JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.

Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road


36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 1/10

JUMO miroVIEW
Smart digital indicator with limit value monitoring function

Brief description
The smart digital indicator is used for the electronic display of various process variables. The pro-
cess variables are acquired by the device via RTD temperature probe, thermocouple, current
0(4) to 20 mA or voltage 0 to 10 V. Further functionalities are limit value monitoring, min/max val-
ue storage, hold function and tare function. The device is available with 2 relays or with 1 relay
and 1 digital output (DC 0/14 V).
The device is characterized by simple, clearly structured operation supported by texts in English,
German, French, and Spanish. Process values, texts, and parameters are shown in two 18-seg-
ment LCD displays. Additional display elements inform about the switch positions of the outputs,
miroVIEW Type 701580
timer status, and temperature unit.
Terminal blocks with PUSH IN technology enable fast electrical installation.
Operation, parameterization, and configuration are carried out via a membrane keyboard with
four keys. The setup program on a PC allows the device to be configured without any problems.
No separate voltage supply is required when configuring via the USB interface (USB-powered).

Block diagram Special features


• Integrated timer function
Analog input Setup interface
• Service and operating hours counter
2-wire RTD temperature probe USB device • Fast wiring through PUSH IN technology
Pt100, Pt1000
• High-quality display and intuitive opera-
or
3-wire RTD temperature probe
tion
Pt100, Pt1000
Digital outputs
• Configuration on the device or with the
or
1 relay (changeover AC 250 V, 10 A)
setup program (accessories) via USB in-
Thermocouples Fe-CuNi "L",
Fe-CuNi "J", NiCr-Ni "K" 1 relay (NO contact AC 250 V, 5 A) terface (USB-powered
Type 701580

or
or
1 relay (changeover AC 250 V, 10 A) • Operator guidance with text support in 4
0(4) to 20 mA 1 digital output DC 0/14 V languages
or
0 to 10 V • Limit value monitoring function
Digital input
Digital input for potential-free contact
(not with 3-wire circuit)
Voltage supply LCD display
- AC 230 V +10/-15 %, 48 to 63 Hz
- AC 115 V +10/-15 %, 48 to 63 Hz
Membrane keypad
- DC 12 to 24 V ±15 %

Approvals and approval marks (see technical data)

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 2/10

Description Service counter


The service counter is used either to count the
Indicator functions switching frequency of a binary signal or to de-
termine its switch-on duration. When the set
In addition to the classic display of the mea- limit value is reached, a binary signal is acti-
sured value, the device has additional func-
vated that needs to be acknowledged.
tions such as min/max value display, a hold
function for freezing the measured value and a In addition, an operating hours counter is
tare function for weighing applications. Some available that determines the device's opera-
functions can be configured via the membrane tion time.
keypad on the front.
Setup program
Inputs and outputs The setup program, which is available as an
RTD temperature probe, thermocouple, cur- accessory, provides the user with an easy and
rent, voltage can be selected as analog input. comfortable way to configure the device using
A combination of 1 changeover contact and 1 a PC. This allows data records to be created,
normally open contact or 1 relay output in edited and transferred to the device, as well as
combination with a digital input is available as read out from there. A recording function for
relay outputs. The digital input is provided to start-up is available.
connect a potential-free contact.
Customer-specific
USB device interface Linearization
The device is equipped with a USB device in- Sensor signals with special characteristic line
terface (micro-B socket on the rear side). This properties can also be used through custom-
is intended for connecting to a PC and for con- er-specific linearization. Programming is car-
figuring the device via the setup program. ried out in the setup program on the basis of a
Thereby the device is powered via the USB in- value table with up to 40 value pairs or through
terface. As a result, no mains supply is re- a formula (4th order polynomial).
quired during the configuration.

Electrical connection
The electrical connection saves time by using
practical spring-cage terminals (Push-In tech-
nology).

Limit value monitoring functions


The device is equipped with three limit value
monitoring functions, each with two configu-
rable alarm functions. Any analog signal from
a selector is selected as the value to be moni-
tored. An absolute value serves as the limit
value. Special functions such as switch-on/
switch-off delay, pulse function, alarm sup-
pression in the switch-on phase or in case of a
parameter change, alarm latch, and lock with
acknowledgment are available. With the limit
value monitoring function, extensive alarm
and limit value functions can be implemented.

