0% found this document useful (0 votes)
40 views53 pages

MX4000 Installation Commission

Uploaded by

mohamed ali haba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views53 pages

MX4000 Installation Commission

Uploaded by

mohamed ali haba
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 53

UK Security Panels Alarmhelp.

net

Technical Data
Sheet

Installation & Commissioning Manual


MX4100, MX4200 & MX4400
Fire Alarm Control Panels

The operation and functions described in


the manual are available from Software
Versions Mx4100-017, Mx4200-017 and
Mx4400-017 onwards.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 1


UK Security Panels Alarmhelp.net

Specifications
Mx-4100 Mx-4200 Mx-4400
Enclosure Steel IP30 Steel IP30 Steel IP30
Dimensions H 320 x 345 x 85 475 x 450 x 115 475 x 450 x 115
x W x D mm
Weight 5Kg 10.5Kg 10.5Kg
Temperature 0°C to 45°C 0°to 45°C 0°C to 45°C
Humidity 95 % Max 95 % Max 95 % Max
Cable Entries 7 x top and 7 x top rear 18 x top, 9 x top rear and 2 x 18 x top, 9 x top rear and 2 x
(20mm bottom bottom
knockouts)
Mains Supply 230V +10%, -15% 220-240V, +10%, -15% 220-240V, +10%, -15%
50/60Hz AC 47 –63 Hz AC 47 –63 Hz AC
0.4A max 1 A max 1 A max
Battery 24V 4Ah Internal (min) 24V 4Ah Internal (min) 24V 4Ah Internal (min)
Capacity (For 24V 7Ah Internal (max) 24V 17Ah Internal (max) 24V 17 Ah Internal (max)
24Hr. standby)
24V 12Ah External max. 24V 48 Ah External (max) 24V 48Ah External (max)

Charging 0.4A 2.4A 2.4A


Current Temperature Compensated Temperature Compensated Temperature Compensated
Power Supply On-board 24V DC, 2A Separate 24V DC, 4A Separate 24V DC, 5A
High Efficiency Switched Universal Input Universal Input
Mode Switched Mode Switched Mode
Number of 100 max 200 max, across 2 loops 200 max, across 4 loops
Fire Zones (250 when networked) (1000 when networked) (1000 when Networked)
Number of 1 1 to 2 1 to 4
Loops
Devices per Apollo 126 detector/call points per loop (max)
Loop Hochiki 127 detector/call points per loop (max)
Loop Current * 500mA max. 500mA max. per Loop 500mA max. per Loop
Protocols Apollo: S90, XP95, Discovery, Explorer & Hochiki ESP
Sounder * 2 x 1A Programmable 2 x 1A Programmable 4 x 1A Programmable
Outputs (Total output current
from panel not to exceed
2Amps)
Relay Outputs 2 x1A 30VAC/DC (max) 2 x 1A 30V AC/DC (max) 2 x 1A 30V AC/DC (max)
10mA 5V (min) 10mA. 5V (min) 10mA. 5V (min)
Programmable Programmable Programmable
Open Collector 2 x Programmable 2 x Programmable 2 x Programmable
Outputs 10mA 30V DC (max) 10mA 30V DC (max) 10mA 30V DC (max)
Digital Outputs --- 6 x Programmable 6 x Programmable
Auxiliary 24V DC, 300mA 24V DC, 300mA 24V DC, 300mA
Supply Output See notes See notes See notes
Event Log 1000 Event & Diagnostic + 500 Fire

Notes
Aux supply tracks a maximum of 0.5V below battery terminal voltage when no mains supply available.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 2


UK Security Panels Alarmhelp.net

Standards:
The Mx-4100, 4200 and Mx-4400 Fire Alarm Control Panels conform to the following standards:
BS EN54-2: 1998 Control and Indicating Equipment
BS EN54-4: 1998 Power Supply Equipment
BS EN60950: 2000 Safety of information technology equipment
BS EN50130-4: 196 Product Family Standard
Electromagnetic Compatibility Directive 89/336/EEC (and the amending directive 92/23/EEC)
Low Voltage Directive 73/23/EEC

