respective button.

17.4 Layout (Display Error Messages)

Here, you can minimize the display of the error messages, if you are bothered by the pop-ups. Error
messages are then only displayed in the status line.

59
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
18 Link Module

18.1 Functions Link Module

• 12 Inputs / 12 Outputs
(DC-separated, max. Switching capacity of the outputs: 50mA)

• Storage for 128 NC - Programs

• Connectivity of Joining Modules

!!! The link module cannot be used at the same time as a bus system!

• Inputs / Outputs Function Outputs:

The following functionalities can be assigned to the • 8 freely defined outputs


12 inputs and outputs: A maximum of 8 freeliy 7 inputs for the transfer of a maximum of 128 program
programable inputs and/or outputs for controlling the numbers
process within programs for the UFM NC-module • Transfer interval receipt program No. Strobe Cycle end
and the transfer of process-specific messages to the • Cycle stop
superordinate control. • PC Life (Connection PC - NC Modul = OK)
• IO
Function Inputs: • NIO
• Quit
• 8 freely defined inputs • Overload limit exceeded (E overloaded)
• 7 Inputs for the transfer of a maximum of • Reference run not successful (E reference)
• program numbers • Block force before block window (E force early)
• Transfer interval program No. (Strobe) • Block force not reached (E no force)
• Reference run • Emergency-off (E EmergencyOff)
• Start • Upper envelope curve or upper limit measurement
• Writing variable exceeded (E U limit)
• Stop • Lower envelope curve or lower limit measurement
• Jog + Move stamp out variable exceeded (L O limit)
• Jog – Move stamp back • Nominal force of the joining unit exceeded (E force error)
• PC key-lock • Fuel set outside the permitted range of 10% (E sensor
error)
• Route exceeded the max. permitted position (E Max
position)
• Axis is being adjusted (Being adjusted)

• Linking of NC-Modules

The link module can speed up the communication, when several terminals are connected to a PC, because the
connection to the PC can be run at a higher Baud rate than the connection PC – NC-module. Furthermore, data
that is transferred in several sets can be buffered by the link module, which accelerated the transfer, as there are
no waiting periods due to the slower communication with the NC-module.

60
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

The Baud rate selected in the PC is automatically recognized by the link module.
The following Baud rates link module – PC are available:

9600 Baud, 19200 Baud, 38400 Baud, 57600 Baud, 115200 Baud
(Max. Baud Rate NC-Module 38400 Baud)

• Program Storage

The program storage serves as storage for a maximum of 128 NC-programs for the UFM NC-
module, which can be submitted by the superordinate control. The assignment of the
programs is performed via the allocation table, which is stored in the link module.

Measurements and Terminal


Assignment

Pin Inputs Outputs


1 nc A1
2 nc 24 VDC
3 E1 A2
4 GND A3
5 E2 24 VDC
6 E3 A4
7 GND A5
8 E4 24 VDC
9 E5 A6
10 GND A7
11 E6 24 VDC
12 E7 A8
13 GND A9
14 E8 24 VDC
15 E9 A10
16 GND A11
17 E10 24 VDC
18 E11 A12
19 GND
20 E12

61
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

Outputs Inputs

PowerSupply
supply
Pin 1 = 0 VDC
Clamp 1 = 0 VDC
Pin 2 = 24 VDC
max. Clamp 2 = 24
500mA Linkmodule
VDC
plus consumption external
senor (total max 1A)

RS RS
RS485
485to to
NC-Module
the NC-
RS485
485from
to PC
the PC
M d l

RS 232

62
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
18.2 Configuration Link Module

Please select the respective item in the service menu for the configuration of the inputs / outputs of the
link module.

Firmware Version of the Link Serial Number Link


Module Module

Please choose here the


function, which you would like
to assign to the respective
outputs and/or inputs.

Please set here the desired Baud


rate between link module and NC-
module.

If this button is activated, the compiled process programs are loaded during a program change
from the link module and not from a possibly connected PC, after they were loaded into the link
module (see 18.3)

18.3 Link Module Sending and Loading of Programs


To send a compiled program from the PC to the link module or to load the programs stored in the link
module to toe PC, you have to complete the following steps:
Open the item “Program Pre-select” in the file menu. Assign the set-up programs to the program
numbers. This is performed by double-clicking on the corresponding field in the column program
name. In the next window, choose the file, which you would like to allocate.

The sending (PC>link) and reading (link>PC) of the programs to the link module or from the link
module is performed via the respective buttons.

63
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
To delete a program, please mark it and activate the button to delete the program.

Deleting of
programs

Loading the programs Sending the programs to


from the link module: the link module:

™ If you edit a program on the PC, it is crucial that you re-enter it into the
allocation table.

