NOTICES TO USERS
Safety Notices
"Important Safety Information"affords very important points about how to
operate the unit safely.To prevent injury to the user or other people and property
damage, the following instructions must be followed. Incorrect operation due to
ignoring of instructions may cause harm or damage.
The safety precautions listed here are divided into two categories. In either
case, important safety information is listed which must be read carefully.
WARNING
CAUTION
Please read the mark of the unit carefully .If you detect any abnormality, such
as abnormal noise, smell, fog, temperature rise, creepage, fire and so on;
Please turn off the power supply immediately and call your dealer or local
service center for instructions. Do not repair the unit by yourself. If necessary,
call the local fire department or Emergency department for help.
WARNING
and so on.
■ Be sure only trained and qualified service personnel to install, repair or service
the equipment. Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to the equipment.
■ Install at a strong and firm location which is able to withstand the set' s weight.
If the strength is not enough or installation is not properly done, the set will
drop to cause injury.
■ While following the instructions in this installation manual, install drain piping
in order to ensure proper drainage and insulate piping in order to prevent
condensation. Improper drain piping may result in water leakage and property
damage.
1
■ Never use or stockpile some flammable objects such as hair spray, alcohol
or paint near the unit. It may cause a fire.
■ Cut off the power of the air conditioner in case of accidents,such as
smelling something burning.
■ Keep the air-conditioning room with good ventilation to avoid of oxygen
deficiency.
■ Do not insert fingers, rods or other objects into the air inlet or outlet.
When the fan is rotating at high speed, it will cause injury.
■ Never try to plug in or pull out the power plug for starting or shutting the
air conditioner.
■ Pay attention to the mounting support in case of damage for a long usage
■ Ask your dealer or qualified service personnel for improvement, repair, and
maintenance. Incomplete improvement, repair, and maintenance may result in
a water leakage, electric shock, and fire.
CAUTION
■ Before installing, check whether the power is safe and keep it accordance
with its nameplate;
■ Before operating, make sure that all connections of cables, drain pipes
and other pipes are in good condition in case of water leakage,refrigerant
leakage, electric shocks, fires.
■ Be sure the air conditioner is grounded. In order to avoid electric shock, make
sure that the unit is grounded and that the earth wire is not connected to gas or
water pipe, lightning conductor or telephone earth wire.
■ Keep the air conditioner running for 5 minutes at least before shutdown,
otherwise,it will do bad to the oil return of the compressor.
■ The child is not allowable to operate the air conditioner.
■ Do not operate the air conditioner with a wet hand.
An electric shock may happen.
■ Cut off the power of the air conditioner prior to cleaning the unit or
replacing the air strainer;
■ Cut off the power of the air conditioner before the unit being idle for a
long time.
■ Do not step on the outdoor unit or avoid placing any object on it.
Falling or tumbling may result in injury.
■ Please electrify the unit and then carry out electric leakage test after the
installation of electric devices;
2
PARTS NAME AND FUNCTION
■ Indoor unit
3
■ Outdoor unit
Air inlet
Air inlet
Air outlet
Air outlet
Air outlet
CAUTION
■ All the pictures in this manual are for explanation purpose only. They may be
slightly different from the air conditioner you purchased(depend on model).
The actual shape shall prevail.
■ This air conditioner just consists of indoor unit and outdoor unit , other
than connecting pipes and ducts .
4
INTRODUCTION OF CONTROLLER
3.1 Instruction of Wire Controller
■ The control panel of Wire controller is in charge of receiving infrared
remote control signal , controlling the system operation through buttons on
it , displaying operating conditions of the whole system via LCD and
communicating with system control panel .
■ The control panel of Wire controller consists of LCD , 9 buttons , infrared
receiver module , communication link , etc .
■ The system control panel supply the power for the wire control panel.
COOL ROOM TEMP.
DRY HEAT
DEFROST
FAN SPEED
TIMER mode
ON/OFF
FAN mode
(For the cooling-only model) TEMP+/- key
Set the temperature and it
TIMER key will be increased or
This key is used to set ON/OFF decreased 1℃ by pressing
the switch-on or switch-off. the button once .