Contents
1 Introduction _____________________________________________________ 6
1.1 EN54 Functions ___________________________________________________________7
1.2 Installation Approvals ______________________________________________________7
1.2.1 Fire System Installations _________________________________________________________ 7
1.2.2 Wiring Regulations______________________________________________________________ 7
2 Installation ______________________________________________________ 8
2.1 Identification of Parts ______________________________________________________8
2.1.1 Mx-4100 ______________________________________________________________________ 8
2.1.2 Mx-4200 & Mx-4400 ____________________________________________________________ 8
2.2 Installing the Mx-4100 Enclosure_____________________________________________9
2.2.1 Removing and Replacing the Enclosure Cover of the Mx-4100 ___________________________ 9
2.2.2 Removing the Chassis ___________________________________________________________ 9
2.2.3 Mounting the Enclosure __________________________________________________________ 9
2.2.4 Remounting the Chassis _________________________________________________________ 10
2.2.5 Recommended Cable Routing Arrangement _________________________________________ 10
2.3 Installing the Mx-4200 & 4400 Enclosures ____________________________________11
2.3.1 Opening the Enclosure Cover_____________________________________________________ 11
2.3.2 Removing the Chassis __________________________________________________________ 11
2.3.3 Mounting the Enclosure _________________________________________________________ 11
2.3.4 Remounting the Chassis _________________________________________________________ 12
2.3.5 Recommended Cable Routing Arrangement _________________________________________ 12
2.3.6 Installing Additional Loop Circuits in the Mx4200 & Mx-4400 __________________________ 13
2.3.7 Removing a Loop Driver Card ____________________________________________________ 13
2.4 Wiring Installation _______________________________________________________14
2.4.1 AC Mains Wiring ______________________________________________________________ 14
2.4.1.1 Cable Gland _____________________________________________________________ 14
2.4.2 Battery Installation _____________________________________________________________ 15
2.4.2.1 Mx-4100 ________________________________________________________________ 15
2.4.2.2 Mx-4200 & Mx-4400 ______________________________________________________ 16
2.4.3 Detector Loop Installation _______________________________________________________ 17
2.4.4 Sounder Circuits _______________________________________________________________ 18
2.4.5 Relay Circuits _________________________________________________________________ 18
2.4.6 Open Collector Outputs _________________________________________________________ 19
Document Reference 680-014 Rev 07 Author PS RFM4100 Page 3
UK Security Panels Alarmhelp.net
2.4.7 Auxiliary Supply Output ________________________________________________________ 19
2.4.8 Switch Inputs _________________________________________________________________ 19
2.4.9 RS232 Interface _______________________________________________________________ 20
3 Programming __________________________________________________ 21
3.1 Introduction ____________________________________________________________ 21
3.1.1 Access Levels ________________________________________________________________ 21
3.1.2 Memory Lock ________________________________________________________________ 21
3.1.3 Navigating through menus _______________________________________________________ 21
3.1.4 Changing Text Descriptions______________________________________________________ 22
3.1.5 Numeric data entry_____________________________________________________________ 23
3.2 Recommended Programming Procedure_____________________________________ 23
3.3 Level 3 Menu Functions __________________________________________________ 23
3.3.1 Loops _______________________________________________________________________ 24
3.3.2 Loops - View/Edit _____________________________________________________________ 24
3.3.2.1 State ___________________________________________________________________ 24
3.3.2.2 Type ___________________________________________________________________ 24
3.3.2.3 Value __________________________________________________________________ 25
3.3.2.4 Zone ___________________________________________________________________ 25
3.3.2.5 Device Text _____________________________________________________________ 25
3.3.2.6 Action __________________________________________________________________ 25
3.3.2.7 Sensitivity_______________________________________________________________ 26
3.3.2.7.1 Mode- Apollo: _________________________________________________________ 26
3.3.2.7.2 Mode- Hochiki: ________________________________________________________ 26
3.3.2.7.3 Delay ________________________________________________________________ 27
3.3.2.7.4 Alarm- Apollo _________________________________________________________ 27
3.3.2.7.5 Alarm- Hochiki ________________________________________________________ 27
3.3.2.7.6 Pre-Alarm ____________________________________________________________ 27
3.3.2.7.7 Minimum Value________________________________________________________ 27
3.3.2.7.8 Special Sensitivity Mode SSM/Clock _______________________________________ 27
3.3.2.8 O/P Group ______________________________________________________________ 28
3.3.2.9 Additional Info ___________________________________________________________ 28
3.3.2.10 Detector Testing __________________________________________________________ 29
3.3.3 Loops - Auto Learn ____________________________________________________________ 29
3.3.3.1 Normal Procedure / Initial learn ______________________________________________ 29
3.3.3.2 Procedure if the Panel finds Devices Missing ___________________________________ 30
3.3.3.3 Procedure if the Panel finds Devices Added ____________________________________ 30
3.3.3.4 Procedure if the Panel finds Devices Changed___________________________________ 30
3.3.4 Loop – Calibrate ______________________________________________________________ 31
3.3.5 Loop – Driver_________________________________________________________________ 31
3.3.6 Zones _______________________________________________________________________ 31
3.3.7 Exit_________________________________________________________________________ 31
3.3.8 Outputs______________________________________________________________________ 32
3.3.8.1 Default Output Settings ____________________________________________________ 32
3.3.8.2 Cause __________________________________________________________________ 33
3.3.8.3 Style ___________________________________________________________________ 34
3.3.8.3.1 Delay ________________________________________________________________ 34
3.3.8.3.2 Mode ________________________________________________________________ 34
3.3.8.3.3 Wait _________________________________________________________________ 34
3.3.8.4 Copying Output Settings to Multiple Zones ____________________________________ 34
3.3.9 Investigation Delays____________________________________________________________ 35
3.3.9.1 Overriding Delays at Level 1 ________________________________________________ 35
3.3.10 Time and Date ______________________________________________________________ 35
3.3.11 View Options ______________________________________________________________ 36
3.3.12 Passwords _________________________________________________________________ 36
3.3.13 Panel _____________________________________________________________________ 36
3.3.14 PC Config _________________________________________________________________ 37
3.3.15 Setup _____________________________________________________________________ 37
3.3.15.1 Network ________________________________________________________________ 37
Document Reference 680-014 Rev 07 Author PS RFM4100 Page 4
UK Security Panels Alarmhelp.net
3.3.15.2 Panel Zone ______________________________________________________________ 37
3.3.15.3 Service Number __________________________________________________________ 37
3.3.15.4 Service Due Date _________________________________________________________ 38
3.3.15.5 Trace Logging Mode_______________________________________________________ 38
3.3.15.6 Detector Blinking _________________________________________________________ 38
3.3.15.7 Company LCD Logo_______________________________________________________ 39
3.3.15.8 Program ID ______________________________________________________________ 39
3.3.15.9 Config Data______________________________________________________________ 39
4 EN54 Optional Features __________________________________________ 40
5 Service and Maintenance _________________________________________ 41
5.1 Maintenance Schedule_____________________________________________________41
5.1.1 Daily Actions _________________________________________________________________ 41
5.1.2 Monthly Actions_______________________________________________________________ 41
5.1.3 Quarterly Actions ______________________________________________________________ 41
5.1.4 Annual Actions________________________________________________________________ 41
5.2 Replacement of Components _______________________________________________42
5.2.1 Batteries _____________________________________________________________________ 42
5.2.1.1 Standby Batteries _________________________________________________________ 42
5.2.1.2 Lithium Battery___________________________________________________________ 42
5.2.2 Liquid Crystal Display __________________________________________________________ 43
6 Appendices ____________________________________________________ 44
6.1 Appendix 1 – Forgotten Level 3 Password ____________________________________44
6.2 Appendix 2 – Recommended Cables _________________________________________45
6.3 Appendix 3 – Battery Standby Calculation Chart ______________________________46
6.3.1 Mx-4100 _____________________________________________________________________ 46
6.3.2 Mx-4400 & Mx-4200 ___________________________________________________________ 47
6.4 Appendix 4 – Cause and Effect Programming Example _________________________48
6.4.1 Introduction __________________________________________________________________ 48
6.4.2 Output Groups ________________________________________________________________ 48
6.4.3 Styles _______________________________________________________________________ 48
6.4.4 Output Group Programming______________________________________________________ 49
6.5 Appendix 5 – Apollo Information ___________________________________________50
6.5.1 View Drift____________________________________________________________________ 50
6.5.2 Rapid Compensation ___________________________________________________________ 50
6.5.3 View EEPROM _______________________________________________________________ 51
6.6 Appendix 6 – Hochiki Esp Information_______________________________________52
6.6.1 Unprocessed Analogue information ________________________________________________ 52
6.6.2 CHQ-BS / CHQ-WS Sounders____________________________________________________ 52
6.7 Appendix 7 – Mx4000 Series Loop Output Drive Capabilty ______________________53
6.7.1 Hochiki ______________________________________________________________________ 53
6.7.2 Apollo_______________________________________________________________________ 53

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 5


UK Security Panels Alarmhelp.net

Cautions and Warnings


BEFORE INSTALLATION – Refer To the Ratings shown on the label inside the product and
to the ‘Specifications Chart’ in this document.
STOP
Please read this manual carefully. If you are unclear on any point, DO NOT proceed. Contact
the manufacturer or supplier for clarification and guidance.