64
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

18.4 Ethernet-Module
Functions:

• Networking of NC modules

• 12 In-- / 12 Outputs (in preparation)

• Storage of NC – programs (in preparation)

power supply

Pin 1 = 0 VDC
Pin 2 = 24 VDC

RS 232 connection to
RS 485 to NC-Module PC

Ethernet connection to
LAN

65
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

18.4.1 IP Address Ethernet module

To enter the IP address please load the utility „Chip Tool“ that was delivered by PROMESS.

To scan for connected Ethernet modules please call „Find“ at the menu „Chip“.

serial number Ethernet chip

Please note the serial numbers.


Now please call „IP config“ in menu „Chip“ and enter the serial number of the Ethernet chip, IP
address and the net mask.

66
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

67
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

19 Technical appendix

19.1. General description and design

The mechanical parts

Determining features are:


• robust construction designed for a long life even under the most severe operational conditions,
• simple design through the realization of the principle “transparent engineering”.

The following figure shows the design of the unit:

Cog belt drive

Force
transducer

AC – servo motor

Ball screw

Press ram

68
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

19.1.2 Weights Mechanics


Artikelnr. Bezeichnung [kg]
64020 UFM 01/100/400 8,2
74003 UFM 03/100/120 14,4
74005 UFM 05/200/240 27,2
74012 UFM 12/200/240 38,6
74020 UFM 20/180/150 72
74023 UFM 20/350/230 80,6
74040 UFM 40/175/150 141
74043 UFM 40/330/240 158
74060 UFM 60/175/150 141
74065 UFM 60/330/240 178,5
74080 UFM 80/330/240 212,6
74101 UFM 100/330/200 220,6
74151 UFM 150/400/145 370
74243 UFM 240/350/120 395

19.2 Specifications and technical features

Specification Value
Rapid traverse vmax = 150 - 240 mm/s
Time that reference force is kept Thalte > at least 5s.
Repeatability without load: < 0.005 mm,
under constant load: < 0.010 mm,
Play-free ball screw Springing of the press ram under nominal load:
(omits stick-slip and reduces load peaks) 50 – 80 µm,
Spring stiffness: 150 N/µm - 250 N/µm
Capacity of the screw spindle and the Cdyn = 2,5 - 3* nominal load
thrust bearing Cstat = 5 - 6 * nominal load
Useful life At least 25000 operating hours,
Verification through a spindle life calculation is supplied on
request
Safety standard Certificate of compliance
EMC – immunity Motor, choking coil, net filter
Axis control The unit is equipped with a resolver and resolver
interface, the amplifier delivers the usual incremental
signals for NC-axis-controls with the 3 lines A, B, Z
Force measuring Strain-gauges integrated in the press unit
Precision: 0.5 %
Drive unit AC servo motor

19.3 The drive

AC servo motor with resolver, digital servo amplifier, with 380 – 480 VAC / 48 - 62 Hz.
Capacity reserves through ample system dimensioning.

69
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

19.4 Power amplifier


NAME UFM01/100/400 UFM03/100/150 UFM05/200/240 UFM12/200/240 UFM20/180/150 UFM20/350/230 UFM40/175/150 UFM40/330/240
Servo amplifier Unidrive 1401 Unidrive 1402 Unidrive 1403 Unidrive 1405 Unidrive 1404 Unidrive 1405 Unidrive 2402 Unidrive 2402
Construction 1 2
size

NAME UFM60/175/150 UFM60/330/240 UFM80/330/240 UFM100/330/200 UFM150/400/145 UFM100/330/200


Servo amplifier Unidrive 2402 Unidrive 2403 Unidrive 3401 Unidrive 3401 Unidrive 3401 Unidrive 3404
Construction 2 3
size

Size 1:
Unidrive Type 1401 1402 1403 1404 1405
Article number: 0121 01220123 0124 0125
Nominal unit capacity / kVA *) 1.4 1.9 2.6 4.0 6.6
Max. motor nominal capacity / kW 0.75 1.1 1.5 2.2 4.0
Max. motor nominal capacity / HP 1.0 1.5 2.0 3.0 5.0
Nominal unit current / A 2.1 2.8 3.8 5.6 9.5
Max. unit current during 60 sec. / A 3.2 4.2 5.7 8.4 14.3
Max. unit current during 4 sec. / A (closed loop only) 3.7 4.9 6.7 9.8 16.6
Unit input current / A 5.4 5.9 6.3 7.1 9.5
Recommended cable cross-section / mm2 2.5
Usable cable cross-section / mm2 2.5
Mains voltage 50 / 60 Hz 3 AC 380V to 480V +/- 10%, 48 – 62 Hz
Unit output voltage 3 AC 0V .... U net
Recommended mains fuse (slow) / A 6 10 10 10 16
Losses / W at 12 kHz frequency 70 90 100 150 250
Ventilation integrated fan
Weight 4 kg
Protection class IP 40

