31-00441 - A - C7355B - Quick Start Guide
31-00441 - A - C7355B - Quick Start Guide
ABOUT
This air quality monitor is specially designed for
monitoring multiple air quality parameters in the air duct.
The sensor is installed in the outdoor or return air duct.
Real time monitoring parameters are particles (PM2.5 and
PM10), carbon dioxide (CO2), TVOC, air temperature and
relative humidity.
33-00550ES-01
C7355B IN-DUCT IAQ MONITOR
Baud Rate:
1-4800
2-9600
3-14400
4-19200
5-38400
6-56000
7-57600
8-115200
Fig. 2. Wiring Terminals. default: 2-9600bps
Start Bits: 1
SPECIFICATIONS
Data Bits: 8
Part Number: C7355B1052
Stop Bits: 1 / 2
Detection Parameters: PM 2.5/PM 10, CO2, TVOC, Tem- default: 1
perature and RH
Parity: None / Odd / Even
Operating Environment: 4 °F–140 °F (-20 °C–60 °C); default: None
0–99%RH (non-condensing)
Register Map
Storage Conditions: 32 °F–122 °F (0 °C–50 °C); Support Function code:
10–60%RH 3 - Read Holding Registers
4 - Read Input Registers
Overall Dimension: 7.09 in x 4.92 in x 2.58 in 6 - Write Single Register
(180 mm x 125 mm x 65.5 mm) 16 - Write Multiple registers
31-00441—01 2
C7355B IN-DUCT IAQ MONITOR
3 31-00441—01
C7355B IN-DUCT IAQ MONITOR
Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
50/1175 PM2.5 hourly average 4 R 1 UINT16 1 0–10000
measurement x10 corresponding to
0–1000.0 μg/m3
51/1176 PM10 hourly average 4 R 1 UINT16 1 0–10000
measurement x10 corresponding to
0–1000.0 μg/m3
54/1179 CO2 hourly average 4 R 1 UINT16 0 0–5000
measurement x1 corresponding to
0–5,000 ppm
55/1180 TVOC hourly average 4 R 1 UINT16 3 0–3575
measurement x1000 corresponding to
–4.000 mg/m3
31-00441—01 4
C7355B IN-DUCT IAQ MONITOR
Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
56/1150 PM2.5 one minute 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0~1000.0 μg/m3
57/1151 PM10 one minute 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
58/1152 Temperature real-time 4 R 1 INT16 2 -2000–6000
measurement x100 corresponding to
-20.00 °C–60.00 °C
59/1153 Humidity real-time 4 R 1 UINT16 2 0–10000
measurement x100 corresponding to
0–100.00% RH
60/1154 CO2 real-time 4 R 1 UINT16 0 0–5000
measurement x1 corresponding to
0–5,000 ppm
61/1155 TVOC real-time 4 R 1 UINT16 3 0–3575
measurement x1000 corresponding to
–4.000 mg/m3
62/1200 PM2.5 24-hour moving 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
63/1201 PM10 24-hour moving 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
66/1204 CO2 24-hour moving 4 R 1 UINT16 0 0–5000
average measurement corresponding to
x1 0–5,000 ppm
67/1205 TVOC 24-hour moving 4 R 1 UINT16 3 0–3575
average measurement corresponding to
x1000 0–4.000 mg/m3
5 31-00441—01
C7355B IN-DUCT IAQ MONITOR
31-00441—01 6
C7355B IN-DUCT IAQ MONITOR
7 31-00441—01
C7355B IN-DUCT IAQ MONITOR