0.

4kV AUXILIARY SECTION 2


3ph.AC, 50Hz, 0.4kV,1000A, 25kA/1s
NEUTRAL
PE

INTERLOCK TO
SECTION I-II BUSTIE CT 100/5A
CLO.5, 10VA

LOCAL OPENING

LOCAL CLOSING
UA
V
4-20 mA
FROM 6.3 kV AUXILIARY SEC 2
- G R MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
VS
-F1,-F2,-F3 6A 6A 16A 16A 6A 16A 80A 80A 200A 25A 80A 6A 6A 32A 32A 16A
SHEET 1/1, C5
25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA
DCS DCS DCS DCS DCS DCS DCS DCS DCS DCS DCS DCS DCS DCS

ACB
ST 1000A
#2 PDC TRANSFORMER 65kA
3200kVA R R R R R R R R R R R R R R R R
CT1,CT2,CT3
VOLT HV :6300 AR AS AT PM
1000/5A G G G G G G G G G G G G G G G G
LV :400 CL0.5, 10VA
-F1,-F2,-F3 -L1 -L2 -L3 I I I I I I I I I I I I I I
AMPERE HV 114.55 Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y
O O O O O O O O O O O O O O
LV 1804.22 R Y B
TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS TOR FCS
IMPEDANCE : 5.5%
VECTOR GROUP : Dyn-5
COOLING TYPE : ONAN

UNITS FEEDER NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17


KKS NO. - - - - - - - - - - - - - - - - -
MAIN LABEL OUTGOING 0.4kV AUXILIARY SECTION 2 COAL COAL COAL SPEED SPEED REDUCER FEEDER OF PRIMARY FAN SECONDARY INDUCED DRAFT SERVICE WATER FEEDER OF SLAG EXHAUST OIL CONDENSATE WATER CONDENSATE WATER RUBBERRY BALL
#2 PDC TRANSFORMER INCOMING NO. 2 SPREADER NO. 2-1 SPREADER NO. 2-2 FEEDER NO. 2 REDUCER NO. 2 FAN SHOOT BLOWER FAN NO. 2 FAN NO. 2 FAN NO. 2 PUMP NO. 2 ESP NO. 2 REMOVAL NO. 2 FAN NO. 2 PUMP NO. 2-1 PUMP NO. 2-2 PUMP NO. 2
NO. 2
RATED POWER / - 613.39kW/885.38A 1.1kW/2.1A 1.1kW/2.1A 4kW/7.5A 4kW/7.5A 0.52kW/1A 4kW/7.5A 30kW/56.6A 37kW/69.8A 90kW/169.8A 11kW/20.8A 35kW/668A 2.2kW/4.2A 0.37kW/0.7A 15kW/28.3A 15kW/28.3A 5.5kW/10.4A
CURRENT
CIRCUIT BREAKER TYPE - MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
RATED CURRENT - 1000A 6A 6A 16A 16A 6A 16A 80A 80A 200A 25A 80A 6A 6A 32A 32A 16A
STARTER TYPE - - INVERTER INVERTER INVERTER INVERTER DIRECT ON LINE - INVERTER STARDELTA INVERTER DIRECT ON LINE - DIRECT ON LINE DIRECT ON LINE DIRECT ON LINE DIRECT ON LINE DIRECT ON LINE
RATING - - 1.1kW 1.1kW 4kW 4kW 0.52kW - 30kW 37kW 90kW 11kW - 2.2kW 0.37kW 15kW 15kW 5.5kW
TRIPPING DEVICE - AMPERE METER - - - - THERMAL OVERLOAD - - THERMAL OVERLOAD - THERMAL OVERLOAD - THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD
MEASURING MODEL/TYPE - ANALOGUE AMPERE METER - - - - - - - - - - - - - - - -
INSTRUMENTS & ANALOGUE VOLTMETER
FUNCTION - A,V - - - - - - - - - - - - - - - -

CT - 1000/5A - - - - - - - 100/5A - - - - - - - -
VT - - - - - - - - - - - - - - - - - -
CURRENT - - - - - - - - - 4-20mA - - - - - - - -
TRANDUCER
INDICATING LAMPS - RED(R), YELLOW(S), BLUE(T) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(ON), GREEN(OFF) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP)
GREEN (ACB OPENED), RED (ACB CLOSED) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT)
POWER CABLE TYPE - OUT OF SCOPE - - - - - - - - - - - - - - - -
SIZE (sqmm) - OUT OF SCOPE - - - - - - - - - - - - - - - -
LENGTH (meter) - OUT OF SCOPE - - - - - - - - - - - - - - - -

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~

0.4kV AUXILIARY SECTION 2


3ph.AC, 50Hz, 0.4kV,1000A, 25kA/1s
NEUTRAL
PE

MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
100A 25A 32A 80A 100A 6A 32A 32A 50A 320A 200A
25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA 25kA
DCS DCS DCS DCS DCS DCS DCS DCS

