M Agile - Erection - Elect - SC Rates
M Agile - Erection - Elect - SC Rates
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
3 All fixing accessories such as foundation bolts, nuts and bolts etc as required.
5 Rubber mats shall be provided in front and back of the HT switchgear as per IS 15652-2006.
Interlocking shall be provided between transformer door and HT breaker panel. When
7
transformer door
open respective SF6 breaker shall be tripped.
10 Provision shall be made for all HT breakers to be hooked up with BAS for status indication.
A HV INSTALLATION
Trivector meter of SECURE make or approved equal by Local Electricity Board of accuracy
class 0.2
Metering cubicle as described above.
Dual Ratio 5 Amps Secondry CT of suitable burden but not less than 15 VA accuracy Class
0.5
1 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
The potential transformer shall be as specified below:
Ratio : 11000/ V3/ 110/ V3/ 110 V
V A Burdan : 100 V A for 100/V3 and 110 V winding
Class : CL –1 for both the windings.
Basic Insulation level : Same as mentioned for VCB in clause -6.
Over voltage factor : 1.2 Continuous
Single phase PT’S shall be used and shall be connected in Star/ Star.
3 Electricity Board Metering Panel (11 KV)-CHECK METER 1 Nos 2,500.00 2,500.00
Trivector meter of SECURE make or approved equal by Local Electricity Board of accuracy
class 0.2
Metering cubicle as described above.
Dual Ratio 5 Amps Secondry CT of suitable burden but not less than 15 VA accuracy Class
0.5
Supply, installation, testing and commissioning of battery charger unit with provisions of
7 Boost Charing, and Float charging. Suitable for 240 V single phase + 10% AC, 50 Hz power 3 Set 2,100.00 6,300.00
supply as per specifications.
Supply and fixing in position the approved “Shock Treatment Charts” written in English and
8 4 No. 80.00 320.00
Local Language. These charts shall be framed in teak wood frame and covered with glass.
9 Supply and fixing in position the fire extinguishers carbon-di-odide type 2.5 Kgs capacity. 4 No. 80.00 320.00
2 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Supply and fixing in position the best quality Danger Boards of approved shape and size as
10 4 No. 40.00 160.00
specified by Local Electricity Authorities written in English & Local Languages.
Supply and fixing in position 1000 mm wide rubber matting of 11KV grade as per electricity
11 50 RM 50.00 2,500.00
rules.
Supply of fire buckets 5 nos. in each set duly filled with fine sand and fixed on an angle iron
12 frame as per requirement of local authorities. Fire buckets shall be painted red from 3 Sets 500.00 1,500.00
outside and white from inside with additional handle at the bottom.
Supply and fixing in position the approved single line diagram framed in 1000 x 800 mm size
13 3 No. 100.00 300.00
glass frame in the sub station.
14 Supply of first aid box of approved make as per specification. 5 No. 100.00 500.00
15 Supply of tool kit with 1 pair 11 KV rubber hand gloves of approved make. 2 No. - -
TOTAL CARRIED TO SUMMARY 64,200.00
The rates under this section shall also include the following:
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
2 Providing and fixing approved cable supports and grouting the same as required.
Ensuring that provision is left in buildings and trenches as the work proceeds, for
4
incorporating of cable
supports at a later date.
5 Providing all, fixing accessories such as clamping devices, nuts and bolts etc.
8 Wherever cables cross walls provide proper sleeves at the time of civil work.
Supplying and laying following size 11 KV grade XLPE aluminium conductor armoured
1
cables laid over MS supports in existing trenches.
3 C x 300 sq.mm 11 KV XLPE cable (between metering panel room to HT panel and HT
1.1 RM 94.00 -
panel to transformers).
3 C x 240 sq.mm 11 KV XLPE cable (between metering panel room to HT panel and HT
1.2 220 RM 80.00 17,600.00
panel to transformers).
3 C x 185 sq.mm 11 KV XLPE cable (between metering panel room to HT panel and HT
1.3 RM 70.00 -
panel to transformers).
Supplying and making cable end terminations for the following size of 11KV grade, XLPE
2 aluminium conductor armoured cable including termination kit complete heat shrinkable
sleeve etc.
3 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Supplying and laying of following 1100 volts grade PVC insulated sheathed copper
4 conductor armoured control cables in existing trenches cables trays, clamped on wall with
suitable saddles, fixing bolts, including testing and commissioning.
4.1 12 Core 2.5 sq mm PVC insulated copper conductor armoured control cables 50 RM 18.00 900.00
Cable end termination of the following PVC insulated sheathed aluminium conductor
5 armoured cables of 1100 volt grade including supplying and fixing of crimping lugs. Double
compression glands with earthing provision and cable sockets
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
Jointing by rivetting and brazing after rivetting in case of copper and welding / bolting in
case
3 of GI earthing.
4 Cutting chases / holes and making good the same wherever required.
All equipment motors, DB’s, panels to be connected on both ends (double earthing) with
suitable
9 strip / wires.
10 Soil resistingly test shall be conducted of the area where earth pits are to be located.
Supply and fixing of following bare copper /GI tapes / wires including all necessary fixing
1
accessories and effecting connections as per specifications.
4 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Providing and laying of 14.35 mm dia and 3 meter length.copper bonded earth rod in 150
mm dia. in an augured hole in ground , surrounded by ground enhancement material as per
specification. Inspection chamber shall be of 400 x 500 mm with concrete base CI manhole
cover with frame painted with bitumastic paint. 2 Nos. of 50 x 6 mm cross section & 300
6.1 mm long copper strip to be clamped with copper claded rod electrode have sufficient nos ( 29 Nos. 4,000.00 116,000.00
But not less than 4 Nos.) of 10 mm dia. GI nuts & bolts for connection to the equipment /
interconnection to the other pits to form equi-potential bonding .The pH value of ground
enhance material shall be 6.9 to 7.2 of 1000gm / lit @ 20 deg.c.The minimum 30 Kg of
ground enhancement material shall provided for each electrode.
