Statement- 1

Name of the Substation: 132/33kV NARAYANAKHED Substation


Name of the FEEDER: 132kV MINPUR FEEDER
Relay: ZIV Make IRL-F Type
Protection Provided on: 132kV MINPUR FEEDER
Available CT Ratio: 600-300/1A
Adopted CT Ratio: 600/1A
Group Group
Group Function Action Name Variable Name Unit Settings

Phase Instantaneous Unit 1 Group 1 Phase IOC Enable No


Phase Instantaneous Unit 1 Group 1 Phase IOC Pickup A -
Phase Instantaneous Unit 1 Group 1 PHASE IOC DELAY s 0
Phase Instantaneous Unit 1 Group 1 Phase IOC Direction None
Phase Instantaneous Unit 1 Group 1 Phase IOC Direct Unit -
Phase Instantaneous Unit 1 Group 1 Phase IOC Harm Blocking No
Phase Instantaneous Unit 2 Group 1 Phase IOC Enable No
Phase Instantaneous Unit 2 Group 1 Phase IOC Pickup A -
Phase Instantaneous Unit 2 Group 1 PHASE IOC DELAY s -
Phase Instantaneous Unit 2 Group 1 Phase IOC Direction -
Phase Instantaneous Unit 2 Group 1 Phase IOC Direct Unit -
Phase Instantaneous Unit 2 Group 1 Phase IOC Harm Blocking -
Phase Instantaneous Unit 3 Group 1 Phase IOC Enable No
Phase Instantaneous Unit 3 Group 1 Phase IOC Pickup A -
Phase Instantaneous Unit 3 Group 1 PHASE IOC DELAY s -
Phase Instantaneous Unit 3 Group 1 Phase IOC Direction -
Phase Instantaneous Unit 3 Group 1 Phase IOC Direct Unit -
Phase Instantaneous Unit 3 Group 1 Phase IOC Harm Blocking -
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Enable Yes
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Pickup A 0.95
[IEC] Inverse
Phase Time Overcurrent Unit 1 Group 1 PHASE TOC CURVE Curve
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Dial 0.075
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Definite Time s -
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Direction Direction
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Direct Unit 67F
Phase Time Overcurrent Unit 1 Group 1 Reset Type Instantaneous
Phase Time Overcurrent Unit 1 Group 1 Phase TOC Harm Blocking No
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Enable No
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Pickup A -
Phase Time Overcurrent Unit 2 Group 1 PHASE TOC CURVE -
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Dial -
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Definite Time s -
Phase Time Overcurrent Unit 2 Group 1 Reset Type -
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Direction -
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Direct Unit -
Phase Time Overcurrent Unit 2 Group 1 Phase TOC Harm Blocking No
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Enable No
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Pickup A -
Phase Time Overcurrent Unit 3 Group 1 PHASE TOC CURVE -
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Dial -
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Definite Time s -
Phase Time Overcurrent Unit 3 Group 1 Reset Type -
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Direction -
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Direct Unit -
Phase Time Overcurrent Unit 3 Group 1 Phase TOC Harm Blocking -

1 of 3
Group Group
Group Function Action Name Variable Name Unit Settings

Ground Instantaneous Unit 1 Group 1 Ground IOC Enable No


Ground Instantaneous Unit 1 Group 1 Ground IOC Pickup A -
Ground Instantaneous Unit 1 Group 1 Ground IOC DELAY s 0
Ground Instantaneous Unit 1 Group 1 Ground IOC Direction None
Ground Instantaneous Unit 1 Group 1 Ground IOC Direct Unit -
Ground Instantaneous Unit 1 Group 1 Ground IOC Harm Blocking No
Ground Instantaneous Unit 2 Group 1 Ground IOC Enable No
Ground Instantaneous Unit 2 Group 1 Ground IOC Pickup A -
Ground Instantaneous Unit 2 Group 1 Ground IOC DELAY s -
Ground Instantaneous Unit 2 Group 1 Ground IOC Direction -
Ground Instantaneous Unit 2 Group 1 Ground IOC Direct Unit -
Ground Instantaneous Unit 2 Group 1 Ground IOC Harm Blocking -
Ground Instantaneous Unit 3 Group 1 Ground IOC Enable No
Ground Instantaneous Unit 3 Group 1 Ground IOC Pickup A -
Ground Instantaneous Unit 3 Group 1 Ground IOC DELAY s -
Ground Instantaneous Unit 3 Group 1 Ground IOC Direction -
Ground Instantaneous Unit 3 Group 1 Ground IOC Direct Unit -
Ground Instantaneous Unit 3 Group 1 GroundIOC Harm Blocking -
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Enable Yes
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Pickup A 0.19
[IEC] Inverse
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Curve Curve
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Dial 0.15
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Delay s -
Ground Time Overcurrent Unit 1 Group 1 Gnd TOC Direction Direction
Ground Time Overcurrent Unit 1 Group 1 Gnd TOC Direct Unit 67G
Ground Time Overcurrent Unit 1 Group 1 Reset Type Instantaneous
Ground Time Overcurrent Unit 1 Group 1 Ground TOC Harm Blocking No
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Enable No
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Pickup A -
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Curve -
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Dial -
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Delay s -
Ground Time Overcurrent Unit 2 Group 1 Reset Type -
Ground Time Overcurrent Unit 2 Group 1 Gnd TOC Direction -
Ground Time Overcurrent Unit 2 Group 1 Gnd TOC Direct Unit -
Ground Time Overcurrent Unit 2 Group 1 Ground TOC Harm Blocking -
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Enable No
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Pickup A -
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Curve -
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Dial -
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Delay s -
Ground Time Overcurrent Unit 3 Group 1 Reset Type -
Ground Time Overcurrent Unit 3 Group 1 Gnd TOC Direction -
Ground Time Overcurrent Unit 3 Group 1 Gnd TOC Direct Unit -
Ground Time Overcurrent Unit 3 Group 1 Ground TOC Harm Blocking -

2 of 3
Group Group
Group Function Action Name Variable Name Unit Settings

Directional Group 1 Phase Characteristic Angle º 45

Directional Group 1 Neutr./Gnd Characteristic Angle º 45


Directional Group 1 NegSeq Characteristic Angle º -
Directional Group 1 PosSeq Characteristic Angle º -
Directional Group 1 Lack of direction blocking Yes
Directional Group 1 Min. Phase Voltage V 0.2
Directional Group 1 Min. Neutr Voltage V -
Directional Group 1 Min. Gnd Voltage V 0.2
Directional Group 1 Min. Neg Seq Voltage V -
Directional Group 1 Min. Pos Seq Voltage V -
Directional Group 1 Coordinating Time ms 0
Directional Group 1 Neutr Volt. Comp. 0
Directional Group 1 Gnd Volt. Comp. 0
Directional Group 1 NegSeq Volt.Comp. 0
Directional Group 1 Neutral/Ground V_POL type Vn

Note:- IG type may be set to IG in General settings.

CHIEF ENGINEER
POWER SYSTEMS

3 of 3