Generator Protection Explained
Generator Protection Explained
Generator Protection
[http://2.bp.blogspot.com/
OXWt9oM9kJ8/UcaiuCjHp4I/AAAAAAAACaA/HlKpsSPD1zw/s1600/8.jpg]
GENERATOR AND ITS PROTECTION
The core of an electrical power system is the generator. There are power units based on steam, gas, naphtha,
water power, diesel engine drive and wind mills. The range of size extends from a few hundred KVA (or even less) for
enginedriven and hydro sets up to turbine driven sets exceeding 500MVA in rating.
Small and medium sized sets may be directly connected to the distribution system. A larger unit is usually
associated with an individual transformer, transmission system. No switchgear is provided between the generator
and transformer may be tapped off the interconnection for the supply of power to auxiliary plant. Provision of a
breaker in between Generator and Transformer makes it possible to draw power for the auxiliaries through the UAT
from the EHV bus, even when machine is not in service. Typical arrangements are given in figure............
Station Transformers:
The vector group of these transformers is StarDelta i.e. the 6.6 KV system is delta connected Or The vector
group of these transformers is StarStar with the 6.6KV side grounded through a high resistance.
Unit Auxilary Transformers :
The vector group of these transformers is Delta – Star (ungrounded Star on 6.6KV System).Any earth fault on
the 6.6 KV system cannot be seen by any E/L relay (since the 6.6 KV system is delta connected or high resistance
grounded or ungrounded Star).However 3O/L relays are provided on the 6.6KV side of the Station Transformers and
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 1/9
12/5/2016 Generator Protection Explained
Unit Auxilary Transformers . An opendelta voltage of the 6.6 KV bus PT is connected to an over voltage relay with a
very low setting. Any earth fault on the 6.6 KV system will cause the presence of opendelta voltage and make the
voltage relay operate which is connected to give alarm. The faulty 6.6 KV feeder can be identified by tripping the 6.6
KV outlets one after the other.
Generating units are the source of the power system and their security against any adverse conditions is
most important in the system. The generator protection must ensure a fast and selective detection of any fault in
order to minimize their dangerous effects.
Protection of passive elements like transmission lines and transformers is relatively simple which involves
isolation of faulty element from the system, whereas protection of generators involves tripping of generator field
breaker, generator breaker and turbine.
Generator Protections are broadly classified into three types.
CLASS – A : This covers all electrical protections for faults within the generating unit in which generator field breaker,
generator breaker and turbine should be tripped.
CLASS – B: This covers all mechanical protections of the turbine in which turbine will be tripped first and following
this generator will trip on reverse power / low forward power protections.
CLASS – C: This covers electrical protection for faults in the system in which generator will be unloaded by tripping
of generator breaker only. The unit will come to house load operation and the UAT will be in
service. Various protections of this class are:
i) 220 KV (HV side of Generator Transformer) busbar protection.
ii) Generator Transformer HV side breaker pole discrepancy.
iii) Generator negative phase sequence protection
iv) Generator Transformer over current / Earth fault protection
v) Reverse power protection without turbine trip.
[http://1.bp.blogspot.com/ygd5AXAkGL0/UcamR
0JEuI/AAAAAAAACaQ/3LR7hMkQ0jw/s1600/8.jpg]
1) Generator Differential Protection (87 G):
It is unit type protection, covering the stator winding for phase to phase faults due to breakdown of insulation between
stator phase windings. This relay is not sensitive for single line to earth faults as the earth fault current is limited due
to the high neutral earthing resistance.
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 2/9
12/5/2016 Generator Protection Explained
If CTs of identical ratios are used on neutral and line side of generator, an operating current setting of 20% it can be
adopted. It is instantaneous in operation and it trips the generator breaker (Class – A) to eliminate the system in –
feed to the fault along with field breaker and turbines.
For all machines of ratings 10 MVA and above, this protection shall be provided.