Providing earthing stations at locations as called for including providing and laying 600 x
600 x 3.15 mm thick tinned copper electrode with 2 Nos 50 x 6 mm thick copper strip,
from earth electrode to inspection chamber,50 mm dia medium class G I pipe CI /
chequered plate funnel with 20 gauge G I wire mesh, masonry chamber 1000 x 500 mm
Nos. 4,500.00 -
with concrete base, CI chequered plate manhole cover with frame and bitumastic paint
and packing of mixture of charcoal and common salt around plate electrode complete
with digging of pit upto permanent misture level but not less than 3 metres and back filling
as required.
The rates for all point wiring items shall also include supplying and fixing of the following:
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
Conduits, conduit supporting structural members including spacers, clamps etc, bushes
2
and other fittings as well as
deeper JB with PVC connectors.
3 Approved GI saddles and grouting the same for exposed conduit work.
Qoated rate for MCB controlled primary point shall include all the materials and works
6
necessary including circuit length from MCB DB upto 1st switch board.
Embedding conduits and accessories in walls and floors etc. during construction and / or
7 cutting chases (with chase cutting machine) and making good the same as necessary in
the case of concealed conduit work.
PVC insulated copper conductor stranded flexible PVC insulated wire of Green colour or
9
Green colour
with yellow band for earthing of fixtures, outlet boxes and third pin of socket outlet.
10 Repainting of conduits, outlet boxes and junction boxes where ever damaged.
5 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
11 All wires shall be IS approved, 1100 volt grade, stranded flexible PVC insulated, FRLS wires.
All sockets shall be shuttered type with earth terminal. All sockets for UPS system shall be
12
provided with distinct RED dot on the socket for easy identification.
Suitable rating of plugs top shall also be provided within the quoted rates for all industrial
13
type and splash proof
socket outlets.
14 Separate neutral and earthing wire shall be provided for each circuit.
PVC conduits shall be used for embeded conduiting where as GI conduits shall be used for
16
surface conduiting
in places with saline & humid climate where as MS conduits shall be used for surface
conduiting in places with
dry climate.
Wiring of following light points with 1.5 sq.mm PVC insulated copper conductor 1100 volts
grade stranded flexible FRLS wires in embeded 25mm dia. heavy duty FRLS PVC conduit as
per IS 9537 part-3 or surface mounted 25 mm dia 16 gauge GI conduit including providing
1
and fixing of 6 amps single pole rocker operated flush mounted switches of approved
quality colour make and design in 1.6 mm thick GI box and earthing of fixture and the
outlet box with 1.5 Sq.mm PVC insulated copper conductor stranded flexible FRLS wire.
MCB controlled Primary point (from DB to switch board & from DB to 1st Light point-Avg
1.1 1098 Pt 720.00 790,560.00
length 30 mtr)
MCB controlled Secondary point ( from light point to light point - cost of switch & board
1.2 2675 Pt 288.00 770,400.00
NOT included-Avg length 12 mtr)
Primary point with switch ( from switch board to first point - cost of switch & board
1.3 665 Pt 275.00 182,875.00
included- Avg length 10 mtr)
Secondary point without switch & Borad ( from light point to light point - cost of switch &
1.4 761 Pt 120.00 91,320.00
board NOT included-Avg length 5 mtr)
Secondary point (from switch board to switch board looping- cost of switch & board NOT
1.5 124 Pt 190.00 23,560.00
included)
Wiring for following 250 volt single phase and neutral 6 amps switch socket outlet with
2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires in
embeded 25mm dia. heavy duty FRLS PVC conduit as per IS 9537 part-3 or surface
2 mounted 25 mm dia 16 gauge GI conduit, including providing and fixing of 6 amps switch
and 6A 3 pin socket of approved make colour and design in 1.6 mm thick GI box with grid
plate and earthing of third pin of the socket outlet and the GI box with 2.5 Sq.mm PVC
insulated copper conductor stranded flexible FRLS wire.(Avg length 30 mtr)
Wiring for 250 volts single phase and neutral 6/16 amps switch and socket outlet with
2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires
in embeded 25mm dia. heavy duty FRLS PVC conduit as per IS 9537 part-3 or surface
3 mounted 25 mm dia 16 gauge GI conduit, including providing and fixing of 16 amps switch
and 5 pin socket of approved make and design in 1.6 mm thick GI boxes with grid plates
and earthing the third pin of socket outlet with 2.5 Sq. mm PVC insulated copper
conductor stranded flexible FRLS wire. (Avg length 30 mtr)
6 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
3.1 Maximum 1 nos. of 6/16A switch socket in one circuit 12 Pts. 750.00 9,000.00
3.2 Maximum 2 nos. of 6/16A switch socket in one circuit 90 Pts. 800.00 72,000.00
Wiring for Exhaust fan point with 2.5 sq. mm. Insulated copper conductor 1100 volts grade
stranded flexible FRLS wires of approved make in 25mm dia. 2mm thick embeded PVC
conduit or surface mounted 25 mm dia 16 gauge GI conduit including providing and fixing of
4 6 amps flush mounted switch at the normal switch level in 2 mm thick GI box and 6 amps 3 20 Pts. 300.00 6,000.00
pin flush mounted socket outlet near exhaust fan and earthing of exhaust fan through the
third pin of the socket outlet and GI box with 2.5 sq. mm. PVC insulated copper
conductor strande flexible FRLS wire.