Timer
After the timer is started, a signal is output for
the duration of the timer running time; this sig-
nal is invertible. It is also possible to start the
timer after the lead time has elapsed or after
reaching a tolerance limit. A timer end signal
can be output after the timer has elapsed (limit
by time or acknowledgement).

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 3/10

Technical data
Analog input
Thermocouples

Designation Type Standard ITS Measuring range Accuracya


Fe-CuNi "L" DIN 43710 (1985-12) IPTS-68 -200 to +900 °C ≤ 0.4 %
Fe-CuNi "J" DIN EN 60584-1:2013 ITS-90 -210 to +1200 °C ≤ 0.4 % from -100 °C
IEC 60584-1:2013
NiCr-Ni "K" DIN EN 60584-1:2013 ITS-90 -270 to +1300 °C ≤ 0.4 % from -80 °C
IEC 60584-1:2013
a
Accuracy refers to the measuring range.

Ambient temperature influence ≤ 300 ppm/K


Cold junction Internal or external (constant)
Cold junction temperature 0 °C (permanently set)
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s

RTD temperature probe

Designation Standard ITS Connection type Measuring range Accuracya Measuring


current
Pt100 DIN EN 60751:2008 ITS-90 Two/three-wire -200 to +600 °C ≤ 0.25 % 500 μA
IEC 60751:2008
Pt1000 DIN EN 60751:2009 ITS-90 Two/three-wire -200 to +600 °C ≤ 0.25 % 100 μA
IEC 60751:2008
Customer-specific 150 to 3000 Ω ≤ 0.25 % < 500 μA
a
Accuracy refers to the measuring range.

Ambient temperature influence ≤ 300 ppm/K


Sensor line resistance Max. 30 Ω per line
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s

Voltage, current (standard signals)

Designation Measuring range Accuracya Input resistance or compli-


ance voltage
Voltage 0 to 10 V ≤ 0.15 % > 100 kΩ
Current 4 to 20 mA ≤ 0.125 % < 2.5 V
0 to 20 mA ≤ 0.125 % < 2.5 V
a Accuracy refers to the maximum measuring range. Small measuring spans lead to reduced linearization accuracy.

Ambient temperature influence ≤ 100 ppm/K


Deviation below/above the measuring According to NAMUR recommendation NE 43 (only current input 4 to 20 mA)
range
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s

Measuring circuit monitoring


The device behavior in the event of a malfunction is configurable.

Measuring probe Measuring range un- Measuring range Short-circuit (probe/ Break (probe/line) Reverse polarity
derflow overflow line)
RTD temperature ++ ++ ++ ++ ---
probe
Thermocouple ++ ++ --- ++ (+)a
Current 0 to 20 mA --- ++ --- --- ---

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 4/10

Measuring probe Measuring range un- Measuring range Short-circuit (probe/ Break (probe/line) Reverse polarity
derflow overflow line)
Current 4 to 20 mA ++ ++ ++ ++ ++
Voltage 0 to 10 V --- ++ --- --- ++
++ = is detected --- = is not detected (+) = is detected in certain conditions
a
Dependent on the set characteristic line

Digital input
Input for potential-free contact
Function Contact closed: input is active (RON < 1 kΩ)
Contact open: input is inactive (ROFF > 100 kΩ)

Digital outputs
1 relay (changeover contact) Order code 23
Switching capacity Max. 10 A at DC 30 V or AC 250 V, resistive load
Contact life 100,000 switching operations at rated load
1 relay (normally open contact)
Switching capacity Max. 5 A at DC 30 V or AC 250 V, resistive load
Contact life 100,000 switching operations at rated load
1 relay (normally open contact) Order code 26
Switching capacity Max. 10 A at DC 30 V or AC 250 V, resistive load
Contact life 100,000 switching operations at rated load
1 digital output DC 0/14 V
Output signal DC 0/14 V ±15 %
Current Max. 20 mA (at nominal voltage 14 V)

Interface
USB device
Connector type Micro-B (socket)
Standard Low-Speed, Full-Speed
Max. cable length 5m

Display
18-segment LCD displays
Upper display: Lower display:
Digit height 13 mm 4 mm
Color white Green
Places, including decimal places 4 7
Decimal places 0, 1, or automatic (configurable)