Only Trained service personnel should undertake the Installation, Programming and
Maintenance of this equipment.

This product has been designed to comply with the requirements of the Low Voltage Safety
and the EMC Directives. Failure to follow the installation instructions may compromise its
adherence to these standards.

This equipment is constructed with static sensitive components. Observe anti-static


precautions at all times when handling printed circuit boards. Wear an anti-static earth
strap connected to panel enclosure earth point. Before installing or removing any printed
circuit boards remove all sources of power (mains and battery).

1 Introduction
This manual covers the installation, programming and commissioning of the Mx-4100, Mx-4200 and Mx-4400
Fire Alarm Control Panels. Refer to the User Manual (Document No. 680-015) for details of how to operate the
panel.

The Mx-4100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel.
The Mx-4200 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to two
loops.
The Mx-4400 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to four
loops.

All three panels are designed for use with the Apollo Discovery, Explorer , XP95 and Series 90 and Hochiki ESP
fire detection devices.

Install the panel, detection loops, sounder circuits, etc. in accordance with the instructions in Section 2 and
then program the operation in accordance with the instructions detailed in Section 3.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 6


UK Security Panels Alarmhelp.net

1.1 EN54 Functions

This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2
and 4 (1997).
In addition to the basic requirements, the following optional functions are provided
and these comply with the requirements of EN54.

C.I.E Optional Functions EN54-2 Clause


Indication Outputs to Fire Alarm Devices 7.8
Outputs Investigation Delays to Outputs 7.11
Controls Co-incidence Detection 7.12
Fault Signals from Points 8.3
Disablement of Points 9.5
Test Condition 10
Standardised I/O 11

P.S.E Functions EN54-4 Clause

Operation from a main power supply 5.1


Operation from a standby battery 5.2
Monitor and Charge the Standby Battery 5.3
Recognise and Notify Supply Faults 5.4

This Fire Alarm Control Panel also supports additional functions that are not covered
by EN54. These are as follows:
Refer to
Additional Function
Paragraphs

Auxiliary Power Supply Output 2.4.7


Auxiliary Relay Outputs 2.4.5
Programmable Cause / Effect on Outputs (Phased Evacuation) 6.4
Printer Option User Manual

1.2 Installation Approvals

1.2.1 Fire System Installations


The panel must be installed and configured for operation in accordance with these instructions and the applicable
fire systems installation regulations appropriate to the country and location of the installation.

1.2.2 Wiring Regulations


The panel and system must be installed in accordance with these instructions and the applicable wiring codes and
regulations appropriate to the country and location of the installation.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 7


UK Security Panels Alarmhelp.net

2 Installation
2.1 Identification of Parts
The following diagram shows the major parts of the panel.

2.1.1 Mx-4100
Chassis
Assembly

Earth Lead
to Cover

Rear
Enclosure
AC Mains Battery
Input Leads

2.1.2 Mx-4200 & Mx-4400


AC Mains
Input

Chassis
Assembly

Battery
Leads

Rear
Enclosure

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 8


UK Security Panels Alarmhelp.net

2.2 Installing the Mx-4100 Enclosure


The panel can weigh in excess of 15kg when the batteries are installed. Use appropriate fixing
hardware to secure the panel to the wall. Observe recommended lifting practices to guard
against spinal injury.

2.2.1 Removing and Replacing the Enclosure Cover of the Mx-4100


The enclosure cover is fixed in place with two tamper resistant hexagon key screws. These require the use of a
2.5mm Allen Key.
The enclosure cover must be connected to earth. When replacing the cover, always ensure that the earth lead
spade terminal is securely seated onto the blade terminal in the backbox.

2.2.2 Removing the Chassis


It is recommended that the chassis be removed before fitting the panel to the wall. To remove the chassis:
Disconnect the earth cable connecting the chassis to the spade terminal on the rear enclosure.
Remove the two screws holding the chassis to the back box. Keep these items in a safe place for later re-use.
Unplug the 3-way connector feeding the power supply to the Base Card. Carefully remove the chassis from the
rear enclosure and place in a safe place to prevent accidental damage.

Do not lift the chassis by holding onto any of the printed circuit cards. Hold the chassis by the
metal plate only.

2.2.3 Mounting the Enclosure


Firstly, remove the required knockouts for the installation wiring. There are sufficient knockouts on the top of the
enclosure for all installation wiring. In addition, there are knockouts at the top of the back wall, if required, for
rear entry cabling.

The enclosure is provided with four fixing points. 340


35 270
The diagram opposite shows the positions of the four holes.
Use all four positions to ensure the panel is held securely to the

17
wall.
Drill the required holes in the supporting wall using a drill bit
Earth
diameter 7.0 mm and plug with a suitable 40mm long Studs x2
expansion plug. Affix the panel to the wall with M5 screws
(length 40mm) or No.10 screws (length 1½”).
274
315

Ensure that there is sufficient space to allow the cover to be


removed / replaced when the panel is mounted. In addition, Cable Tie
there should be sufficient space below the panel to allow Anchor Points x6
access to the RS232 connected, if fitted.
Finally, use a brush to remove any dust or swarf from inside
the enclosure.

Enclosure Size and Fixing Point Dimensions

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 9


UK Security Panels Alarmhelp.net

2.2.4 Remounting the Chassis


Carefully replace the chassis and fix into place using the two screws.
Reconnect the chassis earth cable to the spade terminal in the rear of the enclosure and then reconnect the supply
lead from the transformer to the Base Card.