Size 2:
Unidrive Type 2401 2402 2403
Article number: 9642 - ... 0126 0127 0128
Nominal unit capacity / kVA *) 8.3 11.0 17.0
Max. motor nominal capacity / kW 5.5 7.5 11.0
Max. motor nominal capacity / HP 7.5 10.0 15.0
Nominal unit current / A 12.0 16.0 25.0
Max. unit current during 60 sec. / A 18.0 24.0 37.5
Max. unit current during 4 sec. / A (closed loop only) 21.0 28.0 43.8
Unit input current / A 13.7 16.8 27.0
Recommended cable cross-section / mm2 2.5 4.0 4.0
Usable cable cross-section / mm2 4.0
Mains voltage 50 / 60 Hz 3 AC 380V to 480V +/- 10%, 48 – 62 Hz
Unit output voltage 3 AC 0V .... U net
Recommended mains fuse (slow) / A 16 20 35
Losses / W at 12 kHz frequency 300 390 470
Ventilation integrated fan
Weight 8 kg
Protection class IP 40

Size 3:
Unidrive Type 3401 3402 3403 3404 3405
Article number: 9642 - ... 0131 0132 0133 0134 0135
Nominal unit capacity / kVA *) 23.0 27.0 32.0 41.0 53.0
Max. motor nominal capacity / kW 15.0 18.5 22.0 30.0 37.0
Max. motor nominal capacity / HP 20.0 25.0 30.0 40.0 50.0
Nominal unit current / A 34.0 40.0 46.0 60.0 77.0
70
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
Max. unit current during 60 sec. / A 51.0 60.069.0 90.0 115.5
Max. unit current during 4 sec. / A (closed loop only) 59.5 70.080.5 105.0 134.8
Unit input current / A 34.0 39.049.0 59.0 74.0
Recommended cable cross-section / mm2 6.0 10.010.0 16.0 25.0
Cable connection M8 - screws
Mains voltage 50 / 60 Hz 3 AC 380V to 480V +/- 10%, 48 – 62 Hz
Unit output voltage 3 AC 0V .... U net
Recommended mains fuse (slow) / A 35 50 60 70 80
Losses / W at 12 kHz frequency 500 *) 620 *) 730 *) 890 *) 940 **)
Ventilation integrated fan
Weight 22 kg
Protection class IP 40

*) at 6 kHz frequency
**) at 3 kHz frequency

71
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

19.5 Force measuring

Force measuring is done using strain gauges integrated in the press unit. The advantage of this
arrangement is that there are no moving cables and the connection cables can be placed outside of
the operating area.

The nominal values of the force transducers may change, due to the mounting conditions, therefore
each transducer is calibrated after assembly. The calibration result is documented in a test protocol.

Technical data of the force transducer:

Precision class: 0.5 %*


Input voltage: 10 V
Bridge resistance: 352 Ω
Reference temperature: 23 oC
Nominal temperature -20 ...+60 oC
range:
Zero signal: < 3%*
Limit load: 150 %
Burst load: 500 %

* all percentages stated are related to the nominal load

• Pin assignment:

Input voltage + brown


Input voltage - yellow
Data + +green
Data - white
Shield black

19.6 Distance measuring


Distance measured with resolver on motor.

The resolver transmits a sine-formed signal, which is transformed into an incremental signal in the
power amplifier. This signal is in turn output from the power amplifier in the form of a differential signal
i.e. the usual tracks A, B and C and their inverted signals are available.

Alternatively, distance measuring may be done by means of an integrated scale (magnetic or optical).

Resolution with resolver: 2.5 µm, magnetic scale: 5µm, optical scale: < 1µm.

72
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

19.7 Electrical connections

If you have acquired the press unit in the form of components without the mounting plate,
please refer to the user manual of the Unidrive power supply for data on the electrical
connections.

