Levelflex
Levelflex
Technical Information
Levelflex FMP51, FMP52,
FMP54
Guided wave radar
Application
• Rod, rope or coax probe
• Process connection: Starting 3/4" thread, flange or process connections for hygiene
requirements (Tri-Clamp, 11851)
• Process temperature: –196 to +450 °C (–320 to +842 °F)
• Process pressure: –1 to +400 bar (–14.5 to +5 800 psi)
• Maximum measuring range: Rod 10 m (33 ft); rope 45 m (148 ft); coax 6 m (20 ft)
• Accuracy: ±2 mm (±0.08 in)
• International explosion protection certificates; WHG; marine approval; steam
boiler approval; EN10204-3.1
• Linearity protocol (3-point, 5-point)
Your benefits
• Reliable measurement even for changing product and process conditions
• HistoROM data management for easy commissioning, maintenance and
diagnostics
• Highest reliability due to Multi-Echo Tracking
• Hardware and software developed according to IEC 61508 (up to SIL3)
• Seamless integration into control or asset management systems
• Intuitive user interface in national languages
• Bluetooth® wireless technology for commissioning, operation and maintenance via
free iOS / Android app SmartBlue
• Easy proof test for SIL and WHG
• Heartbeat Technology™
Levelflex FMP51, FMP52, FMP54
Table of contents
2 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 118
Communication-specific accessories . . . . . . . . . . . . . . . 129
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . 130
System components . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Endress+Hauser 3
Levelflex FMP51, FMP52, FMP54
Electrical symbols
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Reference to documentation
Reference to graphic
Result of a step
1, 2, 3, ...
Item numbers
A, B, C, ...
Views
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables
4 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
20 mA
100%
D
E
LN F
4 mA
0%
A0011360
If the εr value is less than 7 in the case of rope probes, measurement is not possible in the area
of the tensioning weight (0 to 250 mm (0 to 9.84 in) from the probe end), (lower blocking
distance).
The reference point R of the measurement is located at the process connection.
Endress+Hauser 5
Levelflex FMP51, FMP52, FMP54
Dielectric constant
The dielectric constant (DC) of the medium directly affects the degree of reflection of the high-
frequency pulses. In the case of large DC values, such as with water or ammonia, there is strong
pulse reflection while, in the case of low DC values, such as with hydrocarbons, pulse reflection is
weak.
Input
The reflected pulses are transmitted from the probe to the electronics. Here, a microprocessor
evaluates the signals and identifies the level echo which was caused by the reflection of the high-
frequency pulses at the product surface. This clear signal detection system benefits from over 30
years of experience with pulse time-of-flight procedures that have gone into the development of the
PulseMaster® software.
The distance D to the product surface is proportional to the time-of-flight t of the pulse:
D = c · t/2,
with c being the speed of light.
Based on the known empty distance E, the level L is calculated:
L=E–D
The Levelflex has functions for interference echo suppression that can be activated by the user. They
guarantee that interference echoes from internal fixtures and struts, for example, are not interpreted
as level echoes.
Output
The Levelflex is preadjusted at the factory to the probe length ordered so that in most cases only the
application parameters that automatically adapt the device to the measuring conditions need to be
entered. For models with a current output, the factory adjustment for zero point E and span F is 4
mA and 20 mA, for digital outputs and the display module 0 % and 100 %. A linearization function
with max. 32 points, based on a table entered either manually or semi-automatically, can be
activated locally or remotely. This function allows the level to be converted into units of volume or
mass, for example.
6 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Interface measurement
When the high-frequency pulses hit the surface of the medium, only a percentage of the
transmission pulse is reflected. In the case of medium with a low DC1, in particular, the other part
enters the medium. The pulse is reflected once more at the interface point to a second medium with
a higher DC2. The distance to the interface layer can now also be determined, taking into account the
delayed time-of-flight of the pulse through the upper medium.
LL
C0
DK1 (DC1) C1 =
DK1
LI
DK2 (DC2)
A0011178
In addition, the following general conditions must be observed for interface measurement:
• The DC of the upper medium must be known and constant 1). The DC can be determined with the
aid of the DC manual CP00019F or the "DC Values App". In addition, if the interface thickness is
known, the DC can be calculated automatically in FieldCare.
• The DC of the upper medium may not exceed 10.
• The DC difference between the upper and lower medium must be >10.
• The minimum thickness of the upper medium is 60 mm (2.4 in).
• Emulsion layers in the area of the interface can greatly attenuate the signal. However, emulsion
layers up to 50 mm (2 in) are permitted.
For the dielectric constants (DC values) of many media commonly used in industry, please refer
to:
• Dielectric constant (DC value) Compendium CP01076F
• The Endress+Hauser "DC Values app" (available for Android and iOS)
1) For FMP55: Under certain conditions measurement is possible even with a changing DC. For such cases, please contact your
Endress+Hauser sales organization.
Endress+Hauser 7
Levelflex FMP51, FMP52, FMP54
Probe selection
FMP51
For level measurement and interface measurement in liquids
8 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A0011387
3 Rod probe
Rod probe
• Maximum probe length
• 4 m (13 ft); inseparable rod probes
• 10 m (33 ft); separable rod probes
• Material:
• 316L; inseparable and separable rod probes
• Alloy C; only inseparable rod probes
A0011388
Rope probe
• Maximum probe length
45 m (148 ft)
• Material:
• 316L
• Alloy C
• PFA>316L
A0011359
5 Coax probe
Endress+Hauser 9
Levelflex FMP51, FMP52, FMP54
Coax probe
• Maximum probe length
6 m (20 ft)
• Material:
• 316L, multiple holes
• Alloy C, one hole
FMP52
For level measurement and interface measurement in corrosive liquids
A0011357
6 Rod probe
Rod probe
• Maximum probe length
4 m (13 ft)
• Material:
PFA>316L
A0011358
Rope probe
• Maximum probe length
45 m (148 ft)
• Material:
PFA>316L
FMP54
For level measurement and interface measurement in liquids
10 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A0011357
8 Rod probe
Rod probe
• Maximum probe length
4 m (13 ft)
• Material:
316L
A0011358
Rope probe
• Maximum probe length
45 m (148 ft)
• Material:
316L
A0011359
10 Coax probe
Endress+Hauser 11
Levelflex FMP51, FMP52, FMP54
Coax probe
• Maximum probe length
6 m (20 ft)
• Material:
316L, multiple holes
12 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Input
Measured variable The measured variable is the distance between the reference point and the product surface.
The level is calculated based on "E", the empty distance entered.
Optionally, the level can be converted to other variables (volume, mass) by linearization (32 points).
Measuring range The following table describes the medium groups and the possible measuring range as a function of
the medium group.
Measuring range 1)
Medium
εr Typical liquids Bare metallic Bare metallic PFA-coated Coax probes
group
Rod probes Rope probes Rope probes
1 1.4 to 1.6 Liquefied gases, e.g. N2, CO2 On request — 6 m (20 ft)
2 1.6 to 1.9 • Liquefied gas, e.g. propane • One-piece: 4 m (13 ft) 15 to 22 m 9 to 14 m 6 m (20 ft)
• Solvents • Separable: 10 m (33 ft) (49 to 72 ft) (30 to 46 ft)
• Freon
• Palm oil
3 1.9 to 2.5 Mineral oils, fuels • One-piece: 4 m (13 ft) 22 to 32 m 14 to 21 m 6 m (20 ft)
• Separable: 10 m (33 ft) (72 to 105 ft) (46 to 69 ft)
6 >7 • Aqueous solutions • One-piece: 4 m (13 ft) 45 m (148 ft) 32 to 45 m 6 m (20 ft)
• Alcohols • Separable: 10 m (33 ft) (105 to 148 ft)
• Ammonia
Endress+Hauser 13
Levelflex FMP51, FMP52, FMP54
Levelflex FMP52
1)
Measuring range
Medium group εr Typical liquids PFA-coated PFA-coated
Rod probes Rope probes
2 1.6 to 1.9 • Liquefied gas, e.g. propane 4 m (13 ft) 9 to 14 m (30 to 46 ft)
• Solvents
• Freon
• Palm oil
• The formation of buildup, particularly of moist products, can reduce the maximum possible
measuring range.
• Due to the high rate of diffusion of ammonia, a gas-tight bushing 2) is recommended for
measurements in this medium.
14 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Blocking distance The upper blocking distance (= UB) is the minimum distance from the reference point of the
measurement (mounting flange) to the maximum level.
R
SD UB
100%
E
F
LN
0%
A0011279
Endress+Hauser 15
Levelflex FMP51, FMP52, FMP54
Output
Output signal HART
• Signal coding:
FSK ±0.5 mA over current signal
• Data transmission rate:
1 200 Bit/s
• Galvanic isolation:
Yes
Bluetooth® wireless technology
• Device version:
Order code 610 "Accessory mounted", option NF "Bluetooth"
• Operation / configuration:
Via the SmartBlue app
• Range under reference conditions:
> 10 m (33 ft)
• Encryption:
Encrypted communication and password encryption prevent incorrect operation by unauthorized
persons
PROFIBUS PA
• Signal coding:
Manchester Bus Powered (MBP)
• Data transmission rate:
31.25 kBit/s, Voltage mode
• Galvanic isolation:
Yes
FOUNDATION Fieldbus
• Signal coding:
Manchester Bus Powered (MBP)
• Data transmission rate:
31.25 kBit/s, Voltage mode
• Galvanic isolation:
Yes
Switch output
For HART devices, the switch output is available as an option.
• Function:
Open collector switch output
• Switching behavior:
Binary (conductive or non-conductive), switches when the programmable switch-on point/switch-
off point is reached
• Failure mode:
Non-conductive
• Electrical connection data:
U = 16 to 35 VDC, I = 0 to 40 mA
• Internal resistor:
RI < 880 Ω
The voltage drop at this internal resistor must be taken into account when planning the
configuration. For example, the resulting voltage at a connected relay must be sufficient to switch
the relay.
• Insulation voltages:
Floating, insulation voltage 1 350 VDC in relation to power supply and 500 VAC ground
• Switch point:
User-programmable, separate for switch-on point and switch-off point
• Switching delay:
User-programmable in the 0 to 100 s range, separate for switch-on point and switch-off point
• Scan rate:
Corresponds to the measuring cycle
16 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Linearization The device's linearization function allows the user to convert the measured value to any length or
volume units. Linearization tables for calculating the volume in cylindrical vessels are
preprogrammed into the device. Other tables of up to 32 value pairs can be entered manually or
semi-automatically.
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.
