Amber Service 24
Amber Service 24
Service Manual
Models: GWH24YE-S6DBA2A
GWH24YE-S6DBA1A
(Refrigerant:R32)
Table of Contents
Table of Contents
Service Manual
9. Maintenance.........................................................................................................................42
9.1 Error Code List............................................................................................................................42
9.2 Procedure of Troubleshooting.....................................................................................................49
9.3 Maintenance Method for Normal Malfunction..............................................................................63
10. Exploded View and Parts List...........................................................................65
10.1 Indoor Unit.................................................................................................................................65
10.2 Outdoor Unit..............................................................................................................................68
11. Removal Procedure....................................................................................................70
11.1 Removal Procedure of Indoor Unit............................................................................................70
11.2 Removal Procedure of Outdoor Unit.........................................................................................75
Appendix:.....................................................................................................................................81
Appendix 1: Reference Sheet of Celsius and Fahrenheit.................................................................81
Appendix 2: Configuration of Connection Pipe..................................................................................81
Appendix 3: Pipe expanding method................................................................................................82
Appendix 4: List of Resistance for Temperature Sensor...................................................................83
Table of Contents
Service Manual
GWH24YE-S6DBA2A/I
GWH24YE-S6DBA1A/I
Outdoor Unit:
GWH24YE-S6DBA2A/O
Models List:
Remote
No. Model Product Code Model Product Code Model Product Code
Controller
YAG1FB3
1 GWH24YE-S6DBA2A CB466000302 GWH24YE-S6DBA2A/I CB466N00302
(WiFi)
2 GWH24YE-S6DBA2A CB466000303 GWH24YE-S6DBA2A/I CB466N00303 GWH24YE-S6DBA2A/O CB466W00300
3 GWH24YE-S6DBA2A CB466000304 GWH24YE-S6DBA2A/I CB466N00304
YAG1FB
4 GWH24YE-S6DBA2A CB466000305 GWH24YE-S6DBA2A/I CB466N00305
5 GWH24YE-S6DBA1A CB437002800 GWH24YE-S6DBA1A/I CB437N02800
Technical Information 1
Service Manual
2. Specifications
2.1 Specification Sheet
GWH24YE-S6DBA2A
Model
GWH24YE-S6DBA1A
CB466000302/CB466000303/CB466000304/CB466000305
Product Code
CB437002800
Rated Voltage V~ 220-240
Power
Rated Frequency Hz 50/60
Supply
Phases 1
Power Supply Mode Outdoor
Cooling Capacity W 7034
Heating Capacity W 7034
Cooling Power Input W 1850
Heating Power Input W 1750
Cooling Power Current A 11
Heating Power Current A 10.76
Rated Input W 3700
Rated Current A /
3
Air Flow Volume(SH/H/M/L/SL) m /h 1250/1100/950/850/-
Dehumidifying Volume L/h 2
EER W/W 3.8
COP W/W 4
SEER W/W 6.5
HSPF W/W /
2
Application Area m 32-50
GWH24YE-S6DBA2A/I
Model of indoor unit
GWH24YE-S6DBA1A/I
CB466N00302/CB466N00303/CB466N00304/CB466N00305
Indoor Unit Product Code
CB437N02800
Fan Type Cross-flow
Diameter Length(DXL) mm Φ106X890
Fan Motor Cooling Speed r/min 1250/1100/1000/950/900/850/800/600
Fan Motor Heating Speed r/min 1400/1250/1100/1050/1000/900/850/-
Output of Fan Motor W 70
Fan Motor RLA A 0.38
Fan Motor Capacitor μF /
Input of Heater W /
Evaporator Form Aluminum Fin-copper Tube
Indoor Unit Pipe Diameter mm Φ7
Row-fin Gap mm 2-1.5
Coil Length (LXDXW) mm 845X25.4X381
Swing Motor Model MP35CJ
Output of Swing Motor W 2.5
Fuse A 3.15
Sound Pressure Level (SH/H/M/L/SL) dB (A) 50/46/43/41/39/37/35/27
Sound Power Level (SH/H/M/L/SL) dB (A) 64/60/57/55/53/51/49/41
Dimension (WXHXD) mm 1101X327X249
Dimension of Carton Box (LXWXH) mm 1164X402X339
Dimension of Package (LXWXH) mm 1167X405X354
Net Weight kg 16.5
Gross Weight kg 20
2 Technical Information
Service Manual
The above data is subject to change without notice; please refer to the nameplate of the unit.
Technical Information 3
Service Manual
14 14
12 12
10 10
Current(A)
Current(A)
8 8
6 6
4 4 Condition
Condition
Indoor:DB 20°C
Indoor:DB27°C WB19°C
2 2 Indoor air flow: Super High
Indoor air flow: Super High
Pipe length:7.5m
Pipe length:7.5m
0 0
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Cooling Heating
110
120
100
110
100
90
Capacity ratio(%)
90
Capacity ratio(%)
80 80
70
70 Condition
60 Indoor:DB 20°C
Condition Indoor air flow:Super High
Indoor:DB 27°C WB19°C 50 Pipe length:7.5m
60 Indoor air flow: Super High
Pipe length: 7.5m 40
-30 -4 5 17.6 32 44.6 50
50
21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 Outdoor temp(°C)
4 Technical Information
Service Manual
Heating:
Rated heating Pressure of gas pipe Inlet and outlet pipe
Compressor
condition(°C) connecting indoor and temperature of heat Fan speed of Fan speed of
Model frequency
(DB/WB) outdoor unit exchanger indoor unit outdoor unit
(Hz)
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 24K 2.8 to 3.0 70 to 35 2 to 4 Super High High 77
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 or 7.5m.
60
55 60
58
24K Heating
Noise dB(A)
50 56
Noise dB(A)
54
45 Cooling
52
40 50
48
35 46
20 30 40 50 60 70 80 90 100
30
Compressor frequency(Hz)
Super Middle Middle Super
High High High Middle Low Low Low
Technical Information 5
Service Manual
W D
Φ55 Φ55
H
38 38
190 140
218
117 685
685 198
194
Φ70
Φ55 Φ55Φ70
43
38 38 43
154 79
190 140
Unit:mm
Model W H D
24K 1101 327 249
Φ70 Φ70
43 43
154 79
6 Technical Information
Service Manual
920 370
790
1003 427
395
Unit:mm
610
Technical Information 7
Service Manual
5HIULJHUDQW6\VWHP'LDJUDP
INDOOR UNIT OUTDOOR UNIT
GAS SIDE
3-WAY VALVE
4-Way valve
Discharge
HEAT
EXCHANGE
(EVAPORATOR) Suction Accumlator
COMPRESSOR
D
HEAT
EXCHANGE
(CONDENSER)
LIQUID SIDE Intercooler
COOLING
HEATING
&RQQHFWLRQSLSHVSHFL¿FDWLRQ
Connection pipe specification:
/LTXLG PP *DV PP )RU. 7$
Liquid pipe:1/4" (6mm)
/LTXLG
Gas pipe: 5/8"PP *DV PP )RU. 7% .
(16mm)
7HFKQLFDO,QIRUPDWLRQ
8 Technical Information
Service Manual
5. Electrical Part
5.1 Wiring Diagram
●Instruction
Note: Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model.
● Indoor Unit
237,21$/
52207(03
78%(7(03
:$51,1*
:,5(' 237,21$/ 3OHDVHGRQ WWRXFKDQ\
5(&(,9(5$1' &21752//(5 :,),02'8/(
6(1625
6(1625
HOHFWURQLFFRPSRQHQWRU
',63/$<%2$5' WHUPLQDOZKHQWKHPDFKLQH
$3 $3 LVUXQQLQJVWRSSLQJRUKDV
$3 EHHQSRZHUHGRIIIRUOHVV
WKDQPLQXWHVWRSUHYHQW
HOHFWULFVKRFN
57 57 &211(&725 &211(&725
7(50,1$/
%/2&.
