Schneider Electric - TeSys-Deca-Contactors - LC1D80M7
Schneider Electric - TeSys-Deca-Contactors - LC1D80M7
Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range TeSys
Poles Description 3P
[Ie] Rated Operational Current 125 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
Complementary
Motor Power Kw 22 kW at 220...230 V AC 50/60 Hz (AC-3)
37 kW at 380...400 V AC 50/60 Hz (AC-3)
45 kW at 415...440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660...690 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)
22 kW at 220...230 V AC 50/60 Hz (AC-3e)
37 kW at 380...400 V AC 50/60 Hz (AC-3e)
45 kW at 415...440 V AC 50/60 Hz (AC-3e)
55 kW at 500 V AC 50/60 Hz (AC-3e)
45 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
30 hp at 200/208 V AC 50/60 Hz for 3 phase motors
30 hp at 230/240 V AC 50/60 Hz for 3 phase motors
60 hp at 460/480 V AC 50/60 Hz for 3 phase motors
60 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947
Rated Breaking Capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated Short-Time Withstand 640 A 104 °F (40 °C) - 10 s for power circuit
Current 990 A 104 °F (40 °C) - 1 s for power circuit
135 A 104 °F (40 °C) - 10 min for power circuit
320 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Pollution Degree 3
Tightening Torque Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.21 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm
Power circuit 106.21 lbf.in (12 N.m) connector hexagonal 0.16 in (4 mm)
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Gtin 3389110442571
Returnability Yes
Country Of Origin US
Packing Units
Unit Type Of Package 1 PCE
Contractual warranty
Warranty 18 months
Transparency RoHS/REACh
Well-being performance
Mercury Free
Pvc Free
EU RoHS Declaration
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins.
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide &
Antimony trioxide, which is known to the State of California to cause cancer. For
more information go to www.P65Warnings.ca.gov
Dimensions Drawings
Dimensions
a 85 85
Wiring