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 5/10

Electrical data
Voltage supply 02 AC 230 V -15/+10 %, 48 to 63 Hz
according to the ordered version 05 AC 115 V -15/+10 %, 48 to 63 Hz
30 DC 12 to 24 V, -15/+15 % SELV
Electrical safety acc. to DIN EN 61010, part 1
Overvoltage category II to 300 V mains voltage,
Pollution degree 2
Power consumption Type AC 230 V: Type AC 115 V: Type DC 12 to 24 V:
Type 701580 Max. 3.3 W Max. 3.6 W Max. 1.7 W
Accuracy of timer 1%
Sampling rate 250 ms
Electrical connection On the back via spring-cage terminals (PUSH IN technology)
Conductor cross section, mechanical
Wire or stranded wire Min. 0.2 mm2, max. 1.5 mm2
(without ferrule)
Stranded wire with ferrule Without plastic collar: min. 0.2 mm2, max. 1.5 mm2
With plastic collar: min. 0.2 mm2, max. 0.75 mm2
Stripping length 8 mm
Conductor cross section, electric
5 A load current Min. 0.75 mm2
10 A load current Min. 1.0 mm2
16 A load current Min. 1.5 mm2

Environmental influences
Ambient temperature range
Storage -30 to +70 °C
Operation -10 to +55 °C
Site altitude Max. 2000 m above sea level
Climatic environmental influences According to DIN EN 60721-3 with extended temperature range
Resistance to climatic conditions ≤ 90 % rel. humidity without condensation
Storage According to class 1K2
Operation According to class 3K3
Mechanical environmental influences According to DIN EN 60721-3
Storage According to class 1M2
Transport According to class 2M2
Operation According to class 3M3
Electromagnetic compatibility (EMC) Product family standard DIN EN 61326-1
Interference emission Class Ba
Interference immunity Industrial requirement
a
The product is suitable for industrial use as well as for households and small businesses

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 6/10

Case
Case type Plastic case for panel mounting according to IEC 61554 (indoor use), cobalt blue RAL 5013
Case front Membrane keyboard,
upper slope cobalt blue RAL 5013, lower slope silver grey RAL 7001
Panel thickness 1 to 10 mm
Case mounting In panel using the supplied mounting frame or both mounting elements
Operating position Anya
Protection type According to DIN EN 60529, IP65 on the front, IP20 on the back
Weight
Type 701580 Max. 154 g
a
The maximum admissible ambient temperature only applies for the installation with the display in a vertical position.

Approvals and approval marks


Approval mark Test facility Certificates/Certification Inspection basis Valid for
numbers
c UL us Underwriters E201387 UL 61010-1 (3rd Ed.), All types
Laboratories CAN/CSA-22.2 No. 61010-1
(3rd Ed.)
The device is approved if the relevant approval mark is pictured on the device.

Dimensions
Type 701580

62
60 76
34,5
28

36

4,8
68,5

73

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 7/10

Panel cut-outs
Panel cut-outs according to DIN IEC 61554

Type Panel cut-out Mounting depth with- Minimum spacing of panel cut-outs
(width x height) out seal (for close mounting)
With terminal blocks Horizontal Vertical
701580 69 +1 mm × 28.5 +1 mm 62 mm 15 mm 30 mm

Galvanic isolation
AC 3000 V
(a)
(10) (1)

(9) AC 3000 V
(a)
(8) (2)

AC 3000 V
(a)
(3)
AC 3000 V
(a)
(7) (4)

(5)
(b)
(6)

a The voltage specifications correspond to the test voltag- b Functional galvanic isolation for
es (alternating voltage, rms values) connecting SELV or PELV
according to DIN EN 61010-1 (VDE 0411-1):2020-03 electrical circuits
1 Type 701580 (order code 23): 2 Type 701580: Not available.
2 relay outputs (changeover contact, normally open con-
tact)
The two relay outputs are not allowed to be operated on
different mains voltage circuits. It is also not admissible
to mix how the relay outputs are operated – using a
SELV electrical circuit and a mains supply circuit.
3 Type 701580 (order code 26): 4 Type 701580 (order code 26):
1 relay output (normally open contact) 1 digital output DC 0/14 V
5 or 6 Voltage supply DC 12 V to 24 V
7 Voltage supply 230 V, 48 to 63 Hz 8 USB interface
115 V, 48 to 63 Hz
9 Digital input 10 Analog input

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 8/10

Display and control elements


(5) (1) (7)

(6) (4) (3) (2) (8)