Supply, installation & wiring of 230 V bulk head lamp with on/off switch for Lift shafts with
3C x 2.5 sq.mm YWY cable in 32 mm dia MS surface mounted conduits including providing
5 and fixing bulk head light, 6A switch with earth wire. For costal area GI conduit accessories
shall be considered where as for non costal areas MS conduits & accessories shall be
considered. (Exclude cost of bulk head fitting)
5.1 10 Nos.Bulk head lamps with switch on one circuit 36 Pts 870.00 31,320.00
Wiring for following 250 volts single phase and neutral 6 amps switched socket outlet for lift
shafts with 3C x 2.5 Sqmm YWY cable in surface mounted 32 mm dia 16 gauge GI conduit
6 including providing and fixing of 16 amps 3 pin switched socket of approved make and
design in 2 mm thick GI boxes with grid plates and earthing of third pin of socket outlet
and GI box
6.1 10 Nos. 6 amps switched socket outlet on one circuit 36 Pts. 890.00 32,040.00
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
Cable supporting structural members including spacers, clamps etc, bushes and other
2
fittings
3 Providing all fixing accessories such as clamping devices nuts, bolts and screws.
4 Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.
Fire retardent paint one meter on both side of wall penetration and at termination as per
8
specifications.
7 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Supplying & laying of following 1100 volt grade XLPE insulated PVC inner sheathed and
FRLS PVC outer sheathed aluminium conductor armoured cables as per specification in
1
existing trenches, cable trays, ducts, clamped to wall with suitable clamps including, saddles
fixing bolts, connecting testing and commissioning.
Supplying & laying of following 1100 volt grade XLPE insulated FRLS PVC outer sheathed
copper conductor armoured cable as per specification in existing trenches, cable trays
2
ducts , clamped to wall with suitable clamps, including fixing bolts, connecting testing and
commissioning.
Providing Mains Wiring from Meter panel panel to DB using copper conductor PVC
insulated FR wires in rigid PVC conduits of 32 mm and 1.8mm wall thickness ISI mark,
3 concealed in wall & ceiling with necessary boxes/pull boxes complete with continuous
earthing up to main switchboard from the Distribution board using PVC insulated green
color copper earth-wire.
3.1 4 x 6 sq.mm + 1 x 4 sq mm copper wire RM 27.00 -
8 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Cable end termination of the following XLPE insulated FRLS PVC outer sheathed
4 aluminium/copper conductor armoured cables of 1100 volt grade including supplying and
fixing of bimettalic crimping lugs, double compression glands with earthing.
4.1 3.1/2 core 400 sq. mm.Aluminium Cable 2 Nos. 450.00 900.00
4.2 3.1/2 core 300 sq. mm.Aluminium Cable 96 Nos. 350.00 33,600.00
4.3 3.1/2 core 240 sq. mm. Aluminium Cable 6 Nos. 300.00 1,800.00
4.4 3.1/2 core 185 sq. mm. Aluminium Cable 30 Nos. 250.00 7,500.00
4.5 3.1/2 core 150 sq. mm. Aluminium Cable 98 Nos. 220.00 21,560.00
4.6 3.1/2 core 120 sq. mm. Aluminium Cable 20 Nos. 180.00 3,600.00
4.7 3.1/2 core 95 sq. mm. Aluminium Cable 18 Nos. 150.00 2,700.00
4.8 3.1/2 core 70 sq. mm. Aluminium Cable 4 Nos. 130.00 520.00
Supply and fixing of factory fabricated GI ladder type cable trays, with radial bends,
5
suspenders and supports as per specification and of the following sizes.
Supply and fixing of perforated type factory fabricated GI cable trays of the following sizes
6
including providing GI suspenders and supports as per specifications..
9 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
TOTAL CARRIED TO SUMMARY 1,387,644.00
A DISTRIBUTION BOARDS
Panels shall be fabricated out of 2 mm thick CRCA sheet steel in cubical formation,
compartmentalized in Form 3b Construction, floor mounted, free standing and shall be dust
and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the
bottom of the panel.
Final distribution panels shall be fabricated out of 1.6 mm thick CRCA sheet steel and shall
be wall mounted. All large panels shall be provided with lifting hooks. Distribution panels
shall be fabricated in accordance with the specifications.
Note :
1.All switchgear feeders shall be with BMS compatible. Additional NO/NC shall be
required for status monitoring and remore tripping arrangement.
2. All energy meters shall be with BMS compatible with required latest communication
mode.
3.Energy meters and necessory metering arrangement shall be such that it will be easily
comunicable with BMS software protocall.
4. Electrical contractor/ panel builder shall be closely design the panel in closely
communication with BMS team.
1 Main LT Panel
(For Transformer supply)
A. Section – I
3 Nos. 96 x 96 sq.mm 0-4000 / 5 amps CTR digital ammeter with 3 nos 4000. / 5 amps, 15
ii
VA Class I CT’s.
96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch through 415 V / Ö3 :
iii
110 V /Ö3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
iv Load Manager conserve EM 6400 with KWH reading for Grid supply
4000 amps TPN electrically operated fully drawout type air circuit breaker with built in
microprocessor based release unit for protection and measurment as per specification and
with following accessories :
10 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
3 Nos. 96 x 96 sq.mm 0-4000 / 5 amps CTR digital ammeter with 3 nos 4000. / 5 amps, 15
viii
VA Class I CT’s.
96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch through 415 V / Ö3 :
ix.
110 V /Ö3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
x
phases, 4 wire.
C. Bus Bars
6300 amps 4 pole (65 KA) Aluminium bus bars with colour coded heat shrinkable insulating
sleeves
D. Outgoing
4000. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
i. indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.
1000. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
ii indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.
4000. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
v indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.(Spear with compartment only)
4000 amps TPN electrically operated fully drawout type air circuit breaker with ON / OFF /
TRIP indicating lamps with control MCB’s, shunt trip, breaker control switch etc.
Section-II
(For transformer supply)
K 4000Amps FP rating Auto Transfer Switch as per specification.
Metering for Grid side & DG side supply.
Phase indicating light through 415 /110 V PT, Primary / Secondary of PT's shall be protected
i.
by 2 amps MCB’s.
3 Nos. 96 x 96 sq.mm 0-4000 / 5 amps CTR digital ammeter with 3 nos 4000. / 5 amps, 15
ii
VA Class I CT’s.