287'22581,7
Technical Information 9
Service Manual
● Outdoor Unit
GWH24YE-S6DBA2A/O
:$51,1*
7(036(1625
7(036(1625
7(036(1625
7(036(1625
:$<9$/9(
3OHDVHGRQ WWRXFKDQ\ &203
28778%(
28778%(
2875220
(;+$867
WHUPLQDOZKHQWKHYROWDJH 8 &203 3(
RIWHUPLQDO3 '& DQG
<(*1
1 '& DW$3LVKLJKHU 0$*1(7,& 9 :
WKDQ9WRSUHYHQWWKH 5,1*
ULVNRIHOHFWULFVKRFN 57 57 57 57 / / /
<9 :+ 3(
%8 <( 5'
<(*1 . . . ;
,1'22581,7
These wiring diagrams are subject to change without notice; please refer to the one supplied with the unit.
10 Technical Information
Service Manual
● Top view
1 2 16 3 17 4
No. Name
1 Neutral wire
2 Needle stand for indoor fan
3 Auto button
14 5 4 Up&down swing motor
5 left&right swing motor
6 Interface of temperature sensor
13 18 7
Terminal for display board
connection
8 Terminal of jumper cap
9 Communication wire
Connect earthing wire(only for
10
the mode with this function)
6 11 Fuse
12 Live wire interface
Interface of health function
13
neutral wire
10 Interface of health function live
7 14
wire
12 15 Detecting plate(WIFI )
Connect earthing wire(only for
16
the mode with this function)
11 Interface of gate control (only
17
for the mode with this function)
Wired controller (only for the
18
mode with this function)
9 8 15
● Bottom view
Technical Information 11
Service Manual
24K
● Top view
1 2 3 4 5 6 7 8 9
No. Name
1 Interface of compressor
10 Interface of temperature
2
sensor
Te r m i n a l o f c o m p r e s s o r
3
overload protection
Low-temperature cooling
11 4
sensor
5 Cooling A valve
6 Cooling B valve
12 7 Interface of outdoor motor
8 Interface of 2-way valve
9 Interface of 4-way valve
Terminal of chassis electric
10
13 heating
Communication wire with
11
indoor unit
Live wire interface of power
12
14 cord
Earthing wire interface of cold
13
plasma
Neutral wire interface of
14
power cord
● Bottom view
12 Technical Information
Service Manual
● This is a general use remote controller, it could be used for the air conditioners with multifunction; For some function, which the
model doesn't have, if press the corresponding button on the remote controller that the unit will keep the original running status.
Technical Information 13
Service Manual
ATUO
Low fan Medium-low fan Medium fan Medium-high fan High fan
Note:
● It’s Low fan speed under Dry mode.
● X-FAN function:Hold fan speed button for 2s in COOL or DRY mode, the icon “ ” is displayed and the indoor fan will continue
operation for a few minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is
defaulted. X-FAN is not available in AUTO, FAN or HEAT mode.
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
● Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for a few minutes. at
low speed. In this period, Hold fan speed button for 2s to stop indoor fan directly.
● Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
Press " + " or " - " button once increase or decrease set temperature 1°C(°F). Holding " + " or " - " button, set temperature on remote
controller will change quickly. On releasing button after setting is finished, temperature indicator on indoor unit will change accordingly.
When setting TIMER ON, TIMER OFF or CLOCK, press " + " or " - " button to adjust time. (Refer to CLOCK, TIMER ON, TIMER OFF
buttons) When setting TIMER ON, TIMER OFF or CLOCK, press " + " or " - " button to adjust time. (Refer to CLOCK, TIMER ON,
TIMER OFF buttons)
OFF
OFF
14 Technical Information
Service Manual
Note:
Outdoor temperature display is not available for some models. At that time, indoor unit receives " " signal, while it displays indoor
set temperature.
Press this button once, to turn on the I FEEL function, then the figure of "I FEEL"will be displayed, after every press of other function button,
every 200ms to sendI FEEL once, after this function started, the remote controller will send temperatureto the main un it in every 10 minutes.
When repress this button, this function will beturned off. When I FEEL function is turned on, the remote controller should be put within the
area where indoor unit can receive the signal sent by the remote controller.
WiFi button
Press " WiFi " button to turn on or turn off WiFi function. When WiFi function is turned on, the " WiFi " icon will be displayed on remote
controller; Under status of remote controller off, press "MODE" and " WiFi " buttons simultaneously for 1s, WiFi module will restore to
factory default setting.
● This function is only available for some models.
Press this button, the Quiet status is under the Auto Quiet mode (display" "and "Auto" signal) and Quiet mode (display " " singal)
and Quiet OFF (there is no signal of " " displayed), after powered on, the Quiet OFF is defaulted.Under the Quiet mode (Display " "
signal).
The Quiet function is only available for some models.
Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) andcancel the Sleep, circulate between these, after electrified,
Sleep Cancel is de-faulted.
Sleep 1 is Sleep mode 1, in Cool modes: sleep status after run for one hour, the main unit setting temperature will increase 1℃, 2 hours,
setting temperatureincreased 2℃, the unit will run at this setting temperature; In Heat mode:sleep status after run for one hour, the setting
temperature will decrease 1℃, 2 hours, setting temperature will decrease 2℃, then the unit will run at this settingtemperature.
Sleep 2 is sleep mode 2, that is air conditioner will run according to the presettinga group of sleep temperature curve.
In Cool mode:
(1) When setting the initial temperature 16℃-23℃, after turned on Sleep function,the temperature will be increased 1℃ in every hour,
after 3℃ the temperaturewill be maintained, after 7hours, the temperature will be decreased 1℃, afterthat the unit will keep on running
under this temperature;
(2) When setting the initial temperature 24℃-27℃, after turned on Sleep function,the temperature will be increased 1℃ in every hour,
after 2℃ the temperaturewill be maintained, after 7hours, the temperature will be decreased 1℃, afterthat the unit will keep on running
under this temperature;
(3) When setting the initial temperature 28℃-29℃, after turned on Sleep function,the temperature will be increased 1℃ in every hour,
after 1℃ the temperature will be maintained, after 7hours, the temperature will be decreased 1℃, afterthat the unit will keep on running
under this temperature;
Technical Information 15
Service Manual
(4) When setting the initial temperature 30℃, under this temperature setting, after 7hours, the temperature will be decreased 1℃, after
that the unit will keep onrunning under this temperature;
In Heat mode:
(1) Under the initial presetting temperature 16℃, it will run under this setting temperature all along.
(2) Under the initial presetting temperature17℃-20℃, after Sleep function started up, the temperature will decrease 1℃ in every hour,
after 1℃ decreased, thistemperature will be maintained.
(3) Under the initial presetting temperature 21℃-27℃, after Sleep function started up, the temperature will decrease 1℃ in every hour,
after 2℃ decreased, thistemperature will be maintained.
(4) Under the initial presetting temperature 28℃-30℃, after Sleep function started up, the temperature will decrease 1℃ in every hour,
after 3℃ decreased, thistemperature will be maintained.
Sleep 3 - the sleep curve setting under Sleep mode by DIY:
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote controller enters into user individuation sleep setting status, at this
time, the time of remotecontroller will display "1hour", the setting temperature "88" will display the corr-esponding temperature of last setting
sleep curve and blink (The first enteringwill display according to the initial curve setting value of original factory);
2) Adjust "+" and "-" button, could change the corresponding setting temperature,after adjusted, press "Trubo" button for confirmation;
(3) At this time, 1hour will be automatically increased at the timer postion on the remote controller, (that are "2hours" or "3hours" or "8hours"),
the place of setting temperature "88" will display the corresponding temperature of last settingsleep curve and blink;
(4) Repeat the above step (2)~(3) operation, until 8hours temperature setting finished,sleep curve setting finished, at this time, the remote
controller will resume theoriginal timer display; temperature display will resume to original setting temperature.
Sleep3 - the sleep curve setting under Sleep mode by DIY could be inquired:The user could accord to sleep curve setting method to inquire
the presetting sleepcurve, enter into user individuation sleep setting status, but do not change the temperature, press "Turbo" button directly
for confirmation.
Note: In the above presetting or enquiry procedure, if continuously within10s, thereis no button pressed, the sleep curve setting status will
be automatically quitand resume to display the original displaying. In the presetting or enquiry pr-ocedure, press "ON/OFF" button, "Mode"
button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
16 Technical Information
Service Manual
3
1. After powered on, press ON/OFF button, the unit will start 5
2
to run. (Note: When it is powered on, the guide louver of
main unit will close automatically.) 1
2. Press MODE button, select desired running mode. WiFi
battery
1. Press the back side of remote controller marked
reinstall
the cover of battery box along the arrow direction.