Endress+Hauser 17
Levelflex FMP51, FMP52, FMP54
Manufacturer ID 17 (0x11)
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• For active interface measurement:
• Interface
• Interface distance
• Upper interface thickness
• Relative interface amplitude
• Electronic temperature
• Relative echo amplitude
Measured values for SV, TV, QV (second, third and fourth variable)
• Level linearized
• Distance
• For active interface measurement:
• Interface linearized
• Interface distance
• Upper interface thickness
• Absolute interface amplitude
• Relative interface amplitude
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Calculated εr value
Start-up current 4 mA
Starting time 80 s
18 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
PROFIBUS PA
Manufacturer ID 17 (0x11)
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Endress+Hauser 19
Levelflex FMP51, FMP52, FMP54
Choice of "Link Master" and "Basic Device" Yes; Factory setting: Basic Device
Number of VCRs 44
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Slot time 4
Transducer Blocks
Block Contents Output values
Setup Transducer Block Contains all the parameters for standard • Level or volume (channel
commissioning 1)
(depending on the block
configuration)
• Distance (channel 2)
Advanced Setup Contains all the parameters for more accurate No output values
Transducer Block measurement configuration
Display Transducer Block Contains parameters to configure the onsite display No output values
Expert Configuration Contains parameters that require the user to have No output values
Transducer Block in-depth knowledge of the operation of the device in
order to configure the parameters appropriately
Expert Information Contains parameters that provide information about No output values
Transducer Block the state of the device
Service Sensor Contains parameters that can only be accessed by No output values
Transducer Block Endress+Hauser Service
Data Transfer Contains parameters for backing up the device No output values
Transducer Block configuration in the display module and for writing
the saved configuration to the device. Access to
these parameters is reserved for Endress+Hauser
Service.
20 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Function blocks
Block Contents Number of Number of Execution Functionality
permanent instantiatable time
blocks blocks
Endress+Hauser 21
Levelflex FMP51, FMP52, FMP54
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated.
22 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Power supply
Terminal assignment
Terminal assignment, 2-wire: 4 to 20 mA HART
A B 2
1 +
+ 2 1 -
- 2
3 3
A0036498
3 4
2 5
1 6
+ +1
- -2 I
A0036499
A B 3
3 + 4
+ 4 3 -
1 4 +
-
+ 2 1 -
- 2
2
1 5 5
A0036500
Endress+Hauser 23
Levelflex FMP51, FMP52, FMP54
3 4
2 5
1 6
+ +1
- -2 I
+3 Y
-4
7
A0036501
A B 3
3 + 4
+ 4 3 -
1 4 +
-
+ 2 1 -
- 2
2
1 5 5
A0036500
24 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
3 4
2 5
1 6
+ +1
- -2 I
+ +3 Y
- -4
7
8
A0036502
1
L+ 2 3
L-
+ 4
-
2
1 3
A0036516
3 4
2 5
1 6
+3
-4 I
L+ 1 Y
L- 2
7
A0036526
Endress+Hauser 25
Levelflex FMP51, FMP52, FMP54
1
L 2 3
N
+ 4
-
2
1 3
A0036519
LCAUTION
To ensure electrical safety:
‣ Do not disconnect the protective ground connection.
‣ Disconnect the device from the supply voltage before disconnecting the protective ground.
Connect protective ground to the inner ground terminal (3) before connecting the supply
voltage. If necessary, connect the potential matching line to the outer ground terminal.
In order to ensure electromagnetic compatibility (EMC): do not ground the device exclusively
via the protective ground conductor of the supply cable. Instead, the functional grounding must
also be connected to the process connection (flange or threaded connection) or to the external
ground terminal.
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN61010).
3 4
2 5
1 6
+3
-4 I
L1 Y
N2
7
A0036527
26 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B 3
3 + 4
+ 4 3 -
1 4 +
-
+ 2 1 -
- 2
2
1 5 5
A0036500
2 3
+ 1
I
- 2
1 + 3 Y
- 4
4
A0036530
Endress+Hauser 27
Levelflex FMP51, FMP52, FMP54
3+
Ri +
-
4-
A0015909
24 Connection of a relay
+
1
2
3+
Ri
4-
A0015910
28 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
HART
+1 10
+2 11 HMX50
12
-3
16
4
17
5 18
6
7
8
9
13
14
15
19
20
21
FXA195
22 23 24 HART
24V DC
A0023287
26 Connection diagram for HART loop converter HMX50 (example: passive 2-wire device and current outputs
connected as power source)
The HART loop converter HMX50 can be acquired using the order number 71063562.
Additional documentation: TI00429F and BA00371F.
Device plug In the case of the device versions with a plug, the housing does not need to be opened to
connect the signal cable.
4 3
1 2
A0011175
Endress+Hauser 29
Levelflex FMP51, FMP52, FMP54
1 3
2 4
A0011176
• Non-hazardous 11.5 to 35 V 3) 4)
R [W]
• Ex nA
• Ex ic 500
• CSA GP
Ex ia / IS 11.5 to 30 V 4)
0
10 20 30 35 U0 [V]
11.5 22.5
A0035511
4) 5)
• Ex d / XP 13.5 to 30 V R [Ω]
• Ex ic[ia]
• Ex tD / DIP
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
30 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
• Ex ia / IS 13.5 to 30 V 3) 4)
• Ex ia + Ex d[ia] / IS + XP 0
10 20 30 U0 [V]
13.5 24.5 35
A0034971
All Channel 1:
13.5 to 30 V 3) 4) 5) R [Ω]
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
Channel 2:
12 to 30 V R [W]
500
0
10 20 30 U0 [V]
12 23
A0022583
Endress+Hauser 31
Levelflex FMP51, FMP52, FMP54
32 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
K: 4-wire 90-253VAC; 4-20mA HART 90 to 253 VAC (50 to 60 Hz), overvoltage 500 Ω
category II
Polarity-dependent No
Nominal current 3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is
set to 3.6 mA on delivery)
PROFIBUS PA
Nominal current 14 mA
Endress+Hauser 33
Levelflex FMP51, FMP52, FMP54
FOUNDATION Fieldbus
FISCO
Ui 17.5 V
Ii 550 mA
Pi 5.5 W
Ci 5 nF
Li 10 μH
34 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Endress+Hauser recommends using twisted, shielded two-wire cables.
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), an overvoltage protection module has to be
installed.
Technical data
Endress+Hauser 35
Levelflex FMP51, FMP52, FMP54
Performance characteristics
Reference operating • Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
conditions • Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflection factor ≥ 0.8 (water surface for coax probe, metal plate for rod and rope probe with min.
1 m (40 in) diameter)
• Flange for rod or rope probe ≥ 300 mm (12 in) diameter
• Distance to obstacles ≥ 1 m (40 in)
• For interface measurement:
• Coax probe
• DC of lower medium = 80 (water)
• DC of upper medium = 2 (oil)
Reference accuracy Typical data under reference operating conditions: DIN EN IEC 61298-2 / DIN EN IEC 60770-1;
percentage values in relation to the span.
Interface measurement:
• Measuring distance up to 500 mm (19.7 in):
±20 mm (±0.79 in)
• Measuring distance > 500 mm (19.7 in): ±10 mm (±0.39 in)
• If thickness of upper medium < 100 mm (3.94 in):
±40 mm (±1.57 in)
36 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Differing from this, the following measured error applies in the area of the lower probe end:
D
80 (3.15)
60 (2.36) DC = 2
40 (1.57)
DC = 80
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
50 (1.97)
100 (3.94)
150 (5.91)
250 (9.84)
300 (11.8)
A
20 (0.79)
200 (7.87)
40 (1.57)
80 (3.15)
A0021480
29 Measured error at the probe end for rod and coax probes
A Distance from the probe end [mm(in)]
D Measured error: Sum of non-linearity, non-repeatability and hysteresis
D
80 (3.15)
60 (2.36) DC = 80
40 (1.57)
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
300 (11.8)
A
0
20 (0.79)
250 (9.84)
A0021482
Endress+Hauser 37
Levelflex FMP51, FMP52, FMP54
D
120 (4.72)
100 (3.94)
80 (3.15) DC = 2
60 (2.36) DC = 80
40 (1.57)
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
-100 (-3.94)
-120 (-4.72)
50 (1.97)
150 (5.91)
300 (11.8)
0 A
30 (0.79)
100 (3.94)
200 (7.87)
250 (9.84)
A0021483
31 Measured error at the probe end in the case of metal centering disks (product structure: feature 610
"Accessory mounted" , version OA, OB or OC)
A Distance from the probe end [mm(in)]
D Measured error: Sum of non-linearity, non-repeatability and hysteresis
If the DC value is less than 7 in the case of rope probes, measurement is not possible in the area
of the tensioning weight (0 to 250 mm from the probe end), (lower blocking distance).
38 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
The following measured error applies in the area of the upper probe end:
R
D
40 (1.57)
30 (1.18) DC = 2
DC = 80
10 (0.39)
2 (0.08)
0 (0)
- 2 (- 0.08)
- 10 (-0.39)
- 30 (- 1.18)
- 40 (- 1.57)
Resolution • Digital: 1 mm
• Analog: 1 μA
Response time The response time can be configured. The following step response times (in accordance with DIN EN
IEC 61298-2 / DIN EN IEC 60770-1) 3) are when damping is switched off:
Level measurement
Interface measurement
Influence of ambient The measurements are performed according to DIN EN IEC 61298-3 / DIN EN IEC 60770-1
temperature • Digital (HART, PROFIBUS PA, FOUNDATION Fieldbus): average TK = 0.6 mm/10 K
For FMP51 and FMP52 with a remote sensor, 4) there is an additional offset error of
±0.3 mm/10K (±0.01 in/10K) per 1 m (3.3 ft) of the remote cable.
• Analog (current output):
• Zero point (4 mA): average TK = 0.02 %/10 K
• Span (20 mA): average TK = 0.05 %/10 K
3) According to DIN EN IEC 61298-2 / DIN EN IEC 60770-1, the step response time is the time that elapses after an abrupt change in the input
signal until the change in the output signal has adopted 90% of the steady-state value for the first time.
4) Product structure: feature 600, version MB, MC or MD)
Endress+Hauser 39
Levelflex FMP51, FMP52, FMP54
Influence of gas phase High pressure reduces the speed of propagation of the measuring signals in the gas/vapor above the
medium. This effect depends on the type of gas phase and its temperature. This results in a
systematic measured error that increases with increasing distance between the reference point of
the measurement (flange) and the surface of the product. The following table shows this measured
error for a few typical gases/vapors (with regard to the distance, a positive value means that too
large a distance is being measured):
°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1450 psi) 200 bar (2900 psi) 400 bar (5800 psi)
°C °F 1 bar 2 bar 5 bar 10 bar 20 bar 50 bar 100 bar 200 bar
(14.5 psi) (29 psi) (72.5 psi) (145 psi) (290 psi) (725 psi) (1450 psi) (2900 psi)
Gas phase compensation PROFIBUS and FOUNDATION Fieldbus devices can receive the signal from an external pressure
with external pressure sensor over the bus and use it to automatically perform a pressure-dependent time-of-flight
sensor (PROFIBUS PA / correction. In the case of saturated steam in the temperature range from
FOUNDATION Fieldbus) 100 to 350 °C (212 to 662 °F), this makes it possible to reduce the distance measurement error of up
to 29 % (without compensation) to below 3 % (with compensation).