NOTE:
1. Do not handle the button with nail or other sharp things , so as avoid the
damages of operation panel .
2. Thanks to technical renovation, the operation panel or remote controller may be
changed without further notice.
5
■ Press ON/OFF key again to stop the unit.
To protect the air conditioner from starting immediately after stopping, the
delayed start function will keep the air conditioner idle for 3 minutes before
automatically starting it.
CAUTION
■ When the ambient temperature is lower than 21℃ or higher than 43℃, please
don't start the cooling operation.
■ When the ambient temperature is lower than -7℃ or higher than 24℃, please
don't start the heating operation.
■ When the room temperature is lower than 18℃ , please don't switch the
operation to DRY mode.
Timing operation
■ Timing OFF operation :
Set the shutdown time and the air conditioner will automatically stop when
the setting time is over.
1 ) Press the TIMER button during running , the air conditioner enters timing
OFF state and "TIMING OFF" will be indicated on the display screen.
2) Press TIME+ / - button to set the desired timing OFF time in the range from
1 to 12 hours.
The number indicated on the display area shows the timing OFF time, that is,
the time left for shutdown and it will decrease by 1 every hour.
3) To cancel the setting, press the TIMING button again. Under operating state,
only TIMING OFF function can be set .
■ Timing ON operation :
Set the starting time and the air conditioner will automatically start when
the setting time is over.
1 ) Press the TIMER button at standby state , the air conditioner enters timing
ON state and "TIMING ON" will be indicated on the display screen.
2) Press TIME+ / - button to set the desired timing ON time in the range from
1 to 12 hours.
The number indicated on the display area shows the timing ON time, that is, the
time left for starting and it will decrease by 1 every hour.
3) To cancel the setting, press TIMING button again. Under standby state,
only TIMING ON function can be set .
6
and 2℃ after 8 hours.If the air conditioner is in HEAT mode while setting
SLEEP mode, the temperature will decrease by 2℃ after 1 hour and another
2 ℃ after 2 hours, and totally decrease by 4℃ after 8 hours .
■ If SLEEP OFF function and TIMING OFF function are set simultaneously,
the system will carry out the function of which the time comes early;
■ During sleeping operation,you can change the operating mode and the
sleeping function will be cancelled automatically when switching to other
mode.
7
3.1. 2.2 Instruction for function operations of Wire
Controller
In the first 5s after powering on,the electric
control main panel will detect whether the wire
controller is available.If the wire controller works
ON/OFF
and the communication fault lasts one minute,
the control panel will display the fault and its TIME+ TIMER TEMP+ MODE
fault code as well as the unit will shut down. TIME- FAN SPEED TEMP- SLEEP
■ ON/OFF key:
When the control panel is powered on for the first time, the work condition is
in default mode,that is,the set temperature is 25℃ (room temperature) and the
swinging mode works and the high speed air is supplied.
If ON/OFF key is hold when the wire controller is powered on,the LCD
can work in a full screen at the first two seconds and then it will display the
room temperature and the buzzer will ring three times.
■ MODE key:
When pressing this key,the operating modes are switched in the order :
Cooling & Heating type: COOL→DRY→HEAT→FAN→COOL
Cooling only type: COOL→DRY→FAN→COOL
■ TIMER key:
This key is used for setting TIMING ON or TIMING OFF function. The
timing ranges of the remote control and the wire control are all from one
hour to 24 hours.
■ TIMER key:
This key is used for setting TIMING ON or TIMING OFF function. The
timing ranges of the remote control and the wire control are all from one
hour to 24 hours.
8
■ "TIME+ "key and "TIME- "key
P3 and P4 icons indicate the hours and the two keys are used for adjusting
the timing time. After setting timing function, the timing time displayed will
increase by one hour and the time won't change any more when it gets to
24 hours;It is the same with “TEMP-" key,that is,the timing time displayed
will reduce by one hour and the time won't change any more when it gets to
one hour.