R R R R R R R R R R R

G G G G G G G G G G G
I I I I I I I I
Y Y Y Y Y Y Y Y Y Y Y
O O O O O O O O
FCS FCS FCS FCS FCS FCS FCS FCS
TOR TOR TOR TOR TOR TOR TOR TOR

UNITS FEEDER NO. 27 26 25 24 24 23 22 21 20 19 18


KKS NO. - - - - - - - - - - -
MAIN LABEL SPARE SPARE SPARE FEEDER OF FEEDER OF ASH DUAL AXIS ROTARY FEED ONCE WATER CIRCULATING WATER FEED WATER
LIGHTING PANEL MAINTENANCE PANEL CONVEYOR NO. 2 STIRRER NO. 2 VALVE NO. 2 PUMP NO.2 PUMP NO. 2 PUMP NO. 2
BOILER NO. 2 BOILER NO. 2
RATED POWER / 50kW/94,3A 11kW/20.8A 15kW/28.3A 40kW/80A 50kW/94,3A 1.1kW/2.1A 11kW/20.8A 1kW/1.9A 18.5kW/50A 160kW/301.9A 90kW/169.8A
CURRENT
CIRCUIT BREAKER TYPE MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
RATED CURRENT 100A 25A 32A 80A 100A 6A 25A 6A 50A 320A 200A
STARTER TYPE - DIRECT ON LINE DIRECT ON LINE - - DIRECT ON LINE DIRECT ON LINE DIRECT ON LINE SOFT STARTER SOFT STARTER SOFT STARTER
RATING - 11kW 15kW - - 1.1kW 11kW 1kW 18.5kW 160kW 90kW
TRIPPING DEVICE - THERMAL OVERLOAD THERMAL OVERLOAD - - THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD THERMAL OVERLOAD
MEASURING MODEL/TYPE - - - - - - - - - - -
INSTRUMENTS
FUNCTION - - - - - - - - - - -

CT - - - - - - - - - - -
VT - - - - - - - - - - -
CURRENT - - - - - - - - - - -
TRANDUCER
INDICATING LAMPS RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(ON), GREEN(OFF) RED(RUN), GREEN(STOP) RED(RUN), GREEN(STOP) RED(ON), GREEN(OFF) RED(ON), GREEN(OFF)
YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT) YELLOW(FAULT)
POWER CABLE TYPE - - - - - - - - - - -
SIZE (sqmm) - - - - - - - - - - -
LENGTH (meter) - - - - - - - - - - -

~ ~ ~ ~ ~ ~

LEGEND : ABBREVIATION NOTES :


CT CURRENT TRANSFORMER 1. EACH MCC EQUIPPED WITH ONE SET OF 3-PHASE AND NEUTRAL MAIN BUSES, A SET OF 3-PHASE AND NEUTRAL AUXILIARY BUSES FOR EACH VERTICAL MULTI-TIER
MAIN BUSBAR V ANALOGUE VOLT METER INDICATING LAMP (GREEN)
PDC POWER DISTRIBUTION CENTRE ARRANGEMENT OF UNITS AND A GROUND BUS.
ACB G
NEUTRAL ACB AIR CIRCUIT BREAKER
VS VOLT METER SELECTOR SWITCH INDICATING LAMP (RED)
MCCB MOULDED CASE CIRCUIT BREAKER
R
GROUND A ANALOGUE AMMETER DCS DISTRIBUTED CONTROL SYSTEM
INDICATING LAMP (YELLOW) FCS FIELD CONTROL STATION
MCCB AR ANALOGUE AMMETER (PHASE R) Y
TOR THERMAL OVERLOAD RELAY
INDICATING LAMP (BLUE) A CURRENT
DRAWOUT FEATURE AS ANALOGUE AMMETER (PHASE S) B PT. ZUG INDUSTRY INDONESIA
TOR V VOLTAGE
AT ANALOGUE AMMETER (PHASE T) M MOTORIZED Hz FREQUENCY
FUSE PF POWER FACTOR
PM POWER METER ST TRIPPING COIL KVAR REACTIVE POWER
kW REAL POWER
INVERTER DCS OPERATED FROM REMOTE LOCAL DISTRIBUTION CONTROL PANEL
TRANSFORMER kWh POWER/HOUR
I PM POWER METER SIAK 2x20 T/H+2x3.5MW electrical
STARDELTA OPERATED FROM FIELD LIGHTING PANEL
O
FCS
CURRENT TRANSFORMER
DIRECT ON LINE MAINTENANCE PANEL 0.4kV AUXILIARY SECTION 2
I START BUTTON SINGLE LINE DIAGRAM
UA
CURRENT TRANDUCER O STOP BUTTON SOFT STARTER
THREE PHASE MOTOR
~ 4-20 mA