40 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Gas phase compensation At high pressures and temperatures, the speed of propagation of the microwave signals in the steam
using reference signal (polar media) is reduced above the liquid to be measured. This causes the Levelflex to display a level
(option for FMP54) that is too low → 40.
An optional version of the FMP54 is available with an automatic gas phase compensation function
that corrects this measured error (feature 540: "Application packages", option EF: "Gas phase comp.
Lref = 300mm" or EG: "Gas phase comp. Lref = 550mm"). In this version, a difference in the diameter of
the probe rod generates a reference reflection at the distance Lref from the flange. This reference
reflection must be at least 150 mm above the highest level. The current speed of propagation is
measured on the basis of this shift in the reference reflection and the level value is corrected
automatically.
(11.8/21.7)
(11.8/21.7)
300/550
300/550
Lref
Lref
Dref
iD
LN
LN
max max
150 (5.91)
150 (5.91)
min min
A0014534
33 FMP54 with reference signal for gas phase compensation; engineering unit: mm (in)
Coax probes with reference reflection can be installed in any vessel (free in the tank or in a
bypass). Coax probes are ready-mounted and adjusted at the factory and are ready for use
without any additional parameter configuration.
The use of rod probes is only recommended if the installation of a coax probe is not possible
(e.g. if the bypass diameter is very small).
Rod probes with reference reflection are only suitable for installation in stilling wells and
bypass chambers. The diameter Dref of the probe rod in the area of the reference distance Lref
must be chosen to suit the pipe internal diameter iD, see the table below. The pipe must be
cylindrical in the area of the reference distance Lref; cross-section changes, e.g. at flange
connections, may not exceed 5% of the internal diameter iD.
In addition, following installation the settings must be checked by expert staff and corrected if
necessary.
Internal diameter iD of stilling well/bypass Diameter Dref of the rod probe in the area of the reference
length Lref
Endress+Hauser 41
Levelflex FMP51, FMP52, FMP54
Reference distance Lref 300 mm (11.8") or 550 mm (21.7"), see feature 540 of the product
structure
Area of application
Level measurements at high pressure and measuring ranges of up to a few meters in polar media
with a dielectric constant DC > 7 (e.g. water or ammonia), which would produce a large measured
error without compensation.
The measuring accuracy under reference conditions is higher the greater the reference distance Lref
and the smaller the measuring range:
45
40
35
Lref = 300 mm
30
Delta [mm]
25
20
Lref = 550 mm
15
10
5
0 500 1000 1500 2000 2500 3000 3500 4000
D [mm]
A0014535
In the event of fast pressure changes, an additional error may occur as the measured reference
distance is averaged with the time constant of the level measurement. Furthermore, states of non-
equilibrium - due to heating for example - may result in density gradients within the medium and
condensation of steam at the probe. As a result, level readings may vary slightly at different
locations in the vessel. These application-related influences can increase the measured error
indicated above by a factor of up to 2 to 3.
42 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Mounting
Mounting requirements Suitable mounting position
1 2 3
A 4
A0012606
Endress+Hauser 43
Levelflex FMP51, FMP52, FMP54
Additional conditions
• When mounting outdoors, a weather protection cover (1) can be used to protect the device against
extreme weather conditions.
• In metallic vessels, preferably do not mount the probe in the center of the vessel (2), as this would
lead to increased interference echoes.
If a central mounting position cannot be avoided, it is essential to perform interference echo
suppression (mapping) after commissioning the device.
• Do not mount the probe in the filling curtain (3).
• Avoid buckling the rope probe during installation or operation (e.g. as a result of product
movement against silo wall) by selecting a suitable mounting location.
In the case of freely suspended rope probes (probe end not fixed at the bottom), the distance
between the probe rope and internal fittings, which can change due to the movement of the
product, must never be less than 300 mm (12 in). Occasional contact between the probe end
weight and the cone of the vessel, however, does not influence the measurement provided that
the dielectric constant is at least DC = 1.8.
When the housing is mounted in a recess (e.g. in a concrete ceiling), observe a minimum
distance of 100 mm (4 in) between the cover of the connection compartment/electronics
compartment and the wall. Otherwise the connection compartment/electronics compartment
will not be accessible after installation.
44 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
A0014794
Endress+Hauser 45
Levelflex FMP51, FMP52, FMP54
Separable probes
14
15 Nm
A0021647
The use of separable rod probes (Ø 16 mm) is advisable in confined mounting conditions (limited
distance to the ceiling).
• Max. probe length 10 m (394 in)
• Max. lateral loading capacity 30 Nm
• Probes can be separated several times, with the individual parts having the following lengths:
• 500 mm (20 in)
• 1 000 mm (40 in)
The joints between the individual rod segments are secured by the enclosed Nord Lock washers.
Install the pre-assembled washers in pairs, cam face to cam face.
46 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
FMP51
Rope 4mm (1/6") 316
5 kN
Rope 4mm (1/6") Alloy C
5 kN
Rope 4mm (1/6") PFA>316L
1 kN
FMP52
Rope 4mm (1/6") PFA>316
2 kN
FMP54
Rope 4mm (1/6") 316
10 kN
FMP51
Rod 8mm (1/3") 316L
10 Nm
Rod 12mm (1/2") 316L
30 Nm
Rod 12mm (1/2") AlloyC
30 Nm
Rod 16mm (0.63") 316L separable
30 Nm
FMP52
Rod 16mm (0.63") PFA>316L
30 Nm
FMP54
Rod 16mm (0.63") 316L
30 Nm
Rod 16mm (0.63") 316L separable
30 Nm
With:
cw: coefficient of friction
ρ [kg/m3]: density of the medium
v [m/s]: flow velocity of the medium, perpendicular to the probe rod
d [m]: diameter of the probe rod
L [m]: level
Endress+Hauser 47
Levelflex FMP51, FMP52, FMP54
Sample calculation
L = LN (unfavorable conditions)
LN
v L
d
A0014175
A0014182-EN
FMP51
Probe Ø 21.3 mm 316L
60 Nm
Probe Ø 42.4 mm 316L
300 Nm
Probe Ø 42.4 mm AlloyC
300 Nm
FMP54
Probe Ø 42.4 mm 316L
300 Nm
48 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Threaded connection
A0015121
Seal
The thread and the type of seal comply with DIN 3852 Part 2, screwed plug, form A.
The following types of sealing ring can be used:
• For thread G3/4": According to DIN 7603 with dimensions 27 mm × 32 mm
• For thread G1/-1/2": According to DIN 7603 with dimensions 48 mm × 55 mm
Use a sealing ring according to this standard in form A, C or D and of a material that offers
appropriate resistance for the application.
Refer to the dimensional drawing for the length of the screwed plug:
Nozzle installation
£150 (6)
H
ø £150 (6)
A0015122
H Length of the centering rod or the rigid part of the rope probe
Endress+Hauser 49
Levelflex FMP51, FMP52, FMP54
Centering rod
In the case of rope probes, it may be necessary to use a version with a centering rod so that the rope
does not come in contact with the nozzle wall during the process.
The length of the optional centering rod determines the maximum nozzle height.
1
3
2
A0014199
50 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
EN
DN40/PN40 4 35 to 55 Nm
DN50/PN16 4 45 to 65 Nm
DN50/PN40 4 45 to 65 Nm
DN80/PN16 8 40 to 55 Nm
DN80/PN40 8 40 to 55 Nm
DN100/PN16 8 40 to 60 Nm
DN100/PN40 8 55 to 80 Nm
DN150/PN16 8 75 to 115 Nm
DN150/PN40 8 95 to 145 Nm
ASME
1½"/150lbs 4 20 to 30 Nm
1½"/300lbs 4 30 to 40 Nm
2"/150lbs 4 40 to 55 Nm
2"/300lbs 8 20 to 30 Nm
3"/150lbs 4 65 to 95 Nm
3"/300lbs 8 40 to 55 Nm
4"/150lbs 8 45 to 70 Nm
4"/300lbs 8 55 to 80 Nm
6"/150lbs 8 85 to 125 Nm
6"/300lbs 12 60 to 90 Nm
JIS
10K 40A 4 30 to 45 Nm
10K 50A 4 40 to 60 Nm
10K 80A 8 25 to 35 Nm
10K 100A 8 35 to 55 Nm
Endress+Hauser 51
Levelflex FMP51, FMP52, FMP54
B
2
A
A0012609
• The end of the rope probe must be secured (fixed down) under the following conditions:
If the probe would otherwise temporarily come into contact with the vessel wall, the cone, internal
fittings/beams or another part of the installation
• A female thread is provided in the probe weight to secure the end of the probe:
Rope 4 mm (1/6"), 316: M 14
• When fixed down, the end of the probe must be either reliably grounded or reliably insulated. Use
an insulated fastening kit if it is not otherwise possible to secure the probe with a reliably
insulated connection.
• To prevent an extremely high tensile load (e.g. due to thermal expansion) and the risk of the rope
breaking, the rope must be slack. Required sag: ≥ 10 mm/(1 m rope length) [ 0.12 in/(1 ft rope
length)].
Pay attention to the tensile loading capacity of rope probes.
52 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
øa
øb
»50 (1.97)
3
ø<25 (1.0)
»3 (0.12)
»50 (1.97) 6
mm (in)
A0012607
NOTICE
Poor grounding of the probe end may cause incorrect measurements.
‣ Use a sleeve with a narrow bore to ensure good electrical contact between the sleeve and the
probe rod.
NOTICE
Welding can damage the main electronics module.
‣ Before welding: Ground the probe rod and remove the electronics.
Endress+Hauser 53
Levelflex FMP51, FMP52, FMP54
A0012608
Coax probes can be secured (fixed) at any point in the ground tube.
54 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B
C
1
ød ød
2 4
(3.94)
³100
3
(3.94)
³100 ød
øD
2 ød 4
5
A0039216
Endress+Hauser 55
Levelflex FMP51, FMP52, FMP54
• The probes must not touch the pipe wall within the measuring range. Support or brace the probe if
necessary. All rope probes are prepared for bracing in vessels (tensioning weight with anchor
hole).
• If a metal centering disk is mounted at the end of the probe rod, the signal for detecting the end of
the probe is reliably defined.
Note: The non-metal centering stars made of PEEK or PFA are recommended for interface
measurements. When using metal centering disks, it is important to ensure that the lower
medium covers the centering disk at all times. Otherwise, incorrect interface measurements can
result.
• Coax probes can be used within any restrictions provided that the pipe diameter permits their
installation.
For bypasses with condensate formation (water) and a medium with a low dielectric constant
(e.g. hydrocarbons):
Over time, the bypass fills with condensate up to the lower outlet. When levels are low, the
level echo is masked by the echo of the condensate as a result. In this range, the level of the
condensate is output and the correct value is only output when levels are higher. For this
reason, ensure that the lower outlet is 100 mm (4 in) below the lowest level to be measured
and fit a metal centering disk at the level of the lower edge of the lower outlet.