■ FANSPEED key
This key can adjust the wind speed and press the key to switch modes in the
order :
Auto wind→ Hi speed →Mid speed→ Low speed →Auto wind.
■ SWING key
Pressing this key, the LCD screen will display swing icon which is
composed of P3,P4,P5,P6,P7 and P8. When the swinging function works,
the icon will swing from P4 to P8;
If the key is pressed,the UP/DOWN and LEFT/RIGHT air guiding slips
are swinging in the specified rang and those air guiding slips will stop
swinging when the key is pressed again.
Emergency key
When the remote controller
Receiving window of the EMERGENCY is out of order, you can press
remote control signal down this key to carry out the
emergency operation.
9
The model of the following remote controller is Jingling common remote
controller ( It can work with the wire controller or the indicator light board ) .
TURBO key, LAMP key, AIR FLOW key and CLEAN key is applicable for
special latest developed new models instead of normal ones.
AUTO F SLEEP
TURBO
LAMP
COOL
DRY
C
HEAT CLEAN
ON
FAN OFF HOLD
Set TEMP key
MODE key MODE TEMP Press▼▲ will decrease or increase
It is used for selecting different modes, the set temperature and the rang is :
such as automatic, cooling, 16℃~32℃
dehumidifying, heating and ventilating.
ON/ OFF
SWING key
ON/OFF key It is used for selecting swing and
It is used for starting or stopping AC. stopping switching circularly.
FAN SPEED key FAN SPEED SWI NG AI R FL OW AIR FLOW key It is used for selecting
It is used for selecting wind speeds ( swing , stable wind, natural wind and
natural wind, high wind, middle wind circulating wind.
and low wind) TI MER HOLD SLE EP
SLEEP key
TIMER key It is used for selecting sleep mode
It is used for setting timing ON/OFF TURBO LAMP CLEA N and canceling sleep mode.
and regards hour as its union.
HOLD key
It is used for selecting hold mode and
canceling hold mode.
TURBO key
T h e k e y d o e s n’ t i n d i c a t e w i n d
speed and setting sleep mode or CLEAN key
changing modes will cancel TURBO It is used for selecting purification or
operation. canceling purification.
10
■ FAN SPEED key: The default wind speed is in the automatic wind mode when
starting firstly. The remote control won’t react by pressing the key because
the wind speed can’t be adjusted and in low speed in dehumidifying mode. In
other mode, press the key to switch modes in the order : automatic wind→ high
speed →middle speed→ low speed →automatic wind.
■ SWING key : In dehumidifying mode, the swing mode is in the stable wind
mode without change. In other mode, press the key to switch modes in the
order: swing →stable wind→natural wind →swing.
■ AIR FLOW key : The default air flow is in the swing mode when starting firstly
and press the key to switch modes in the order: SWING →STOP →SWING.
■ TIMER key : The default mode is in no timing state, press the key to set timing
time . The switch order is: 1H→2H→ … →24H→cancel→1H… . Press the key
to set timing starting in the OFF state and set timing stopping in the ON state.
After setting timing function, the time keeps decreasing per hour until the
time decreasing to the timing on or timing off and the timing display will be
cancelled at the same time . Pressing MODE key can’t cancel timing in
timing mode which will set out timing time by pressing other key.
■ HOLD key: The default state is in no HOLD key state, press the key to select
modes in order: HOLD key →cancel HOLD key→ HOLD key ; In HOLD key
mode, all keys except HOLD key of the remote control can’t work .
( NOTE: In HOLD key mode, the remote and operation panel of the unit both
will be locked automatically by pressing the key and press the key again , they
will be unlocked. As for the split unit , it only hold the control other than
EMERGENCY key and the panel will make a reaction.)
■ SLEEP key : Press the key to switch modes in the order: SLEEP→ cancel
SLEEP→ SLEEP. The sleeping function won’t be cancelled for changing
modes. Press the key to set sleep mode and the wind speed will automatically
be switched to low speed and it can adjust the wind speed by pressing the
FAN SPEED key (except dehumidifying mode).
