Staad Project Overview and Building Loads Final
Staad Project Overview and Building Loads Final
I. Project Overview
These are the sections need to be defined and apply to elements accordingly
Columns
PURLINS (C200x75x2.3mm)
PROJECT LOCATION
II. Building Loads
A. DEAD LOADS
The dead loads used in this project were determined by referencing various standards
and textbooks to find the corresponding values for their weights. Approximate values
were assumed when ranges were listed depending on how dense the layouts were, as
well as considering the life history and usage of the building.
- Floor loads
- Member loads
- 8.64 kN/m member load, this came from 4” (100mm) CHB load
- 15.79 kN/m member load, this came from 4” (100mm) CHB load
- 6.85 kN/m member load, this came from 4” (100mm) CHB load
Height of 4” CHB = 6.0 m(story height) – 1.4m (truss depth) = 4.6 m * ½ (to
consider triangular load)
B. LIVE LOADS
The live loads used in this project were calculated in accordance with NSCP 2015 and
ASCE 7-16.
C. WIND LOADS
Wind loads were calculated in accordance with NSCP 2015, Chapter 2. The simplified
method was used to calculate wind loads for Main Wind-Force Resisting System
(MWFRS) and Components and Cladding (C&C).
In order to use the simplified procedure, all conditions of Section 207C.6.2 of the NSCP
2015 must be satisfied:
Therefore, wind pressures for both the MWFRS and C&C can be used on the
design using the simplified method.
The project is categorized as Exposure B due to its urban setting and location in
Intramuros Manila. The basic wind speed was found to be 250 kph per Figure 207A.5-1A
in NSCP 2015.
Wind pressure diagrams were drawn of the final forces acting on the building. Wind
forces for MWFRS and C&C were calculated by hand and then applied to STAAD.Pro 2D
and 3D model. These diagrams and calculations can be found on succeeding pages of
this book.
Structure Data
Roof Framing
a: 10 percent of least horizontal dimension or 0.4h, whichever is smaller, but not less than
either 4% of least horizontal dimension or 3 ft (0.9 m).
or a = 0.4(16.2 m) = 6.48 m
or a = 0.9m
Wind Pressure diagram for Wind Load Calculation for MWFRS
Where:
λ adjustment factor for building height and exposure from Fig. 207E.5-1
pnet9 net design wind pressure for Exposure B, at h = 9 m, from Fig. 207E.5-1
Minimum Design Wind Pressures: the design wind pressure for C&C shall not be less
than a net pressure (including internal pressures) of 0.77 KN/m2 acting in either
direction normal to the surface
Purlins design involving Zone 1 and Zone 2 wind, use purlin spacing = 0.8 m
L = 3.0m (least purlin span or truss spacing), smaller space considered between 3.0
m and 3.75 m
W = 0.8m or not smaller than 1/3 of span, 3.0m / 3 = 1.0 m, 1.0 m governs
Input to STAAD.Pro = 0.10 KN/m2 x purlin spacing = 0.10 x 0.8 = 0.08 KN/m
Input to STAAD.Pro = 0.60 KN/m2 x purlin spacing = 0.60 x 0.8 = 0.48 KN/m
Below are the primary load cases and load combinations will be used in the purlin
design
TABLE 1604.3
DEFLECTION LIMITS
CONSTRUCTION L S or W D+L
Roof Members
Supporting plaster or stucco ceiling 𝑙⁄360 𝑙⁄360 𝑙⁄240
Supporting non-plaster ceiling 𝑙⁄240 𝑙⁄240 𝑙⁄180
Not supporting ceiling 𝑙⁄180 𝑙⁄180 𝑙⁄120
Floor members 𝑙⁄360 - 𝑙⁄240
Exterior Walls and Interior Partitions
With plaster or stucco finishes - 𝑙⁄360 -
With other brittle finishes - 𝑙⁄240 -
With flexible finishes - 𝑙⁄180 -