In thermally insulated vessels, the bypass should also be insulated in order to prevent
condensate formation.
56 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A0014141
1 Coax probe
Endress+Hauser 57
Levelflex FMP51, FMP52, FMP54
Underground tanks
A0014142
In the case of nozzles with large diameters, use a coax probe to avoid reflections at the nozzle wall.
58 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Mounting at an angle
LN
a
A0014145
Endress+Hauser 59
Levelflex FMP51, FMP52, FMP54
Non-metal vessels
A0012527
1 Non-metal vessel
2 Metal sheet or metal flange
60 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Plastic and glass vessels: Mounting the probe on the outside wall
In the case of plastic and glass vessels, the probe can also be mounted on the outside wall under
certain conditions.
1
3
A0014150
Requirements
• Dielectric constant of the medium: εr > 7.
• Non-conductive vessel wall.
• Maximum wall thickness (a):
• Plastic: < 15 mm (0.6 in)
• Glass: < 10 mm (0.4 in)
• No metal reinforcements on the vessel.
Note the following when mounting the device:
• Mount the probe directly on the vessel wall without any space between the wall and probe.
• To prevent any influence on the measurement, fit a plastic half pipe with a diameter of at least
200 mm (8 in), or a similar protective unit, on the probe.
• For vessel diameters less than 300 mm (12 in):
On the opposite side of the vessel, fit a grounding plate that is conductively connected to the
process connection and covers around half of the vessel's circumference.
• For vessel diameters of 300 mm (12 in) and higher:
At the process connection, fit a metal plate with a diameter of at least 200 mm (8 in) at a right
angle to the probe (see above).
Endress+Hauser 61
Levelflex FMP51, FMP52, FMP54
2 3
1
MAX MAX
A0014653
2 3
40 (1.57)
40 (1.57)
1
MAX MAX
mm (in)
A0014654
A0014657
62 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2 3
2 3
MAX MAX MAX MAX
1 1
A0014658
Endress+Hauser 63
Levelflex FMP51, FMP52, FMP54
A0014153
Planning instructions:
• In normal cases, use a rod probe. When installing into a metal displacer chamber up to 150 mm,
you have all the advantages of a coax probe.
• Contact between the probe and the side wall must be avoided. Where necessary, use a centering
disk or centering star at the bottom end of the probe.
• The centering disk or centering star must be adapted as accurately as possible to the internal
diameter of the displacer chamber to also ensure correct operation around the probe end.
Additional information regarding interface measurement
• In the case of oil and water, the centering star should be positioned at the lower edge of the lower
outlet (water level).
• There should not be any changes in the diameter of the pipe. Use the coax probe if necessary.
• It must be ensured that rod probes do not come into contact with the wall. Where necessary, use a
centering star at the end of the probe.
• The non-metal centering stars made of PEEK or PFA are recommended for interface
measurements. When using metal centering disks, it is important to ensure that the lower
medium covers the centering disk at all times. Otherwise, incorrect interface measurements can
result.
64 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Environment
Ambient temperature Measuring device –40 to +80 °C (–40 to +176 °F)
Local display –20 to +70 °C (–4 to +158 °F), the readability of the local display may be impaired
at temperatures outside the temperature range.
1) This range applies if the option JN "Transmitter ambient temperature –50 °C (–58 °F)" has been selected in
order code 580 "Test, certificate". If the temperature is permanently below –40 °C (–40 °F), higher failure
rates can be expected.
Ambient temperature limits The following diagrams only consider functional aspects. Additional restrictions may apply for
certified device versions. See the separate Safety Instructions for more information.
Endress+Hauser 65
Levelflex FMP51, FMP52, FMP54
In the event of temperature (Tp) at the process connection, the permitted ambient temperature (Ta)
is reduced as indicated in the following diagram (temperature derating):
[°C] ([°F])Ta
Ta
+80 (+176)
GT20: +58(+136)
Tp
GT18: +48(+118)
A: 4...20 mA HART GT19: +29(+84)
-40 (-40)³ Tp
-40 +82 +200 [°C]
(-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +54(+129)
C: 4...20 mA HART
4...20 mA GT18: +48(+118)
K: 90...253 VAC GT19: +29(+84)
L: 10.4...48 VDC
M: Modbus
-40 (-40)³ Tp
-40 +74 +200 [°C]
(-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +57(+134)
GT18: +48(+118)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
-40 (-40) Tp
-40 +81 +200 [°C]
(-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +54(+129)
GT18: +48(+118)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
-40 (-40) Tp
-40 +79 +200 [°C]
(-40) (+174) (+392) ([°F])
A0013687
66 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +57(+135)
Tp
GT18: +49(+120)
Endress+Hauser 67
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +59(+138)
Tp
GT18: +53(+127)
GT19: -34(-29) A: 4...20 mA HART GT19: +33(+91)
GT18: -37(-34)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +82 +200 [°C]
(-58) (-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165)
4...20 mA HART GT20: +55(+131)
C:
4...20 mA GT18: +51(+124)
K: 90...253 VAC GT19: +33(+91)
GT19: -34(-29) L: 10.4...48 VDC
GT18: -37(-34) M: Modbus
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +74 +200 [°C]
(-58) (-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +58(+136)
GT18: +53(+127)
1
G : PROFIBUS PA
FOUNDATION Fieldbus
GT18: -37(-35)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +81 +200 [°C]
(-58) (-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +55(+131)
2
PROFIBUS PA GT18: +51(+124)
G :
FOUNDATION Fieldbus
Switch output
GT18: -37(-35)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +79 +200 [°C]
(-58) (-40) (+174) (+392) ([°F])
A0013689
68 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
T a [°C] ([°F])Ta
+80(+176)
GT20: +60(+140)
Tp GT18: +53(+127)
GT19: +38(+100)
GT19: -36(-33) A: 4...20 mA HART
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +82 +200 [°C]
(-58) (-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +56(+133)
C: 4...20 mA HART GT18: +51(+124)
4...20 mA GT19: +38(+100)
GT19: -36(-33) K: 90...253 VAC
GT18: -37(-35)
GT20: -38(-36) L: 10.4...48 VDC
-40(-40) Tp
-50 -40 +74 +200 [°C]
(-58) (-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81(+178)
GT20: +59(+138)
GT18: +53(+127)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +81 +200 [°C]
(-58) (-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79(+174)
GT20: +56(+133)
GT18: +51(+124)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +79 +200 [°C]
(-58) (-40) (+174) (+392) ([°F])
A0013633
1) In the case of PROFIBUS PA and FOUNDATION Fieldbus, the temperature derating depends on whether
the switch output (terminals 3 and 4) is used (G2) or not (G1).
2) The process temperature should not exceed 150 °C (302 °F) for saturated steam applications. Use FMP54
for higher process temperatures.
Endress+Hauser 69
Levelflex FMP51, FMP52, FMP54
T a [°C] ([°F])Ta
+80(+176)
Tp GT20: +62(+144)
GT18: +56(+133)
GT19: +42(+108)
GT19: -5(+23) A: 4...20 mA HART
GT18: -16(+3)
GT20: -23(-9)
-40 (-40)³ Tp
-196 -40 +82 +280 [°C]
(-321) (-40) (+180) (+536) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +59(+138)
GT18: +52(+126)
C: 4...20 mA HART
GT19: +42(+108)
4...20 mA
GT19: -5(+23)
K: 90...253 VAC
GT18: -16(+3)
GT20: -23(-9) L: 10.4...48 VDC
-40 (-40)³ Tp
-196 -40 +74 +280 [°C]
(-321) (-40) (+165) (+536) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +61(+142)
GT18: +55(+130)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -16(+3)
GT20: -23(-9)
-40 (-40) Tp
-196 -40 +81 +280 [°C]
(-321) (-40) (+178) (+536) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +58(+137)
GT18: +55(+126)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -16(+3)
GT20: -23(-9)
-40 (-40) Tp
-196 -40 +79 +280 [°C]
(-321) (-40) (+174) (+536) ([°F])
A0013631
70 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +56(+133)
Tp GT18: +54(+129)
[°C] ([°F])Ta
+81(+178)
GT20: +55(+131)
GT18: +53(+127)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -27(-16)
GT20: -28(-18)
-40 (-40) Tp
-196 -40 +81 +450 [°C]
(-321) (-40) (+178) (+842) ([°F])
[°C] ([°F])Ta
+79(+174)
GT20: +52(+126)
GT18: +50(+123)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -27(-16)
GT20: -28(-18)
-40 (-40) Tp
-196 -40 +79 +450 [°C]
(-321) (-40) (+173) (+842) ([°F])
A0013632
Endress+Hauser 71
Levelflex FMP51, FMP52, FMP54
Storage temperature • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use original packaging.
• Option for FMP51 and FMP54: –50 to +80 °C (–58 to +176 °F)
This range applies if the option JN "Transmitter ambient temperature" –50 °C (–58 °F) was selected
in order code 580 "Test, Certificate". If the temperature is permanently below –40 °C (–40 °F),
higher failure rates can be expected.
Cleaning the probe Dirt or buildup may form on the probe depending on the application. A thin, even layer has little
impact on the measurement. Thick layers can dampen the signal and reduce the measuring range.
Very uneven deposit formation or caking (e.g. due to crystallization) can result in incorrect
measurements. In such cases, use a non-contact measuring principle, or regularly inspect the probe
for contamination.
Cleaning with sodium hydroxide solution (e.g. in CIP procedures): if the coupling is wetted, larger
measurement errors can occur than under reference operating conditions. Wetting can cause
temporary incorrect measurements.
Electromagnetic Electromagnetic compatibility in accordance with all the relevant requirements outlined in the EN
compatibility (EMC) 61326 series and NAMUR Recommendation EMC (NE 21). For details, refer to the Declaration of
Conformity.
Download at www.endress.com.
72 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Process
Process temperature range The maximum temperature permitted at the process connection is determined by the O-ring version
ordered:
FMP51 FKM (Viton GLT) –30 to +150 °C (–22 to +302 °F) FDA
FMP52 — –50 to +200 °C (–58 to +392 °F); fully coated FDA, 3A,
EHEDG, USP Cl.
VI 3)
For FMP52: High process temperatures (> 150 °C (302 °F)) may favor the diffusion of the
medium through the probe coating, which may reduce the operating time.
The sensor material 1.4404/316L is resistant to attack from intergranular corrosion according
to AD 2000 - instruction sheet W2 at operating temperatures up to 400 °C (752 °F) and with an
operating time of 100,000 hours (11.4 years). For higher temperatures, the suitability of the
material must be checked by the operator. Acids, in particular, may cause corrosion.
With uncoated probes, the medium temperature may be higher provided that the process
temperature specified in the table is not exceeded at the process connection.
When using rope probes, the stability of the probe rope is reduced by structural changes at
temperatures above 350 °C (662 °F), however.