2.2.5 Recommended Cable Routing Arrangement


It is recommended that the routing arrangement Relay Sounder Loop Tie-Wrap
AC Mains Outputs Outputs Circuit Positions
shown in the diagram opposite be employed.
Segregate the low voltage wiring (Loop Circuit,
Sounder Circuits and AUX Supply) from the
AC Mains Wiring.
Segregate any wiring connected to the relay
contacts.
Eyelets are provided in the rear of the backbox
to enable the cables to be securely fastened
using tie-wraps.
Refer to Appendix 2 – Recommended Cables
for further information on cable types to be
used.
Refer to specific sections on how to install AC
Mains input and loop, sounder, relay and AUX
outputs circuits. Internal arrangement showing recommended routing of cables.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 10


UK Security Panels Alarmhelp.net

2.3 Installing the Mx-4200 & 4400 Enclosures


The panel can weigh in excess of 20kg when the batteries are installed. Use appropriate fixing
hardware to secure the panel to the wall. Observe recommended lifting practices to guard
against spinal injury.

2.3.1 Opening the Enclosure Cover


The Mx4200 & Mx-4400 are provided with a key-lock assembly for securing the hinged door to the backbox.
Insert and turn the key to open the enclosure.

2.3.2 Removing the Chassis


It is recommended that the chassis be removed
before fitting the panel to the wall. To remove the
chassis:
Fixing
Refer to the diagram opposite. Screws.
Disconnect the earth cable connecting the chassis
to the spade terminal on the rear enclosure.
Remove the bottom two screws holding the chassis
to the back box. Keep these items in a safe place
for later re-use.
Loosen the top two screws holding the chassis to
the backbox via the keyhole slots. The chassis
assembly can now be removed. Earth
Connection
Carefully remove the chassis from the rear
enclosure and place in a safe place to prevent
accidental damage.

Do not lift the chassis by holding onto any of the printed circuit cards. Hold the chassis by the
metal plate only.

2.3.3 Mounting the Enclosure


Firstly, remove the required knockouts for the
installation wiring. There are sufficient knockouts on 450
the top of the enclosure for all installation wiring. In
addition, there are knockouts at the top of the back 35 380
wall, if required, for rear entry cabling. 25
The diagram opposite shows the positions of the four Earth
holes. Use all four positions to ensure the panel is held Studs
x4
securely to the wall.
Drill the required holes in the supporting wall using a
drill bit diameter 7.0 mm and plug with a suitable
Cable Tie
40mm long expansion plug. Affix the panel to the wall Anchor Points x9
with M5 screws (length 40mm) or No.10 screws 475 405
(length 1½”).
Ensure that there is sufficient space to allow the door to
be opened when the panel is mounted. In addition,
there should be sufficient space below the panel to
allow access to the RS232 connected, if fitted.
Finally, use a brush to remove any dust or swarf from Enclosure Size and Fixing Point Dimensions
inside the enclosure.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 11


UK Security Panels Alarmhelp.net

2.3.4 Remounting the Chassis


Carefully replace the chassis and locate onto the upper two screws. Replace the bottom two screws and tighten all
four screws to hold the chassis securely to the backbox.

Reconnect the chassis earth cable to the spade terminal in the rear of the enclosure.

2.3.5 Recommended Cable Routing Arrangement


It is recommended that the routing arrangement
shown in the diagram opposite be employed. Relays Sounders + AUX
AC Mains Ad-NeT /
LOOPS Network
Segregate the low voltage wiring (Loop Circuit,
Sounder Circuits, RS485 and AUX Supply)
from the AC Mains Wiring.
Segregate any wiring connected to the relay
contacts.
Eyelets are provided in the rear of the backbox
to enable the cables to be securely fastened
using tie-wraps.
Sounders and AUX wiring should be routed
behind the chassis assembly and tie-wrapped to
the backbox.
Cable screens / shields should be connected to Sounders + AUX
the backbox using the threaded studs provided
near the knockout holes.
Refer to Appendix 2 – Recommended Cables
for further information on cable types to be
used. Internal arrangement showing recommended routing of cables.
Refer to specific sections on how to install AC
Mains input and loop, sounder, relay and AUX
outputs circuits.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 12


UK Security Panels Alarmhelp.net

2.3.6 Installing Additional Loop Circuits in the Mx4200 & Mx-4400

To extend the number of detector loops or to replace an


existing loop driver card follow the procedure
described below.
An example of the loop driver is shown opposite. This
is provided with a plastic grip handle on the top edge to
ease removal of the card from the Base Card.

Isolate ALL sources of power before


installing or removing printed circuit
boards.

Observe anti-static precautions at all


times when handling printed circuit
boards. Loop Driver – Component Side View

Open the enclosure and then open the display plate (it
is hinged on the right hand side and there is a magnetic
catch strip on the left-hand side) to gain access to the
Base Card.
A section of the Base Card identifying the locations for
each loop driver is shown in the picture opposite Component side of
Loop Driver Card
To install a loop driver, remove the retaining strap, then
gently guide the loop driver printed circuit card into the
guide slots of the machined end blocks and then push
into place onto the connector on the Base Card.
Ensure that the pins of the connectors are correctly
aligned. The loop driver should be inserted with the
component side of the board placed on the left-hand
side. Replace the retaining strap.
The Base Card can accept up to four loop driver cards – Machined End
it does not matter which positions are used. Ensure that Block 1 2 3 4
the detector loop wiring is made to the terminal block LOOPS
positions appropriate to the loop driver cards actually
installed.
NB: The Mx-4200 only has positions 1 & 2 available.
Close the chassis display plate and then close up the
enclosure.

2.3.7 Removing a Loop Driver Card


To remove a loop driver, remove all power and follow
the procedure above but:
Take a firm hold of the lever located on top of the loop
driver card. Gradually and carefully pull the loop driver
vertically away from the base card and guide it out of
the slots in the machined end blocks.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 13


UK Security Panels Alarmhelp.net

2.4 Wiring Installation

2.4.1 AC Mains Wiring


Route the high voltage mains AC wiring into the Panel Wiring
enclosure at the upper left corner only. Keep the AC FUSE 1 A
Yellow
wiring away from the circuit boards and all other LIVE
wiring. Green
EARTH
The panel must be connected to the supply earth
through the power cable.
NEUTRAL
The mains input connector is shown in the diagram
opposite. Note the positions of the earth, neutral and
live terminal connections. These are clearly marked on AC Mains terminations – Mx-4100.
the label next to the connector. The connector block
contains an integral fuse holder. Panel Wiring
FUSE 3 .1 5 A
Brown
LIVE
Secure the mains input wiring by tie wrap as close to Green
EARTH
the terminal block as possible.