■ TURBO key: The default state for the control is no turbo and the key don’t
work in the AUTOMATIC mode, DRY mode and FAN mode ( It will not display
any contents and not send out any codes). The control, however, will switch
between on and off by pressing the key in other mode. The wind speed isn’t
indicated in turbo mode and it will be cancelled for changing modes and
setting sleep mode.
■ LAMP key : The default state is in no LAMP key state, press the key to select
modes in order : LAMP key →cancel LAMP key→ LAMP key; In LAMP key
mode, pressing MODE key can’t cancel the show of LAMP key.
■ CLEAN key : The default state is in no purification state, press the key to select
modes in order : CLEAN →cancel CLEAN→ CLEAN; In CLEAN mode,
pressing CLEAN key can’t cancel CLEAN function. Press the key when
the remote control is closed, the control will switch modes in the order :
CLEAN →cancel CLEAN→ CLEAN; When you stop the unit and turn on the
purification switch, except the wind, the stable swing and air door swing speed
aren’t adjusted.
11
3 . 2 . 2 Notices for operating the remote control
① Don’t place the control near high heat source such as Electric blanket, warm
furnace and so on.
② Don’t expose the control in sun.
③ Take care for it and prevent it from damage for falling down.
④ Don’t place any rolling obstacle between the signal acceptor of AC and the
control, otherwise it may affect sending or incepting signals.
⑤ Don’t spray water or other liquid on the control.
⑥ Don’t place any clog on the control.
NOTE: When the remote control is out of work, please replace the battery and
operated it once ; If the failure hasn’t be cancelled, please take urgent operation
methods to restart the AC.
NOTE
12
INSTALLATION OF THE UNIT
4. 1 Install Indoor unit
4.1.1 Outline view and dimensions of Indoor unit
■ Outline view and dimension of Indoor units(applicable for Low-static
pressure type(TA) series)
Air outlet
Air inlet
Fig 1
13
■ Outline view and dimension of Indoor units(applicable for Mid-static
pressure type(TB) series)
Fig 2
24
36,48,60
Fig 3
14
■ Outline view and dimension of Indoor units(applicable for High-static
pressure type(TH) 96 series)
Fig 4
Table 4: unit :mm
Items
Model(kBtu/h)
96
Fig 5
15
4.1.3 Selection of the installation site
■ Make sure top hangers can bear the weight of the unit;
■ Make sure that the drain pipe can drain the water conveniently;
■ Make sure that the air inlet and the outlet of the indoor unit should not be
blocked, with a good ventilation.
■ There is enough space for maintenance and installation as listed in Fig 4;
■ Keep the unit off heat source, inflammable gas or smog.
■ The unit is ceiling type or concealed in-the -ceiling type;
■ Make sure that indoor unit, outdoor unit, power wires and connecting
wires are 1 meter at least away from TV or radio in case of noise or
image inteference.Depending on the radio waves, a distance of 1 meter may
not be sufficient enough to eliminate the noise.
Fig 6
Indoor unit
Hoisting screw
Hook
Fig 7
16
■ Install the indoor unit on the ceiling(refer to Fig 8)
Hoisting screw
Hook
Nut
Nut
Fig 8
CAUTION
■ Before installation, please finish the installation of all ducts ( refrigerant duct,
drainage duct)and the connection of the all power lines(the power lines of the
outdoor unit), once the installation has finished, the ducts and the power lines
can be connected with the indoor units immediately.
■ In order to keep the ceiling level and from vibrating , please reinforce the
ceiling before digging an opening in the ceiling .