Endress+Hauser 73
Levelflex FMP51, FMP52, FMP54
[bar] ([psi]) p
420 (6090)
400 (5800)
380 (5510)
350 (5075)
320 (4640)
300 (4350) Tp
-196 -100 0 +100 200 300 400 450 [°C]
(-321) (-148) (+32) (+212) (+392) (+572) (+752) (+842) ([°F])
A0014005
The range indicated can be reduced by the choice of process connection. The maximum working
pressure (MWP) indicated on the nameplate refers to a reference temperature of 20 °C, and of
100 °F for ASME flanges. Observe pressure-temperature dependency.
Please refer to the following standards for the pressure values permitted at higher
temperatures:
• EN 1092-1: 2007 Tab. G.4.1-x
With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are
grouped together under 13E0 in EN 1092-1: 2007 Tab. G.3.1-1. The chemical composition of
the two materials can be identical.
• ASME B 16.5a - 2013 Tab. 2-2.2 F316
• ASME B 16.5a - 2013 Tab. 2.3.8 N10276
• JIS B 2220
Extension of the rope probes Elongation from temperature increase from 30 °C (86 °F) to 150 °C (302 °F): 2 mm / m rope length
due to temperature
74 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Mechanical construction
Dimensions Dimensions of the electronics housing
R110 98 (3.86)*
78 (3.07) 90 (3.54)
07)
(4.
3.5
146 (5.75)
ø108.5 (4.27)
142 (5.59)
115.25 (4.54)
ø10
A0011666
R110
99 (3.9)*
78 (3.07) 90 (3.54)
)
.17
6 (4
144 (5.67)
ø106 (4.17)
ø10
113.5 (4.47)
A0011346
R110 98 (3.86)*
78 (3.07) 90 (3.54)
07)
(4.
ø112 (4.41)
145.5 (5.73)
3.5
141.5 (5.57)
ø108.5 (4.27)
ø10
61 (2.4)
A0020751
Endress+Hauser 75
Levelflex FMP51, FMP52, FMP54
A B
ø42...60
(1.65...2.36)
52 (2)
122 (4.8) 127...140
161 (6.34) (5...5.51)
162...175
(6.38...6.89)
(3.4)
(2.8)
86
70
A0014793
With "remote sensor" device versions (see feature 060 in the product structure), the mounting
bracket is included in the scope of delivery. However, it can also be ordered separately as an
accessory (order number: 71102216).
122(4.8)
(2.05)
52
15 (0.6)
ø10
(0. .2
4)
(2.4)
61
43 (1.7)
ø82.5
(3.25)
A0023856
45 Connection piece for remote probe; length of connecting cable: as per order. Unit of measurement mm (in)
76 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
(0.98)
25
(2.72)
69
36 mm
R G¾
NPT¾
E F G H
7 mm 7 mm 7 mm
ø4 (0.16) ø4 (0.16)
ø8 (0.31) ø22 (0.87)
LN
150 (5.91)
20 (0.79)
12 (0.47)
4 (0.16)
2 (0.08)
A0012645
Endress+Hauser 77
Levelflex FMP51, FMP52, FMP54
B C D
78 (3.1)
78 (3.1)
78 (3.1)
(0.98)
(1.02)
25
26
55 mm 55 mm
R
G1½ NPT1½
I J K L M N
10 mm R
(1.54)
14 mm
39
10 mm ø16 (0.63)
ø4 (0.16)
1000 (39.4)
LN
500 (19.7)
ø4 (0.16) 14 mm
ø12 (0.47)
40 (1.57)
14 mm
2.2 (0.09)
min. 50 (1.97)
max. 551 (21.7)
max. 1051 (41.4)
150 (5.91)
20 (0.79)
12 (0.47)
4 (0.16)
P
9 (0.35)
Q Q
S
78 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
OA Rod centering disk 316L; pipe diameter DN80/3" + DN100/4" S = 4 mm (0.16 in) T = 75 mm (2.95 in)
OB Rod centering disk 316L; pipe diameter DN50/2" + DN65/2-1/2" S = 4 mm (0.16 in) T = 45 mm (1.77 in)
OC Rope centering disk 316L; pipe diameter DN80/3" + DN100/4" S = 4 mm (0.16 in) T = 75 mm (2.95 in)
OD Rod centering star PEEK; interface measurement; pipe diameter S =7 mm (0.28 in) T = 48 to 95 mm (1.9 to 3.7 in)
DN50/2" + DN100/4"
OE Rod centering star PFA; interface measurement; pipe diameter P = 10 mm (0.39 in) Q = 37 mm (1.46 in)
DN40/1-1/2" + DN50/2"
OK Rope centering weight 316L for DN50/2" 60 mm (2.4 in) 45 mm (1.77 in)
OL Rope centering weight 316L for DN80/3" 30 mm (1.18 in) 75 mm (2.95 in)
OM Rope centering weight 316L for DN100/4" 30 mm (1.18 in) 95 mm (3.7 in)
M40
8 (0.31)
A0035223
Endress+Hauser 79
Levelflex FMP51, FMP52, FMP54
A B C D E
64 91
2.52 3.58
(3.19)
(3.23)
(3.31)
(3.23)
(3.23)
81
82
84
82
82 R
F G
ø16 (0.63)
ø16 (0.63)
LN
ø4 (0.16)
ø37 (1.46)
118 (4.65)
ø22 (0.87)
A0012757
80 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B C D
60 mm 60 mm
60 mm
132 (5.2)
132 (5.2)
60 mm
342 (13.5)
315 (12.4)
267 (10.5)
240 (9.45)
159 (6.26)
159 (6.26)
ø90 ø90
ø90 ø90 (3.54) (3.54)
(3.54) (3.54)
R
37 (1.46)
37 (1.46)
8 (0.31)
8 (0.31)
8 (0.31)
8 (0.31)
14 mm 14 mm 14 mm 14 mm
E F G H I
ø16 (0.63)
40 (1.57)
14 mm 14 mm
ø4 (0.16) ø4 (0.16)
14 mm 14 mm
2.2 (0.09)
max. 1051 (41.4)
min. 50 (1.97)
M
150 (5.91)
20 (0.79)
12 (0.47)
L
9 (0.35)
4 (0.16)
2 (0.08)
M
N
A0012778
Endress+Hauser 81
Levelflex FMP51, FMP52, FMP54
N Thickness of centering disk or centering star; for table of values, see below
O Diameter of centering disk or centering star: for table of values, see below
R Reference point of measurement
OA Rod centering disk 316L; pipe diameter DN80/3" + DN100/4" N = 4 mm (0.16 in) O = 75 mm (2.95 in)
OB Rod centering disk 316L; pipe diameter DN50/2" + DN65/2-1/2" N = 4 mm (0.16 in) O = 45 mm (1.77 in)
OC Rope centering disk 316L; pipe diameter DN80/3" + DN100/4" N = 4 mm (0.16 in) O = 75 mm (2.95 in)
OD Rod centering star PEEK; interface measurement; pipe diameter N = 7 mm (0.28 in) O = 48 to 95 mm (1.9 to 3.7 in)
DN50/2" + DN100/4"
OE Rod centering star PFA; interface measurement; pipe diameter L = 10 mm (0.39 in) M = 37 mm (1.46 in)
DN40/1-1/2" + DN50/2"
OK Rope centering weight 316L for DN50/2" 60 mm (2.4 in) 45 mm (1.77 in)
OL Rope centering weight 316L for DN80/3" 30 mm (1.18 in) 75 mm (2.95 in)
OM Rope centering weight 316L for DN100/4" 30 mm (1.18 in) 95 mm (3.7 in)
82 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Surface roughness of AlloyC Ra = 3.2 µm (126 µin); lower surface roughness available on request.
coated flanges
This value applies to flanges with "AlloyC>316/316L"; see product structure, feature 100 "Process
connection". For other flanges, the surface roughness corresponds to the relevant flange standard.
Shortening probes If necessary, probes can be shortened by observing the following instructions:
Endress+Hauser 83
Levelflex FMP51, FMP52, FMP54
Weight Housing
Part Weight
Sensor Approx. 0.8 kg Rod probe 8 mm Approx. 0.4 kg/m probe length
Rope probe 4 mm Approx. 0.1 kg/m probe length Coax probe Approx. 1.2 kg/m probe length
Sensor Approx. 1.2 kg + weight of Rod probe 16 mm Approx. 1.1 kg/m probe length
flange
Rope probe 4 mm Approx. 0.1 kg/m probe length Coax probe Approx. 3.0 kg/m probe length
FMP52
Part Weight Part Weight
Sensor Approx. 1.2 kg + weight of Rope probe 4 mm Approx. 0.5 kg/m probe length
flange
FMP54
Part Weight Part Weight
Sensor - version Approx. 6.7 kg + weight of Rope probe 4 mm Approx. 0.1 kg/m probe length
XT flange
Sensor - version Approx. 7.7 kg + weight of Rod probe 16 mm Approx. 1.6 kg/m probe length
HT flange
84 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2.2
5.2
6
5.1
7
4 3 9 8
A0036037
2.2
5.2
6
5.1
7
4 9 8
A0013788
Endress+Hauser 85
Levelflex FMP51, FMP52, FMP54
2.2
5.2
6
5.1
7
4 3 9 8
A0036037
86 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Materials: Process Endress+Hauser supplies DIN/EN flanges and process connections with threaded connection in
connection stainless steel as per AISI 316L (DIN/ EN material number 1.4404 or 14435). With regard to
their stability-temperature property, the materials 1.4404 and 1.4435 are grouped together
under 13E0 in EN 1092-1: 2007 Tab. G.3.1-1. The chemical composition of the two materials
can be identical.