Blue NEUTRAL
The fuses are rated as follows:
T 1.0A H 250V (for Mx-4100) AC Mains terminations – Mx-4200 & Mx4400
T 3.15A H 250V (for Mx-4200 and MX4400)
Replace with correct rating and specification only.
Connect the Control Panel to the mains supply via a
readily accessible; disconnect device (Isolation Switch)
and suitable earth fault protection incorporated in the
building installation wiring. The Mains cable should be
0.75mm2 cable rated at 250V and fused via a 5A anti-
surge fuse.

2.4.1.1 Cable Gland


The cable gland and any cord clamp bushing s used in routing the Mains cable through the
20mm knockout must have a minimum flame-retardant rating of 94HB.
Suggested glands and bushings are: -
Type Manufacturer
Gland IP65 – Brass M20, EExd / Eexe Lappcable
Gland IP68 – Nylon 66 M20 Black, UL94V2 Multicomp
Bushing – Nylon 66 M20 Black, UL94V2 Multipcomp

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 14


UK Security Panels Alarmhelp.net

2.4.2 Battery Installation


The panel requires two 12V batteries Base Card Terminations
for standby operation.

BAT –
BAT +

AUX +
AUX -
The battery leads are connected onto
the base card via a two-part plug and BAT +
socket, as shown in the diagram BAT –
opposite. AUX -

Refer to the Specifications for AUX +

minimum and maximum battery sizes


FS2 BAT FS1 Supply
allowed.

Mx-4100 Mx-4200& Mx4400


Link Cable BLACK
Place the batteries in the bottom of the enclosure and
connect the ‘Red’ lead to the positive (+) terminal of -
battery #1 and the ‘Black’ lead to the negative (-)
terminal of battery #2. Connect the negative of battery +
#1 to the positive of battery #2 using the supplied link
cable. RED

Ensure that the battery terminals do not short out + - + -


against any part of the enclosure, circuit board or #2
#1
chassis plate.

Do not make the final battery connections until the installation wiring is completed and the
system is to be powered up.
Always connect the AC Mains input before connecting the battery.

New batteries require ‘top-charging’ before installation. Refer to Section 5.2.1.1 for a list of
recommended batteries.

2.4.2.1 Mx-4100
The diagram opposite shows the
recommended location and orientation for the
7AH batteries within the panel.
For battery sizes greater than 7AH, the
batteries must be installed in a separate
enclosure suitable for fire protection use with
wiring connected to the panel through rigid
conduit.

Replacement Fuses
FS1 T5A 125V Anti-Surge
FS2 T5A 125V Anti-Surge

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 15


UK Security Panels Alarmhelp.net

2.4.2.2 Mx-4200 & Mx-4400


The diagrams opposite show the
recommended location and orientation for the
12AH and 17AH batteries within the panel.
For battery sizes greater than 17AH, the
batteries must be installed in a separate
enclosure suitable for fire protection use with
wiring connected to the panel through rigid
conduit.
For battery sizes greater than 12AH, it will be
necessary to remove the spade terminals
fixed to the battery leads and replace these
with connection fixings suitable for the
installed batteries.

12AH 12AH

Replacement Fuse
FS1 T6.3A 250V Anti-Surge

17AH 17AH

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 16


UK Security Panels Alarmhelp.net

2.4.3 Detector Loop Installation

Maximum of 32 Sensors / Call Points between Isolators.

The Detection Loop Circuit should be installed as a continuous loop with isolator
modules such that a short circuit condition does not remove more than 32 input
devices.
Section 12.5.2

Form the loop starting at the Loop Out + and –


terminals on the base card.

OUT +
OUT –
Route the wires around the loop connecting all devices

IN +
IN –
in accordance with the manufacturers’ data sheet
supplied with each unit.
Ensure that the devices are correctly installed with
regard to their positive and negative terminal polarity
(especially Loop Isolator Modules).
Connect the return wires to the Loop IN + and –
terminals on the base card. Base Card Terminations (Typical).
The diagram opposite shows the typical arrangement of
the loop connections on the base cards.
Refer to Section 2.3.6 for details on installing
additional loop drivers on the multi-loop panels.

When screened cable is used, it is vital to connect the screen / drain wire to the chassis / earth at
the cable gland input / earth stud in the panel. Always ensure that all segments of the cable loop
have continuity of the screen and take care to ensure that the screen is not exposed to any other
earth point (e.g. metalwork, cable trays, junction boxes, etc.).

The Loop Driver Circuit on the Base card is equipped Isolators


with in-built isolators to take care of short circuit
conditions on the wiring between the panel and the first -
device on the loop. Do not fit loop isolators at the panel +
outputs.
The diagram opposite shows a typical loop -
arrangement. +
Maximum recommended cable loop length is 1500 to
2000 Metres. Refer to Appendix 2 – Recommended Typical Loop Arrangement.
Cables for further information on cable types to be
used.

Take care that the voltage drop at full load is within the detector rating – refer to the detector
manufacturers’ data sheet for minimum values.
To maintain signal line wiring supervision, break the wiring run at each loop device.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 17


UK Security Panels Alarmhelp.net

2.4.4 Sounder Circuits


The Mx-4100 & Mx4200 are equipped with two

SND B +

SND A +
supervised sounder circuits. These are denoted as

SND A –
SND B –
Circuits A and B.
The Mx-4400 is equipped with four supervised sounder
circuits. These are denoted as Circuits A, B, C and D.
Each Sounder output is rated at a maximum of 1
Ampere.
The terminal connections on the base card are shown in
the diagram opposite.
Base Card Connections – Typical.
The sounder outputs are monitored (supervised) for
open and short circuit conditions using reverse polarity
signals. Sounder must be equipped with an in-built -

EOL
blocking diode that prevents the sounder from taking +
power when the output is in the supervising condition.
An End-of-Line Resistor (EOLR) of value 10,000Ω, ½ Typical
Watt must be fitted to the last sounder / bell. Arrangement

Refer to Appendix 2 – Recommended Cables for


further information on cable types to be used. Typical Sounder Arrangement.

When screened cable is used, it is vital to connect the screen to the chassis / earth at the cable
gland input / earth stud in the panel. Always ensure that all segments of the cable loop have
continuity of the screen and take care to ensure that the screen is not exposed to any other
earth point (e.g. metalwork, cable trays, junction boxes, etc.).

2.4.5 Relay Circuits

Fault Output.

Relay 1 is arranged for failsafe operation as standard.