The optionally supplied connection cable set must be connected according to the numbering key.
!! Preferably install the motor cable in a conduit, separated from the data cables.
• Input voltage 380 – 480 VAC / 48 - 62 Hz

Fuses:
Press modules Fuses Cable cross-section
UFM 01/100/400 6A/K 1,5 mm2
UFM 03/100/120 10 A / K 2,5 mm2
UFM 05/200/240 10 A / K 2,5 mm2
UFM 12/200/240 16 A / K 2,5 mm2
UFM 20/180/150 10 A / K 2,5 mm2
UFM 20/350/230 16 A / K 2,5 mm2
UFM 40/175/150 20 A / K 4 mm2
UFM 40/330/240 20 A / K 4 mm2
UFM 60/175/150 20 A / K 4 mm2
UFM 60/330/240 35 A / K 4 mm2
UFM 80/330/240 35 A / K 6 mm2
UFM 100/330/200 35 A / K 6 mm2
UFM 150/400/245 35 A / K 6 mm2
UFM 240/350/120 70 A / K 16 mm2

Connection 220 VAC

Fuse: 4A

Cable cross-section: 1.5 mm2

73
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

19.8 SG pre-amplifier
The force transducer is driven by an analog SG pre-amplifier.

Technical data:

Precision class 0.2%


Nominal resolution 1 mV/V
Fine-tuning range of the nominal resolution ±20 %
Input voltage for the SG bridge 10 VDC
Signal output 0 - 20 mA
Temperature coefficient:
- of the zero point < 0.07 %
- of the amplification < 0.07 %
Power supply:
- Voltage range 19 ... 28 VDC
- Current consumption ca. 35 mA
Operating temperature range -25 ...+60 oC
Storage temperature range -40 ...+70 oC
Protection class according to DIN 40050: IP 40

Pin assignment

Force Transducer
1 - Supply - (ye)
3 2 - Supply + (br)
2 4 3 - not used
6 4 - Bridge + (gr)
1 5 5 - Bridge - (wt)
6 - not used
description of contact pins

Offset Gain
0 BA 604 V
1 - Supply 0V (wt)
3 2 - Supply 24V (gr)
4 2 3 - not used
4 - Out 20mA (br)
5 1 5 - Out 0mA (ye)

Output / Supply Voltage

74
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

19.9 Transducer calibration

The integrated SG transducer can be calibrated in various ways. You can use a reference
transducer or a spring with known and constant spring characteristics. You can calibrate the
electronics using a calibration resistor connected to the system.

Sequence of operations to calibrate the system:

Note: The hints, concerning the calibration, are kept very general and must be understood as
an aid only. The sequence of operations described may cause damage to the press unit, the
adapters or parts, depending on the offset of the reference point, the type of tool and part
adapters used.

PROMESS accepts no responsibility for damages occurring during calibration.

• Press the Emergency Stop,


• Install the reference transducer in the adapter. Ensure that the nominal load of the reference unit
corresponds to the permissible load of the press unit,
• Release the Emergency Stop,
• Make a reference positioning,
• Select the register card "Sensor input" in the system configuration to verify the permissible load,
• Exit from the menu and select the manual mode of the press unit (F5),
• Position the unit close to the reference transducer,

Verify the zero point of the analog signal. To do this, toggle to the service menu and select the point
Inputs/Outputs.

Digital display force


(Channel 1): 0 – 4000

!! Zero point = 2000

Adjust if necessary to the value 2000 with the potentiometer P2 (zero point displacement).
(See diagram of amplifier)

Change to manual travel (F5)

75
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
Before applying a load, set the speed to a very low value (e.g. 0.5 mm/s)
Travel in small steps to ca. 80 % of the nominal load. Keep an eye on the force display in the
right half of the window.

Warning! If you reach the overload limit, an Emergency Stop is triggered.

Adjust the amplifier using the potentiometer P1 (amplification) until the display of the press unit is the
same as the display of the reference transducer. Move the unit back.

Warning: Please avoid staying in this position for too long at higher loads.
Relieve the unit during the adjustment procedure.

Repeat this step until you are certain that the system is correctly calibrated.
Move the unit to the reference position.
Disengage the Emergency Stop and remove the reference transducer.

To calibrate the unit on a regular basis, PROMESS recommends that a calibration program be
created.
This program could appear as follows:

Program step Function Description


1 Positioning Position just before reference
transducer
2 Press to block Application of specific force
3 Holding period 2 s Recording of applied force
4 Positioning Return of unit

Location of the adjustment potentiometer


Amplification
P1

Zero point displacement P2


80 mm
65 mm

60 mm

Output
76
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS
19.10 Wheight of toools

The maximal allowable weight for the assembly units can be taken from the table below:

Artikelnr. Bezeichnung Nennlast (kN) Gewicht (kg)


64002 UFM01 1 0,5
74003 UFM03 3 2
74005 UFM05 5 5
74012 UFM12 12 8
7402X UFM20 20 20
7404X UFM40 40 20
7406X UFM60 60 50
7408X UFM80 80 80
741XX UFM100 100 and higher 100

If the weights are higher, you have to to add a holding brake to the unit, to avoid the bagging of the
ram in case of lost power. Stempel

77
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

19.11 Integration of a holding break into the control

The break must be integrated into the control due to the function. The holding break should only be
used, when heavy tools are needed for the assembly operation. Tools with extreme weight might
cause the ram, to move downwards in case, the axis is not in control-loop (disabled).