Levelflex FMP51
Levelflex FMP52
1 316L (1.4404)
1 2 ASME: 316/316L
1 1 EN: 316L (1.4404)
3 1
2
3
JIS: 316L (1.4435)
5 3 3 3 316L (1.4404)
4 4 4 4 4 4 Coating 2 mm (0.08 in): PTFE (Dyneon USP Cl.VI 1)
A0013868
A0013865
A0013866 A0013867
A0013869
TFM1600)
5 304L (1.4307)
1) Plastic components in contact with the medium have been tested in accordance with USP <88> Class VI-70°C
Levelflex FMP54
1 316L (1.4404)
1 1 2 316L (1.4404)
1 1
3 ASME: 316/316L
EN: 316L (1.4404)
2
7 2 7 2 JIS: 316L (1.4435)
2
7 7 3
4 Alloy C22 (2.4602)
3 4
4
5
4 5 5 316L (1.4404)
4 5 6
5 6 6 Nordlock washer: 1.4547
6 A0013883
6 A0013882
A0013880 A0013881
7 Ceramic Al2O3 99.5 %, pure graphite
Endress+Hauser 87
Levelflex FMP51, FMP52, FMP54
• AA: 8mm 316L • AC: 12mm 316L • AL: 12mm AlloyC • BA: 16mm 316L 500mm separable
• AB: 1/3" 316L • AD: 1/2" 316L • AM: 1/2" AlloyC • BB: 0.63in 316L 20inch separable No. Material
• BC: 16mm 316L 1000mm separable
• BD: 0.63in 316L 40inch separable
3
A0036651 A0036585 A0013912 A0036586
2 316 (1.4401)
1.1 1.2
3 Cylinder screw:
2 1.2 A4-80
A0039226
88 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
5
1.1 1.1
1.1
7 6
7 A0036588
A0039226
3 Spacer: PFA
Endress+Hauser 89
Levelflex FMP51, FMP52, FMP54
Levelflex FMP52
1 316L (1.4404)
1 1
2 Coating 2 mm (0.08 in): PFA
2
5 2
2
A0013870
A0036593
1) Feature 610 "Accessory mounted" = OE "Rod centering star d=37mm, PFA, interface measurement"
1 316L (1.4404)
1 1 1 2 316 (1.4401)
A0039227
90 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
• AE: rod 16mm • BA: rod 16mm, 500mm separable • UA: ... mm, coax
• AF: rod 0.63in • BB: rod 0.63in, 20inch separable • UB: ... inch, coax No. Material
• BC: rod 16mm, 1000mm separable
• BD: rod 0.63in, 40inch separable
1 316L (1.4404) 1)
A0036598
1) In the version with gas phase compensation, is also the material of the reference rod.
2) Feature 610 "Accessory mounted" = OD "Rod centering star d=48-95mm, PEEK"
3) Feature 610 "Accessory mounted" = OA "Rod centering disk d=75mm" or OB "Rod centering disk d=45mm"
4) Feature 610 "Accessory mounted" = OE "Rod, centering star d=37mm, PFA, interface measurement"
Endress+Hauser 91
Levelflex FMP51, FMP52, FMP54
12
12
11
10
A0015143
Screws/nuts A4-70
92 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
4 3
A0021722
1 Cable FRNC
Screw A4-70
Endress+Hauser 93
Levelflex FMP51, FMP52, FMP54
Materials: weather
protection cover 1
6
4
5
A0015473
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Operating languages
• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык (Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語 (Japanese)
• 한국어 (Korean)
• Bahasa Indonesia
• tiếng Việt (Vietnamese)
• čeština (Czech)
Feature 500 in the product structure determines which of these languages is preset on delivery.
94 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Endress+Hauser 95
Levelflex FMP51, FMP52, FMP54
A0036312 A0036313
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating local operation with 3 push buttons (, , ) external operation via touch control; 3
elements optical keys: , ,
A0036314
96 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2
A0036790
This operation option is only available for devices with Bluetooth module. There are the following
options:
• The device has been ordered with a Bluetooth module:
Feature 610 "Accessory Mounted", option NF "Bluetooth"
• The Bluetooth module has been ordered as an accessory (ordering number: 71377355) and has
been mounted. See Special Documentation SD02252F.
1 2 3
A0034939
Endress+Hauser 97
Levelflex FMP51, FMP52, FMP54
9
2 3 6 8
1 4 5 7
A0044334
2 3
1 PROFIBUS DP
PROFIBUS PA
T
4 4 4
A0050944
1 Segment coupler
2 Computer with PROFIusb and operating tool (e.g. DeviceCare/FieldCare )
3 PLC (programmable logic controller)
4 Transmitter
5 Additional functions (valves etc.)
98 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
IN
. -
FF-HSE BT
1
FF-H1 SB 2
PS BT
LD 4
3
BT
PS
FF-H1
BT
1
2
A0017188
IN Industrial network
SB Safety Barrier
BT Bus Terminator
Endress+Hauser 99
Levelflex FMP51, FMP52, FMP54
1 2 3
A0039148
100 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Integration into the Tank The Endress+Hauser Tank Side Monitor NRF81 has integrated communication functions for sites
Gauging System with multiple tanks, wherein each tank can have one or more sensors, e.g. radar, spot or average
temperature sensors, capacitance probes for water detection and/or pressure sensors. As the Tank
Side Monitor supports multiple protocols, it can work with virtually all industry standard tank
gauging protocols. Optional connectivity of 4-20 mA sensors, digital inputs/outputs and analog
outputs simplifies the full integration of all sensors on the tank. Use of the proven concept of the
intrinsically safe HART bus for all on-tank sensors enables extremely low wiring costs, while at the
same time ensuring maximum safety, reliability and data availability.
1 2 3
4 5
8 6
7
A0016590
Endress+Hauser 101
Levelflex FMP51, FMP52, FMP54
SupplyCare inventory SupplyCare is a web-based operating program for coordinating the flow of material and information
management software along the supply chain. SupplyCare provides a comprehensive overview of the levels of
geographically distributed tanks and silos, for instance, providing complete transparency over the
current inventory situation, regardless of time and location.
Based on the measuring and transmission technology installed onsite, the current inventory data are
collected and sent to SupplyCare. Critical levels are clearly indicated and calculated forecasts provide
additional security for material requirements planning.
The main functions of SupplyCare:
Inventory visualization
SupplyCare determines the inventory levels in tanks and silos at regular intervals. It displays current
and historical inventory data and calculated forecasts of future demand. The overview page can be
configured to suit the user's preferences.
Master data management
With SupplyCare you can create and manage the master data for locations, companies, tanks,
products and users, as well as user authorization.
Report Configurator
The Report Configurator can be used to create personalized reports quickly and easily. The reports
can be saved in a variety of formats, such as Excel, PDF, CSV and XML. The reports can be
transmitted in many ways, such as by http, ftp or e-mail.
Event management
Events, such as when levels drop below the safety stock level or plan points, are indicated by the
software. In addition, SupplyCare can also notify pre-defined users by e-mail.
Alarms
If technical problems occur, e.g. connection issues, alarms are triggered and alarm e-mails are sent to
the System Administrator and the Local System Administrator.
Delivery planning
The integrated delivery planning function automatically generates an order proposal if a pre-set
minimum inventory level is undershot. Scheduled deliveries and disposals are monitored
continuously by SupplyCare. SupplyCare notifies the user if scheduled deliveries and disposals are not
going to be met as planned.
Analysis
In the Analysis module, the most important indicators for the inflow and outflow of the individual
tanks are calculated and displayed as data and charts. Key indicators of material management are
automatically calculated and form the basis for optimizing the delivery and storage process.
Geographical visualization
All the tanks and the tank inventories are represented graphically on a map (based on Google Maps).
The tanks and inventory situations can be filtered by tank group, product, supplier or location.
Multi-language support
The multi-language user interface supports 9 languages, thereby enabling global collaboration on a
single platform. The language and settings are recognized automatically using the browser settings.
SupplyCare Enterprise
SupplyCare Enterprise runs by default as a service under Microsoft Windows on an application server
in an Apache Tomcat environment. The operators and administrators operate the application via a
Web browser from their workstations.
102 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2
3
10
5 7 8
9
.
A0034288
Endress+Hauser 103
Levelflex FMP51, FMP52, FMP54
1
3
WWW
4
10
5 7 8
9
.
A0034289
With SupplyCare Hosting, users do not need to make the initial software purchase or install and run
the IT infrastructure needed. Endress+Hauser constantly update SupplyCare Hosting and enhance
the capability of the software in conjunction with the customer. The hosted version of SupplyCare is
thus always up-to-date and can be customized to meet different customer requirements. Other
services are also offered in addition to the IT infrastructure and the software that is installed in a
secure, redundant Endress+Hauser data center. These services include defined availability of the
global Endress+Hauser Service and Support Organization and defined response times in a service
event.
104 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
CE mark The measuring system meets the legal requirements of the applicable EU directives. These are listed
in the corresponding EU Declaration of Conformity together with the standards applied.
The manufacturer confirms successful testing of the device by affixing to it the CE mark.
RoHS The measuring system meets the substance restrictions of the Directive on the Restriction of the Use
of Certain Hazardous Substances 2011/65/EU (RoHS 2) and the Delegated Directive (EU) 2015/863
(RoHS 3).
RCM marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products bear the RCM marking on the nameplate.
A0029561
Ex-approval The devices are certified for use in hazardous areas and the relevant safety instructions are provided
in the separate "Safety Instructions" (XA, ZD) document. Reference is made to this document on the
nameplate.
The separate "Safety Instructions" documentation (XA) containing all the relevant explosion
protection data is available from your Endress+Hauser sales organization.
Dual seal according to The devices have been designed according to ANSI/ISA 12.27.01 as dual seal devices, allowing the
ANSI/ISA 12.27.01 user to waive the use and save the cost of installing external secondary process seals in the conduit
as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC) These
instruments comply with the North-American installation practice and provide a very safe and cost-
saving installation for pressurized applications with hazardous fluids.
Further information can be found in the Safety Instructions (XA) of the relevant devices.
Functional safety Use for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous redundancy), independently
evaluated by TÜV Rheinland in accordance with IEC 61508, refer to the "Functional Safety Manual"
SD00326F for more information.
Sanitary compatibility Information regarding device versions that meet the requirements of 3A Sanitary Standard No. 74
and/or are certified by the EHEDG:
SD02503F
Suitable fittings and seals must be used to ensure hygiene-compliant design according to 3A
and EHEDG specifications.
The gap-free connections can be cleaned of all residue using the typical cleaning methods
within this industry (CIP and SIP).
Wetted non-metal parts of the FMP52 comply with FDA 21 CFR 177.1550 and USP Class VI.
Endress+Hauser 105
Levelflex FMP51, FMP52, FMP54
ASME B31.1 and B31.3 • The design, the material used, the pressure and temperature ranges and the labeling of the devices
meet the requirements of ASME B31.1 and B31.3
• Declaration of Conformity: see the product structure, feature 580, version KV.
Pressure equipment with Pressure instruments with a flange and threaded boss that do not have a pressurized housing do not
allowable pressure ≤ fall within the scope of the Pressure Equipment Directive, irrespective of the maximum allowable
200 bar (2 900 psi) pressure.
Reasons:
According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as
"devices with an operational function and having pressure-bearing housings".
If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber
of its own), there is no pressure accessory present within the meaning of the Directive.
Pressure equipment with Pressure equipment designated for application in every process fluid having a pressurized volume V
allowable pressure > of <0.1 l and a max. allowable pressure PS > 200 bar (2 900 psi) shall satisfy the essential safety
200 bar (2 900 psi) requirements set out in Annex I of the Pressure Equipment Directive 2014/68/EU. According to
Article 13 pressure equipment shall be classified by category in accordance with Annex II. The
conformity assessment of the pressure equipment shall be determined by the category I under
consideration of the above-mentioned low pressurized volume. These devices shall be provided with
CE marking.