96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch through 415 V / Ö3 :
iii
110 V /Ö3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
iv Load Manager conserve EM 6400 with KWH reading for Grid supply
4000 amps FP electrically operated fully drawout type air circuit breaker with built in
microprocessor based release unit for protection & measurment as per specification and
with following accessories :
11 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
iii. Under voltage release
3 Nos. 96 x 96 sq.mm 0-1250 / 5 amps CTR digital ammeter with 3 Nos.1250. / 5 amps 15
viii
VA CL:1 CT’s
0-500 Volt digital voltmeter with selector switch 96 x 96 mm sq. through 415 V / √3 : 110
ix.
V /√3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
x
phases, 4 wire.
M Bus Bars
6300 amps 4 pole (65 KA) Aluminium bus bars with colour coded heat shrinkable insulating
sleeves
N Outgoing
4000. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
i. indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.
1250. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
ii indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.
4000. amps FP electrically operated fully drawout type air circuit breaker with ON/OFF/TRIP
v indicating lamps with MCB’s and microprocessor based release for protection & indication
as per specification.(Spear with compartment only)
Notes :
i. All outgoing feeders shall have suitable range of followings (except capacitor feeders)
ii. All breakers shall be electrically/ mechanically interlocked as per schematic diagram.
iii. All MCCB’s shall be suitable for 50. KA (ICS) breaking capacity.
iv. All ACB's shall be suitable for …50kA( Icu=Ics=Icw for 1 sec.)
v. 415 / 110 V suitable rating control transformer shall be provided for aux. Control supply
Wiring with space heater, thermostat and control MCB’s shall be provided all vertical
vi.
sections of main LT panel.
12 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
All outgoing MCCB’s feeders shall be provided with built-in microprocessor release unit
vii.
with earth fault protection and time delay.
viii. All incoming as well as outgoing feeders shall have pad locking facility.
x. All bus bar section / backside panels shall have pad locking facility and hinged type door.
A Incoming
1000. amps, FP electrically operated fully drawout type air circuit breaker with
ON/OFF/TRIP indicating lamps with MCB’s and microprocessor based release for protection
& indication as per specification.
3 Nos. 96 x 96 sq.mm 0-1000 / 5 amps CTR digital ammeter with 3 Nos.1000 / 5 amps 15 VA
viii
CL:1 CT’s
0-500 Volt digital voltmeter with selector switch 96 x 96 mm sq. through 415 V / √3 : 110
ix
V /√3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
x
phases, 4 wire.
B Bus Bars
1250. amps 4 pole (50 KA) Aluminium bus bars with colour coded heat shrinkable insulating
i
sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
13 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
3 Nos. 96 x 96 sq.mm 0-1250 / 5 amps CTR digital ammeter with 3 nos 1250 / 5 amps, 15 VA
ii
Class I CT’s.
96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch through 415 V / Ö3 :
iii
110 V /Ö3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
iv Load Manager conserve EM 6400 with KWH reading for Grid supply
B Incoming
1250. amps 4 pole electrically operated fully drawout type air circuit breaker with
ON/OFF/TRIP indicating lamps with MCB’s and microprocessor based release for protection
& indication as per specification.
3 Nos. 96 x 96 sq.mm 0-1250 / 5 amps CTR digital ammeter with 3 Nos.1250 / 5 amps 15 VA
viii
CL:1 CT’s
0-500 Volt digital voltmeter with selector switch 96 x 96 mm sq. through 415 V / √3 : 110
ix
V /√3 PT’s, Primary and Secondary of PT’s shall be protected by 2 amp TP MCB’s
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
x
phases, 4 wire.
C Bus Bars
1250. amps 4 pole (50 KA) Aluminium bus bars with colour coded heat shrinkable insulating
i
sleeves
D Outgoing
14 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
A Incoming
200amps TPN MCCB with following accessories:
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-200 Amps digital electronic ammeter with selector switch and 200/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
iv Load Manager conserve EM 6400 with KWH reading for Grid supply
B Bus Bars
i 250 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
vii
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
15 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
0-320 Amps digital electronic ammeter with selector switch and 320/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
i 400 amps FP Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
6 Elevator Panel-01
A Incoming
320amps TPN MCCB with following accessories:
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-320 Amps digital electronic ammeter with selector switch and 320/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
iv
phases, 4 wire.
B Bus Bars
i 400 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
16 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
0-160 Amps digital electronic ammeter with selector switch and 160/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
i 200 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
8 Elevator Panel-02
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400 Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
Class – C, 20KA, TVSS surge arrestor(Lines to Neutral) & (Neutral to Earth) suitable for 3
iv
phases, 4 wire.
B Bus Bars
i 500 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-200 Amps digital electronic ammeter with selector switch and 200/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
17 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
B Bus Bars
i 250 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-200 Amps digital electronic ammeter with selector switch and 200/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
i 250 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
ii. 0-63 Amps digital electronic ammeter with selector switch and 63/5 amps 15 VA, CL 1 CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
i 63 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
18 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
C Outgoing
ii 25 amps DP MCB
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
ii. 0-63 Amps digital electronic ammeter with selector switch and 63/5 amps 15 VA, CL 1 CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
i 63 amps TPN Aluminium bus bars with coloured heat shrinkable insulated sleeve.