Section 8.8

The panels are equipped with two relay outputs. These


are normally programmed to activate on Fault and Fire RELAY 2 RELAY 1
Alarm conditions respectively.
COM
COM
NO

NO
NC
NC

Each output is unsupervised with volt-free changeover


contacts rated at 30V AC/DC, 1 Ampere.
Optional relay cards are available if additional relays
are required.

Base card arrangement – typical.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 18


UK Security Panels Alarmhelp.net

2.4.6 Open Collector Outputs


The Mx-4100, Mx-4200 & Mx-4400 are equipped with
two open collector type outputs that can sink up to
10mA each from the AUX Power Output.
These are fully programmable and can be used to
control external relays.
The connections of the base card are shown in the
diagram opposite.

O/C1 DRIVE

O/C2 DRIVE
AUX + (24V)
AUX + (24V)
No external back-emf diodes are required.

O /C 1 D R IVE
The Mx-4200 & Mx-4400 are equipped with two open O /C 2 D R IVE
collector and six digital programmable outputs via a
O UTP UT 3
10-pin connector – see opposite.
O UTP UT 4
An optional 8-way relay card is available to connect to
this connector. O UTP UT 5

O UTP UT 6

O UTP UT 7

O UTP UT 8

AU X + (2 4 V)

AU X + (2 4 V)

2.4.7 Auxiliary Supply Output


All panels are equipped with an Base Card Connections. A U X – (G N D )
auxiliary 24V DC, 300mA power
A U X + (2 4 V )
supply output. This can be used for
powering ancillary equipment. It is only BAT +
BAT –
BAT +

to be used for powering localised


BAT –
internal equipment.
A U X – (G N D )

A U X + (2 4 V )

FS2 BAT FS1 Supply

Mx-4100 Mx-4200/4400

2.4.8 Switch Inputs


Key switch inputs can be used for changing access level, performing “class change” etc. by changing the “Action”
of these inputs. An optional 8 way input board is also available for this connector.
COMMON
COMMON
I/P 8
I/P 7
I/P 6
I/P 5
I/P 4

I/P 3
I/P 2
I/P 1

DISPLAY PCB

See separate Tech sheets for examples.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 19


UK Security Panels Alarmhelp.net

2.4.9 RS232 Interface


The Mx-4100 is equipped with a non-isolated RS232

GND
I/F Circuit at the bottom left-hand side of the base card.

RX
TX
The Mx4200 & Mx-4400 are equipped with an isolated
RS232 I/F Circuit at the bottom of the base card.
RS232
The terminal block connections are shown opposite.
TX = Transmit Data from the panel, RX = Receive
Data into the panel, GND = Ground Reference.
The RS232 I/F can be used with the RS232 I/F Cable
Kit. This kit consists of the cable and a bulkhead
mounting connector thereby enabling external
connection without opening the door.
Base Card Connections - typical.

The internal RS232 I/F Cable Kit option provides


connections, via a standard 9-way d-type connector,
from the outside of the enclosure.
To install the cable:
1. Remove the cover plate in the bottom face of the
back box.
2. Secure the D-Type Connector in the mounting hole
using the fixing hardware supplied.
3. Plug the end of the cable into the socket header on
the base card.
(Refer to the RS232 Interface Section above for details
of the terminal block signals).
The D-Type connector can be used with:
A PC Cable Kit to connect the panel directly to a PC.
RS232 Cable &
A Modem and Cable Kit for remote PC connection.
Recommended Routing
A Printer Adapter and Cable Kits for connection to a
printer. Typical Internal Arrangement – Mx-4100 shown
Contact your supplier for the relevant part numbers and
order information for option kits.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 20


UK Security Panels Alarmhelp.net

3 Programming
3.1 Introduction

3.1.1 Access Levels


The panel operation is protected from inadvertent and erroneous misuse by means of three access levels. These
levels are as follows:

Level 1 Untrained user


Level 2 Authorised User
Level 3 Commissioning, Service and Maintenance

This document covers the Level 3 functions.


For details on the operation and use of the panel at Levels 1 & 2, refer to User Manual 680-015.

A level 3 password is required to enter the commissioning menus. For details of Passwords, refer to Section
3.3.12.

Level-3 Passwords.
If this number is lost, it is not possible to enter commission mode functions.
Refer to 6.1 for further formation.

3.1.2 Memory Lock


The configuration memory is protected against MEM
LOCK
inadvertent change by means of a memory lock. OPEN
POSITION
Before making any configuration data changes, move CLOSE
J1
the jumper strap to the OPEN position.
MEM
After all changes have been made, move the jumper LOCK
CLOSED
strap back to the CLOSE position to protect the POSITION
memory against inadvertent change. CLOSE
J1

Refer to the diagram opposite for information on the


jumper settings. Typical View – Mx-4100

3.1.3 Navigating through menus


The display will revert to status mode after 60s. Press the ‘Menu’ button to restore the display.

[Commission Menu 1]

LOOPS ZONES EXIT


OUTPUTS TIME/DATE VIEW
Next Menu

When a menu is displayed, use the ÍÏÐÎ buttons to highlight the required menu option and then press the 
button to select it.

Press the ‘Esc’ button from within a menu option to return to the previous menu.
The display can be forced back into status mode by pressing the ‘Esc’ button when at the top level commissioning
menu (or by waiting 60s).

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 21


UK Security Panels Alarmhelp.net

3.1.4 Changing Text Descriptions


Various parameters can have a text description defined. These include loop devices, zones, etc. The zone and
device text descriptions will be shown on the display in the Fire Alarm, Fault and Warning Conditions, etc. to
provide a quick and clear indication of the source of the problem.

To change the text description, first highlight the text description within the appropriate programming option and
then press the  button. The display then changes to show the text entry dialogue screen. For example:

>RESTAURANT <

KEY IN THE REQUIRED TEXT

The method of entering the characters is similar to the method employed on mobile
telephones. The number buttons provide both their appropriate number and several
letters of the alphabet. An example of the keypad is shown opposite. 1 2abc 3 def
For example, Button 2 allows entry of the number 2 and letters A, B and C. 4 ghi 5 jkl 6 mno
When a button is pressed, the number is first shown on the display at the current cursor
position. If the button is pressed again within ½ second, the first character replaces the 7pqrs 8 tuv 9wxyz
number. A further press displays the second available character and so on. After pressing
the button to obtain the required character, wait for 1-second and the character will be Esc 09 Menu
entered and the cursor will move to the next character in the text description.
Pressing another button will immediately enter the previous character and move the
cursor on to the next character.
Use the ÍÎ buttons to move backwards or forwards along the line.
When the text description is as required, press the  button to confirm the change.
If the text has been entered incorrectly, press the ‘Esc’ button to cancel all changes and return to the previous
display.
The following table shows the numbers, characters and symbols assigned to each button on the keypad.

