Application
The module 560BOR01 of the RTU560 product line can R01
C01
O01
be used for the control of 16 binary process signals using Microcontroller
Port A
R02
O02
relay contacts. The allocation of an output signal to the 1
R03
RAM 9 R05
O05
R06
RTU I/O bus
O06
following types of signals: CPU
Port D R07
UART R08
pole output Voltage monitoring CMD O08
C02
R17
R13
Characteristics
Binary outputs The binary output unit can execute the following
processing functions on the individual signal types:
Relay contacts are used for the binary outputs. • Control of the command output duration
The 16 outputs are combined into two groups. Each 8 Command monitoring functions:
outputs have a common return. The groups are isolated • (m out of 16) check of the output relays on the module
from one another as well as from the internal electronic. • monitoring of the output bit patterns by reading back
the output state
The supply voltage for the coils of the relays (24 V DC) • switching voltage monitoring (24 V DC coil voltage)
is switched by an internal switching transistor and is before and during output
monitored internally before and during the command • command output duration monitoring
output. During initialization and operation the module executes
a number of tests. If a fault occurs it is reported to the
The command output to the process equipment can be communication unit. All fault conditions impairing the
effected either directly or in conjunction with a command function of the module are displayed as a common fault
output supervision module. The command output signal by a red LED. A failure of the connected module(s)
supervision module covers the (1 out of n) check of the is detected and signalized by the communication unit.
output circuits. Further details can be found in the data
sheet of the command output monitoring module.
Performance criteria A
Current consumption for power supplied via RTU560 Radiated radio-frequency 20 V/m (level x)
backplane Electromagnetic field
5 V DC 120 mA IEC 61000-4-3 Performance criteria A
Ordering information
560BOR01 R0002 1KGT036800R0002
P.O. Box 42 01 30 document without prior notice. With regard Any reproduction, disclosure to third parties or for a Hitachi Energy company.
68280 Mannheim, Germany to purchase orders, the agreed particulars utilization of its contents – in whole or in parts – is
shall prevail. Hitachi Energy does not accept forbidden without prior written consent of Hitachi
any responsibility whatsoever for potential Energy.
errors or possible lack of information in this © 2024 Hitachi Energy
hitachienergy.com/rtu document. All rights reserved