1 Display 1 - 18-segment LCD display (e.g. analog in- 2 Display 2 - 18-segment LCD display (e.g. text), 7-digit
put), 4-digit, white; green;
also for displaying menu items, parameters and text displaying of menu items, parameters, text and values;
here individually configured measuring point designa-
tion (ZONE 1)
3 Timer (illuminated = on, flashing = started), 4 Switch position of the digital outputs (yellow = active)
Temperature Unit
5 Up (in the menu: increase value, select previous menu 6 Down (in the menu: reduce value, select next menu
item or parameter) item or parameter)
7 Back (in menu: back to previous menu level, exit editing 8 Menu/OK (call up main menu, switch to submenu/level,
mode without change; in basic status: configurable switch to editing mode, exit editing mode with change)
function)

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 9/10

Connection diagram
The connection diagram in the data sheet provides information on product selection.
For the electrical connection, only use the installation instructions or the operating manual.

Type 701580

Terminal strip 2: Terminal strip 3: Terminal strip 4:


Analog input, digital input L1(L+), N(L-) Digital outputs
RTD temperature probe in three-wire circuit (no digi- Voltage supply (see name- 1 relay changeover contact,
tal input) plate) 1 relay normally open contact
AC 230 V, 48 to 63 Hz
1 2 3 or Digital output 1 (changeover contact) and
AC 115 V, 48 to 63 Hz digital output 2 (normally open contact):
or
DC 12 to 24 V
RTD temperature probe in two-wire circuit and
1 2
Digital input

1 2 3 1 2 3 4 5

Thermocouple and The two relays are not allowed to be operated on dif-
digital input ferent mains voltage circuits. It is also not admissible
to mix how the relays are operated – using a SELV
1 2 3 electrical circuit and a mains supply circuit.

Current 0(4) to 20 mA and 1 relay normally open contact,


digital input 1 digital output DC 0/14 V

3 Digital output 1 (normally open contact) and


1 2
digital output 2 (DC 0/14 V):

Ix

Voltage 0 to 10 V and
1 2
digital input
DC 0/14V

1 2 3 1 2 3 4 5

Ux

V1.00/EN/2022-12-01 70158000T10Z001K000
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.
Delivery address: Mackenrodtstraße 14 JUMO House 6724 Joy Road
36039 Fulda, Germany Temple Bank, Riverway East Syracuse, NY 13057, USA
Postal address: 36035 Fulda, Germany Harlow, Essex, CM20 2DY, UK Phone: +1 315 437 5866
Phone: +49 661 6003-0 Phone: +44 1279 63 55 33 Fax: +1 315 437 5860
Fax: +49 661 6003-607 Fax: +44 1279 62 50 29 Email: [email protected]
Email: [email protected] Email: [email protected] Internet: www.jumousa.com
Internet: www.jumo.net Internet: www.jumo.co.uk

Data Sheet 701580 Page 10/10

Order details
(1) Basic type
701580 Type 701580 with max. 2 relays, format (76 x 36 x 62) mm
(2) Version
0 Standard version
1 Customized hardware
2 Customized software
3 Customized hardware and software
(3) Input (measurement input groups)a
01 1 RTD temperature probe Pt100, Pt1000 in two-wire circuit, 1 digital input
02 1 RTD temperature probe Pt100, Pt1000 in three-wire circuit
04 1 thermocouple and 1 digital input
05 0(4) to 20 mA and 1 digital input
(4) Output
23 1 relay (changeover contact AC 250 V, 10 A) and 1 relay (normally open contact AC 250 V, 5 A), resistive load
26 1 relay (normally open contact AC 250 V, 10 A) resistive load and 1 digital output DC 0/14 Vb
(5) Voltage supply
02 AC 230 V, +10/-15 %, 48 to 63 Hz
05 AC 115 V, +10/-15 %, 48 to 63 Hzc
30 DC 12 to 24 V +15/-15 %
(6) Extra codes
000 None
a
It is not possible to switch from one measurement input group to another
b Minimum order quantity 50 pieces
c Minimum order quantity 50 pieces

(1) (2) (3) (4) (5) (6)


Order code / - - - /
Order example 701580 / 0 - 01 - 23 - 02 / 000

Scope of delivery
1 device in the ordered version
1 quick start guide
1 mounting frame

Accessories
Description Part no.
Setup program 00777355
USB cable, A connector to Micro-B connector, length 3 m 00616250

V1.00/EN/2022-12-01 70158000T10Z001K000