■ If the ceiling is not strong enough , please install a angle iron bracket
and lay the unit on the bracket ;
17
Fig 9
18
■ Outline view and dimension of Outdoor units(Applicable for 36-48
series)
Fig 10
19
■ Outline view and dimension of Outdoor units(Applicable for 48-60
series)
Fig 11
Table 7: unit :mm
20
■ Outline view and dimension of Outdoor units(Applicable for 96
series)
C
E D
B A
Items A B C D E
Model(kBtu/h)
21
4.2.2 Installation dimensions of Outdoor unit
Fig 13 Fig 14
The outdoor unit should be installed in the location that meets the following
requirements:
■ There is enough room for installation and maintenance and make sure the
exhaust does not flow back;
■ The place where there is a good ventilation so that the unit can suck or
drain out sufficient airflow. Besides, make sure that air outlet and air inlet
are not impeded, otherwise, please remove the obstacles
■ The support is flat and horizontal and can stand the weight of the outdoor unit.
and the installation site has sound proofing and damping function so that
the neighborhood will not feel uncomfortable with the noise or expelled air.
■ In case of exposure to direct sunlight,you'd better install an awning.
■ Make sure that the installation site can drain out the rain and condensate
water;
■ Select the position where it will not be subject to snow drifts, rubbish or oil
smog. If unavoidable, please cover it with a shelter.
■ Locate the outdoor unit in the place not facing the strong wind directly.
22
Cloth, between the rope and the unit during hoisting;
3. Take care when handing and hoisting ,the force in each point of hoisting
must be uniform.
■ The following methods in hoisting are for your reference:
1. Hoisting by hand, hoisting by forklift;
2. Putting round logs (or pipes) under the unit for movement by worker with hands.
■ Fixing up the unit
The following work must be done after hoisting is completed:
1. After hoisting the unit on the base,please adjust the unit as level as
possible with the gradient error no more than 0.1%.
2. Fixing up the unit with the force on each fixing point uniform when the unit
is in a proper level .
Note:
Fixing Two spanners must be used: One is normal
spanner, the other is torque spanner.
Fig 15
When connecting the copper pipes, please adjust the torque spanner according
to the following torque parameters in Table 9 before operation.
23
Table 9
6.35 1.4~1.7
9.52 1.4~1.7
12.7 4.8~6.2
15.88 4.8~6.2
19.05 6.9~9.9
Outdoor unit
Indoor unit
Wall hole
Gradient
2-5 Cut the sleeve short according
to the thickness of the wall
Fig 16
■ Pressure test, vacuumize and leakage check for connection pipes and indoor
pipeline:
After installing the units and connection ducts , keep filling the connection
duct and the pipeline of the indoor units with nitrogen gas until the pressure in the
duct reach 2.4-3.0MPa (absolute pressure); Maintain this pressure for about 24
hours with the value change no less than 0.03Mpa. Meanwhile, the leak test
should be carried out to each joint and weld points by using soap bubble , if there
is no leak point, please discharge the nitrogen gas until the pressure reduces
to 130Pa (absolute pressure), and maintain this pressure value for about 24
hours with the value change no less than 20pa. At last,open the valve of the
main machine to start the commission. If the refrigerant pipe is longer than the
stated one,please charge more refrigerant R22 according to the following
experienced formula:
24
R= L1×0.030kg/m+L2×0.065kg/m+L3×0.115kg/m+ L4×0.190kg/m+
L5×0.290kg/m+L6×0.380kg/m+L7×0.580kg/ m+L8×0.760kg/m
Remarks:
R--Total charging amount of refrigerant;
L1–-Total length of φ6.4 Liquid pipe
L2–-Total length of φ9.5 Liquid pipe
L3–-Total length of φ12.7 Liquid pipe
L4–-Total length of φ16.9 Liquid pipe
L5–-Total length of φ19.1 Liquid pipe
L6–-Total length of φ22.2 Liquid pipe
L7–-Total length of φ25.4 Liquid pipe
L8–-Total length of φ28.6 Liquid pipe
CAUTION
■ Heat Insulation:
When everything is normal after leakage inspection and pressure testing,
carry out heat insulation operation accordance with the requirements as below:
① The insulated material must be wrapped tightly without any cracks ;
② The thickness of the insulated material is no less 8 mm .
③ After wrapping with insulated material,please carry on rainproof and
dampproof treatment for the surface,such as wrap it with some bands.
