Date

aps
10/11/2023

Created with DIALux


aps

Preface

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
aps

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


Philips - RS141B 1xLED12-32-/840 (1x LED12-32-/840) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
............................
Regent - System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80 (1x . . . . . . . . . . . . . . . . . . . . . . . . . 8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAQ ICE INS m1200 LED4450-840 WB WH DALI)

Site 1
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
.............................

Site 1

Building 1
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
.............................

Site 1 - Building 1

Storey 1
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 .............................
Room list / Light scene 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 .............................
Calculation objects / Light scene 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 .............................

Site 1 - Building 1 - Storey 1

Room 1
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 .............................
Summary / Light scene 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 .............................
Calculation objects / Light scene 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 .............................
Working plane (Room 1) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . 38
.............................
aps

Table of Contents

Working plane (Room 1) / Light scene 2 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . 39


.............................

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
.............................
aps

Description

5
aps

Luminaire list

Φtotal Ptotal Luminous efficacy


331812 lm 2520.0 W 131.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 Philips RS141B 1xLED12-32-/840 16.0 W 1196 lm 74.7 lm/W

72 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

6
aps

Product data sheet

Philips - RS141B 1xLED12-32-/840

P 16.0 W

ΦLamp 1200 lm

ΦLuminaire 1196 lm

η 99.65 %

Luminous efficacy 74.7 lm/W

CCT 4000 K Polar LDC

CRI 80

CoreLine Recessed Spot – for every project, where light really matters
CoreLine Recessed Spot delivers on the CoreLine promise of
innovative, easy to use and high-quality luminaires. CoreLine
Recessed Spot is a recessed spot range designed to replace
halogen-based luminaires. Its halogen-like look and attractive price
make it easier for customers to make the switch to LED. This product
provides a natural lighting effect for accent lighting applications, as
well as instant energy savings and much longer lifetime – an
environmentally friendly solution. With the push-in connectors,
installation is fast and straightforward.

Cone diagram

7
aps

Product data sheet

Regent - System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80

Article No. 2005.5045 - TRAQ


ICE INS m1200
LED4450-840 WB WH
DALI

P 33.0 W

ΦLamp 4450 lm

ΦLuminaire 4459 lm
Polar LDC
η 100.19 %

Luminous efficacy 135.1 lm/W

CCT 4000 K

CRI 80

System batten luminaire Traq ICE m1200, for mounting on ICE


mounting rail, with LED, system power: 28 W, standby power 0.5 W,
luminous flux of luminaire 4450 lm, colour rendering index CRI > 80,
colour temperature 4000 K, neutral white, colour tolerances SDCM 3,
lifetime LED L80 72'000 h, photobiological safety: the luminaire poses
no danger (RG0), 230 V, direct light emission, gear tray made of
aluminium white similar to RAL 9016 with UV-resistant LED optics in
polymethyl methacrylate (PMMA), wide beam, 1 integral control gear,
DALI2, with halogen-free wiring, support profile and system
components to be ordered separately
protection class I, ingress protection IP20, impact strength: IK
06, service temperature range 0 to +35 °C, this product contains a
light source of energy efficiency class B and EPREL registration
number: 1249135 L = 1186 mm, B = 65 mm, H = 66 mm
UGR diagram (SHR: 0.25)

8
aps

Site 1
Luminaire layout plan

9
aps

Site 1
Luminaire layout plan

Manufacturer Philips P 16.0 W

Article name RS141B 1xLED12-32- ΦLuminaire 1196 lm


/840

Fitting 1x LED12-32-/840

9 x Philips RS141B 1xLED12-32-/840

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.517 m / 21.193 m /
3.859 m 1.517 m 21.193 m 3.859 m 29

X-direction 9 pcs., Centre - 4.551 m 21.193 m 3.859 m 30


centre, 3.034 m
7.585 m 21.193 m 3.859 m 31
Y-direction 1 pcs., Centre -
centre, 5.208 m 10.619 m 21.193 m 3.859 m 32

