Unit - 2 - P.F. Improving Methods
Unit - 2 - P.F. Improving Methods
1. Static capacitor. The power factor can be improved by connecting capacitors in parallel
with the equipment operating at lagging power factor. The capacitor (generally known as static**
* The treatment can be used for 3-phase balanced loads e.g., 3-φ induction motor. In a balanced 3-φ load,
analysis of one phase leads to the desired results.
** To distinguish from the so called synchronous condenser which is a synchrnous motor running at no load
and taking leading current.
Dr. Raju Chintakindi EEE Vaagdevi
Advantages
(i) By varying the field excitation, the magnitude of current drawn by the motor can be changed
by any amount. This helps in achieving stepless † control of power factor.
If the motor is ideal i.e., there are no losses, then φm = 90 . However, in actual practice, losses do occur in
o
*
o
the motor even at no load. Therefore, the currents Im leads the voltage by an angle less than 90 .
† The p.f. improvement with capacitors can only be done in steps by switching on the capacitors in various
groupings. However, with synchronous motor, any amount of capacitive reactance can be provided by
changing the field excitation.
Dr. Raju Chintakindi EEE Vaagdevi
Synchronous Condenser
From the phasor diagram, it is clear that after p.f. correction, the lagging reactive component of
the load is reduced to I′sin φ2.
Obviously, I′ sin φ2 = I sin φ1 − IC
or IC = I sin φ1 − I′ sin φ2
∴ Capacitance of capacitor to improve p.f. from cos φ1 to cos φ2
=
IC FG
∵ XC = V = 1
IJ
ωV H IC ω C K
Power triangle. The power factor correction can also be illustrated from power triangle. Thus
referring to Fig. 6.7, the power triangle OAB is for the power factor cos φ1, whereas power triangle
OAC is for the improved power factor cos φ2. It may be seen that
active power (OA) does not change with power factor improve-
ment. However, the lagging kVAR of the load is reduced by the
p.f. correction equipment, thus improving the p.f. to cos φ2.
Leading kVAR supplied by p.f. correction equipment
= BC = AB − AC
= kVAR1 − kVAR2
= OA (tan φ1 − tan φ2)
= kW (tan φ1 − tan φ2)
Knowing the leading kVAR supplied by the p.f. correction equipment, the desired results can be
obtained.
Example 6.1 An alternator is supplying a load of 300 kW at a p.f. of 0·6 lagging. If the power
factor is raised to unity, how many more kilowatts can alternator supply for the same kVA loading ?
Dr. Raju Chintakindi EEE Vaagdevi