[http://3.bp.blogspot.com/pqkySaNmDmc/UcanTiU9znI/AAAAAAAACac/irQYlYMk_r0/s1600/9.jpeg]
2) Generator – Transformer Differential Protection (87T):
This is similar to Generator Differential Protection, which covers from the generator terminals upto the HV
breaker of generator transformer. . Sometimes this relay is not provided where Generator and Generator
Transformer Overall Differential relay (87O) is provided. 87G & 87T functions should have the features of through
fault restraint, magnetising inrush restraint.
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 3/9
12/5/2016 Generator Protection Explained
[http://2.bp.blogspot.com/
mZKdLE5ohAk/UcaoNkV48LI/AAAAAAAACao/dXe71Vc7cfQ/s1600/images.jpg]
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 4/9
12/5/2016 Generator Protection Explained
[http://2.bp.blogspot.com/
_4NqZER1hvU/Ucaq2SzKzGI/AAAAAAAACbA/zNYTW0ngdiA/s1600/2.JPG]
a) 95% stator earth fault protection (64G1)
It is an over voltage relay monitoring the voltage developed across the secondary of the neutral grounding
transformer in case of ground faults. It covers generator, LV winding of generator transformer and HV winding of
UAT. A pickup voltage setting of 5% is adopted with a time delay setting of about 1.0 Sec. For all machines of ratings
10 MVA and above this shall be provided.
drawing power from the system. This protection detects low forward power conditions of the generator and trips
generator breaker after a time delay, avoiding motoring of generator
The low forward power relay will be provided with ‘turbine trip’ interlock in thermal machines. A setting of 0.5%
of rated active power of generator with a time delay of 2.0 Sec. shall be adopted.
[http://3.bp.blogspot.com/
AxZTnbHqyYw/UcasaH5Y3pI/AAAAAAAACbU/bJdK1w3uaLQ/s1600/3.JPG]
A
[http://3.bp.blogspot.com/AxZTnbHqyYw/UcasaH5Y3pI/AAAAAAAACbU/bJdK1w3uaLQ/s1600/3.JPG]modern generating
unit is a complex system comprising the generator stator winding and associated transformer and unit
transformer, the rotor with its field winding and exciters, and the turbine and its associated condenser
and boiler complete with auxiliary fans and pumps. Faults of many kinds can occur within this system
for which diverse protection applied will be governed by economic considerations, taking into account
the value of the machine and its importance to the power system as a whole
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 6/9
12/5/2016 Generator Protection Explained
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 7/9
12/5/2016 Generator Protection Explained
Setting recommendations:
As this relay pickup for faults in the system, it has to be time graded with the transmission lines
emanating from that generating station. Normally IDMT relay is provided
Operating Current Setting = 20% In
Operating Time = 1.5 to 2.0 Sec.
(or)
Greater than (max.) Zone3 time of adjacent
Transmission Lines.
The following hazards require consideration.
a) Stator insulation faults
b) Overload
c) Overvoltage
d) Unbalanced loading
e) Rotor faults
f) Loss of excitation
g) Loss of synchronism
h) Failure of prime mover
i) Low vacuum
j) Lubrication oil failure
k) Loss of boiler firing
l) Overspeeding
m) Rotor distortion
n) Difference in expansion between rotating and stationary parts
o) Excessive vibration
Small capacity induction generators also are in service, mostly mini hydel and windmills of
capacity of 200KW to 2000KW, which depend on the system for excitation. Their protection
requirements are very simple such as overcurrent relays.
The protective relays generally used for the synchronous generators are listed at in the
following page.
Instead of independent relays for each function, microprocessor based numerical relay,
which can take care of the entire Generator protections the latest entry.
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 8/9
12/5/2016 Generator Protection Explained
[http://4.bp.blogspot.com/
Ea39QBivvyY/UcbkXuRSAsI/AAAAAAAACdg/PN1tx9iCPVQ/s1600/2.jpg]
0 Add a comment
http://powerplantpro.blogspot.in/2014/03/generatorprotectionexplained.html 9/9