Reasons:
• Pressure Equipment Directive 2014/68/EU, Article 13 and Annex II
• Pressure equipment directive 2014/68/EU, Commission's Working Group "Pressure", Guideline
A-05
Note:
A partial examination shall be performed for pressure instruments that are part of safety equipment
for the protection of a pipe or vessel from exceeding allowable limits (equipment with safety
function in accordance with Pressure Equipment Directive 2014/68/EU, Article 2, point 4).
The conformity assessment was performed according to module A; and proof of static strength and
fatigue strength according to EN 13445 and AD2000.
The FMP54 is not suitable for use with unstable gases at nominal pressures above 200 bar (2900
psi).
Steam boiler approval The FMP54 is approved as a limiting device for high water (HW) and low water (LW) for liquids in
vessels which are subject to the requirements of EN12952-11 and EN12953-9 (certified by TÜV
Nord).
Product structure: feature 590 "Additional approval", version LX "Steam boiler approval".
106 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
For details refer to Safety Instructions SD00349F and Planning Instructions SD01071F.
Devices with a steam boiler approval always also have a SIL approval.
DNV GL ABS LR BV KR
FMP51
FMP52
FMP54 - -
Radio approval Satisfies "Part 15" of the FCC rules for an unintentional radiator. All probes meet the requirements
for a Class A digital device.
In addition, coax probes and all probes in metal vessels meet the requirements for a Class B digital
device.
CRN approval Some device versions have CRN approval. Devices are CRN approved if the following two conditions
are met:
• The device has a CSA or FM approval (product structure: feature 010 "Approval")
• The device has a CRN-approved process connection according to the following table:
AAJ NPS 2" Cl. 600 RF, 316/316L flange ASME B16.5
ABJ NPS 3" Cl. 600 RF, 316/316L flange ASME B16.5
AEJ NPS 1-1/2" Cl. 150 RF, 316/316L flange ASME B16.5
AFJ NPS 2" Cl. 150 RF, 316/316L flange ASME B16.5
AGJ NPS 3" Cl. 150 RF, 316/316L flange ASME B16.5
AHJ NPS 4" Cl. 150 RF, 316/316L flange ASME B16.5
AJJ NPS 6" Cl. 150 RF, 316/316L flange ASME B16.5
AKJ NPS 8" Cl. 150 RF, 316/316L flange ASME B16.5
AOJ NPS 4" Cl. 600 RF, 316/316L flange ASME B16.5
AQJ NPS 1-1/2" Cl. 300 RF, 316/316L flange ASME B16.5
ARJ NPS 2" Cl. 300 RF, 316/316L flange ASME B16.5
ASJ NPS 3" Cl. 300 RF, 316/316L flange ASME B16.5
Endress+Hauser 107
Levelflex FMP51, FMP52, FMP54
ATJ NPS 4" Cl. 300 RF, 316/316L flange ASME B16.5
AZJ NPS 4" Cl. 900 RF, 316/316L flange ASME B16.5
A6J NPS 2" Cl. 1500 RF, 316/316L flange ASME B16.5
A7J NPS 3" Cl. 1500 RF, 316/316L flange ASME B16.5
A8J NPS 4" Cl. 1500 RF, 316/316L flange ASME B16.5
• Process connections that do not have CRN approval are not listed in this table.
• Please refer to the product structure to discover which process connections are available for a
specific device type.
• CRN-approved devices are labeled with registration number 0F14480.5C on the nameplate.
108 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
KG 3.1 Material certificate+PMI test (XRF), internal procedure, wetted metal parts, • FMP51
EN10204-3.1 inspection certificate • FMP54
KR Penetrant testing ASME VIII-1 (PT), wetted/pressurized metal parts, inspection • FMP51
certificate • FMP54
Test reports, declarations and inspection certificates are available in electronic format in the
W@M Device Viewer:
Enter the serial number from the nameplate (www.endress.com/deviceviewer)
This concerns the options for the following order codes:
• 550 "Calibration"
• 580 "Test, certificate"
Endress+Hauser 109
Levelflex FMP51, FMP52, FMP54
Product documentation on A printed (hard copy) version of test reports, declarations and inspection certificates can optionally
paper be ordered via order code 570 "Service", option I7 "Product documentation on paper". The documents
are then supplied with the product.
110 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Endress+Hauser 111
Levelflex FMP51, FMP52, FMP54
Ordering information
Ordering information Detailed ordering information is available for your nearest sales organization
www.addresses.endress.com or in the Product Configurator under www.endress.com :
1. Click Corporate
2. Select the country
3. Click Products
4. Select the product using the filters and search field
5. Open the product page
The Configuration button to the right of the product image opens the Product Configurator.
112 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
3-point linearity protocol The following points must be considered if option F3 (3-point linearity protocol) was selected in
feature 550 ("Calibration").
The 3 points of the linearity protocol are defined as follows, depending on the selected probe:
A
1 1
2 2
LN
B
3 3
C
A0021843
Rod or coax probe 1) Separable rod probe Rope probe Rope probe
LN ≤ 6 m (20 ft) LN > 6 m (20 ft) LN ≤ 6 m (20 ft) LN > 6 m (20 ft)
Position of 1st measuring • FMP51/FMP52/FMP54 without gas phase compensation/ A = 350 mm (13.8 in) A = 350 mm (13.8 in)
point FMP55:
A = 350 mm (13.8 in)
• FMP54 with gas phase compensation, Lref = 300 mm (11 in):
A = 600 mm (23.6 in)
• FMP54 with gas phase compensation, Lref = 550 mm (21 in):
A = 850 mm (33.5 in)
Position of 2nd measuring In the middle between the In the middle between the 1st and In the middle between the In the middle between the
point 1st and 3rd measuring 3rd measuring point 1st and 3rd measuring 1st and 3rd measuring
point point point
Position of 3rd measuring Measured from bottom: Measured from top: Measured from bottom: Measured from top:
point C = 250 mm (9.84 in) A+B = 5 750 mm (226 in) C = 500 mm (19.7 in) A+B = 5 500 mm (217 in)
Minimum measuring B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in)
range
Minimum probe length LN ≥ 1 000 mm (39.4 in) LN ≥ 1 000 mm (39.4 in) LN ≥ 1 250 mm (49.2 in) LN ≥ 1 250 mm (49.2 in)
• In the case of rod and rope probes, the linearity check is performed with the entire device.
• For separable rod probes, a reference rod probe is used instead of the original probe.
• In the case of coax probes, the device electronics unit is mounted on a reference rod probe
during the test and the linearity check is performed.
• The linearity check is performed under reference operating conditions.
Endress+Hauser 113
Levelflex FMP51, FMP52, FMP54
5-point linearity protocol The following points must be considered if option F4 (5-point linearity protocol) was selected in
feature 550 ("Calibration").
The 5 points of the linearity protocol are evenly distributed over the measuring range (0% - 100%).
Empty calibration (E) and Full calibration (F) must be specified in order to define the measuring
range 5).
The following restrictions must be considered when selecting E and F:
A
E
B
F
C
A0014673
FMP54 without gas phase compensation A ≥ 250 mm (10 in) B ≥ 400 mm (16 in)
FMP54 with gas phase compensation, Lref = 300 mm A ≥ 450 mm (18 in) B ≥ 400 mm (16 in)
FMP54 with gas phase compensation, Lref = 550 mm A ≥ 700 mm (28 in) B ≥ 400 mm (16 in)
5) If (E) and (F) are not specified, probe-dependent default values will be used instead.
114 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
• In the case of rod and rope probes, the linearity check is performed with the entire device.
• In the case of coax probes, the device electronics unit is mounted on a reference rod probe
during the test and the linearity check is performed.
• The linearity check is performed under reference operating conditions.
The selected values for Empty calibration and Full calibration are only used to create the
linearity protocol. Afterwards, the values are reset to the default values specific for the probe. If
values other than the default values are required, they must be ordered as a customized
parameterization → 116.
Endress+Hauser 115
Levelflex FMP51, FMP52, FMP54
Customized If the option IJ: "Customized parameterization HART", IK "Customized parameterization PA" or IL
parameterization "Customized parameterization FF" has been selected in feature 570 "Service", presettings that differ
from the default settings can be selected for the following parameters:
Labeling (optional) Various types of measuring point labeling can be selected in the Product Configurator.
This includes:
• Tag
• Adhesive label
• RFID TAG
• Labeling according to DIN91406, also with NFC.
Tag name
3 lines with a maximum of 18 characters per line
Labeling in the electronic nameplate (ENP)
The first 32 characters of the tag name
Labeling on the display module
The first 12 characters of the tag name
Application packages
Heartbeat Diagnostics Availability
Available in all device versions.
Function
• Continuous self-monitoring of the device.
• Diagnostic messages output to
• the local display.
• an asset management system (e.g. FieldCare/DeviceCare).
• an automation system (e.g. PLC).
Advantages
• Device condition information is available immediately and processed in time.
• The status signals are classified in accordance with VDI/VDE 2650 and NAMUR recommendation
NE 107 and contain information about the cause of the error and remedial action.
Detailed description
See the "Diagnostics and troubleshooting" section of the Operating Instructions for the device.
116 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Advantages
• No onsite presence is required to use the function.
• The DTM triggers verification in the device and interprets the results. No specific knowledge is
required on the part of the user.
(DTM: Device Type Manager; controls device operation via DeviceCare, FieldCare or a DTM-based
process control system.)
• The verification report can be used to prove quality measures to a third party.
• Heartbeat Verification can replace other maintenance tasks (e.g. periodic check) or extend the
test intervals.
SIL/WHG-locked devices
Only relevant for devices with SIL or WHG approval: order code 590 ("Additional approval"), option
LA ("SIL") or LC ("WHG").
• The Heartbeat Verification module contains a wizard for the proof test which must be performed
at appropriate intervals for the following applications:
• SIL (IEC61508/IEC61511)
• WHG (German Water Resources Act)
• To perform a proof test, the device must be locked (SIL/WHG locking).
• The wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
In the case of SIL-locked and WHG-locked devices, it is not possible to perform verification
without taking additional measures (e.g. bridging the output current) because the output
current must be simulated (Increased safety mode) or the level must be approached manually
(Expert mode) during subsequent re-locking (SIL/WHG locking).
Detailed description
SD01872F
Function
• In addition to the verification parameters, the corresponding parameter values are also logged.
• Existing measured variables, such as the echo amplitude, are used in the Foam detection and
Build-up detection wizards.
In the Levelflex FMP5x, the Foam detection and Build-up detection wizards cannot be used
together.
Endress+Hauser 117
Levelflex FMP51, FMP52, FMP54
Advantages
• Early detection of changes (trends) to ensure plant availability and product quality.
• Use of information for the proactive planning of measures (e.g. cleaning/maintenance).
• Identification of undesirable process conditions as the basis to optimizing the facility and the
processes.
• Automated control of measures to remove foam or buildup.
Detailed description
SD01872F
Accessories
Device-specific accessories Weather protection cover
The weather protection cover can be ordered together with the device via the "Accessory enclosed"
product structure.