Button 1st Press 2nd Press 3rd Press 4th Press 5th Press
1 1
2 A B C 2
3 D E F 3
4 G H I 4
5 J K L 5
6 M N O 6
7 P Q R S 7
8 T U V 8
9 W X Y Z 9
0 Blank 0

Alternatively, press the ÏÐ buttons to scroll through a list of characters. When the required character is shown,
press the Î button to move on to the next character. The list of characters available and the order of presentation
is as follows:

Blank !“#$%&‘()*+,-./ 0123456789 :;<=>?@ ABCDEFGHIJKLMNOPQRSTUVWXYZ [‘]^_

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 22


UK Security Panels Alarmhelp.net

3.1.5 Numeric data entry

Numbers are entered by moving to the required field, then typing in the required number, followed by the 
button.

If the number is entered incorrectly, press the ‘Esc’ button to restore the previous number.

3.2 Recommended Programming Procedure


• Step 1 – SET-UP, Define General Set-up Information (Phone Numbers, etc.).
• Step 2 – PASSWORDS, Define Level 2 and Level 3 Passwords as required.
• Step 3 – AUTO-LEARN, Let the panel learn the devices on the loop(s).
• Step 4 – VIEW DEVICES, Enter Zone Numbers, Location text and Change Group Assignments if required.
• Step 5 – OUTPUTS, Program Output Groups as required.
• Step 6 – ZONES, Enter Zone Texts as required.

3.3 Level 3 Menu Functions


The following table gives a list of the Level 3 Menu Functions, the sub-functions available within each main
function and a brief description for each function.

Main Menu Sub Menus Comments


Option
3 LOOPS View/Edit View, test and configure the loop devices
Auto Learn Learn the Devices Present on the Loop.
Calibrate Calibrates devices on the loop
6 ZONES -- Configure the Zones.
EXIT -- Cancel Level 3 Access and return to Level 2 Menu Options.
5 OUTPUTS -- Configure the Operating Characteristics of the Output Circuits.
TIME/DATE -- Change the Date and Time Settings.
4 VIEW Fires View Zones and Inputs that are reporting a fire alarm condition.
Faults View Zones and Inputs that are reporting a fault condition.
Alarms View Zones and Inputs that are reporting an alarm condition during test.
Disabled View Zones, Inputs and Outputs that are disabled.
Inputs View the current state of Zones and Inputs.
Outputs View the current operational condition of all output circuits.
Log View the Event Log.
Panel View the operational state, voltage & current loading of the panel I/O.
Network View Network Diagnostics
2 PASSWORDS -- Configure the Level 2 and Level 3 passwords.
PANEL -- Change the default zone assignments and output groups for all panel I/O.
PC-LINK -- Enable the PC Link for transfer of configuration data to and from the panel.
1 SETUP -- Configure General Operating Parameters.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 23


UK Security Panels Alarmhelp.net

3.3.1 Loops
For Multi-loop panels only – On selecting the LOOPS option, the display will prompt for the loop to be viewed /
programmed. E.g. for the Mx4400: -
[Select Loop]

1st-Loop 2nd-Loop 3rd-Loop 4th-Loop

9 9 x x

The list of loops available will be adjusted automatically to show only those loops that have a loop driver card
installed. In the above example, loop drivers are installed in positions 1 and 2.
Press the ÏÐÍÎ buttons to scroll through the list of loops available and then press the  button to select the
loop required.
The display will then show a list of programming options as follows: (Note: On selecting the LOOPS option on
the Mx4100, this display will be shown directly).
[Loop 1]

VIEW/EDIT AUTO LEARN CALIBRATE


DRIVER

3.3.2 Loops - View/Edit


The VIEW/EDIT option shows a list of the devices connected to the loop learnt by the panel. For example:
[Loop 1] More>
Address State Type Value
001.0 Normal CALL POINT 16
002.0 Normal MULTI.SENSOR 28
003.0 Normal ION SMOKE 23
004.0 Normal HEAT 21

The first device on the loop is shown at the top of the list and is highlighted. Press the ÏÐ buttons to scroll
through the list of devices.
Press the ÍÎ buttons to view additional information. The display highlights a particular parameter. To change
the value of this parameter (if not view only), press the  button and appropriate options will be shown on the
display.

3.3.2.1 State
This parameter shows the current operational status of the device. For example, this can show Normal, Fire
Alarm, Device Missing, etc.
This parameter cannot be changed.

3.3.2.2 Type
This parameter shows the type of device learnt by the panel. For example, this can show Call Point, Multi-Sensor,
ION Smoke, Heat, etc.
This parameter cannot be changed.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 24


UK Security Panels Alarmhelp.net

3.3.2.3 Value
This parameter shows the analogue value returned by the device. The number displayed will vary according to the
type of device fitted. A ‘H’ (High) and ‘L’(Low) is shown for logic inputs. This parameter cannot be changed.

3.3.2.4 Zone
This parameter shows to which Zone the device has been assigned. Use the number keys to change the zone
assigned to the device.

3.3.2.5 Device Text


This parameter shows the 26-character location text assigned to this device.
For guidance on how to change the text, refer to Section 3.1.4.

3.3.2.6 Action
This parameter shows the action that will be performed when this device indicates an active (alarm) condition. For
example:
[Loop 1 Devices] <More>
Address Action Sensitivity O/P
001.0 FIRE SIGNAL DEFAULT
002.0 FIRE SIGNAL DEFAULT
003.0 FIRE SIGNAL DEFAULT
004.0 FIRE SIGNAL DEFAULT

Press the  button to change the action assigned to this input device. A pop-up window is then shown on the
display from which an action can be selected.