Arrangement A2 13.653 m 21.193 m 3.859 m 33

16.687 m 21.193 m 3.859 m 34

19.722 m 21.193 m 3.859 m 35

22.756 m 21.193 m 3.859 m 36

25.790 m 21.193 m 3.859 m 37

10
aps

Site 1
Luminaire layout plan

Manufacturer Regent P 33.0 W

Article No. 2005.5045 - TRAQ ΦLuminaire 4459 lm


ICE INS m1200
LED4450-840 WB WH
DALI

Article name System batten


luminaire Traq ICE
m1200 28W 4450lm
CRI > 80

Fitting 1x TRAQ ICE INS


m1200 LED4450-840
WB WH DALI

35 x Regent System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 3.115 m / 1.700 m /
3.800 m 3.115 m 1.700 m 3.800 m 1

X-direction 5 pcs., Centre - 8.491 m 1.700 m 3.800 m 2


centre, 5.376 m
13.867 m 1.700 m 3.800 m 3
Y-direction 7 pcs., Centre -
centre, 3.400 m 19.243 m 1.700 m 3.800 m 4

Arrangement A1 3.115 m 5.099 m 3.800 m 5

8.491 m 5.099 m 3.800 m 6

13.867 m 5.099 m 3.800 m 7

19.243 m 5.099 m 3.800 m 8

3.115 m 8.499 m 3.800 m 9

8.491 m 8.499 m 3.800 m 10

11
aps

Site 1
Luminaire layout plan

X Y Mounting Luminaire
height

13.867 m 8.499 m 3.800 m 11

19.243 m 8.499 m 3.800 m 12

3.115 m 11.898 m 3.800 m 13

8.491 m 11.898 m 3.800 m 14

13.867 m 11.898 m 3.800 m 15

19.243 m 11.898 m 3.800 m 16

3.115 m 15.298 m 3.800 m 17

8.491 m 15.298 m 3.800 m 18

13.867 m 15.298 m 3.800 m 19

19.243 m 15.298 m 3.800 m 20

3.115 m 18.697 m 3.800 m 21

8.491 m 18.697 m 3.800 m 22

13.867 m 18.697 m 3.800 m 23

19.243 m 18.697 m 3.800 m 24

3.115 m 22.097 m 3.800 m 25

8.491 m 22.097 m 3.800 m 26

13.867 m 22.097 m 3.800 m 27

19.243 m 22.097 m 3.800 m 28

24.619 m 1.700 m 3.800 m 38

24.619 m 5.099 m 3.800 m 39

24.619 m 8.499 m 3.800 m 40

24.619 m 11.898 m 3.800 m 41

24.619 m 15.298 m 3.800 m 42

24.619 m 18.697 m 3.800 m 43

12
aps

Site 1
Luminaire layout plan

X Y Mounting Luminaire
height

24.619 m 22.097 m 3.800 m 44

13
aps

Site 1
Luminaire list

Φtotal Ptotal Luminous efficacy


166829 lm 1299.0 W 128.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 Philips RS141B 1xLED12-32-/840 16.0 W 1196 lm 74.7 lm/W

35 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

14
aps

Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


164983 lm 1221.0 W 135.1 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

37 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

15
aps

Building 1 · Storey 1 (Light scene 1)


Room list

16
aps

Building 1 · Storey 1 (Light scene 1)


Room list

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


1221.0 W 649.81 m² 1.88 W/m² = 0.51 W/m²/100 lx (Room) 370 lx
2.04 W/m² = 0.55 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

37 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80 33.0 W 4459 lm
- TRAQ ICE
INS m1200
LED4450-
840 WB
WH DALI

17
aps

Building 1 · Storey 1 (Light scene 2)


Room list

18
aps

Building 1 · Storey 1 (Light scene 2)


Room list

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


924.0 W 649.81 m² 1.42 W/m² = 0.46 W/m²/100 lx (Room) 310 lx
1.54 W/m² = 0.50 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

28 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80 33.0 W 4459 lm
- TRAQ ICE
INS m1200
LED4450-
840 WB
WH DALI

19
aps

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


164983 lm 1221.0 W 135.1 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

37 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

20
aps

Building 1 · Storey 1 (Light scene 1)