2. Replace two 7# (AAA 1.5V) dry batteries, and remove
make sure the position of "+" polar and "-" polar
are correct.
3. Reinstall the cover of battery box.
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
● Signal may be interfered easily in the room where there is fluorescent lamp
or wireless telephone; remote controller should be close to indoor unit during
operation.
● Replace new batteries of the same model when replacement is required.
● When you don’t use remote controller for a long time, please take out the
batteries.
● If the display on remote controller is fuzzy or there’s no display, please
replace batteries.
2. FAN button
Press this button, Auto, Low, Medium-low, Medium, Medium-high, High speed can be circularly selected. After powered on, Auto fan speed
is default. Under DRY mode, Low fan speed only can be set up.
ATUO
Note: It’s Low fan speed
under Dry mode.
Low fan Medium-low fan Medium fan Medium-high fan High fan
3. MODE button
Press this button, Auto, Cool, Dry, Fan, Heat mode can be selected circularly. Auto mode is default while power on. Under Auto mode, the
temperature will not be displayed;Under Heat mode, the initial value is 28°C( 82°F);Under other modes, the initial value is 25°C(77°F).
OFF
7. button
Press this button to set swing angle,which circularly changes as below:
OFF
This remote controller is universal. If it receives threes kinds of following status,the swing angle will remain origial.
If guide louver is stopped when it is swinging up and down,it will remain its present position.
8. CLOCK button
Press this button, the clock can be set up,signal blink and display.Within 5 seconds, the value can be adjusted by pressing + or - button,
if continuously press this button for 2 seconds above,in every 0.5 seconds, the value on ten place of Minute will be increased 1.During
After
powered on, 12:00 is defaulted to display and signal will be displayed. If there is signal be displayed that denotes the current time
value is Clock value, otherwise is Timer value.
9. TIMER ON/TIMER OFF button
● Timer On setting: Signal “ON”will blink and display,signal will conceal,the numerical section will become the timer on setting status.
During 5 seconds blink,by pressing + or - button to adjust the time value of numerical section,every press of that button,the value will be
increased or decreased 1 minute.Hold pressing + or - button,2 seconds later,it quickly change,the way of change is: During the initial 2.5
seconds,ten numbers change in the one place of minute,then the one place is constant,ten numbers change in the ten splace of minute at
2.5 seconds speed and carry. During 5s blink,press the Timer button,the timer setting succeeds.The Timer On has been set up,repress the
timer button,theTimer On will be canceled. Before setting theTimer,please adjust the Clock to the current actual time.
● One press this key to enter into TIMER OFF setup, in which case the TIMER OFF icon will blink. The method of setting is the sameas for
TIMER ON.
10. TEMP button
Press this button, you can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor unit’s display.
The setting on remote controller is selected circularly as below:
no display
When selecting " " with remote controller or no display, temperature indicator on in-door unit displays set temperature; When selecting " "
with remote controller, tem-perature indicator on indoor unit displays indoor ambient temperature; When selecting " " with remote controller,
temperature indicator on indoor unit displays outdoor ambient temperature. 3s later it will return to the setting temprature or it depends on the
other received signal within 3s.Attention: When displaying the outdoor ambient, the displaying range is 0-60℃ When it goes beyond the range,
it keeps the threshold data (the smallest—0℃and the largest 60℃)
Warm tips: When operating buttons on the cover please make sure the cover is closed completely.
Note:Outdoor temperature display is not available for some models. At that time, indoor unit receives " " signal, while it displays indoor
set temperature.
11. / button(This function is only available for some models)
scavenging function;LCD displays“ ”.Press the button for the second time to start healthy and scavenging functions simultaneously;LCD
displays“ ”and “ ” .Press this button for the third time to quit healthy and scavenging functions simultaneously.Press the button for the
fourth time to start healthy function; LCD display“ ” .Press this button again to repeat the operation above.
NOTE: This function is applicable to partial of models.
12. I FEEL button
button, every 200ms to send I FEEL once, after this function started,the remote control will send temperature to the main un it in every 10
minutes.When repress this button, this function will be turned off.
When I FEEL function is turned on, the remote controller should be put within the area where indoor unit can receive the signal sent by
the remote controller.
13. LIGHT button
Press this button at unit On or Off status,Light On and Light Off can be set up.After powered on, Light On is defaulted.
14. X-FAN button
Pressing X-FAN button in COOL or DRY mode,the icon is displayed and the indoor fan will continue operation for 2 minutes in order
to dry the indoor unit even though you have turned off the unit.After energization, X-FAN OFF is defaulted.X-FAN is not available in
AUTO,FAN or HEAT mode.
15. QUIET button
Press this button, the Quiet status is under the Auto Quiet mode (display" "and "Auto" signal) and Quiet mode (display " " singal)
and Quiet OFF (there is no signal of " " displayed), after powered on, the Quiet OFF is defaulted.Under the Quiet mode (Display " "
signal).The Quiet function is only available for some models.
16. SLEEP button
●Press this button, can select Sleep 1 ( ), Sleep 2 ( ),Sleep 3 ( ) and cancel the Sleep, circulate between these, after
●Sleep 1 is Sleep mode 1, in Cool, Dehumidify modes: sleep status after run for one hour, the main unit setting temperature will increase 1°C,
2 hours,setting temperature increased 2°C, the unit will run at this setting temperature; In Heat mode: sleep status after run for one hour,
the setting temperature will decrease 1°C, 2 hours, setting temperature will decrease 2°C, then the unit will run at this setting temperature.
●Sleep 2 is sleep mode 2, that is air conditioner will run according to the presetting a group of sleep temperature curve.
In Cool mode:
(1) When setting the initial temperature 16~23°C, after turned on Sleep function, the temperature will be increased 1°C in every hour,after
3°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(2) When setting the initial temperature 24~27°C, after turned on Sleep function, the temperature will be increased 1°C in every hour,after
2°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(3) When setting the initial temperature 28~29°C, after turned on Sleep function, the temperature will be increased 1°C in every hour, after
1°C the temperature will be maintained, after 7hours,the temperature will be decreased 1°C, after that the unit will keep on running under
this temperature;
(4) When setting the initial temperature 30°C, under this temperature setting, after 7hours, the temperature will be decreased 1°C, after
that the unit will keep on running under this temperature;
In Heat mode:
(1) Under the initial presetting temperature 16°C, it will run under this setting temperature all along.
(2) Under the initial presetting temperature17~20°C, after Sleep function started up, the temperature will decrease 1°C in every hour, after
1°C decreased, this temperature will be maintained.
(3) Under the initial presetting temperature 21~27°C, after Sleep function started up, the temperature will decrease 1°C in every hour,after
2°C decreased, this temperature will be maintained.
(4) Under the initial presetting temperature 28~30°C, after Sleep function started up, the temperature will decrease 1°C in every hour, after
3°C decreased, this temperature will be maintained
●Sleep 3- the sleep curve setting under Sleep mode by DIY:
(1) Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation sleep setting status, at this time,
the time of remote control will display "1hour ", the setting temperature "88" will display the corresponding temperature of last setting sleep
(3) At this time, 1hour will be automatically increased at the timer postion on the remote control, (that are "2hours" or "3hours" or "8hours "),
the place of setting temperature "88" will display the corresponding temperature of last setting sleep curve and blink;
control will resume the original timer display;temperature display will resume to original setting temperature.
●Sleep3- the sleep curve setting under Sleep mode by DIY could be inquired:
The user could accord to sleep curve setting method to inquire the presetting sleep curve, enter into user individuation sleep setting status,
Note: In the above presetting or enquiry procedure, if continuously within10s, there is no button pressed, the sleep curve setting status will
be automatically quit and resume to display the original displaying. In the presetting or enquiry procedure, press "ON/OFF" button, "Mode"
button, "Timer" button or "Sleep" button, the sleep curve setting or enquiry status will quit similarly.
17. About X-FAN function
This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould.
(1)Having set X-FAN function on: After turning off the unit by pressing ON/OFF button indoor fan will continue running for about 2 min. at
low speed. In this period, press X-FAN button to stop indoor fan directly.
(2)Having set X-FAN function off: After turning off the unit by pressing ON/OFF button, the complete unit will be off directly.
18. About AUTO RUN
When AUTO RUN mode is selected, the setting temperature will not be displayed on the LCD, the unit will be in accordance with the room
temp. automatically to select the suitable running method and to make ambient comfortable.