C Outgoing
ii 25 amps DP MCB
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-250. Amps digital electronic ammeter with selector switch and 250/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
320 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
19 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
iii
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-250. Amps digital electronic ammeter with selector switch and 250/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
320 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-320. Amps digital electronic ammeter with selector switch and 320/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
400 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
20 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel(1st & 2nd floor) -1 As described above 2 3,950.00 7,900.00
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-320. Amps digital electronic ammeter with selector switch and 320/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
400 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel(1st & 2nd floor) -2 As described above 2 3,950.00 7,900.00
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
21 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel (3rd,4th,7th & 8th floor) -1 As described above 4 3,950.00 15,800.00
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel (3rd,4th,7th & 8th floor) -2 As described above 4 3,500.00 14,000.00
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
22 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel (5th,6th & 9th floor) -1 As described above 3 3,950.00 11,850.00
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
iii
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
Office Meter Panel (5th,6th & 9th floor) -2 As described above 3 3,950.00 11,850.00
A Incoming
23 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
A Incoming
0-500 volts digital electronic volt meter with selector switch through 415 V / √3 : 110 V / √3
i.
PT, primary and secondary of PT shall be protected by 2 amps TP MCB's.
0-400. Amps digital electronic ammeter with selector switch and 400/5 amps 15 VA, CL 1
ii.
CTs .
iii. Phase indicating light through 230 V, shall be protected by 2 amps SP MCB's.
B Bus Bars
500 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves
C Outgoing
Dual source Load Manager (All Load Managers to have parameters like KW, KVA, A, V,
PF,KVAR, Active & Reactive component of power, as required & desired to complete the
v
system.) with KWH reading for Grid supply. Digital energy meter shall be as per BMS
comunication requirement.
24 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
INCOMING:
1000. amps 4 pole electrically operated fully drawout type air circuit breaker with
ON/OFF/TRIP indicating lamps with MCB’s and microprocessor based release for protection
& indication as per specification.
BUSBAR:
1000 Amps, Al Busbars continuous duty,FP with heat shrinkable sleeves, supported on
SMC supports Of 50 KA design.
ON,OFF,TRIP Indication Lamps -3 No's - 1 set
LED Type R - Y - B Phase Indicating Lamps -3 No's - 1 set
2A, MCB's - 2 Nos.
0-1000 Amps Ammeter with selector switch - 1 set
1 No. 0-500V Voltmeter with selector switch-1 set
CT of ratio 1000/5A accuracy class 0.5 - 1 No.
OUTGOING:
FOR MAIN PUMPS - 2 NOS.
Star delta Starter Suitable for Rating of Pumps. Contactor to submit Coordination chart of
the proposed make. Contractor to consider on size higher for Starter- 2 Nos.
Auto manual selector switch - 2 Nos.
Fire barriers including necessary supports and louvers for ventilation, fabricated out of
extruded aluminium/ GI sheet painted with approved paint shade as per specification
including 2 Nos. of 50x6 mm copper earthing conductor through out the length of the bus
duct. (Phase sequence shall be matched).( end connection of each length should be copper
tips )
4000.. amps 4 pole bus ducts from Main LT Panel to Rising main including 90 deg bends &
a 530 RM 1,950.00 1,033,500.00
flanges to connect LT panel.
Supply, installation, testing and commissioning of tap off boxes made out of 14 gauge CRCA
sheet steel in case of Air Insulated Rising Mains & extruded Aluminium/ GI sheet duly
26
painted in case of sandwich type Rising Mains mounted on the rising mains including
providing of following MCCB’s.
25 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
a 400 amps TPN Pole MCCB of 36 KA (Ics). with MS Enclosure No. 434.00 -
b 320 amps TPN Pole MCCB of 36 KA (Ics). with MS Enclosure No. 325.00 -
a 250 amps TPN Pole MCCB of 25 KA (Ics). with MS Enclosure 14 No. 265.00 3,710.00
b 200 amps TPN Pole MCCB of 16 KA (Ics). with MS Enclosure 20 No. 180.00 3,600.00
c 160 amps TPN Pole MCCB of 16 KA (Ics). with MS Enclosure 4 No. 180.00 720.00
d 125 amps TPN Pole MCCB of 16 KA (Ics). with MS Enclosure 3 No. 135.00 405.00
e 100 amps TPN Pole MCCB of 16 KA (Ics). with MS Enclosure 4 No. 90.00 360.00
f 63 amps TPN Pole MCCB of 16 KA (Ics). with MS Enclosure 6 No. 90.00 540.00
g 63 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure 4 No. 90.00 360.00
h 40 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure 13 No. 90.00 1,170.00
40 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure & star-delta Starter Suitable for
i 3 No. 90.00 270.00
Rating of Pumps. Contactor to submit Coordination chart of the proposed make.
j 25 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure 22 No. 90.00 1,980.00
25 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure & DOL Starter Suitable for Rating
k 2 No. 90.00 180.00
of Pumps. Contactor to submit Coordination chart of the proposed make.
l 16 amps TPN Pole MCB of 10 KA (Ics). with MS Enclosure 6 No. 90.00 540.00
Supply, installation, testing and commissioning of Auto Transfer Switch with encloser out of
28
14 gauge CRCA sheet steel providing of following ATS’s.
400Amps FP rating Auto Transfer Switch/ Contactor Logic for change over as per
a NO. 3,200.00 -
specification.
320Amps FP rating Auto Transfer Switch/ Contactor Logic for change over as per
b NO. 3,000.00 -
specification.
250Amps FP rating Auto Transfer Switch/ Contactor Logic for change over as per
c NO. 2,400.00 -
specification.
Supply, installation, testing and commissioning of the following FDB's fabricated out of 1.6
mm thick CRCA sheet steel , double door construction, powder coated with approved
shade and partitions to segregate phases. Approved lockable covers with padlocking
arrangement for each phase, recessed in wall or surface mounted final distribution boards
of the following description:
26 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Class - C (For SPN final distribution boards) (lines to Neutral) (Neutral to earth) suitable for
1 Phase as per specification and Class - C (For TPN final distribution boards) (lines to
Neutral) (Neutral to earth) suitable for 3 Phase as per specification
B Outgoing
i 32 amps TP MCB with following accessories:
2 SUB ELEVATOR DB
A Incoming
63 amps TPN Pole MCCB of 16 KA (Ics).