222 (8.74)
A0015466
118 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
226 (8.9)
11
12.5°×10 7.2
°
! 6.6
20 ×
A0015472
Material
316L
Order number for accessories:
71162242
Accessories Description
ø42...60
(1.65...2.36)
52 (2)
86
70
A0014793
With "remote sensor" device versions (see feature 060 in the product structure), the mounting bracket is included in
the scope of delivery. However, it can also be ordered separately as an accessory (order number: 71102216).
Endress+Hauser 119
Levelflex FMP51, FMP52, FMP54
Accessories Description
1 Nozzle height
2 Extension rod
3 Centering disk
010 Approval:
A Non-hazardous area
1 ATEX II 1G
2 ATEX II 1D
A Not selected
120 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories Description
A0013586
The mounting kit can also be ordered directly with the device (Levelflex
product structure, feature 620 "Accessory enclosed", version PG "mounting kit,
insulated, rope").
Endress+Hauser 121
Levelflex FMP51, FMP52, FMP54
Centering star
Accessories Description
7 (0.28)
• FMP51 10 (0.39)
• FMP54
3)
.6
(0
6
ø1
< 50 (1.97)
ø48 (1.89)
ø75 (2.95)
ø95 (3.74)
A0014576
The centering star is suitable for probes with a rod diameter of 16 mm (0.6 in) and
can be used in pipes from DN50 to DN100. The markings make it easer to cut to
size, ensuring that the centering star can be adjusted to the pipe diameter. See also
Operating Instructions SD02316F.
• Material of centering star: PEEK
• Material of retaining rings: PH15-7Mo (UNS S15700)
• Permitted process temperature range: –60 to +250 °C (–76 to +482 °F)
• Order number: 71069064
Ifbypass
the centering star is used in a bypass, it must be positioned below the lower
outlet. This must be taken into account when choosing the probe
length. In general, the centering star should not be mounted more than 50
mm (1.97") above the probe tip. It is advised not to use the PEEK centering
star in the measuring range of the rod probe.
The PEEK centering star can also be ordered directly with the device
(Levelflex product structure, feature 610 "Accessory mounted", option OD). In
this case, it is not secured to the rod using the retaining rings, but instead is
secured using a hexagonal-headed bolt (A4-70) and a Nord Lock washer
(1.4547) at the tip of the probe rod.
122 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories Description
10 (0.39)
• 16.4 mm (0.65 in)
• 37 mm (1.46 in)
suitable for
• FMP51
• FMP52
• FMP54
A: ø16.4 (0.65)
B: ø37 (1.46)
A0014577
The centering star is suitable for probes with a rod diameter of 8 mm (0.3 in),
12 mm (0.47 in) and 16 mm (0.63 in) (including coated rod probes) and can be
used in pipes from DN40 to DN50. See also Operating Instructions
BA00378F/00/A2.
• Material: PFA
• Permitted process temperature range: –200 to +250 °C (–328 to +482 °F)
• Order number
• Probe 8 mm (0.3 in) : 71162453
• Probe 12 mm (0.47 in): 71157270
• Probe 16 mm (0.63 in): 71069065
product
The PFA centering star can also be ordered directly with the device (Levelflex
structure, feature 610 "Accessory mounted", option OE).
Endress+Hauser 123
Levelflex FMP51, FMP52, FMP54
Accessories Description
5,5 (0.22)
48 to 95 mm
(1.9 to 3.7 in)
suitable for Ø4 (0.16)
• FMP51
• FMP52
• FMP54
)
)
.2
89
(1.
(0
48
5
Ø
Ø75 (2.95)
Ø9
5(
3.7
4)
A0035182
The centering star is suitable for probes with a rope diameter of 4 mm (¹⁄₆ in)
(including coated rope probes). See also Operating Instructions SD01961F.
• Material: PEEK
• Permitted process temperature range: –60 to +250 °C (–76 to +482 °F)
• Order number
• 71373490 (1x)
• 71373492 (5x)
124 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Centering weight
Accessories Description
suitable for
• FMP51
• FMP54
Ø20 (0.79)
Ø30 (1.18)
12 (0.47)
60 (2.36)
Ø5,5 (0.22)
12 (0.47)
Ø11 (0.43)
Ø45 (1.77)
A0038923
The centering weight is suitable for probes with a rope diameter of 4 mm (¹⁄₆ in)
and can be used in DN50/2" pipes.
Material: 316L
The centering weight can be ordered directly with the device (product structure
Levelflex) or as a probe without a process connection (product structure XPF0005-)
using feature 610 "Accessory mounted", version OK (for pipe DN50/2").
Endress+Hauser 125
Levelflex FMP51, FMP52, FMP54
Accessories Description
Ø20 (0.79)
ØA
12 (0.47)
Ø30 (1.18)
30 (1.18)
12 (0.47)
Ø5,5 (0.22) Ø8 (0.31)
11 (0.43)
ØB
A0038924
The centering weight is suitable for probes with a rope diameter of 4 mm (¹⁄₆ in)
and can be used in DN80/3" or DN100/4" pipes.
Material: 316L
The centering weight can be ordered directly with the device (product structure
Levelflex) or as a probe without a process connection (product structure XPF0005-)
using feature 610 "Accessory mounted", version OL (for pipe DN80/3") or OM (for
pipe DN100/4").
1.
3.
2.
4.
A0019128
126 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Technical data
• Material:
• Plastic PBT
• 316L/1.4404
• Aluminum
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
• SD02 (push buttons)
• SD03 (touch control)
• Connecting cable:
• Cable supplied with device up to 30 m (98 ft)
• Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature:–40 to 80 °C (–40 to 176 °F)
• Ambient temperature (option): –50 to 80 °C (–58 to 176 °F) 6)
Ordering information
• If the remote display is to be used, the device version "Prepared for display FHX50" must be
ordered.
For the FHX50, the option "Prepared for display FHX50" must be selected under "Measuring device
version".
• If a measuring device has not been ordered with the version "Prepared for display FHX50" and is to
be retrofitted with an FHX50, the version "Not prepared for display FHX50" must be ordered for the
FHX50 under "Measuring device version". In this case, a retrofit kit for the device is supplied with
the FHX50. The kit can be used to prepare the device so that the FHX50 can be used.
Use of the FHX50 may be restricted for transmitters with an approval. A device may only be
retrofitted with the FHX50 if the option "Prepared for FHX50" is listed in the associated Safety
Instructions (XA) under Basic specifications, "Display, operation".
Also pay attention to the Safety Instructions (XA) of the FHX50.
Retrofitting is not possible on transmitters with:
• An approval for use in areas with flammable dust (dust ignition-proof approval)
• Type of protection Ex nA
For details, see the "Special Documentation" SD01007F
Overvoltage protection
The surge arrester for loop-powered devices can be ordered together with the device via the
"Accessory mounted" section of the product order structure.
The surge arrester can be used for loop-powered devices.
• 1-channel devices - OVP10
• 2-channel devices - OVP20
A0021734
6) This range applies if the option JN "Transmitter ambient temperature" –50 °C (–58 °F) was selected in feature 580 "Test, Certificate". If the
temperature is permanently below –40 °C (–40 °F), higher failure rates can be expected.
Endress+Hauser 127
Levelflex FMP51, FMP52, FMP54
Technical data
• Resistance per channel: 2 × 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold surge voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal leakage current (8/20 μs): 10 kA
• Suitable for conductor cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
If retrofitting:
• Order number for 1-channel devices (OVP10): 71128617
• Order number for 2-channel devices (OVP20): 71128619
• The use of the OVP module may be restricted depending on the transmitter approval. A device
may only be retrofitted with the OVP module if the option NA (overvoltage protection) is listed
under Optional specifications in the Safety Instructions (XA) associated with the device.
• In order to keep the necessary safety distances when using the surge arrester module, the housing
cover also needs to be replaced when the device is retrofitted.
Depending on the housing type, the suitable cover can be ordered using the following order
number:
• Housing GT18: 71185516
• Housing GT19: 71185518
• Housing GT20: 71185517
For details, see the "Special Documentation" SD01090F
A0036493
Technical data
• Quick and easy setup with the SmartBlue app
• No additional tools or adapters needed
• Signal curve via SmartBlue (app)
• Encrypted single point-to-point data transmission (tested by Fraunhofer Institute) and password-
protected communication via Bluetooth® wireless technology
• Range under reference conditions:
> 10 m (33 ft)
• When the Bluetooth module is used, the minimum supply voltage of the device increases by up to
3 V.
If retrofitting:
• Order number: 71377355
• The use of the Bluetooth module may be restricted depending on the transmitter approval. A
device may only be retrofitted with the Bluetooth module if the option NF (Bluetooth module) is
listed under Optional specifications in the Safety Instructions (XA) associated with the device.
For details, see the "Special Documentation" SD02252F
128 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Commubox FXA291
Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser Common Data
Interface) and the USB port of a computer or laptop
Order number: 51516983
For details, see "Technical Information" TI00405C
Fieldgate FXA42
Fieldgates enable communication between connected 4 to 20 mA, Modbus RS485 and Modbus TCP
devices and SupplyCare Hosting or SupplyCare Enterprise. The signals are transmitted either via
Ethernet TCP/IP, WLAN or mobile communications (UMTS). Advanced automation capabilities are
available, such as an integrated Web-PLC, OpenVPN and other functions.
For details, see "Technical Information" TI01297S and Operating Instructions BA01778S.
Endress+Hauser 129
Levelflex FMP51, FMP52, FMP54
FieldCare SFE500
FDT-based plant asset management tool
It can configure all smart field units in your system and helps you manage them. By using the status
information, it is also a simple but effective way of checking their status and condition.
Technical Information TI00028S
RN221N
Active barrier with power supply for safe separation of 4 to 20 mA standard signal circuits. Offers
bidirectional HART transmission.
Technical Information TI00073R and Operating Instructions BA00202R
RN221
Supply unit for powering two 2-wire measuring devices solely in the non-Ex area. Bidirectional
communication is possible via the HART communication jacks.
Technical Information TI00081R and Brief Operating Instructions KA00110R
Supplementary documentation
The following document types are available in the Downloads section of the Endress+Hauser website
(www.endress.com/downloads):
For an overview of the scope of the associated Technical Documentation, refer to the following:
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the
nameplate
• Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
matrix code on the nameplate
Brief Operating Instructions Guide that takes you quickly to the 1st measured value
(KA) The Brief Operating Instructions contain all the essential information from incoming acceptance to
initial commissioning.
Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They
are an integral part of the Operating Instructions.
The nameplate indicates the Safety Instructions (XA) that are relevant to the device.
Functional Safety Manual Depending on the SIL approval, the Functional Safety Manual (FY/SD) is an integral part of the
(FY/SD) Operating Instructions and applies in addition to the Operating Instructions, Technical Information
and ATEX Safety Instructions.
The different requirements that apply for the protective function are described in the
Functional Safety Manual (FY / SD).