Precaution:
The holding break cannot be used to reach higher safety demands, e.g. due to EN954-1, cat. 4. In
these cases, a mechanical safety break with integrated monitoring functions must be used.

When must the break be activated?

The break must hold the ram of the assembly unit in position, when:

• The emergency-circuit is opened (e.g. when the protecting door with safety switches is
opened or the red emergency button is pressed down),
• The drive is disabled or switched off,
• The drive has an internal fault and is disabled (control-loop is off).

PROMESS provides a PROFIBUS-output for these cases:

“DRIVE-DISABLE”

When this output is set, the break can be activated.

Technical data of the break

The break is a permanently-exitated single-disk-break, which is operated with direct current.

Nominal current: 0,75A.

Protecting circuit:

Due toe the inductivity of the break voltage preaks will be occur, when the break is disactivated
(current is switched off). The voltage can reach 1000 V. To avoid these peaks, a protecting circuit
should be used.
PROMESS recommends to use a Varistor R - type 069-X3022.

+
Switching contact

UN

R
holding break
-

Precaution: As the holding break is a permanent-magnet-break, the right polarity has


to be regarded, when the break is wired.
78
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

20 PLC Interface

1. Remarks

The interface is designed to ensure a complete handshake, so that times do not have to be
programmed or considered for the signal transmission.

2. Acknowledgement

The output signal "Ack." is used to confirm "System ready" and to acknowledge the detection of a PLC
signal.

3. Signal description

Signal Function Meaning


Reference motion Input Start of reference motion
Cycle start Input Cycle start
OK Output Part OK and cycle end
NOK Output Part NOK and cycle end
Ack Output Acknowledgement signal
Reference request Output Reference request from the NC module
OK/NOK Outputs Program interruption / cycle stop

20.1 Reference motion after start-up

Reference request

Ack

Reference motion start

Description

• After a start-up of the NC module, the reference request and Ack are set
• The PLC sets the signal reference motion,
• The NC module acknowledges the signal by resetting the Ack signal,
• The PLC resets the signal start reference motion, when the signal reference request has been
reset by the NC module,
• The NC module confirms that the signal start reference motion has been reset, by setting the Ack
signal.

If the signal start reference motion is cancelled during execution of the command, the PC stops the
reference motion and the signal reference request remains set.

79
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

20.2 Reference motion without a request

Reference request

Ack

Reference motion

Description

• The PLC sets the signal reference motion,


• The NC module confirms the signal by resetting the Ack signal and setting the signal reference
request,
• The PLC resets the signal start reference motion, when the signal reference request has been
reset,
• The NC module confirms that the signal start reference motion has been reset by setting the Ack
signal.

If the signal start reference motion is cancelled during execution of the command, the PC stops the
reference motion and the signal reference request remains set.

80
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

20.3 Cycle start

Description
Home request

ts 4
Life Bit

1
Start

2 5
Ack

OK
3
NOK

ta tprg tb

• The PLC sets the start signal


• The NC module confirms the signal by resetting the Ack signal and resetting OK or NOK
• The PLC detects the cycle end through the signal OK or NOK
• The NC module confirms the start-signal reset, by setting the Ack signal

If the signal start is cancelled during the program cycle, the NC module stops the motion and the
signals Ack, OK and NOK are set.

20.4 Emergency Stop during a motion

Emergency-Stop

Ack

Start

Ref-request

Description

• In the case of an Emergency Stop, the Emergency Stop chain is opened,


• The press unit reacts by stopping the motion,
• The PLC resets the start signal, when an Emergency Stop situation is detected,
• After clearing the Emergency Stop situation, the PC confirms the flank change of the Emergency
Stop signal after the start-signal has been reset,

81
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

20.5 Emergency Stop during standstill

Emergency-Stop

Ack

Description

• In the case of an Emergency Stop, the Emergency Stop chain is opened,


• The NC module confirms by resetting the Ack,
• Closing of the Emergency Stop chain is responded to by setting the Ack.

82
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

20.6 Cycle Stop

Ref. request.

ts
L Bit
4
1
Start
5

2
Quit
3
OK

NOK
6

Cycle stop
tsch
ta
tb

ta >= 10ms, tb >= 20ms, tsch = Duration of program step to cycle stop

ts = Save data in database

Description
The PLC sets the start signal when live bits are present and no reference request is present.
The NC module acknowledges the signal by resetting the acknowledgement.
The PLC recognizes the cycle stop from the OK or NOK signal plus Quit or from the signal cycle stop.
(This signal is only available via the bus system or the expansion module)
The PLC resets the start signal.
Setting the start signal again continues the cycle.
The outputs OK or NOK plus Quit are reset.