B Outgoing
i 63 amps FP ELCB,300mA with following accessories:
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, DP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
12 WAY TPN LDB1 & LDB2-BASEMENT 1,2,LG Floor As described above 8 1,100.00 8,800.00
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, FP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
27 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, FP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, DP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
12 WAY TPN LIFT LOBBY DB (BASEMENT-2 TO P6 FLOOR) As described above 1 1,100.00 1,100.00
B SUB Incoming
25 amps DP RCCB, 30mA -
C Outgoing
i 16. amps SP MCB
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, DP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
12 WAY TPN LDB1 & LDB2 - Podiums - 1,2,3,4,5,6,7 As described above 14 1,100.00 15,400.00
28 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
9 12 WAY TPN LDB1 & LDB3-1st to 5th Lift Lobby & passage
A Incoming
25 amps TPN MCB with following accessories:
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, DP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
12 WAY TPN LDB1 & LDB3-1st to 5th Lift Lobby & passage As described above 2 1,100.00 2,200.00
B SUB Incoming
25 amps DP RCCB, 30mA -
25A, DP Contactor with (0-24 Hr) timer
C Outgoing
i 10. amps SP MCB
12 WAY TPN LDB2 & LDB4- 12 WAY 6th to 10th common Area As described above 2 1,100.00 2,200.00
B SUB Incoming
25 amps DP RCCB, 30mA -
C Outgoing
i 10. amps SP MCB
8 WAY TPN -LDB6 PARKING AREA (PMC UNDER) Lower Ground As described above 1 950.00 950.00
C Outgoing
i 16. amps SP MCB
13 8 WAY SPN LDB3 & LDB4 BASEMENT 2, Lower Ground & LDB3 Ground floor
A Incoming
40 amps DP RCBO,30mA with following accessories:
B Outgoing
i 16. amps SP MCB
29 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
All MCB's shall be of …10.. KA (Ics) breaking capacity.
8 WAY SPN LDB3 & LDB4 BASEMENT 2, Lower Ground & LDB3 Ground floor As described
5 900.00 4,500.00
above
14 12 WAY SPN LDB3 & LDB4 BASEMENT 1 & LDB4 Ground floor
A Incoming
40 amps DP RCBO,30mA with following accessories:
B Outgoing
i 16. amps SP MCB
12 WAY SPN LDB3 & LDB4 - BASEMENT 1 LDB4 Ground floor As described above 3 900.00 2,700.00
B Outgoing
i 16. amps SP MCB
SPN 8 WAY LDB1 & LDB2-Office Floor(1st to 10th) As described above 20 700.00 14,000.00
B Outgoing
i 16. amps SP MCB
17 12 WAY SPN ELDB1 & ELDB2 BASEMENT 1, 2 & ELDB2 Ground Floor
A Incoming
16 amps DP RCBO with following accessories:
B Outgoing
i 10. amps SP MCB
B Outgoing
i 16. amps SP MCB
8 WAY SPN ELDB1 & ELDB3 LG & ELDB1 GF As described above 3 700.00 2,100.00
30 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
19 12 WAY SPN LIFT LOBBY EDB2 BASEMENT-2 TO P6 FLOOR
A Incoming
16 amps DP RCBO with following accessories:
B Outgoing
i 10. amps SP MCB
12 WAY SPN LIFT LOBBY EDB2 BASEMENT-2 TO P6 FLOOR As described above 1 700.00 700.00
Outgoing
10. amps SP MCB
B Outgoing
i 10. amps SP MCB
SPN 8 WAY ELDB1 & ELDB2 -PODIUM 1,2,3,4,5,6 & 7 As described above 14 700.00 9,800.00
B Outgoing
i 10. amps SP MCB
ii 20 amps SP MCB
SPN 12 WAY ELDB-1 For (1st to10th) floor As described above 5 700.00 3,500.00
The rates for the capacitor bank panels apart from the switches and instruments shall also
include
the following :
The breaking capacity of MCCB’s/ ACB's are mentioned panel wise. MCCB’s/ ACB's shall
6
be
with thermal magnetic releases.
31 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Rubber mats shall be provided in front of all panels and the back where they are accessable
7
from
the back as per IS 15652-2006.
Automatic capacitor control panels shall be powder coated with Siemens Grey RAL 7032 of
8
IS-5.
10 All MCCB / ACB shall be provided with operating mechanism for door interlock.
Current density of aluminium shall be 1 sq mm for 1.0 amps for rated current of bus bars
11
current
density of copper shall be 1 sq.mm for 1.25 amps of rated current of bus bars.
12 TPN MCCB shall means 3 pole MCCB with adequate size of neutral link.
14 Tinned copper / GI earth bus shall be provided through out the length of each panel.
15 All hinged door shall be earthed through 2.5 sq.mm tinned braided copper wire.
16 All PT’s / Control transformer shall be provided with centre tap earth secondary.
18 All bus bars section / backside panels shall have pad locking facility and hinged type doors.
19 All steps of capacitor unit shall be connected with super fast electronic fuse.
It shall provide rated 25/20/10/5 KVAR in suitable nos. of steps & of suitable rating of
capacitors ( 12steps for above 360 kVAR bank), as per specification. The panel shall also
comply with following :
630 Amps TP Manual drawout type MCCB incomer with 50_KA breaking capacity to be
1
provided :
32 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Microprocessor APFC controller shall continuously monitor all three phases and displays
various Electrical Parameters like voltage, input current, capacitive current, KVA
demand,KW, Power Factor, self diagnostic error code indication with printout facility of the
2
above with RS 232C port. Controller should mounted on the front side of the panel. It shall
have data logging for minimum 2 months, it shall provide thyristor output for maximum 16
stages.
MCCBs of the proper rating to be used for grouping the capacitor banks. Capacitor shall be
4
connected with fast discharge resistances.
Necessary control and firing card with proper wiring and lugs of the required rating to be
6
provided.
Auto/manual selector switch with necessary wiring to operate APFC panel in manual mode
10
bypassing APFC relay.