19. About turbo function
If start this function, the unit will run at super-high fan speed to cool or heat quickly so that the ambient temp. approachs the preset temp.
as soon as possible.
20. About lock
Press + and - buttons simultaneously to lock or unlock the keyboard. If the remote controlleris locked, the icon will be displayed on it, in
.
21. About swing up and down
(1)Press swing up and down button continuously more than 2s,the main unit will swing back and forth from up to down, and then loosen
the button, the unit will stop swinging and present position of guide louver will be kept immediately.
(2)Under swing up and down mode, when the status is switched from off to , if press this button again 2s later, status will switch to off
status directly; if press this button again within 2s,the change of swing status will also depend on the circulation sequence stated above.
22. About swing left and right(This function is only available for some models)
(1)Press swing left and right button continuously more than 2s,the main unit will swing back and forth from left to right, and then loosen the
button, the unit will stop swinging and present position of guide louver will be kept immediately.
(2)2. Under swing left and right mode, when the status is switched from off to , if press this button again 2s later, status will switch to
off status directly; if press this button again within 2s,the change of swing status will also depend on the circulation sequence stated above.
23. About switch between Fahrenheit and Centigrade
Under status of unit off, press MODE and - buttons simultaneously to switch °C and °F.
24. Combination of " TEMP" and "CLOCK" buttons : About Energy-saving Function
Press “TEMP” and “CLOCK” simultaneously in COOL mode to start energy-saving function.Nixie tube on the remote controller displays “SE”.
Repeat the operation to quit the function.
25. Combination of " TEMP" and "CLOCK" buttons : About 8°C Heating Function(This function is only available for some models)
Press “TEMP” and “CLOCK” simultaneously in HEAT mode to start 8°C Heating Function.Nixie tube on the remote controller displays"
"and a selected temperature of “8°C” (46°F if Fahrenheit is adopted). Repeat the operation to quit the function.
26. About Quiet function
When quiet function is selected:
1. Under cooling mode: indoor fan operates at notch 4 speed. 10 minutes later or whenindoor ambient temperature≤28℃, indoor fan will
operate at notch 2 speed or quietmode according to the comparison between indoor ambinet temperature and set tem-perature.
2. Under heating mode: indoor fan operates at notch 3 speed or quiet mode accordingto the comparison between indoor ambient
temperature and set temperature.
3. Under dry, fan mode: indoor fan operates at quiet mode.
4. Under auto mode: the indoor fan operates at the auto quiet mode according to actual cooling, heating or fan mode.
Operation Guide
4
1. General operation
(1)After powered on, press ON/OFF button, the unit will start to run. (Note: When it is powered on, the 3
5
guide louver of main unit will close automatically.)
2
(2)Press MODE button, select desired running mode.
(3)Pressing + or - button, to set the desired temperature (It is unnecessary to set the temp. at AUTO 1
mode.)
(4)Pressing FAN button, set fan speed, can select AUTO FAN,LOW, MEDIUM-LOW, MEDIUM, MEDIUM-
HIGH and HIGH.
(5)Pressing and button, to select the swing.
2. Optional operation
4
(1)Press SLEEP button, to set sleep.
(2)Press TIMER ON and TIMER OFF button, can set the scheduled timer on or timer off.
2
(3)Press LIGHT button, to control the on and off of the displaying part of the unit (This function may be not
available for some units).
3 1
(4)Press TURBO button, can realize the ON and OFF of TURBO function.
Internet
Gree Cloud
Gree
intelligent Home Wi-Fi Cellular/
home Other Wi-FI
appliances
Home wireless router
Home Wi-Fi
GREE+ APP
Operating Systems
Scan the QR code or search "GREE+" in the application market to download and install it. When "GREE+" App is installed, register the
account and add the device to achieve long-distance control and LAN control of Gree smart home appliances.
For more information, please refer to "Help" in App.
Internet
Cloud
Operating Systems
Scan the QR code or search "Ewpe Smart" in the application market to download and install it. When "Ewpe Smart" App is installed,
register the account and add the device to achieve long-distance control and LAN control of smart home appliances.
For more information, please refer to "Help" in App.
Tpreset –2 ˚C
Stop cooling
≥ 6 min. ≥ 3 min. ≥ 6 min.
Outdoor fan
Compressor 3 min
30S
Outdoor fan
Indoor fan Preset speed
Run Stop
(2) Dehumidifying Mode
① Working conditions and process of dehumidifying
If Tamb.>Tpreset, the unit will enter cooling and dehumidifying mode, in which case the compressor and the outdoor fan will operate and the indoor
fan will run at low speed.
If Tpreset-2°C(3.6°F)≤Tamb.≤Tpreset, the compressor remains at its original operation state.
If Tamb.< Tpreset-2°C(3.6°F), the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will operate at low speed.
② Protection function
Protection is the same as that under the cooling mode.
(3) Heating Mode
① The condition and process of heating
If Tamb.≤Tpreset+2°C(3.6°F), heating mode will act, the compressor, outdoor fan and reversal valve will run, the indoor fan will delay 3min to stop at
the latest
If Tpreset +2°C(3.6°F)<Tamb.<Tpreset +5°C(9°F),the unit will keep running in the original mode.
If Tamb.≥Tpreset+5°C(9°F), the compressor will stop, the outdoor fan will delay 30s to stop and indoor fan will blow 60s at low speed, the fan speed
cannot be shifted within blow residual heat.
◆ In this mode, the temperature setting range is 16 ~30°C(68~86°F).
◆ The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient temperature.
◆ When the unit is turned off in heating mode, or switched to other mode from heating mode, the four-way valve will be powered off after the
compressor stops.
Stop heating
Tpreset+5
Original operating status
Tpreset+2
Tamb.
6min. 3min. 6min. Start heating
Outdoor fan
60s 60s
Indoor fan <2 min. preset <2 min. preset
wind wind
Reversing valve
Run Stop
c.For heating and cooling unit, when 22°C(71.6°F)<Tindoor ambient<26°C(78.8°F) (for cooling only unit, 22°C(71.6°F)<Tindoor
ambient<26°C)(78.8°F), it will keep the original running mode. If the unit is energized for the first time, it will run in fan mode.
② Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor willremain
unchanged for at least 6 minutes.
(7)Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
① Overload protection
Ttube: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat exchanger under
heating mode.
1) Cooling overload
a.If T tube≤52°C(125.6°F), the unit will return to its original operation state.
b.If T tube≥55°C(131°F), frequency rise is not allowed.
c.If T tube≥58°C(136.4°F), the compressor will run at reduced frequency.
d.If T tube≥62°C(143.6°F), the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a.If T tube≤50°C(122°F), the unit will return to its original operation state.
b.If T tube≥53°C(127.4°F), frequency rise is not allowed.
c.If T tube≥56°C(132.8°F), the compressor will run at reduced frequency.
d.If T tube≥60°C(140°F), the compressor will stop and the indoor fan will blow residue heat and then stop.
② Exhaust temperature protection of compressor
If exhaust temperature≥98°C(208.4°F), frequency is not allowed to rise.
If exhaust temperature≥103°C(217.4°F), the compressor will run at reduced frequency.
If exhaust temperature≥110°C(230°F),, the compressor will stop.
If exhaust temperature≤90°C(194°F), and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its operation.
③ Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system will stop.
④ Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the compressor will
resume its operation. If module protection occurs six times in succession, the compressor will not be started again.
⑤ Overload protection
If temperature sensed by the overload sensor is over 115 , the compressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If temperature is below 95 , the overload protection will be relieved.
⑥ DC bus voltage protection
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time lag of 30 seconds.
When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least 3 minutes, the compressor will
resume its operation.
⑦ Faults of temperature sensors
Designation of sensors Faults
Indoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Indoor tube temperature The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Outdoor ambient temperature The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds, and no
Outdoor tube temperature
detection is performed within 10 minutes after defrost begins.
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or
Exhaust
short-circuited for successive 30 seconds.
After the compressor has operated for 3 minutes, the sensor is detected to be open-circuited or
Overload
short-circuited for successive 30 seconds.
3. Other Controls
(1) ON/OFF
Press the remote button ON/OFF: the on-off state will be changed once each time you press the button.