83
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

20.7 Transfer of program number

E Start

E Reference start

E Prog. Bit 1

E Prog. Bit 2
1

E Prog. Bit n

2 4
E Strobe

A Prog. Bit 1

A Prog. Bit 2
3

A Prog. Bit n

5
A Strobe Prog.
tb
tload ta

ta >= 10ms, tb >= 20ms, tload = Program load time

Description:
Assignment of binary coded program number
Set strobe for transfer
Reflection of program number
Strobe acknowledgement after program loaded
Reset strobe of PLC and NC module

84
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

21 Lubrication advice
Preliminary Remarks

All electro-mechanical presses from PROMESS must be re-lubricated. Over-lubrication should be


avoided, however, damage to the bearings due to overheating caused by over-lubrication is not to be
expected. Over-lubrication as no negative consequences.

Lubrication Points

The following components are lubricated ex works:

• The gliding guides: Lubrication Points A and B,


• The ball screw: Lubrication Point C,
• The thrust bearing: Lubrication Point D.

AMOUNT OF LUBRICANT FOR LUBRICATION POINTS A AND B: Approx. 1 sq cm

The lubrication points A and B consist of two opposite lubrication fittings in the centre of the press
casing.

AMOUNT OF LUBRICANT FOR LUBRICATION POINT C:

Lubrication point C is located behind the seal cap M20*1,5. To re-lubricate the ball screw nut,
complete the following steps:

• Remove the cover flap,
• manually move the spindle slowly downwards, until you see the lubrication opening on
the now open drill hole.
• Please screw in the lubrication fitting

Type threat
UFM 3 - 12 M6
UFM20-150 M8 × 1
UFM 240 mounted

• Now you can be re-lubricate with a lubrication press.

85
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS
AMOUNT OF LUBRICANT FOR LUBRICATION POINT D:

The thrust bearing – especially on the units starting at 20kN nominal load – must be lubricated very
carefully. As from the lubrication fitting to the rolling body running path also hollow spaces have to be
filled, the following lubricant amounts are necessary:

Type C [sq cm] D [sq cm] Interval [strokes]


2 000 000
UFM 01 0,15 *
2 000 000
UFM 03 – UFM 05 0.3 0.3
2 000 000
UFM 12 0.6 0.8
700 000
UFM 20 / 30 1 1
700 000
UFM 40 – UFM 100 1.8 2

* Lubrication fitting behind the front cover

Thread for lubrication fitting

Type Thread Thread extension


UFM 03 / 05/ 12 / 20 / 30 M6
UFM 40 / 60 / 80 / 175 /150 M8 * 1
UFM 40 / 60 / 80 / 330 /240 M8 * 1 M6
UFM 100 / 330 /200 M8 * 1 M6
UFM 150 / 400 / 145 M8 * 1
UFM 240 / 350 /120 M8 * 1

Lubricant
A high-quality roll bearing lubricant must be used.
PROMESS recommends the following lubricant brands:
Klüber - ISOFLEX NBU 15, Klüber - ISOFLEX NCA 15, FAG ARCANOL and comparable types.

86
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

A B

377.5
253.5

253.5
30° 30°

A C
D
Schmierstellen:
A - Nutschmierung
B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung

mittel Ges. für Montage- und


PROMESS Prüfsysteme mbH
DIN 7168
Schaffhausener Str. 52 D-12099 Berlin Telefon 030/628872-0
Bearb. 12.02.04 Paulsen Maástab

Gepr. 10.02.04 Lechler Schmiermöglichkeiten


Norm
UFM 05/200 1:5
Werkstoff, Halbzeug

74005
Maß AO AU 74005

87
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

A B

C
418

391
247

247

D
C
A
Schmierstellen:
A - Nutschmierung
B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung
B
45°

mittel Ges. für Montage- und


PROMESS Prüfsysteme mbH
DIN 7168
Schaffhausener Str. 52 D-12099 Berlin Telefon 030/628872-0
Bearb. 14.10.03
Paulsen Maástab

Gepr. 14.10.03
Lechler Schmiermöglichkeiten
Norm
UFM 12/200 1:5
Werkstoff, Halbzeug