④ Condensation on the surface of the copper pipes is not allowed during
cooling operation.
25
Table 10
Rated refrigeration
(KBtu/h)
<24 24~60 ≥96
Value
Max.length (m) 15 20 50
Max . number
10 10 10
of bends(piece)
CAUTION
The case of the outdoor located The case of the indoor located
higher than the indoor unit higher than the outdoor unit
Outdoor unit
Non-return bend Non-return bend Indoor unit
Gas pipe
Gas pipe
Oil loop
Oil loop Liquid pipe
Liquid pipe
Fig 17
CAUTION
● The radius of oil loops shall be as small as possible and one is allocated
every 5 meters as shown in the above figures.
● When the height difference is more than 5 meters between the indoor
unit and the outdoor unit , some oil loops or non-return bends need to
be installed in the pipeline system.
● The figures above are just for the multi-connecting unit with one
indoor unit, it is the same with ones with several indoor units.
26
4.6 Install condensate pipes
As for the condensate pipe of indoor unit of cental air-conditioning, the following
points shall be considered :
①The large drainage amount of the condensate ;
②The loss of refrigeration capacity;
③ For built-in types,it is not convenient to maintain the unit and the leakage
might occur at this place.
4.6.1 Select the material of condensate pipes
The materials of condensation water pipe may be U-PVC pipe and Zinc-plated
pipe. Considering the problems of sanitary and rusting, the U-PVC pipe is
recommended.
4.6.2 Requirement of installation:
■ The water outlet outside the house must have water seal which shall be fixed.
■ The gradient of the drainage pipe is no less than 1% .
■ The indoor part of the condensate pipe shall be sleeved with insulating pipe or
wrapped with thermal insulating asbestos.
■ After the installation of condensate pipes, leakage test must be carried out
by pouring some water to confirm no leakage in any connecting point and the
drainage is smooth . For the installation, please see Fig 18 :
Heat insulation
treatment
Duct unit
h
Condensate pipe
water seal
h:1cm/100Pa Ground
Fig 18
27
Air adjuster
Supply air
Fresh air
Return air
Fig 19
4.7.2 Install blast tubes
The rectangular blast tubes can be connected directly with the outlet of indoor
unit and lead to the air diffuser with the total length less than 6 m.
The flow speed at each outlet of the air diffuser shall be basically uniform
to meet the requirement of air-conditioning in the room as shown in Fig 20:
Rivet hole
Fig 20
28
4
2 6
Fig 21
insulating layer
steel washer
20 mixed paint
30
1.0
glass screen
pitch mortar
black sheet
fastening point
flange
Fig 22
29
CAUTION
Table 11
On the side of air pipe or under it On the top side of air pipe
12 pcs/ m 2
5 pcs/ m 2
4.7.5 Others
It is recommended that the distance between the wall and the edge of return air
tube is more than 150 mm. The following figure is the diagram of hoisting of air
duct unit :
12 10
11
Heat lnsulation
treatment
Fresh air inlet h
condenser pipe
5 gradinet>1%
water seal
Fig 23
CAUTION
30
4.8 Plenum chamber
4.8.1 Location and function of Plenum chamber
In the air outlet of the unit,the plenum chamber should be allocated and
affixed with sound absorbing material,which not only make the air flow stable
but also effectively reduce the fan noise result from abrupt change of plenum
chamber sectional area and sound-absorbing function of the inner surface.
(a)
(b)
31
e. The plenum chamber is mainly used for reducing the aerodynamic noise.
As for the noise generated by the ventilator, some measures for shock proof
shall be executed.
■ Installation requirement of the plenum chamber
a. The plenum chamber should be installed in the proper place against
moisture or damage;
b. Keep the punching plate clean without corrosion and holes not blocked;
c. The supports for plenum chamber and sound-absorbing elbow shall be
located separately.
d. The fixing screws for plenum chambers are distributed equably and the
joints are even and firm.
e. Make sure glass fiber cloth on the outside surface of sound-absorbing
baffle is even and no scratch and rusting.
