C7355B In-Duct IAQ Monitor

QUICK START GUIDE

ABOUT
This air quality monitor is specially designed for
monitoring multiple air quality parameters in the air duct.
The sensor is installed in the outdoor or return air duct.
Real time monitoring parameters are particles (PM2.5 and
PM10), carbon dioxide (CO2), TVOC, air temperature and
relative humidity.

The intelligent control algorithms built into the device


help to minimize the influence of ambient temperature
and humidity on the measured values. The device is
packaged with numerous presets suitable for most
commercial building requirements that enable quick and
easy initial setup.
Fig. 1. Indicator Lights.
The device, with pilot tube inlet and outlet design instead
of common air pump, adapts to a wider range of air speeds
and ensures a long lifetime of usage. It provides Modbus When the power is on, it will illuminate to
RTU (RS-485) communication protocol and easily indicate the device is working. Otherwise, the
integrates with the building management system. device is faulty.
This light indicates the one minute average
value of PM2.5, and changes color depending
INITIAL SETUP on concentration.
When PM2.5 <35 μg/m3 green light on
The device will power on when voltage is connected. 35–75 μg/m3 yellow light on
NOTE: Upon first use or re-use after long time shelving, > 75 μg/m3 red light on
the device should be continuously powered-on
for at least 48 hours to ensure stable output of all
measured values. COMMUNICATION SETTINGS
Wired communication (Modbus RS-485) is available for
LIGHT INDICATION the device. The wiring terminals are shown below for
detailed wiring and installation, please refer to Mounting
The bottom right side of the device is the indicator area. Instructions.
For this monitor (Part number: C7355B1052), only refer to
the ON and SCALE indicators.

33-00550ES-01
C7355B IN-DUCT IAQ MONITOR

Certification Standard: CE/FCC

Modbus Register Table


Mode: RTU (MSB First)

Baud Rate:
1-4800
2-9600
3-14400
4-19200
5-38400
6-56000
7-57600
8-115200
Fig. 2. Wiring Terminals. default: 2-9600bps

Start Bits: 1
SPECIFICATIONS
Data Bits: 8
Part Number: C7355B1052
Stop Bits: 1 / 2
Detection Parameters: PM 2.5/PM 10, CO2, TVOC, Tem- default: 1
perature and RH
Parity: None / Odd / Even
Operating Environment: 4 °F–140 °F (-20 °C–60 °C); default: None
0–99%RH (non-condensing)
Register Map
Storage Conditions: 32 °F–122 °F (0 °C–50 °C); Support Function code:
10–60%RH 3 - Read Holding Registers
4 - Read Input Registers
Overall Dimension: 7.09 in x 4.92 in x 2.58 in 6 - Write Single Register
(180 mm x 125 mm x 65.5 mm) 16 - Write Multiple registers

Net weight: 1.87 lb (850 g)

Table 1. Modbus Register Table.


Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
0/1050 PM2.5 hourly average 4 R 2 Float-Big 1 0–1000.0 μg/m3
measurement Endian
2/1052 PM10 hourly average 4 R 2 Float-Big 1 0–1000.0 μg/m3
measurement Endian
8/1058 CO2 hourly average 4 R 2 Float-Big 0 0–5,000 ppm
measurement Endian
10/1060 TVOC hourly average 4 R 2 Float-Big 3 0–4000 mg/m3
measurement Endian
12/1000 PM2.5 one minute 4 R 2 Float-Big 1 0–1000.0 μg/m3
average measurement Endian
14/1002 PM10 one minute 4 R 2 Float-Big 1 0–1000.0 μg/m3
average measurement Endian
16/1004 Temperature real-time 4 R 2 Float-Big 2 -20.00 °C–60.00 °C
measurement Endian
18/1006 Humidity real-time 4 R 2 Float-Big 2 0–100.00% RH
measurement Endian
20/1008 CO2 real-time 4 R 2 Float-Big 0 0–5,000 ppm
measurement Endian
22/1010 TVOC real-time 4 R 2 Float-Big 3 0–4000 mg/m3
measurement Endian
24/1100 PM2.5 24-hour moving 4 R 2 Float-Big 1 0–1000.0 μg/m3
average measurement Endian

31-00441—01 2
C7355B IN-DUCT IAQ MONITOR

Table 1. Modbus Register Table.


Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
26/1102 PM10 24-hour moving 4 R 2 Float-Big 1 0–1000.0 μg/m 3
average measurement Endian
32/1108 CO2 24-hour moving 4 R 2 Float-Big 0 0–5,000 ppm
average measurement Endian
34/1110 TVOC 8-hour moving 4 R 2 Float-Big 3 0–4000 mg/m3
average measurement Endian
1300 Primary pollutant 24- 4 R 2 Float-Big 1300
hour average Endian
measuring value (One
of PM2.5/PM10/CO2/
TVOC) (Calculated
based on 24-hour or
1-hour moving average
measurement)
1302 Primary pollutant type 4 R 1 INT16 1-PM25, 2-PM10,
(One of 3-CO2; 4-TVOC
PM2.5/PM10/CO2/
TVOC) (Calculated
based on 24-hour or
1-hour moving average
measurement)
1303 Index level of the 4 R 1 INT16 Level 1-Excellent
primary pollutant (One Level 3-Light
of PM2.5/PM10/CO2/ pollution
TVOC) (Calculated Level4-Medium
based on 24-hour or pollution
1-hour moving average Level 5-Heavy
measurement) pollution
Level 6-Severe
pollution
1304 AQI value of the primary 4 R 1 INT16 0–500
pollutant) (One of
PM2.5/PM10/CO2/
TVOC) (Calculated
based on 24-hour or
1-hour moving average
measurement)

