Transmission Line Protection Principles
Transmission Line Protection Principles
Protection Principles
1. Introduction
Transmission lines are a vital part of the electrical distribution
system, as they provide the path to transfer power between
generation and load. Transmission lines operate at voltage levels
from 69kV to 765kV, and are ideally tightly interconnected for
reliable operation.
There are two methods to account for the phase shift between The other common issue is pulse asymmetry of the carrier signal.
line terminals due to the communications channel delay. One Carrier sets may extend, either the mark (on) or space (of) signals
method is to measure the round-trip channel delay, and shift at the receiving end compared with the originally sent signal.
the local current phase by an angle equal to ½ of the round-trip This diference is measured during commissioning by using
delay time. This method is simple to implement, but creates a oscillography data, and simply entered as a setting in the phase
transient error when the communications channel is switched. comparison element.
In addition, the diferential element will be temporarily blocked
when the communications channel switches, or noise in the In addition, the L60 supports some other methods to improve
communications channel causes communications packet loss. the reliability of protection communications. For short lines with
negligible charging current, the channel delay measurement can
The L90 Line Diferential Relay employs a diferent method, be automated by running a loop-back test during normal system
using synchronous sampling by internally synchronizing the conditions and measuring the diference between the sent and
clocks on each L90. This method achieves high reliability, as the received pulses. The L60 also supports automated check-back of
round-trip channel delay is not vitally important. The diferential the carrier system. Under normal conditions, the relay can initiate
element successfully operates during channel switching or after transmission of and modulate the analog signal to exchange small
packet loss, because the communications packets are precisely amounts of information. This automatic loop-back can replace
synchronized. the carrier guard signal, and more importantly, veriies the entire
communications path, including the relays on both ends.
In the L90, synchronization is accomplished by synchronizing the
clocks to each other rather than to a master clock. Each relay 3.3 Security for Dual-Breaker Terminals
compares the phase of its clock to the phase of the other clocks
and compares the frequency of its clock to the power system Dual-breaker terminal line terminals, such as breaker-and-a-half
frequency and makes appropriate adjustments. The frequency and ring bus terminals, are a common design for transmission
and phase tracking algorithm keeps the measurements at lines. The standard practice is to sum the currents from each
all relays within a plus or minus 25 microsecond error during circuit breaker externally by paralleling the CTs, and using this
normal conditions for a 2 or 3 terminal system. In all cases, an external sum as the line current for protection relays. This practice
estimate of phase error is computed and used to automatically
adapt the restraint region of the diferential element. The time
Relay 1 Relay 2
synchronization algorithm can also use a GPS satellite clock to
f f
compensate for channel asymmetry. The use of a GPS clock is not +
System
Frequency +
normally required, except in applications such as a SONET ring
- -
where the communications channel delay may be asymmetric. Compute
Frequency
Compute
Frequency
f - f1 Deviation f1 f2 Deviation f - f2
When current lows through a dual-breaker line terminal, the line The dual-breaker line terminal supervisory logic essentially
current measured by a relay using external summation matches determines if the current low through each breaker is either
the actual line current only if the two CTs are accurate. The most forward or reverse. Both currents should be forward for an internal
signiicant relaying problem is CT saturation in either CT. The current fault, and one current should be forward and one reverse for an
measured by the relay may contain a large error current, which external line fault. The supervisory logic uses, on a per-phase
can result in the relay operating due to an incorrect magnitude or basis, a high-set fault detector (FDH), typically set at 2-3 times the
direction decision. This incorrect operation may also occur if the nominal rating of the CT, and a directional element for each CT
linear error current of the CTs due to accuracy class is close to the input to declare a forward fault, for each breaker. The logic also
through current level. These errors appear in the measured phase uses, on a per-phase basis, a low-set fault detector (FDL), typically
currents. As a result, relays that calculate the negative sequence set at 1.5-2 times the nominal rating of the CT, and a directional
and zero sequence currents from the measured phase currents element to declare a reverse fault, for each breaker.
may also see errors.
Tripping is permitted during all forward faults, even with weak
Distance: Distance relays applied at dual-breaker line terminals infeed at the dual-breaker terminal. Tripping is blocked for all
are vulnerable to mis-operation on external faults. During a close- reverse faults when one breaker sees forward current and one
in reverse external fault, the voltage is depressed to a very low breaker sees reverse current. During an evolving external-to-
level, and the security of the relay is maintained by directional internal fault, tripping is initially blocked, but when the second
supervision. If one of the line CTs saturates, the current measured fault appears in the forward direction, the block is lifted to permit
by the relay may increase in magnitude, and be in the opposite tripping.