(d)
Room A Room B
(b)
(e)
Room A Room B
(c)
Fig 25
CAUTION
After installation of the unit, make sure to call the after-sale personnel
of our company for debugging,or the aftereffect will be charged with the
user or installation people.
32
ELECTRIC WIRING
5.1 Connect wires to amphenol connectors
CAUTION
■ Make sure that the power specification is of accordance with one listed
on the nameplate;
■ Make sure that the capacity of power supply is proper and the section-
cross-area of room wires is more than 2.5mm 2;
■ Wiring construction must be carried out by professional;
■ As for fixed lines, the leakage protective switch and air switch should be
allocated and make sure that the distance between electrode tips is more
than 3 mm;
■ Solid cable wiring:
a. Strip off the insulating material with wire stripper about 25 mm at the
end of the solid cable;
b. Take down screws of the air-conditioner terminal;
c. Make the end of solid cable into a ring with size as large as screws
with the clamp;
d. Get screws through the ring and then fix it on the terminal;
■ Stranded wire wiring:
a. Strip off the insulating material with wire stripper about 10 mm at the
end of the stranded wire;
b. Then put the corresponding number tubes on the stripped wires(Pay
attention to the terminal number of indoor unit and outdoor unit )
c. Insert the stranded wire into connector with size as large as screws
with the clamp;
d. Take down screws of the air-conditioner terminal;
e. Get screws through the connector of the stranded wire and then fix it
on the terminal;
NOTE: Please connect power wires and connecting wires to corresponding
connectors.
WARNING
If supply cords and signal wires are broken, please replace them with
special cords.
■ Prior to wiring,affirm voltages of all parts listed on the nameplate and
then carry out the wiring construction according to Electric wiring diagram;
■ The air-conditioner should apply special power supply, leakage protective
switch and air switch in case of overload trouble.
■ In case of electric shock, get the air conditioner grounded unfailingly;
■ All wires should apply with clamping connectors or solid cable.If stranded
wires is connected to terminal, it may lead to fires.
33
■ In case of air conditioner breakdown or damage, the wiring contruction
will be firmly conformed to the electric wiring diagram;
■ Never get the cables in touch with refrigerant pipe,compressor,fan or
other operating parts;
Not remove wires of the air conditioner,or it may lead to damage or
breakdown and the manufacturer will not take responsibility for the aftermath.
CAUTION
34
5. 4 Power wiring diagram
There are many kinds of power wiring diagram for different user powers
and models, make sure the section-cross area of wire that users purchased
is not less than those specifications list in the following figures:
Fig 1 Fig 2
Fig 3 Fig 4
Fig 5 Fig 6
35
Outdoor unit Indoor unit Outdoor unit Indoor unit
Fig 7 Fig 8
Fig 9
NOTE:
1. The signal terminal block includes five types: 3 terminals, 4 terminals,
5, 6 and 7 terminals.Therefore, please connect the units according to the
actual ones so that indoor unit is connected to the outdoor unit with the
same terminals.As for the terminals of indoor unit is less than 3 ,just
connect the unit with the outdoor unit with 4 terminals.
2.If there is no 4 Line for the outdoor electric control panel (connecting line
of outdoor coil temperature sensors),please carry out electric wiring
according to the actual electric wiring nameplate,otherwise, the system will
display faults.
36
5. 4 Electric wiring
NOTE:The cross-section areas of wires or lines should not be less than the
corresponding ones listed in the table below; Besides, if the power wires is
quite long from the unit, please choose the windings with larger cross-
section area to guarantee the nomal power supply.
2 2 2
Cooling only 3×1.0 mm 4×0.75 mm 5×4.0 mm
2
Cooling &Heating 3×1.5 mm
96 KBtu/h 3×0.75 mm +
2
2
Cooling &Heating 2 2
5×4.0 mm
5×2.5 mm 4×0.75 mm
with Auxiliary heater
37
5. 5 Fault codes
Fault codes table(ZKX-FE-02/D , ZKX-FEM-02/D)
38