74012
Maß AO AU 74012

88
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

Initiator ohne
mech. Endschalter

Initiator mit
mech. Endschalter

A B

614
538.5
513.5

425.5

425.5
60°
A
Schmierstellen:
A - Nutschmierung
30°

B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung

D C 60°

Ges. für Montage- und


DIN-ISO PROMESS Prüfsysteme mbH
2768-m
Nunsdorfer Ring 29 D-12277 Berlin Telefon 030/628872-0
Bearb. 03.03.05 Paulsen Maßstab

Gepr. 03.03.05 Lechler Schmiermöglichkeiten


Norm
UFM 20/350/230 1:5
Werkstoff, Halbzeug

74023
Maß AO AU 74023

89
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

D
Initiator ohne
mech. Endschalter

Initiator mit
mech. Endschalter

A B

524
448.5
423.5

335.5

335.5
60
°
A
Schmierstellen:
A - Nutschmierung
30°

B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung

D C °
60

Ges. für Montage- und


DIN-ISO PROMESS Prüfsysteme mbH
2768-m
Nunsdorfer Ring 29 D-12277 Berlin Telefon 030/628872-0
Bearb. 09.02.06 Paulsen Maßstab

Gepr. 09.02.06 Lechler Schmiermöglichkeiten


Norm
UFM 20/180/150 1:5
Werkstoff, Halbzeug

74020
Maß AO AU 74020

90
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

D
Initiator ohne
mech. Endschalter

Initiator mit
mech. Endschalter

A B

524
448.5
423.5

335.5

335.5
60
°
A
Schmierstellen:
A - Nutschmierung
30 °

B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung

D C °
60

Ges. für Montage- und


DIN-ISO PROMESS Prüfsysteme mbH
2768-m
Nunsdorfer Ring 29 D-12277 Berlin Telefon 030/628872-0
Bearb. 09.02.06 Paulsen Maßstab

Gepr. 09.02.06 Lechler Schmiermöglichkeiten


Norm
UFM 30/180/230 1:5
Werkstoff, Halbzeug

74021
Maß AO AU 74021

91
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

92
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

B A

C D A
Gesellschaft für produktions-
PROMESS techn. Messen GmbH
Schaffhausener Str. 44-50 D-12099 Berlin Tel.: (030) 628935-0

Bearb.
Gepr.
23.6.97 Kreibich
Fügeeinheit 40 / 60kN Maßstab

Norm
180mm Hub
Schmiermöglichkeiten
1:2
Werkstoff, Halbzeug
74040 / 74060
Maß A O AU 98500503

93
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

A B

620
404
374

374
30°
C
A D
Schmierstellen:
A - Nutschmierung
B - Nutschmierung
C - Spindelschmierung
D - Lagerschmierung

B
30°

Um die Spindel zu schmieren, muß die Presse um ca. 117 mm ausgefahren


werden. Dieser Wert kann um ± 3 mm variieren, da der Näherungsschalter nicht
bei jeder Presse an der gleichen Stelle vom Stempel bedämpft wird.

mittel Ges. für Montage- und


PROMESS Prüfsysteme mbH
DIN 7168
Schaffhausener Str. 52 D-12099 Berlin Telefon 030/628872-0
Bearb. 06.11.03
Paulsen Maástab

Gepr. 06.11.03
Lechler Schmiermöglichkeiten
Norm
UFM 80/330 1:10
Werkstoff, Halbzeug

74080
Maß AO AU 74080

94
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

21.1 Gear box oil

For those press modules containing a gearbox, the oil must be changed after 5,000 operating hours or
at latest after 4 years.

Type of gear box Typ UFM Quantity Oil

MPS 0 UFM 20/180/150 40 ml Klüber, D68EP

MPS 1 UFM 40/175/150 125 ml Klüber, D68EP

UFM 60/175/150

MPS 2 UFM 80 300 ml Klüber, D68EP

UFM 100

95
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

22 Software Update

If you update the software in the PC, it will also be necessary to overwrite the firmware in the NC-
module with a newer version. This will be necessary if the PC software displays the following message
after restarting:

!!! The firmware can only be updated using the RS 232 interface (Com 1 - 4).
If the PC and the module are connected via the RS 485, you will also require connection via the RS
232.

Start the program "UFM_UPDATE.EXE" in the installation directory "UFM_NC.EXE". You will see the
following start window.

Create the connection to the NC module by clicking on the "Find" button. Once the program has found
the station, the "UPDATE" button is activated.

!!! Please shut down the UFM NC Module software, or disconnect the station you want to update.

If you use the Ethernetmodule please choose the IP adress of the station you like to update.

Before continuing with "Update", please press the Emergency Stop button to disconnect the motor
from the power component.

96
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3
PROMESS

Select the file "Node_1.BFH“ in the following dialog box to download the firmware to the NC module.