Farm buildings - - 𝑙⁄180
Greenhouses - - 𝑙⁄120
2. WIND LOAD CALCULATION FOR COMPONENTS AND CLADDING (C&CS) FOR TRUSS
DESIGN
λ adjustment factor for building height and exposure from Fig. 207E.5-1
pnet9 net design wind pressure for Exposure B, at h = 9 m, from Fig. 207E.5-1
Minimum Design Wind Pressures: the design wind pressure for C&C shall not be
less than a net pressure (including internal pressures) of 0.77 KN/m 2 acting in
either direction normal to the surface
Truss design involving Zone 1 and Zone 2 wind, use truss spacing = 3.75 m
W = 3.75 m or not smaller than 1/3 of span, 22.5 m / 3 = 7.5 m, 3.75 m governs
Input to STAAD.Pro = 0.20 KN/m2 x max truss spacing = 0.2 x 3.75 = 0.75 KN/m (top chord load)
Input to STAAD.Pro = 0.15 KN/m2 x max truss spacing = 0.15 x 3.75 = 0.56 KN/m (bottom chord
load)
Live Load Roof live load = 0.6 kN/m2 (top chord load)
Input to STAAD.Pro = 0.60 KN/m2 x purlin spacing = 0.6 X 3.75 = 2.25 KN/m (top chord load)
Below are the primary load cases and load combinations will be used in the truss design
TABLE 1604.3
DEFLECTION LIMITS
CONSTRUCTION L S or W D+L
Roof Members
Supporting plaster or stucco ceiling 𝑙⁄360 𝑙⁄360 𝑙⁄240
Supporting non-plaster ceiling 𝑙⁄240 𝑙⁄240 𝑙⁄180
Not supporting ceiling 𝑙⁄180 𝑙⁄180 𝑙⁄120
Floor members 𝑙⁄360 - 𝑙⁄240
Exterior Walls and Interior Partitions
With plaster or stucco finishes - 𝑙⁄360 -
With other brittle finishes - 𝑙⁄240 -
With flexible finishes - 𝑙⁄180 -
Farm buildings - - 𝑙⁄180
Greenhouses - - 𝑙⁄120
Below are the available angle sections can be used in the truss design.
2L 100 x 100 x 8 mm (double angle) (A36 steel), f y = 248 N/mm2, for bottom cord and
top chord
L 100 x 100 x 6 mm (single angle) (A36 steel), fy = 248 N/mm2, for web and girts
(intermediate trusses)
D. SEISMIC LOADS
The seismic loads were calculated in accordance with section 1630.2 Static Force Procedure
of UBC 1997 and 208.5.2 of NSCP 2015.
➢ Seismic load has vertical and orthogonal effects (100% + 30%) as recommended by UBC
97 (1633.1) and NSCP 2015 (208.7.1)
➢ Reliability/Redundancy Factor (r) = 1.0, for regular framing
➢ E = r Eh + Ev is used to account for seismic vertical effects
➢ Ev = 0.5 Ca I, Ca = 0.44,
➢ Na = 1.0 and Nv = 1.2, since the structure is 10.0 km from the nearest seismic source
Seismic parameters
➢ Z = 0.4
➢ I = 1.0
➢ Rx = 8.5 (Concrete Special Moment Resisting Frame)
➢ Rz = 8.5 (Concrete Special Moment Resisting Frame)
➢ Ct = 0.0731
➢ Soil = D (D is assumed as soil report is not available)
➢ Na = 1.0
➢ Nv = 1.2
E. PRIMARY LOAD CASE AND LOAD COMBINATIONS
The seismic loads were calculated in accordance with section 1630.2 Static Force Procedure
of UBC 1997 and 208.5.2 of NSCP 2015.
➢ Seismic load has vertical and orthogonal effects (100% + 30%) as recommended by
UBC 97 (1633.1) and NSCP 2015 (208.7.1)
➢ Reliability/Redundancy Factor (r) = 1.0, for regular framing
➢ E = r Eh + Ev is used to account for seismic vertical effects
➢ Ev = 0.5 Ca I, Ca = 0.44,
➢ Na = 1.0 and Nv = 1.2, since the structure is 10 km from the seismic source
➢ For TABLE 1 combination see UBC 97 (1612.2.1 and 1633.1) or NSCP 2015 (203.3.1
and 208.7.1)
➢ For TABLE 2 combination see UBC 97 (1630.9.1 and 1612.2.1) or NSCP 2015
(208.6.4.1)
➢ For TABLE 4 combination see UBC 97 (1612.3.1) or NSCP 2015 (203.4.1)
➢ For TABLE 5 combination see UBC 97 (1612.2.1) or NSCP 2015 (203.3.1)
A. PURLIN DESIGN
B. TRUSS DESIGN