Protections :
a. Over voltage.
b. Voltage imbalance.
Over temperature-system should be in standby mode and automatically restart after above
c.
condition restored.
Capacitor Units shall have 480 V and rating shall be suitably increased considering reactors
12
into account.
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
Jointing by rivetting and brazing after rivetting in case of copper and welding / bolting in
case
3 of GI earthing.
4 Cutting chases / holes and making good the same wherever required.
33 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
All equipment motors, DB’s, panels to be connected on both ends (double earthing) with
suitable
9 strip / wires.
10 Soil resistingly test shall be conducted of the area where earth pits are to be located.
Supply and fixing of following bare copper /GI tapes / wires including all necessary fixing
1
accessories and effecting connections as per specifications.
Providing and laying of 14.35 mm dia and 3 meter length.copper bonded earth rod in 150
mm dia. in an augured hole in ground , surrounded by ground enhancement material as per
specification. Inspection chamber shall be of 400 x 500 mm with concrete base CI manhole
cover with frame painted with bitumastic paint. 2 Nos. of 50 x 6 mm cross section & 300
6.1 mm long copper strip to be clamped with copper claded rod electrode have sufficient nos ( 46 Nos. 4,500.00 207,000.00
But not less than 4 Nos.) of 10 mm dia. GI nuts & bolts for connection to the equipment /
interconnection to the other pits to form equi-potential bonding .The pH value of ground
enhance material shall be 6.9 to 7.2 of 1000gm / lit @ 20 deg.c.The minimum 30 Kg of
ground enhancement material shall provided for each electrode.
Providing earthing stations at locations as called for including providing and laying 600 x
600 x 3.15 mm thick tinned copper electrode with 2 Nos 50 x 6 mm thick copper strip,
from earth electrode to inspection chamber,50 mm dia medium class G I pipe CI /
chequered plate funnel with 20 gauge G I wire mesh, masonry chamber 1000 x 500 mm
Nos. 4,000.00 -
with concrete base, CI chequered plate manhole cover with frame and bitumastic paint
and packing of mixture of charcoal and common salt around plate electrode complete
with digging of pit upto permanent misture level but not less than 3 metres and back filling
as required.
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
2 All fixing accessories such as brass saddles, brass screws rawl plugs etc.
34 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Jointing by rivetting and brazing after rivetting in case of copper and by welding / bolting
3
in case of GI.
4 Cutting chases, holes and making good the same wherever required.
3Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind
5 load. OBO Type No. 101 VL3000 ( 5401 98 9 ). 4 Nos 54.00 216.00
Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is
erected. OBO Type No. F- FIX 16 ( 5403 20 0 ).
Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.
6 4 Nos 135.00 540.00
16 KG stone of 365 mm diameter, high level of stability. Quick and easy mounting of
interception rod using anchors. Concrete, frost-resistant, can be stacked.OBO Type No. F-
FIX S16 ( 5403 22 7 )
Providing of cross universal connector: For T and cross connection, to route vertical down
conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc
7 55 Nos 70.00 3,850.00
as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . OBO Type
No.251 8- 10 ( 5312 03 5 )
Providing of expansion piece with connector: For equalising temperature related length
changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU.
8 39 Nos 40.00 1,560.00
OBO Type No. 172 AR ( 5218 92 6 )
Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt
M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN
9 78 Nos 40.00 3,120.00
VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). OBO Type No. 249 8-10 ST ( 5311 50 0
)
Providing of Bridging cable: From flexible CU cable of
16mm2 with black colur coating, chlorinated India rubber
10 mixture .Exclusively used for indoor & outdoor application to 10 Nos 40.00 400.00
make continuity at terminals.OBO Type No. 853 300 ( 5331
01 3)
Down Conductor
35 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Supply of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the
11 requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 1570 Mtr 18.00 28,260.00
62305) , OBO Type No. RD 8/ALU (5021 28 6 )
Supply of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by
13 30x3 mm GI strip as specified in drawing and directed by Engineer OBO Type No. 271 8-10 22 Nos 40.00 880.00
( 5317 40 1 )
Lightnig counter - To count no of lightning strike & it can record the date and time of the
14 1 Nos 350.00 350.00
lightning incident also tested as per IEC 62561-6. OBO Type No. LSC I+II ( 5091 72 2 )
Earthing
Supply of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground
as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm square
According to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of
15 480 Mtr 27.00 12,960.00
VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx:70 micron coating)
Should be tested and used exclusively for lightning protection earthing system and ring
equipotential bonding. OBO Type No. 5052 DIN 30X3 ( 5019 34 4 )
Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed
16 37 Nos 70.00 2,590.00
with 4 nos of hexagonal plate. OBO Type No. 255 FL30 FT (5314 53 4 )
Providing of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts.OBO
17 Type No. 166 LS 70 ( 5226 57 22 Nos 40.00 880.00
0)
Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of
18 2 Nos 27.00 54.00
petrolatum- coated chemical fibre fabric. OBO Type No.356 50 ( 2360 05 5 )
19 Supply of UL Listed & CPRI tested maintenance free ,Low carbon copper coated earth rod of 11 Nos 315.00 3,465.00
20 3 metre electrode having diameter of 14.2 mm with copper coating thickness of 250micron 11 Nos 180.00 1,980.00
21 tested as per IEC 62561-2 ( OBO Type No. 14 3000 CCER)& is provided with universal clamp 11 Nos 135.00 1,485.00
22 made of SS to connect rod with flat conductor ( OBO Type No. 14 25 RTC) . Earth 11 Nos 18.00 198.00
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
The rates shall include all components that may be required to make the supply complete in
2
all respects such as :
a. Including All lamps, accessories & electronic ballast unless otherwise specified.
c. Earthing terminal.
Supply of the following lighting fixtures with all fixing accessories etc. as required.
1X18W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
1 1690 No.