Once selected, the software will initiate the download of the system files or binary coded firmware.

Once download is successfully completed, close the program.

! After the successful update, it is essential to back up your parameter set.

97
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Modul V3
PROMESS

• Index
Acknowledgement ................................................ 79 Pin assignment..................................................... 72
Analog inputs........................................................ 14 PLC interface........................................................ 79
Analog output ................................................. 24, 47 Polling of the stations ........................................... 56
Analoge Input ....................................................... 45 Positioning............................................................ 16
ASCII data export data path ................................. 59 Power amplifier..................................................... 70
Baud rate .............................................................. 56 Press to Force ...................................................... 17
Cable cross-section .............................................. 73 Press to signal...................................................... 19
Calibration ............................................................ 21 Printer settings ..................................................... 40
CAN Open ............................................................ 47 Printer setup ......................................................... 40
Conditional jump................................................... 22 Printing graphics................................................... 41
Configuration ........................................................ 56 Printing the CNC program .................................... 42
Configuration Link-Module.................................... 63 Profibus DB participant address ........................... 47
Contents of supply.................................................. 5 Program end......................................................... 23
Control of external signal ...................................... 20 Program parameters........................................43, 46
Correct usage ......................................................... 7 Program pushbuttons ........................................... 13
Cycle Stop ............................................................ 83 Program settings .................................................. 45
Cycle Stop ............................................................ 83 Program start........................................................ 11
Database filters..................................................... 37 Program window................................................... 12
Database maintenance......................................... 33 Programming........................................................ 15
Database Structure............................................... 34 Pushbuttons ......................................................... 13
Delay time............................................................. 21 Record measurement values................................ 30
Dialog window ...................................................... 25 Register a new station .......................................... 53
Distance measuring.............................................. 72 Register an NC module ........................................ 53
Drive ..................................................................... 69 Register measuring values ................................... 27
Edit limit curves .................................................... 29 Safety precautions.................................................. 7
Error messages .................................................... 55 Save measurement values as ASCII data ............ 31
Error messages / Link-Module.............................. 60 Save measurement values in database................ 32
Ethernet-Module ................................................... 65 Save measurement values via bus systems......... 32
Expansion parameter ........................................... 46 Screen settings..................................................... 12
Filters.................................................................... 37 Serial communicationRS232/RS485 .................... 56
Force - distance - development ........................... 27 Serielle communikation Ethernetmodule .............. 57
Force measuring................................................... 72 Service ................................................................. 43
Force transducer outside permissible offset ......... 55 Set outputs ........................................................... 24
Force transducer outside the permitted offset area Set status ............................................................. 25
......................................................................... 35 SG pre-amplifier ................................................... 74
Functions Linkmodule........................................... 60 Signal description PLC interface .......................... 79
Fuses.................................................................... 73 Signal flow cycle start ........................................... 81
General description and design ............................ 68 Signal flow during Emergency Stop during standstill
Graphics colours curves ....................................... 46 ......................................................................... 82
I/O Configuration .................................................. 43 Signal flow Emergency Stop during a motion ....... 81
In / outputs............................................................ 49 Signal flow reference motion after start-up ........... 79
Integration of a holding break into the control....... 78 Signal flow reference motion without a request .... 80
Introduction............................................................. 4 Signal process of Emergency Stop during standstill
IP address Ethernetmodule .................................. 66 ......................................................................... 84
Language.............................................................. 58 Software installation ............................................. 10
LEDs..................................................................... 13 Software Update................................................... 95
Link Module Sending and Loading of Programs ... 63 Start settings of window........................................ 58
Linking of NC-Modules ......................................... 60 Station address .................................................... 49
Link-module .......................................................... 60 Switching Programs.............................................. 54
Linkmodule Inputs- / Outputs................................ 52 Teach-in strategy.................................................. 16
Lubrication advice................................................. 85 Technical appendix .............................................. 68
Main window......................................................... 12 Technical features ................................................ 69
Manual operation.................................................. 14 Transducer calibration .......................................... 75
Manual positioning................................................ 14 Transport ................................................................ 6
Manual registration ............................................... 56 Type of Memory Programs in the NC Module ...... 44
Measurement variables ........................................ 30 Unidrive Parameter input...................................... 11
Monitoring............................................................. 27 Variables .............................................................. 21
Motion Control ...................................................... 22 Weights Mechanics .............................................. 69
Parameter NC module .......................................... 50 Zoom .................................................................... 29
Password protection ............................................. 58 Zoom grahics........................................................ 29

98
 Promess Montage- und Prüfsysteme GmbH Berlin
UFM NC-Module V3

You might also like