(2) Mode Selection:
Press the remote button MODE, then select and show in the following ways: AUTO, COOL, DRY, FAN, HEAT, AUTO.
(3) Temperature Setting Option Button
Each time you press the remote button TEMP+ or TEMP-, the setting temperature will be up or down by 1°C(1.8°F). Regulating Range:
16(60.8°F)~30°C(86°F), the button is useless under the AUTO mode.
(4) Time Switch
You should start and stop the machine according to the setting time by remote control.
(5) SLEEP State Control
1. In cooling mode:
1.1 When the initial set temperature is16-23°C(60.8~73.4°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set;the
temperature will not change after rising 3°C(5.4°F) ;after running for 7hours,the temperature will decrease1°C(1.8°F) and it will not change
after that.
1.2 When the initial set temperature is 24-27°C(75.2~80.6°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set; the
temperature will not change after rising 2°C(3.6°F) ;after running for 7 hours, the temperature will decrease 1°C(1.8°F) and it will not change
after that.
1.3 When the initial set temperature is 28-29°C(82.4~84.2°F),the temperature will rise 1°C(1.8°F) by every hour after sleep function is set; the
temperature will not change after rising 1°C(1.8°F) ; after running for 7 hours, the temperature will decrease 1°C(1.8°F) and it will not change
after that.
1.4 When the initial set temperature is 30°C(86°F) , the unit will keep on running at this temperature; after running for 7 hours, the temperature
will decrease 1°C(1.8°F) and it will not change after that.
Relationship between set temperature and running time:
2. In heating mode:
2.1 When the initial set temperature is 16°C(60.8°F), the unit will keep on running at this temperature;
2.2 When the initial set temperature is 17-20°C(62.6~68°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is set;
the temperature will not change after decreasing 1°C(1.8°F);
2.3 When the initial set temperature is 21-27°C(69.8~80.6°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is
set; the temperature will not change after decreasing 2°C(3.6°F);
2.4 When the initial set temperature is 28-30°C(82.4~86°F), the temperature will decrease 1°C(1.8°F) by every hour after sleep function is set;
the temperature will not change after decreasing 3°C(5.4°F);
Relationship between set temperature and running time:
Initial Temp. Running time(T)
0(start) 1 2 3 4 5 6 7 8
16 16 16 16 16 16 16 16 16
17 16 16 16 16 16 16 16 16
18 17 17 17 17 17 17 17 17
19 18 18 18 18 18 18 18 18
20 19 19 19 19 19 19 19 19
21 20 19 19 19 19 19 19 19
22 21 20 20 20 20 20 20 20
23 22 21 21 21 21 21 21 21
24 23 22 22 22 22 22 22 22
25 24 23 23 23 23 23 23 23
26 25 24 24 24 24 24 24 24
27 26 25 25 25 25 25 25 25
28 27 26 25 25 25 25 25 25
29 28 27 26 26 26 26 26 26
30 29 28 27 27 27 27 27 27
(6) Indoor Fan Control
Indoor fan could be set at ultra-high, high, medium, low speed by wireless remote controller and operated as that speed.
Auto fan speed could be set as well, indoor fan will operate under auto fan speed as following:
1. Under heating mode: auto speed under heating or auto heating mode:
a. When Tamb.≤Tpreset+1°C(1.8°F), indoor fan will operate at high speed;
b. When Tpreset+1°C(1.8°F)<Tamb.<Tpreset+3°C(5.4°F), indoor fan will operate at medium speed;
c. When Tamb.≥Tpreset+3°C(5.4°F), indoor fan will operate at low speed;
There should be at least 180s operation time during switchover of each speed.
2. Under cooling mode: auto speed under cooling or auto cooling mode:
a. When Tamb.≥Tpreset+2°C(3.6°F), indoor fan will operate at high speed;
b. When Tpreset<Tamb.<Tpreset+2°C(3.6°F), indoor fan will operate at medium speed;
c. When Tamb.≤Tpreset, indoor fan will operate at low speed
There should be at least 210s operation time during switchover of each speed.
(7) Buzzer Control
The buzzer will send a “Di” sound when the air conditioner is powered up or received the information sent by the remote control or there is
a button input, the single tube cooler doesn’t receive the remote control ON signal under the mode of heating mode.
(8) Auto button
If the controller is on, it will stop by pressing the button, and if the controller is off, it will be automatic running state by pressing the button,
swing on and light on, and the main unit will run based on the remote control if there is remote control order.
(9) Up-and-Down Swinging Control
Heating angle O(0°)
When power on, the up-and-down motor will firstly move the air
Cooling angle Heating angle O(0°) Coolin
O(0°)
deflector to o counter-clockwise, close the air outlet.
After starting the machine, if you don’t set the swinging functi on, L1
heating mode and auto-heating mode, the up-and-down air deflector L A1 L
will move to D clockwise; under other modes, the up-and-down A air B1 A
deflector will move to L1. If you set the swinging function whenB you start C1 B
the machine, then the wind blade will swing between L and D.CThe air D1 C
deflector has 7 swinging states: Location L, Location A, Location D B, Location C, D
Location D, Location L to Location D, stop at any location between L-D (the included angle between L~D is the same).
The air deflector will be closed at 0 Location, and the swinging is effectual only on condition that setting the swinging order and the inner
fan is running. The indoor fan and compressor may get the power when air deflector is on the default location.
(10) Display
① Operation pattern and mode pattern display
All the display patterns will display for a time when the power on, the operation indication pattern will display in red under standby status.
When the machine is start by remote control, the indication pattern will light and display the current operation mode (the mode light in-
cludes: Cooling, heating and dehumidify). If you close the light key, all the display patterns will close.
② Double-8 display
According to the different setting of remote control, the nixie light may display the current temperature (the temperature scope is from 16°C
(60.8°F)to 30°C(86°F)) and indoor ambient temperature. The set temperature displayed in auto cooling and fan mode is 25°C(77°F) and
the set temperature displayed in auto heating mode is 20°C(68°F). Under heating mode, nixie tube displays H1 or heating indicator is off 0.5s
and blinks 10s in defrosting.(If you set the fahrenheit temperature display, the nixie light will display according to fahrenheit temperature)(11)
Protection function and failure display
E2: Freeze-proofing protection E4: Exhausting protecti on E5: Overcurrent protection E6: Communication failure
F1: Indoor ambient sensor start and short circuit (continuously measured failure in 5s)
F2: Indoor evaporator sensor start and short circuit (continuously measured failure in 5s)
F3: Outdoor ambient sensor start and short circuit (continuously measured failure in 30s)
F4: Outdoor condenser sensor start and short circuit (continuously measured failure in 30s, and don’t measure within 10 minutes after
defrosted)
F5: Outdoor exhausting sensor start and short circuit (continuously measured failure in 30s after the compressor operated 3 minutes)
H3: Overload protection of compressor H5: Module protection PH: High-voltage protection PL: Low-voltage protection
P1: Nominal cooling and heating test P2: Maximum cooling and heating test
P3: Medium cooling and heating test P0: Minimum cooling and heating test
(12) Drying Function
You may start or stop the drying function under the modes of cooling and dehumidify at the starting status (The modes of automatism,
heating and air supply do not have drying function). When you start the drying function, after stop the machine by pressing the switch
button, you should keep running the inner fans for 2 minutes under low air damper (The swing will operate as the D1 status within 2
minutes, and other load is stopped), then stop the entire machine; When you stop the drying function, press the switch button will stop the
machine directly.When you start the drying function, operating the drying button will stop the inner fans and close the guide louver.
(13) Memory Function
When interrupting the power supply memory content: mode, swing function, light, set temperature and wind speed.
After interrupted the power supply, the machine will start when recovering the power according to the memory content automatically.
Warnings
cient fixing bolt must be installed; make sure the installation
support is firm.
4. Ware safety belt if the height of working is above 2m.
5. Use equipped components or appointed components dur-
ing installation.
Electrical Safety Precautions: 6. Make sure no foreign objects are left in the unit after fin-
ishing installation.
1. Cut off the power supply of air conditioner before
checking and maintenance. Refrigerant Safety Precautions:
2. The air condition must apply specialized circuit and
prohibit share the same circuit with other appliances. 1. Avoid contact between refrigerant and fire as it generates
3. The air conditioner should be installed in suitable poisonous gas; Prohibit prolong the connection pipe by
location and ensure the power plug is touchable. welding.
