Product datasheet

Specifications

High power contactor, TeSys Giga,


3 pole (3NO), AC-3 <=440V 185A,
standard version, 100…250V wide
band AC/DC coil
LC1G185KUEN

Main
Range TeSys

Range Of Product TeSys Giga

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Contactor

Device Short Name LC1G

Contactor Application Power switching


Motor control

Utilisation Category AC-1


AC-3
AC-3e
AC-4
AC-5a
AC-5b
AC-6a
AC-6b
AC-8a
AC-8b
DC-1
DC-3
DC-5

Poles Description 3P

[Ue] Rated Operational Voltage <= 1000 V AC 50/60 Hz


<= 460 V DC

[Ie] Rated Operational Current 305 A (at <40 °C) at <= 1000 V AC-1
185 A (at <60 °C) at <= 440 V AC-3

[Uc] Control Circuit Voltage 100...250 V AC 50/60 Hz


100...250 V DC

Control Circuit Voltage Limits Operational: 0.8 Uc Min...1.1 Uc Max (at <60 °C)
Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)

Complementary
[Uimp] Rated Impulse Withstand 8 kV
Voltage
Overvoltage Category III

[Ith] Conventional Free Air 305 A (at 40 °C)


Thermal Current
Rated Breaking Capacity 1610 A at 440 V

[Icw] Rated Short-Time Withstand 1.5 kA - 10 s


Current 0.92 kA - 30 s
0.74 kA - 1 min
0.5 kA - 3 min
0.4 kA - 10 min

Associated Fuse Rating 200 A aM at <= 440 V for motor


160 A aM at <= 690 V for motor
315 A gG at <= 690 V

19 Jun 2024 1
Average Impedance 0.00017 Ohm

[Ui] Rated Insulation Voltage 1000 V

Power Dissipation Per Pole 20 W AC-1 - Ith 305 A


6 W AC-3 - Ith 185 A

Compatibility Code LC1G

Pole Contact Composition 3 NO

Auxiliary Contact Composition 1 NO + 1 NC

Motor Power Kw 55 kW at 230 V AC 50/60 Hz (AC-3e)


90 kW at 400 V AC 50/60 Hz (AC-3e)
90 kW at 415 V AC 50/60 Hz (AC-3e)
110 kW at 440 V AC 50/60 Hz (AC-3e)
110 kW at 500 V AC 50/60 Hz (AC-3e)
110 kW at 690 V AC 50/60 Hz (AC-3e)
75 kW at 1000 V AC 50/60 Hz (AC-3e)
55 kW at 230 V AC 50/60 Hz (AC-3)
90 kW at 400 V AC 50/60 Hz (AC-3)
90 kW at 415 V AC 50/60 Hz (AC-3)
110 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
55 kW at 230 V AC 50/60 Hz (AC-4)
90 kW at 400 V AC 50/60 Hz (AC-4)
90 kW at 415 V AC 50/60 Hz (AC-4)
100 kW at 440 V AC 50/60 Hz (AC-4)
110 kW at 500 V AC 50/60 Hz (AC-4)
110 kW at 690 V AC 50/60 Hz (AC-4)
75 kW at 1000 V AC 50/60 Hz (AC-4)

Motor Power Hp 50 hp at 200/208 V 60 Hz


60 hp at 230/240 V 60 Hz
125 hp at 460/480 V 60 Hz
150 hp at 575/600 V 60 Hz

Irms Rated Making Capacity 2310 A at 440 V

Coil Technology Built-in bidirectional peak limiting

Mechanical Durability 8 Mcycles

Inrush Power In Va (50/60 Hz, Ac) 540 VA

Inrush Power In W (Dc) 380 W

Hold-In Power Consumption In Va 12.4 VA


(50/60 Hz, Ac)
Hold-In Power Consumption In W 7.8 W
(Dc)
Operating Time 40...70 ms closing
15...50 ms opening

Maximum Operating Rate 600 cyc/h AC-3


600 cyc/h AC-3e
300 cyc/h AC-1
150 cyc/h AC-4

Connections - Terminals Power circuit: bar 2 - busbar cross section: 25 x 6 mm


Power circuit: lugs-ring terminals 1 185 mm²
Power circuit: bolted connection
Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable
end
Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: push-in 2 0.5…1.0 mm² with cable end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: solid stranded without cable
end
Control circuit: push-in 0.75…2.5 mm² - cable stiffness: flexible with cable end

Connection Pitch 35 mm

Mounting Support Plate

2 19 Jun 2024
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
JIS C8201-5-1

Product Certifications CB Scheme


CCC
cULus
EAC
CE
UKCA
EU-RO-MR by DNV-GL

Tightening Torque 18 N.m

Height 193 mm

Width 108 mm

Depth 193 mm

Net Weight 3.6 kg

Environment
Ip Degree Of Protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106

Ambient Air Temperature For -25…60 °C


Operation
Ambient Air Temperature For -60…80 °C
Storage
Mechanical Robustness Vibrations 5…300 Hz 2 gn contactor open
Vibrations 5…300 Hz 4 gn contactor closed
Shocks 10 gn 11 ms contactor open
Shocks 15 gn 11 ms contactor closed

Colour Dark grey

Protective Treatment TH

Permissible Ambient Air -40…70 °C at Uc


Temperature Around The Device

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 25.500 cm

Package 1 Width 17.000 cm

Package 1 Length 32.000 cm

Package 1 Weight 4.570 kg

Unit Type Of Package 2 S06

Number Of Units In Package 2 6

Package 2 Height 75.000 cm

Package 2 Width 60.000 cm

Package 2 Length 80.000 cm

Package 2 Weight 41.034 kg

19 Jun 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

 Halogen Free Plastic Parts Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

4 19 Jun 2024
Product datasheet LC1G185KUEN

Installation

Installation Videos

TeSys Giga - How to install the auxiliary contact block


TeSys Giga - How to install and remove remote wear diagnosis module
TeSys Giga - How to install mechanical interlock kit
TeSys Giga - How to install cable memory kit
TeSys Giga - How to directly mount LR9G overload relay
TeSys Giga - How to replace control module
TeSys Giga - How to replace switching modules
TeSys Giga - How to assemble reverser solution
TeSys Giga - How to assemble change-over solution

19 Jun 2024 5

You might also like