TYPICAL WIRING DIAGRAM 053-264 ISSUE: 1

NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator DEEP SEA ELECTRONICS
manual, refer to DSE Publication: 057-346 DSE2610 Operator Manual available from DSE2610 INSTALLATION INSTRUCTIONS
www.deepseaelectronics.com for more information.
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR

NOTE: Accessing the ‘Running’ Configuration Editor on the DSE2610 module does not
cause the host DSE controller to enter its ‘Running’ Configuration Editor.

• The ‘Running’ Configuration Editor can be entered without stopping the engine. All protections
remain active whilst using the ‘Running’ Configuration Editor.

• Press and hold the (Tick) button to enter the ‘Running’ Conifguration Editor.

EDITING A PARAMETER

NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is
automatically exited.

• Enter the editor as described above.

• Press the (Right) or (Left) buttons to cycle to the section to view/change.

• Press the (Up) or (Down) buttons to select the parameter to view/change within
the currently selected section.

• To edit the parameter, press the (Tick) button to enter edit mode. The parameter begins
to flash to indicate editing.

• Press the (Up) or (Down) buttons to change the parameter to the required value.

• Press the (Tick) button to save the value. The parameter ceases flashing to indicate that
it has been saved.

• To exit the editor and save the changes, press and hold the (Tick) button.

Deep Sea Electronics Ltd. Deep Sea Electronics Inc.


Tel:+44 (0)1723 890099 Tel: +1 (815) 316 8706
Email: [email protected] Email: [email protected]
Web: www.deepseaelectronics.com Web: www.deepseaelectronics.com
‘RUNNING’ CONFIGURATION EDITOR PARAMETERS REQUIREMENTS FOR UL CERTIFICATION
Section Parameter As Shown On Display Value Specification Description
Display Contrast 0% Screw Terminal
• 4.5 lb-in (0.5 Nm)
Language English, Other Tightening Torque
Load Demand Priority 1 Conductors • Terminals suitable for connection of conductor size 13 AWG to 20 AWG
) Commissioning Screens Active / Inactive (0.5 mm² to 2.5 mm²).
Override Starting Alarms Active / Inactive • Conductor protection must be provided in accordance with NFPA 70,
Voltage Adjust Article 240
0%
(manual mode only, breaker open) • Low voltage circuits (35 V or less) must be supplied from the engine
Frequency Adjust starting battery or an isolated secondary circuit.
0%
(manual mode only, breaker open) • The communication, sensor, and/or battery derived circuit conductors shall
Mains Decoupling Test Mode Active / Inactive be separated and secured to maintain at least ¼” (6 mm) separation from
Active / Inactive the generator and mains connected circuit conductors unless all
Voltage and Frequency Injection Testing conductors are rated 600 V or greater.
(Remains active for 3 minutes)
Engine Governor Gain 0.0 Communication
• Must be connected to communication circuits of UL Listed equipment
Frequency Adjust Offset 0.0 Hz Circuits
DPF Auto Regen Inhibit Active / Inactive DC Output Pilot Duty • 0.5 A
DPF Manual Regen Active / Inactive Mounting • Suitable for flat surface mounting in Type 1 Enclosure Type rating with
Power Const Power / Frequency- surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Power Control Mode • Suitable for pollution degree 3 environments when voltage sensing inputs
Levels Power / Voltage-Power
Const Power Factor / Voltage- do not exceed 300 V. When used to monitor voltages over 300 V device to
kVAr Control Mode Reactive Power / Power-Power be installed in an unventilated or filtered ventilation enclosure to maintain a
Factor / Const Reactive Power pollution degree 2 environment.
Load Parallel Power 0% Operating
• -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Load Parallel kVAr 0% Temperature
Load Parallel PF 0.00 pf
Frequency Droop Offset 0.00 % (0.00 Hz)
Freq. Droop Ramp Rate 0.0 % DIMENSIONS AND MOUNTING
Voltage Droop Offset 0.00 % (0.0 V)
Voltage Droop Ramp Rate 0.0 % Parameter Specification
About Variant 2610 Dimensions 245 mm X 184 mm X 51 mm (9.6” X 7.2” X 2.0”)
Application V0.0.0 Panel Cutout 220 mm X 160 mm (8.7” X 6.3”)
USB ID 0 Weight 0.98 kg (2.16 lb)
Bootloader V0.0.0 Operating Temperature -30 ºC to +70 ºC (-22 ºF to +158 ºF)
Storage Temperature -40 ºC to +80 ºC (-40 ºF to +176 ºF)

FIXING CLIPS

NOTE: In conditions of excessive vibration, mount the control panel on suitable anti-vibration
mountings

The module is held into the control panel fascia using the supplied fixing clips.
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the
clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the DSE module’s case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip
are inside their allotted slots.
• Turn the fixing clip screws clockwise until they make contact with the panel fascia.
• Turn the screws a quarter of a turn to secure the module into the control panel’s fascia. Care must be
taken not to over tighten the fixing clip screws.