4. Make sure each wiring terminal is connected firmly 2. Apply specified refrigerant only. Never have it mixed with
during installation and maintenance. any other refrigerant. Never have air remain in the refrigerant
5. Have the unit adequately grounded. The grounding line as it may lead to rupture or other hazards.
wire cant be used for other purposes. 3. Make sure no refrigerant gas is leaking out when
6. Must apply protective accessories such as protective installation is completed.
boards, cable-cross loop and wire clip. 4. If there is refrigerant leakage, please take sufficient
7. The live wire, neutral wire and grounding wire of measure to minimize the density of refrigerant.
power supply must be corresponding to the live wire, 5. Never touch the refrigerant piping or compressor without
neutral wire and grounding wire of the air conditioner. wearing glove to avoid scald or frostbite.
8. The power cord and power connection wires cant be
pressed by hard objects. Improper installation may lead to fire hazard, explosion,
9. If power cord or connection wire is broken, it must be electric shock or injury.
replaced by a qualified person.
Warnings
1. When installing or relocating the unit, be sure to keep the refrigerant circuit free from air or substances other than the
specified refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause system pressure rise or compressor rupture, resulting in
injury.
2.When installing or moving this unit, do not charge the refrigerant which is not comply with that on the nameplate or
unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical malfunction or even series safety accident.
3.When refrigerant needs to be recovered during relocating or repairing the unit, be sure that the unit is running in cooling
mode.Then, fully close the valve at high pressure side (liquid valve).About 30-40 seconds later, fully close the valve at low
pressure side (gas valve), immediately stop the unit and disconnect power. Please note that the time for refrigerant recovery
should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause pressure rise or compressor rupture, resulting in injury.
4.During refrigerant recovery, make sure that liquid valve and gas valve are fully closed and power is disconnected before
detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
5.When installing the unit, make sure that connection pipe is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not yet connected, air will be sucked in and cause pressure
rise or compressor rupture, resulting in injury.
6.Prohibit installing the unit at the place where there may be leaked corrosive gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
7.Do not use extension cords for electrical connections. If the electric wire is not long enough, please contact a local service
center authorized and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
8.Use the specified types of wires for electrical connections between the indoor and outdoor units. Firmly clamp the wires so
that their terminals receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections and insecure wire terminals may cause electric shock or fire.
WARNING:
●Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacture.
Should repair be necessary,contact your nearest authorized Service Centre. Any repairs carried out by unqualified
personnel may be dangerous. The appliance shall be stored in a room without continuously operating ignition sources. (for
example:open flames , an operating gas appliance or an operating electric heater.)
●Do not pierce or burn.
●Appliance shall be installed, operated and stored in a room with a floor area larger than 4m (or 6m ).
●Appliance filled with flammable gas R32. For repairs, strictly follow manufacturers instructions only.Be aware that refrigrants
not contain odour.
●Read specialists manual.
Installation notes
●The air conditioner is not allowed to use in a room that has running fire (such as fire source,working coal gas ware,
operating heater).
●It is not allowed to drill hole or burn the connection pipe.
●The air conditioner must be installed in a room that is larger than the minimum room area.
The minimum room area is shown on the nameplate or following table a.
●Leak test is a must after installation.
Table a - Minimum room area(m2)
Charge amount (kg) ≤1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5
floor location / 14.5 16.8 19.3 22 24.8 27.8 31 34.3 37.8 41.5 45.4 49.4 53.6
Minimum
room window mounted / 5.2 6.1 7 7.9 8.9 10 11.2 12.4 13.6 15 16.3 17.8 19.3
area( m 2 )
wall mounted / 1.6 1.9 2.1 2.4 2.8 3.1 3.4 3.8 4.2 4.6 5 5.5 6
ceiling mounted / 1.1 1.3 1.4 1.6 1.8 2.1 2.3 2.6 2.8 3.1 3.4 3.7 4
Maintenance notes
●Check whether the maintenance area or the room area meet the requirement of the nameplate.
— Its only allowed to be operated in the rooms that meet the requirement of the nameplate.
●Check whether the maintenance area is well-ventilated.
— The continuous ventilation status should be kept during the operation process.
●Check whether there is fire source or potential fire source in the maintenance area.
— The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.
●Check whether the appliance mark is in good condition.
— Replace the vague or damaged warning mark.
Welding
●If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below:
a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding
●Make sure that there isnt any naked flame near the outlet of the vacuum pump and its well-ventilated.
●The refrigerant should be recycled into the specialized storage tank.
10. Pipe pliers, pipe cutter 11. Pipe expander, pipe bender 12. Soldering appliance, refrigerant container
8. Installation
8.1 Installation Dimension Diagram
At least 5 7/8
At least 98 7/16
A t stru
ob
he
ot
et
ac
Sp
n
ctio
s tru
ob 16
he 13/
t ot 11
c e st
Sp a lea
ac Sp At
et
ot
At he
lea wa
st 1 ll
11
3/1
6
o
cti Drainage pipe
s tru /8
ob 85
he t7
tot as Sp
ac
ce le
pa At At
et
ot
S lea he
st 1 ob
91 str
1/1 uc
6 tio
n
Installation procedures
Start installation
Finish installation
Note: this flow is only for reference; please find the more detailed installation steps in this section.
Wall Wall
Mark in the middle of it Level meter
Space Space
to the to the
wall wall Insulating pipe Fig.7
above above
150mm 150mm
Refer to the following table for wrench moment of force:
Left Right
Φ70mm Φ70mm
Rear piping hole Rear piping hole Hex nut diameter(mm) Tightening torque(N.m)
Φ6 15~20
Fig.1 Φ9.52 30~40
(2) Open a piping hole with the diameter of Φ70mm on the Φ12 45~55
selected outlet pipe position.In order to drain smoothly, slant Φ16 60~65
the piping hole on the wall slightly downward to the outdoor Φ19 70~75
side with the gradient of 5-10°.(As show in Fig.2)
6. install drain hose
Indoor Outdoor
(1) Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
Φ70mm
5-10°
Fig.8
Fig.2
Note: Drain hose
(1) Pay attention to dust prevention and take relevant safety Outlet pipe
measures when opening the hole.
(2) The plastic expansion particles are not provided and should
Outlet Drain hose Tape
be bought locally. pipe
Fig.9
4. Outlet Pipe
(1) The pipe can be led out in the direction of right, rear right,
Note:
left or rear left.(As show in Fig.3)
(2) When selecting leading out the pipe from left or right, please (1) Add insulating pipe in the indoor drain hose in order to
cut off the corresponding hole on the bottom case.(As show in prevent condensation.
Fig.4) (2) The plastic expansion particles are not provided.
(As show in Fig.10)
Drain hose
Left Rear left
Fig.3 Rear right
Right
Left Right Insulating pipe Fig.10
Cut off
Fig.4
the hole
(2) Make the power connection wire go through the cable-cross Indoor and
hole at the back of indoor unit and then pull it out from the front Indoor unit
outdoor power cord
Gas
side.(As show in Fig.12) pipe
Power connection
wire
Connection pipe Drain hose
Band
Fig.12
(3) Remove the wire clip; connect the power connection wire
and signal control wire to the wiring terminal according to the
Fig.15
color; tighten the screw and then fix them with wire clip.(As
Indoor power cord
show in Fig.13)
Note:
(1) The power cord and control wire can't be crossed or
N(1) 2 3
winding.
blue black brown yellow-
green (2) The drain hose should be bound at the bottom.
Note:
Indoor Outdoor
(1) All wires of indoor unit and outdoor unit should be
Wall pipe Fig.17
connected by a professional. Sealing gum
(2) If the length of power connection wire is insufficient, please Upper hook
contact the supplier for a new one. Avoid extending the wire by
yourself.
(3) For the air conditioner with plug, the plug should be
reachable after finishing installation.
(4) For the air conditioner without plug, an air switch must be Fig.16 Lower hook of
installed in the line. The air switch should be all-pole parting wall-mounting frame
and the contact parting distance should be more than 3mm. Note:
Do not bend the drain hose too excessively in order to prevent
blocking.
8.6 Installation of Outdoor Unit (3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
1. Fix the Support of Outdoor Unit(Select it according to
Refer to the following table for wrench moment of force:
the actual installation situation)
(1) Select installation location according to the house structure.