direction of the actual fault current, leading to an incorrect
operation of the forward distance element for an external fault. Line Diferential: Line diferential protection is prone to tripping
due to poor CT performance on dual-breaker terminals, as the
The D90Plus Line Protection System and the D60 Line Distance error current from the CTs is directly translated into a diferential
Relay handles the challenge of dual-breaker line terminals by current. The only possible solution for traditional line diferential
supporting two three-phase current inputs to support breaker relays is to decrease the sensitivity of the diferential element,
failure, overcurrent protection, and metering for each circuit which limits the ability of the diferential element to detect low
breaker. The relays then mathematically add these currents magnitude faults, such as highly resistive faults.
together to form the total line current used for distance and
directional overcurrent relaying. The L90 Line Diferential Relay supports up to four three-phase
current inputs for breaker failure, overcurrent protection, and
Directly measuring the currents from both circuit breakers allows metering for each circuit breaker. The relay then uses these
the use of supervisory logic to prevent the distance element individual currents to form the diferential and restraint currents
and directional overcurrent elements from operating incorrectly for the diferential protection element.
for reverse faults due to CT error. This supervisory logic does
CT 1 saturates
i2 is reduced 10 - 15 pu
i2 i 2
IF + ILine IF + ILine >0.1 pu error with
> 0.1 pu error
CT 1 CT 1 iLine shows incorret
magnitude, direction
iLine iLine Id > 0.2 pu
52 52 52 >0.2 pu error 52
Ir = 10 - 15 pu
Relay Relay Relay L90 NO TRIP
ILine ILine
10 - 15 pu 10 - 15 pu
Id > 0.2 pu
IF IF Ir > 0.2 pu
52 52 52 503 TRIP 52 503
10 - 15 pu
with
CT 2 CT 2 > 0.1 pu error
i1 i1 >0.1 pu error
Figure 3. Figure 4.
Impact of CT saturation on two-breaker line applications Sensitivity of line diferential system for dual-breaker applications.
a) Accurate CTs preserve the reverse line current direction under weak
remote feed.
b) Saturation of the CT carries the reverse current may invert the line
current as measured from the externally summated CTs.
(I ) + MULT • (I )
restraining of the diferential element.
I LOC _ RESTRAINT =
2 2
LOC _ REST _ TRAD LOC _ ADA Phase Comparison: The L60 Line Phase Comparison Relay
supports two three-phase current inputs for breaker failure,
The starting point for the restraint is the locally measured overcurrent protection, and metering for each circuit breaker. The
current with the largest magnitude. This ensures the restraint is relay then uses these individual currents to form the local phase
based on one of the measured currents for all fault events, and angle information for use in the phase comparison scheme.
increases the level of restraint as the fault magnitude increases.
A phase comparison relay operates by comparing the relative
ILOC_REST_TRAD is this maximum current magnitude applied
phase angles of the current from each end of the transmission line.
against the actual diferential characteristic settings. ILOC_ADA is
When the measured current exceeds the level of a fault detector,
the sum of the squares estimate of the measurement error in the
and the phase angles from each end of the line are in phase, the
current, and is used to increase the restraint as the uncertainty of
phase comparison relay operates. For a dual-breaker application
actual measurement increases, such as during high magnitude
using an external sum, the saturation of one CT may cause the
fault events and CT saturation. MULT is an additional factor that
relay current to increase high enough to operate the fault detector.
increases the error adjustment of the restraint current based
Because the current from the unsaturated CT predominates in this
on the severity of the fault event and the likelihood the fault is
waveform, the phase angle of the relay current may change. If the
an external fault, when CT saturation is most likely to cause an
phase angle of the relay current is in phase with the relay current
incorrect operation.
at the remote end of the line, the relay will trip.
CT 1 CT 1
52 52
52 52
CT 2 CT 2
Figure 5.
Redundancy Requirements - Alternate main protection possibilities from GE Multilin.
Alternative D30-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
V S
3Y 67P 67N 25 79
2
V S
Alternative D60-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
21P 21G 67P 67N 50BF D90P-A-E-S-S-01-S-S-S-X-H-X-A-X-A-X-X-01-X
3 3 + Additional functions Included in typical
V S 25 79 No 50BF in D30
+ Synchrophasors D60-N06-HCH-F8L-H6P-MXX-PXX-UXX-WXX
D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X
Synchrophasors
52
Phasor Measurement Unit
+ Synchrophasors D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X
D60-N06-HCH-F8L-H6P-MXX-PXX-UXX-WXX
G.703 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7S
C37.94 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W77
+ Synchrophasors D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X
3Y 21P 21G 67P 67N 50BF D60-N06-HCH-F8L-H6P-M8L-PXX-UXX-WXX
3 3 2 External electrical sum of D60-N00-HCH-F8L-H6P- MXX-PXX-UXX-WXX
V S 25 79 85 breaker currents (traditional
2 method)
G.703 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7S
C37.94 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W77
+ Synchrophasors L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7K
G.703 L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7S
C37.94 L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W77
+ Synchrophasors
52 L90-N08-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7W
52
87
3Y PC 67P 67N 50BF
Identical relay
2
on other line
21P 21G 25 79 85 terminals
3 3
0925-v5