Calculation objects

21
aps

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 370 lx 81.9 lx 707 lx 0.22 0.12 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

22
aps

Building 1 · Storey 1 (Light scene 2)


Calculation objects

23
aps

Building 1 · Storey 1 (Light scene 2)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 310 lx 52.0 lx 635 lx 0.17 0.082 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

24
aps

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area 649.81 m² Clearance height 2.800 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.800 m – 3.000 m


Walls: 34.1 %,
Floor: 88.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

25
aps

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 370 lx ≥ 200 lx WP1

Uo (g1 ) 0.22 ≥ 0.40 WP1

Lighting power density 2.04 W/m² –

0.55 W/m²/100 lx –

Energy estimation(2) Consumption [161.18 - 201.47] kWh/a max. 22750 kWh/a

Room Lighting power density 1.88 W/m² –

0.51 W/m²/100 lx –

(1) Based on a rectangular space of 27.307 m x 23.797 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

37 Regent 2005.5045 System batten luminaire Traq ICE m1200 – 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 28W 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

26
aps

Building 1 · Storey 1 · Room 1 (Light scene 2)


Summary

Ground area 649.81 m² Clearance height 2.800 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.000 m


Walls: 34.1 %,
Floor: 88.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

27
aps

Building 1 · Storey 1 · Room 1 (Light scene 2)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 310 lx ≥ 200 lx WP1

Uo (g1 ) 0.17 ≥ 0.40 WP1

Lighting power density 1.54 W/m² –

0.50 W/m²/100 lx –

Energy estimation(2) Consumption [120.24 - 152.46] kWh/a max. 22750 kWh/a

Room Lighting power density 1.42 W/m² –

0.46 W/m²/100 lx –

(1) Based on a rectangular space of 27.307 m x 23.797 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

28 Regent 2005.5045 System batten luminaire Traq ICE m1200 – 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 28W 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

28
aps

Building 1 · Storey 1 · Room 1


Luminaire layout plan

29
aps

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer Regent P 33.0 W

Article No. 2005.5045 - TRAQ ΦLuminaire 4459 lm


ICE INS m1200
LED4450-840 WB WH
DALI

Article name System batten


luminaire Traq ICE
m1200 28W 4450lm
CRI > 80

Fitting 1x TRAQ ICE INS


m1200 LED4450-840
WB WH DALI

28 x Regent System batten luminaire Traq ICE m1200 28W 4450lm CRI > 80

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.413 m / 1.170 m /
3.000 m 4.413 m 1.170 m 3.000 m 1