Hex nut diameter(mm) Tightening torque(N.m)
(2) Fix the support of outdoor unit on the selected location with
Φ6 15~20
expansion screws.
Φ9.52 30~40
Note: Φ12 45~55
(1) Take sufficient protective measures when installing the Φ16 60~65
outdoor unit. Φ19 70~75
(2) Make sure the support can withstand at least four times the
unit weight. 5. Connect Outdoor Electric Wire
(3) The outdoor unit should be installed at least 3cm above the (1) Remove the wire clip; connect the power connection wire
floor in order to install drain joint.(As show in Fig.18) and signal control wire (only for cooling and heating unit) to the
(4) For the unit with cooling capacity of 2300W~5000W, 6 wiring terminal according to the color; fix them with screws.(As
expansion screws are needed; for the unit with cooling capacity show in Fig.23)
of 6000W~8000W, 8 expansion screws are needed; for the
unit with cooling capacity of 10000W~16000W, 10 expansion Handle N(1) 2 3 L N
screws are needed. Fig.23
yellow- blue black brown brown blue yellow-
green (black) green
L N
(2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe.(As show in Fig.22) Fig.25
U-shaped curve
Fig.24
Liquid pipe Pipe joint
Drain hose
Liquid gas pipe
valve
Union nut
gas valve
Fig.22
9. Maintenance
9.1 Error Code List
Display Method of Outdoor
Display Method of Indoor Unit
Unit
Indicator has 3 kinds of
Indicator Display (during
Malfunction display status and during
NO. Dual-8 blinking, ON 0.5s and OFF blinking, ON 0.5s and OFF A/C status Possible Causes
Name
Code 0.5s) 0.5s
Display
Operation Cool Heating Yellow Red Green
Indicator Indicator Indicator Indicator Indicator Indicator
Compressor
Min Showing during min. cooling or
23 P0
frequence in min. heating test
test state
Compresso r
rated Showing during nominal cooling or
24 P1
frequenc e in nominal heating test
test state
Compressor
maximum Showing during max. cooling or
25 P2
frequence in max. heating test
test state
Compressor
intermediate Showing during middle cooling or
26 P3
frequence in middle heating test
test state
Static
32 dedusting H2
protection
Frequency OFF 1S
48 limiting and blink
(power) 13 times
OFF 1S
49 Compressor and blink
running once
The
temperature OFF 1S
50 for turning and blink
on the unit is 8 times
reached
Frequency
limiting OFF 1S
51 and blink
(module
11 times
temperature)
Malfunction
55 of detecting JF
plate(WIFI )
No
No Is malfunction
eliminated
No
No Is malfunction Yes
eliminated
Replace it with a
temperature sensor with
the same model
Yes
No Is malfunction
eliminated
Yes
End
Start
Turn unit on
Yes to check whether the
No malfunction is
eliminated.
Turn unit on
No No to check whether the Yes
malfunction is
eliminated.
Connect power and restart the unit. It's the malfunction of main board.
Test whether the voltage between terminal 1 and terminal 2 No Replace a new main board that is
of motor interface is within 280~310VDC. of the same model.
Yes
Yes
Then check whether the voltage It's the malfunction of main board.
between terminal 2 and terminal 3 No Replace a new main board that is
of the same model.
of the motor interface is 15VDC.
Yes
Then check whether there is voltage It's the malfunction of main board.
between terminal 2 and terminal 4 No Replace a new main board that is
of the motor interface. of the same model.
Yes
Start
No Appearance of the
Is there jumper cap on the mainboard?
jumper cap
No Is malfunction
eliminated
No Is malfunction Yes
eliminated
Is malfunction Yes
eliminated
Yes
No
End
Start
No No
Is the supply voltage too low Yes Adjust the supply voltage to maintain it Is malfunction Yes
with overload? within normal range eliminated
No No
Is the indoor / outdoor Yes Clean the indoor and outdoor heat Is malfunction Yes
heat exchanger dirty,or are the air inlet exchangers and remove the blockage eliminated
and outlet blocked? of air inlet and outlet
No
No
The fan is abnormal? Fan Yes Check the motor and reinstall the Is malfunction Yes
speed is too low or fan doesn’t rotate motor to have the fan run normally eliminated
No No
Yes No
No No
No
End
5. Communication Malfunction E6
Start
Yes
No
Yes
No
Replace
Communication cord is damaged? Yes communication Malfunction eliminated? Yes
cord
No
No
Replace IDU's
main board
Yes
Replace ODU's
Malfunction eliminated? No
main board.
Yes
End
Start
Yes
Is malfunction
eliminated
The end
Outdoor Unit
1. Capacity charging malfunction (outdoor unit malfunction) (AP1 below means control board of outdoor unit)
Main detection points:
● Detect if the voltage of L and N terminal of XT wiring board is between 210VAC-240VAC by alternating voltage meter;
● Is reactor (L) well connected? Is connection wire loosened or pulled out? Is reactor (L) damaged?
Malfunction of
Voltage higher Replace outdoor
Yes the outdoor
than 200V? mainboard
mainboard AP1
No
Power supply is
abnormal; repair
Voltage within the power supply Power on and
No Is the Vmalfunction Yes
180VAC~260VAC? to restore the range restart the unit
eliminated?
between 180VAC
~260VAC
Yes
Connect the
If the wiring of connection Power on and
No Is the Vmalfunction Yes
reactor L is normal? wire of reactor restart the unit
eliminated?
L correctly
Yes
Replace outdoor
mainboard AP1 No
End
2. IPM protection(H5), desynchronizing malfunction(H7), overcurrent of compressor phase current (P5) (AP1 below means
control board of outdoor unit)
Main detection points:
● Is voltage input within the normal range
● If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct?
● Heat exchange of unit is not good (heat exchanger is dirty and unit radiating environment is bad);
● If the system pressure is too high?
● If the refrigerant charging amount is appropriate?
● If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● If the work load of unit is heavy? If radiating of unit is good?
Malfunction diagnosis process:
H5, H7 or P5 is
displayed after
turning on the unit
Yes
No
Yes
No
No
No
No
Replace compressor
End
3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit)
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
E8 is displayed
No No
No
No
Yes
Yes
Replace Fan
Fan capacitor is broken? Yes
capacitor
Replace outdoor
mainboard
No
No
Replace mainboard
End
4. Start-up failure (LC) (AP1 below means control board of outdoor unit)
Main detection points:
● If the compressor wiring is correct?
● If the stop time of compressor is sufficient?
● If the compressor is damaged?
● If the refrigerant charging amount is too much?
Yes
Does the unit
start up normally?
If the refrigerant charging No
amount is too much?
Yes
No
Replace outdoor
mainboard AP1
No
Replace the
compressor
End
H3 or E4 is displayed
No
Yes
Yes
Connect wire
If the wiring terminal FA of electronic according to wiring
No
expansion valve is well connected? diagram
No
Yes
No
No
No
Heat exchange of unit is not good (heat exchanger
is dirty and unit radiating environment is bad); Is the malfunction Y
Yes
improve the radiating environment and clean the eliminated?