Equivalent as confirmed by Client/Architect)
36 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
1X18W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
2 5 No.
Equivalent as confirmed by Client/Architect)
1X15W LED Single Luminaire Ceiling Mounted Surface Down Light Fixture (Philips or
3 1103 No.
Equivalent as confirmed by Client/Architect)
1X11W LED Single Luminaire Ceiling Mounted Surface Down Light Fixture (Philips or
4 520 No.
Equivalent as confirmed by Client/Architect)
1X13W LED Single Luminaire wall (Terrace)Mounted Light Fixture (Philips or Equivalent as
5 60 No.
confirmed by Client/Architect)
1X13W LED Single Luminaire wall Mounted Ramp Light Fixture (Philips or Equivalent as
6 180 No.
confirmed by Client/Architect)
1X28W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
7 155 No.
Equivalent as confirmed by Client/Architect)
9W LED Luminarire Wall Mounted Mirror Light Fixture (Philips or Equivalent as confirmed
8 140 No.
by Client/Architect)
Bulk head lighting fixtures Philips make FXC 101 or approved equal in quality and design 9
9 360 No.
watt CFL lamps.
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
The rates shall include all components that may be required to make the supply complete in
2
all respects such as :
a. Suitable length of GI down rod, hanger and connecting wires where called for..
b. Wires for connecting the fixtures to the point through connector block.
Fixing clamps, GI bolts and nuts, brass screws, saddles, rawl bolts and other fixing
4
accessories as required.
Installation of the following lighting fixtures with all fixing accessories etc. as required.
1X18W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
1 1690 No. 120.00 202,800.00
Equivalent as confirmed by Client/Architect)
2X18W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
2 5 No. 120.00 600.00
Equivalent as confirmed by Client/Architect)
1X15W LED Single Luminaire Ceiling Mounted Surface Down Light Fixture (Philips or
3 1103 No. 100.00 110,300.00
Equivalent as confirmed by Client/Architect)
1X11W LED Single Luminaire Ceiling Mounted Surface Down Light Fixture (Philips or
4 520 No. 95.00 49,400.00
Equivalent as confirmed by Client/Architect)
37 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
1X13W LED Single Luminaire wall (Terrace)Mounted Light Fixture (Philips or Equivalent as
5 60 No. 100.00 6,000.00
confirmed by Client/Architect)
1X13W LED Single Luminaire wall Mounted Ramp Light Fixture (Philips or Equivalent as
6 180 No. 100.00 18,000.00
confirmed by Client/Architect)
1X28W LED Single Luminaire Ceiling Mounted Surface tube Light Fixture (Philips or
7 155 No. 120.00 18,600.00
Equivalent as confirmed by Client/Architect)
9W LED Luminarire Wall Mounted Mirror Light Fixture (Philips or Equivalent as confirmed
8 140 No. 70.00 9,800.00
by Client/Architect)
Bulk head lighting fixtures Philips make FXC 101 or approved equal in quality and design 9
9 360 No. 120.00 43,200.00
watt CFL lamps.
This schedule of Quantities shall be read in conjuction with the technical specification,
1
General & Special conditions as well as all tender drawings.
2 All component that may be required to make the installation complete in all respects.
Fixing clamps, GI bolts and nuts / brass screws, saddles, rawl bolts and other fixing
4
accessories as required.
Suitable size junction boxes with connector block for loop in loop out where ever
6
applicable.
Supply installing, testing and commissioning of the following lighting fixtures and poles
1
including excavation and back filling, foundation of pole, base plate as required.
lighting fixture with 60 watts LED Light including, capacitor a cast aluminium adapter Single
1.1 piece Street light with side reflectors with internal starter and with all necessary 21 No. 150.00 3,150.00
accessories.
Supply, laying, testing and commissioning of following size PVC insulated sheathed copper
conductor 1100 V grade armoured cable as per specification including excavation of earth,
2
300 mm thick and all around the cable, brick protection refilling, watering and ramming or
providing to earth etc. complete.
38 of 39
Erection
SL ITEM DESCRIPTION QTY UNIT
RATE AMOUNT
Making end termination of following size PVC insulated sheathed copper conductor 1100 V
3 grade armoured cable including cost of crimping lugs, sockets, double compression glands
with earthing facility etc. complete.
Supplying and fixing of following bare GI tapes including all necessary fixing accessories
4
and effecting connections.
5 Supply & installation of 7.8 M high MS decorative poles (6 M above & 1.8 M below ground) 21 Nos. 3,150.00 66,150.00
Wiring with 2 x 2.5 sq. mm. PVC insulated copper conductor 1100 V in 16 gauge 25 mm dia
GI conduit including connecting at terminals of lighting fixtures complete. The cost shall
7 140 RM 17.00 2,380.00
include supply and installation of conduit pipe, chasing of wall and making good. (
From Pole junction box to lamp)
Supply, installation, testing and commissioning of the following FDB's fabricated out of 1.6
mm thick CRCA sheet steel , double door construction, powder coated with approved
8 shade and partitions to segregate phases. Approved lockable covers with padlocking
arrangement for each phase, recessed in wall or surface mounted final distribution boards
of the following description:
Providing and laying earth electrode system comprising of 80 mm dia concentric GI pipe,
with 2 Nos 50 x 6 mm GI. strips from electrode to inspection chamber, 50 mm dia medium
class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber C I heavy duty /
9 chequered plate manhole cover with frame painted with bitumastic paint and packing 4 Nos. 3,000.00 12,000.00
with special compound in rocky soil around electrode including digging or boring of pit
upto permanent moisture level and as per soil condition but not less than 3 meters and
back filling as required.for external lighting.
I. INVERTER SYSTEM
20 KVA Offline inverter input 3 phase (415 V + 10%) output 3 phase (415 V + 10%) with
1.1 1 Set 3,200.00 3,200.00
sealed maintenance free batteries suitable for 30 minutes backup
39 of 39