1320 PM2.5 AQI value 4 R 1 INT16 0–500


(Calculated based on
24-hour moving
average measurement)
1321 PM10 AQI value 4 R 1 INT16 0–500
(Calculated based on
24-hour moving
average measurement)
1322 CO2 AQI value 4 R 1 INT16 0–500
(Calculated based on
24-hour moving
average measurement)
1323 TVOC AQI value 4 R 1 INT16 0–500
(Calculated based on
24-hour moving
average measurement)

3 31-00441—01
C7355B IN-DUCT IAQ MONITOR

Table 1. Modbus Register Table.


Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
1350 PM2.5 Pollution index 4 R 1 INT16 1–6
level (Calculated based
on 24-hour moving
average measurement)
1351 PM10 Pollution index 4 R 1 INT16 1–6
level (Calculated based
on 24-hour moving
average measurement)
1352 CO2 Pollution index 4 R 1 INT16 1–6
level (Calculated based
on 24-hour moving
average measurement)
1353 TVOC Pollution index 4 R 1 INT16 1–6
level (Calculated based
on 24-hour moving
average measurement)
78 3 color LED status 4 R 1 INT16 0-OFF, 1-Green,
2-Yellow, 3-Red
0 Modbus Address 3/6 R/W 1 UINT16 1–247 1
1 Modbus rate (bps) 3/6 R/W 1 UINT16 1-4800, 2-9600, 2
3-14400, 4-19200,
5-38400, 6-56000,
7-57600, 8-115200
2 Modbus Parity check bit 3/6 R/W 1 UINT16 1-NONE, 1
1STOP_BIT,
2-NONE,
2STOP_BIT,
3-Odd, 1STOP_BIT,
4-Even, 1STOP_BIT
4 Temperature correction 3/16 R/W 2 Float-Big 2 -3.0–3.0 °C/ -2.0
value Endian -6.0–6.0 °F
6 Humidity correction 3/16 R/W 2 Float-Big 2 -5.0–5.0%RH 0
value Endian
14 CO2 compensation 3/16 R/W 2 Float-Big 0 -300.0–300.0 ppm 0
value Endian
In order to reserve the decimal part, the measuring value with decimal will be magnified 10/100/1000 times, marked as
x10/x100/x1000.

Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
50/1175 PM2.5 hourly average 4 R 1 UINT16 1 0–10000
measurement x10 corresponding to
0–1000.0 μg/m3
51/1176 PM10 hourly average 4 R 1 UINT16 1 0–10000
measurement x10 corresponding to
0–1000.0 μg/m3
54/1179 CO2 hourly average 4 R 1 UINT16 0 0–5000
measurement x1 corresponding to
0–5,000 ppm
55/1180 TVOC hourly average 4 R 1 UINT16 3 0–3575
measurement x1000 corresponding to
–4.000 mg/m3

31-00441—01 4
C7355B IN-DUCT IAQ MONITOR

Starting Quantity of
Register Read/ Registers Data Range,
Decimal Data Description Function Write (2Bytes/16bit) Format Decimals Data Description Default
56/1150 PM2.5 one minute 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0~1000.0 μg/m3
57/1151 PM10 one minute 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
58/1152 Temperature real-time 4 R 1 INT16 2 -2000–6000
measurement x100 corresponding to
-20.00 °C–60.00 °C
59/1153 Humidity real-time 4 R 1 UINT16 2 0–10000
measurement x100 corresponding to
0–100.00% RH
60/1154 CO2 real-time 4 R 1 UINT16 0 0–5000
measurement x1 corresponding to
0–5,000 ppm
61/1155 TVOC real-time 4 R 1 UINT16 3 0–3575
measurement x1000 corresponding to
–4.000 mg/m3
62/1200 PM2.5 24-hour moving 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
63/1201 PM10 24-hour moving 4 R 1 UINT16 1 0–10000
average measurement corresponding to
x10 0–1000.0 μg/m3
66/1204 CO2 24-hour moving 4 R 1 UINT16 0 0–5000
average measurement corresponding to
x1 0–5,000 ppm
67/1205 TVOC 24-hour moving 4 R 1 UINT16 3 0–3575
average measurement corresponding to
x1000 0–4.000 mg/m3

5 31-00441—01
C7355B IN-DUCT IAQ MONITOR

31-00441—01 6
C7355B IN-DUCT IAQ MONITOR

7 31-00441—01
C7355B IN-DUCT IAQ MONITOR

Honeywell Building Technologies


Honeywell
715 Peachtree Street NE
Atlanta, GA 30308
customer.honeywell.com

Honeywell Building Technologies


Honeywell GmbH
Böblinger Strasse 17
® U.S. Registered Trademark
71101 Schönaich, Germany ©2020 Honeywell International Inc.
31-00441—01 M.S. 11-20
buildings.honeywell.com Printed in United States

You might also like