heat exchanger
No
No
Replace outdoor
mainboard AP1
End
start
No
No
No
Replace outdoor
N
No
mainboard AP1
End
E6
No
No
Yes
Yes
Yes End
14 15 16
38 39 40 41 42
13
12
11 17
10
9
7 8 18
5 6 19
4 20
2 3
1
21
22
23
26 25 24
27
28
29
30 37
36
31 35
34
32 33
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH24YE-S6DBA2A/I GWH24YE-S6DBA1A/I Qty
Product Code CB466N00304 CB466N00305 CB437N02800
1 Front Panel Assy 00000300009302 00000300009303 20000300059 1
2 Filter Sub-Assy 1101200702 1101200702 11012007 2
3 Screw Cover 2224219101P 2224219101P01 22242191 3
4 Front Case Assy 0000020006403 0000020006404 00000200064 1
5 Air Louver(Manual) 10512741 10512741 10512741 3
6 Flail(Gray) 10512743 10512743 10512743 1
7 Helicoid Tongue 26112513 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 10512037 1
9 Rear Case assy 00000100170 00000100170 00000100170 1
10 Rubber Plug (Water Tray) 76712012 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 10352057 1
14 Evaporator Support 24212178 24212178 24212178 1
15 Evaporator Assy 011001000095 011001000095 011001000095 1
16 Cold Plasma Generator 1114001602 1114001602 1114001602 1
17 Wall Mounting Frame 01252229 01252229 01252229 1
18 Motor Press Plate 26112515 26112515 26112515 1
19 Fan Motor 15012136 15012136 15012136 1
20 Connecting pipe clamp 26112514 26112514 26112514 1
21 Drainage Hose 0523001405 0523001405 0523001405 1
22 Stepping Motor 1521240210 1521240210 1521240210 1
23 Crank 73012005 73012005 73012005 1
24 Stepping Motor 1521210704 1521210704 1521210704 1
25 Air Louver 10512744 10512744 10512744 1
26 Guide Louver 1051250301P 1051250301P01 10512503 1
27 Axile Bush 10542036 10542036 10542036 2
28 Electric Box 2011221102 2011221102 2011221102 1
29 Terminal Board 42011233 42011233 42011233 1
30 Electric Box Cover2 2011221004P 2011221004P01 2011221001 1
31 Main Board 300002000101 300002000101 300002000101 1
32 Display Board 300001000095 300001000095 30565260 1
33 Shield cover of Electric Box 01592176 01592176 01592176 1
34 Electric Box Cover 2011220901 2011220901 2011220901 1
35 Jumper 4202021908 4202021908 4202021908 1
36 Lower Shield of Electric Box 01592139 01592139 01592139 1
37 Electric Box Assy 100002000608 100002000608 100002060299 1
38 Power Cord / / / /
39 Connecting Cable 4002052317 4002052317 4002052317 0
40 Connecting Cable / / / /
41 Temperature Sensor 3900031302 3900031302 3900031302 1
42 Remote Controller 30510137 30510137 30510137 1
Part Code
Description
No. GWH24YE-S6DBA2A/I GWH24YE-S6DBA2A/I Qty
Product Code CB466N00302 CB466N00303
1 Front Panel Assy 200003000063 20000300006301 1
2 Filter Sub-Assy 11012007 1101200702 2
3 Screw Cover 22242191 2224219101 3
4 Front Case Assy 000003000093 0000020006402 1
5 Air Louver(Manual) 10512741 10512741 3
6 Flail(Gray) 10512743 10512743 1
7 Helicoid Tongue 26112513 26112513 1
8 Left Axile Bush 10512037 10512037 1
9 Rear Case assy 00000100170 00000100170 1
10 Rubber Plug (Water Tray) 76712012 76712012 1
11 Ring of Bearing 26152025 26152025 1
12 O-Gasket sub-assy of Bearing 7651205102 7651205102 1
13 Cross Flow Fan 10352057 10352057 1
14 Evaporator Support 24212178 24212178 1
15 Evaporator Assy 011001000095 011001000095 1
16 Cold Plasma Generator 1114001602 1114001602 1
17 Wall Mounting Frame 01252229 01252229 1
18 Motor Press Plate 26112515 26112515 1
19 Fan Motor 15012136 15012136 1
20 Connecting pipe clamp 26112514 26112514 1
21 Drainage Hose 0523001405 0523001405 1
22 Stepping Motor 1521240210 1521210704 1
23 Crank 73012005 73012005 1
24 Stepping Motor 1521210704 1521210704 1
25 Air Louver 10512744 10512744 1
26 Guide Louver 10512503 1051250301 1
27 Axile Bush 10542036 10542036 2
28 Electric Box 2011221102 2011221102 1
29 Terminal Board 42011233 42011233 1
30 Electric Box Cover2 2011221001 2011221004 1
31 Main Board 300002000858 300002000101 1
32 Display Board 300001000095 300001000134 1
33 Shield cover of Electric Box 01592176 01592176 1
34 Electric Box Cover 2011220901 2011220901 1
35 Jumper 4202021908 4202021908 1
36 Lower Shield of Electric Box 01592139 01592139 1
37 Electric Box Assy 100002004011 100002060162 1
38 Power Cord 4002048716 / 1
39 Connecting Cable 4002052317 4002052317 0
40 Connecting Cable 4002053603 / 0
41 Temperature Sensor 3900031302 3900031302 1
42 Remote Controller 305001000139 30510137 1
Above data is subject to change without notice.
32
The component picture is only for reference; please refer to the actual product.
Part Code
Description
No. GWH24YE-S6DBA2A/O Qty
Product Code CB466W00300
1 Front Grill 22415011 1
2 Fan Motor 15010400000102 1
3 Electric Box (Fireproofing) / /
4 Radiator 4901521501 1
5 Main Board 300027000308 1
6 Electric Box Assy 100002000609 1
7 Electric Box Cover 20125002 1
8 Terminal Board 420101943 1
9 Handle 26233053 2
10 Left Side Plate 01305043P 1
11 Coping 01255006P 1
12 Motor Support Sub-Assy 017012000015 1
13 Condenser Support Plate 01175092 1
14 Clapboard Sub-Assy 017021000067 1
15 Condenser Assy 011002000285 1
16 Rear Grill 01475013 1
17 Wiring Clamp 26115004 1
18 Temp Sensor 39000072 1
19 Right Side Plate 0130504401P 1
20 Big Handle 26235001 1
21 Cut off Valve 0713517901 1
22 Valve Support Sub-Assy 0170506101P 1
23 Baffle(Valve Support) 26115007 1
24 Electronic Expansion Valve 07133909 1
25 4-Way Valve Assy 030152000260 1
26 Compressor and Fittings 00105274 1
27 Drainage Connecter 06123401 1
28 Chassis Sub-assy 017000000166 1
29 Drainage hole Cap 06813401 3
30 Axial Flow Fan 10335013 1
31 Cabinet 01435004P 1
32 Valve Cover 22245003 1
Step Procedure
1.Remove filter
Horizontal louver
Step Procedure
Groove
Screw
Vertical louver
Loosen the connection clasps between
vertical louver and bottom case to
remove vertical louver.
Clasps
Step Procedure
Wiring terminal
Pull out the wiring terminal of motor and
of motor
wiring terminal of step motor from the
mainboard.
Note:
When pulling out the wiring terminal,
pay attention to loose the clasp and don’t
pull it so hard. Wiring terminal
of step motor
Step Procedure
Screw
Connection pipe
Screws
Step motor
Step Procedure
Motor clamp
a. Remove the screws fixing motor clamp Screws
and then remove the motor clamp.
Screw Motor
Cross flow
Holder sub-assy
Steps Procedure
1.Remove handle
Twist off the screws used for fixing the handle and
valve cover, pull the handle and valve cover up
ward to remove it.
handle
valve cover
top panel
Remove the screws connecting the top
panel with the front panel and left&right
side plate, and then remove the top panel.
Steps Procedure
Steps Procedure
electric box
8.Remove motor
motor
Steps Procedure
motor support
isolation sheet
4-way valve
a Unsolder the pipeline between compressor,
condenser, gas and liquid valve, and then
remove the 4-way valve. (note: release all
refrigerant before unsoldering).
Steps Procedure
liquid valve
valve support
14.Remove compressor
compressor
Steps Procedure
condenser
chassis
Appendix:
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(°C) Celsius(°C) Celsius(°C)
temperature (°F) temperature (°F) temperature (°F)
(°F) (°F) (°F)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
Ambient temperature
Fahrenheit Fahrenheit Fahrenheit
display Fahrenheit display Fahrenheit display Fahrenheit
Celsius(°C) Celsius(°C) Celsius(°C)
temperature (°F) temperature (°F) temperature (°F)
(°F) (°F) (°F)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
Note: The additional refrigerant charging amount in Sheet 2 is recommendedvalue, not compulsory.
Improper pipe expanding is the main cause of refrigerant leakage.Please Pipe cutter
expand the pipe according to the following steps:
Leaning Uneven Burr
A:Cut the pip
● Confirm the pipe length according to the distance of indoor unit and outdoor unit.
● Cut the required pipe with pipe cutter.
● Remove the burrs with shaper and prevent the burrs from getting into the pipe. Shaper
Downwards
C:Put on suitable insulating pipe
Smooth surface
F:Inspection
● Check the quality of expanding port. If there is any blemish, expand the
Improper expanding
port again according to the steps above.
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor (15K)
Resistance Table of Tube Temperature Sensors for Indoor and Outdoor (20K)