X-direction 4 pcs., Centre - 9.888 m 1.170 m 3.000 m 2


centre, Distances not
equal 15.363 m 1.170 m 3.000 m 3

Y-direction 7 pcs., Centre - 21.763 m 1.170 m 3.000 m 4


centre, Distances not
equal 4.413 m 4.651 m 3.000 m 5

Arrangement A1 9.888 m 4.651 m 3.000 m 6

15.363 m 4.651 m 3.000 m 7

21.763 m 4.651 m 3.000 m 8

4.413 m 8.132 m 3.000 m 9

9.888 m 8.132 m 3.000 m 10

30
aps

Building 1 · Storey 1 · Room 1


Luminaire layout plan

X Y Mounting Luminaire
height

15.363 m 8.132 m 3.000 m 11

21.763 m 8.132 m 3.000 m 12

4.413 m 11.613 m 3.000 m 13

9.888 m 11.613 m 3.000 m 14

15.363 m 11.613 m 3.000 m 15

21.763 m 11.613 m 3.000 m 16

4.413 m 15.094 m 3.000 m 17

9.888 m 15.094 m 3.000 m 18

15.363 m 15.094 m 3.000 m 19

21.763 m 15.094 m 3.000 m 20

4.413 m 18.575 m 3.000 m 21

9.888 m 18.575 m 3.000 m 22

15.363 m 18.575 m 3.000 m 23

21.763 m 18.575 m 3.000 m 24

4.413 m 22.056 m 3.000 m 25

9.888 m 22.056 m 3.000 m 26

15.363 m 22.056 m 3.000 m 27

21.763 m 22.056 m 3.000 m 28

Individual luminaires

X Y Mounting Luminaire
height

26.781 m 20.380 m 2.800 m 29

26.716 m 16.749 m 2.800 m 30

26.563 m 13.187 m 2.800 m 31

31
aps

Building 1 · Storey 1 · Room 1


Luminaire layout plan

X Y Mounting Luminaire
height

26.665 m 7.742 m 2.800 m 32

26.748 m 3.179 m 2.800 m 33

0.708 m 20.380 m 2.800 m 34

1.238 m 14.724 m 2.800 m 35

0.968 m 9.407 m 2.800 m 36

0.968 m 2.407 m 2.800 m 37

32
aps

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy


164983 lm 1221.0 W 135.1 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

37 Regent 2005.5045 System batten luminaire Traq ICE m1200 28W 33.0 W 4459 lm 135.1 lm/W
- TRAQ ICE 4450lm CRI > 80
INS m1200
LED4450-
840 WB
WH DALI

33
aps

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

34
aps

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 370 lx 81.9 lx 707 lx 0.22 0.12 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

(1) Based on a rectangular space of 27.307 m x 23.797 m and SHR of 0.25.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

35
aps

Building 1 · Storey 1 · Room 1 (Light scene 2)


Calculation objects

36
aps

Building 1 · Storey 1 · Room 1 (Light scene 2)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 310 lx 52.0 lx 635 lx 0.17 0.082 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

(1) Based on a rectangular space of 27.307 m x 23.797 m and SHR of 0.25.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

37
aps

Building 1 · Storey 1 · Room 1 (Light scene 1)


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 370 lx 81.9 lx 707 lx 0.22 0.12 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

38
aps

Building 1 · Storey 1 · Room 1 (Light scene 2)


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 310 lx 52.0 lx 635 lx 0.17 0.082 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

39
aps

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464- 1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas- discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3,300 K
neutral white (nw) ≥ 3,300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

Control group A group of luminaires that are dimmed and controlled together. For each lighting scene,
a control group provides its own dimming value. All luminaires within a control group
share this dimming value. The control groups with their luminaires are automatically
determined by DIALux on the basis of the created light scenes and their luminaire
groups.

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13.3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

40
aps

Glossary

Daylight autonomy Describes what percentage of the daily working time the required illuminance is met by
daylight. The nominal illuminance is used from the room profile, unlike described in EN
17037. The calculation is not done in the centre of the room but at the placed sensor
measuring point. A room is considered sufficiently supplied with daylight if it achieves at
least 50% daylight autonomy.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Energy evaluation Based on an hourly calculation procedure for daylight in indoor spaces, considering the
project geometry and any existing daylight control systems. Orientation and location of
the project are also considered. The calculation uses the specified system power of the
luminaires to determine the energy demand. A linear relationship between power and
luminous flux in the dimmed state is assumed for daylight-controlled luminaires. Times
of use and nominal illuminance are determined from the usage profiles of the spaces.
Switched-on luminaires that are explicitly excluded from control also consider the
specified times-of-use. The daylight control systems use a simplified control logic that
closes them at an outdoor horizontal illuminance of 27,500lx.

The calendar year 2022 is used as a reference only. It is not a simulation of this year. The
reference year is only used to assign the days of the week to the calculated results. The
changeover to summer time is not considered. The reference sky type used is the
average sky described in CIE 110 without direct sunlight.

The method was developed together with the Fraunhofer Institute for Building Physics
and is available for review by the Joint Working Group 1 ISO TC 274 as an extension of
the previous annual regression-based method.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

41
aps

Glossary

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/(m² * a)

42
aps

Glossary

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

43
aps

Glossary

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

R(UG) max Measure of the psychological glare in indoor spaces.


In addition to the luminance of luminaires, the level of the R(UG) value also depends on
the observer position, the viewing direction and the ambient luminance. The calculation
is made according to the table method, see CIE 117. Among other things, EN 12464-
1: 2021 specifies maximum permissible R(UG)- values R(UGL) for various indoor workplaces.

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

44
aps

Glossary

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.