[Select New Action]


FIRE SIGNAL .
PRE-ALARM
FAULT SIGNAL

Press the ÏÐ buttons to scroll through the list of Actions and then press the  button to confirm the change. The
display reverts to the device list showing the new action assigned to this device. Alternatively, press the ‘Esc’
button to cancel the changes and return to the device list display. The following Actions are available (Additional
actions are available on a PC)

Action Description
Fire Signal A Fire Alarm Condition will be generated whenever the input is active.
Pre-Alarm A Pre-Alarm Condition will be generated whenever the input is active.
Fault Signal A Fault Condition will be generated whenever the input is active.
Security A Security Alert Condition will be generated whenever the input is active.
Record A Record Entry will be stored in the Log whenever the input is active. This will be
hidden from the panel status display.
Create Alarm 1 An “Alarm 1” condition will be generated whenever this input is active.
Create Alarm 2 An “Alarm 2” condition will be generated whenever this input is active.
Create Alarm 3 An “Alarm 3” condition will be generated whenever this input is active.
Key Lock Inhibits front panel controls (Disable, Mute, Reset etc.)
- No Action is assigned to the input.
Control Signal Allows control of Outputs without displaying “Fault” or “Fire” or sounding buzzer

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 25


UK Security Panels Alarmhelp.net

Fire Alarm Conditions are latched.


By default, all other conditions are non-latching.
The action for smoke and certain other detectors is always fire and cannot be changed.

3.3.2.7 Sensitivity
This parameter shows if the device sensitivity is set to it’s “DEFAULT” or “CUSTOM” settings. For example:
[Loop 1 Devices] <More>
Address Sensitivity
001.0 DEFAULT
002.0 DEFAULT
003.0 CUSTOM
004.0 DEFAULT

Press the  button to change the sensitivity assigned to an input device. When selected a new screen displays the
sensitivity settings assigned. For example, with an Apollo Discovery

SENSITIVITY ADJUST MODE (ION SMOKE )

[ Alarm = 55 ]
[ Mode = 3 ][ Pre-Alarm= 45 ]
[ Delay = 5s][ Min.Value= 8 ]
[SAM/SSM]

Press the ÍÏÐÎ buttons to highlight the required menu option and then press the  button to select it. Use the
number buttons to enter the required value. Alternatively, press the ‘Esc’ button to cancel the changes.

The alarm thresholds and delay times can be unique for every device if required.

Always ensure that the values chosen are suitable for the particular installation and that reliable
fire coverage is maintained at all times.

3.3.2.7.1 Mode- Apollo:


This is applicable to Discovery devices only.
The panel fully supports the sensitivity modes within the Discovery devices. Refer to the Apollo technical
documentation for a detailed description and recommended use of these bands.
Different sensitivity modes can be chosen for both day and night periods. This field can be set in the range 1 – 5.

3.3.2.7.2 Mode- Hochiki:


This is applicable to Multi-sensor devices only:
• Mode 0: (Default) Combined optical & heat detectors
• Mode 1: Optical mode only
• Mode 2: Heat mode only

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 26


UK Security Panels Alarmhelp.net

3.3.2.7.3 Delay
The value in this field defines the delay from detecting an alarm to entering the alarm condition. The delay time
can be changed in 1-second increments.

3.3.2.7.4 Alarm- Apollo


The Alarm Level is the level of the analogue value returned by the detector at which the panel will enter a Fire
Alarm Condition. The default value is 55. Setting the value higher will mean that more smoke / higher
temperature is required before the panel will enter the alarm condition. Setting the value lower will mean that less
smoke / temperature is required before the panel will enter the fire alarm condition.
The alarm level cannot be set outside the safe operating limits defined for the particular device.
Apollo Discovery devices always use a value of 55.

3.3.2.7.5 Alarm- Hochiki


The Alarm Level of the Analogue value returned by the detector at which the panel will enter a fire condition is
set to Hochiki Alarm thresholds (expressed as a % value) This is normally 3% for Multi-sensor & Optical devices.
Refer to Hochiki Data Sheets for further information.

3.3.2.7.6 Pre-Alarm
The Pre-Alarm Level is the level of the analogue value returned by the detector at which the panel will enter a
pre-alarm condition.

3.3.2.7.7 Minimum Value


If the detector analogue output falls below the minimum value programmed, the panel will enter a fault warning
condition. This parameter is normally left at a value of 8 for Apollo detectors and 0 for Hochiki.

3.3.2.7.8 Special Sensitivity Mode SSM/Clock


In addition to the “SENSITIVITY ADJUST MODE”, a device can also run in a “SPECIAL SENSITIVITY
MODE” (SSM) under time-clock control.

The Mx4100 supports 3 independent, 7-day time clocks.


The Mx4200 supports 10 independent, 7-day time clocks.
The Mx4400 supports 10 independent, 7-day time clocks.

With the SAM/SSM Option highlighted, press the  button to view the Special Sensitivity Mode settings. For
example:
SPECIAL SENSITIVITY MODE (MULTI.SENSOR)

[SSM/Clock = 2 ][ Alarm = 55 ]
[ Mode = 5 ][ Pre-Alarm= 40 ]
[ Delay = 5s][ Min.Value= 8 ]
[SAM/SSM]

In the above example the panel is using special sensitivity mode 2 (and time clock number 2). Enter “0” in the
SSM/Clock field to cancel Special Sensitivity Mode.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 27


UK Security Panels Alarmhelp.net
A number must be entered in the SSM/Clock field to select the appropriate SSM number and time clock. To view
the time clock settings, highlight the SSM/Clock field, and press the  button.
For example:
[Time Clock 2]
DAY ON -> OFF ON -> OFF
MON 00:00 00:00 19:00 00:00
TUE 00:00 06:30 00:00 00:00
WED 00:00 00:00 00:00 00:00
THU 00:00 00:00 00:00 00:00

The panel supports two independent times for each day of the week during which the SSM mode will be switched
on (i.e. during which the Special Sensitivity Mode settings are active)
In the above example the SSM will be active between 19:00 on Monday and 06:30 on Tuesday.
Press the ÍÏÐÎ buttons to select the appropriate time field and use the number buttons to enter the required
times. Press the ‘Esc’ button to return to the previous menu display.
Every type of device (the device type is shown in the top, right hand corner) supports unique SSM settings for
each SSM/Clock number. In the previous example the Special Sensitivity Mode settings have been defined for a
Multi-Sensor that is using SSM/Clock number 2. If other Multi-sensors on the same panel also require the same
settings, then you only need to set them to SSM/Clock 2. If instead another Multi-Sensor requires a different
setting, use a different SSM/Clock number.

3.3.2.8 O/P Group


The Output Group assigned to the Sounder or Relay Devices determines the manner in which the outputs will
operate when a fire alarm or other programmed condition occurs.
For example:
[Loop 1 Devices] <More>
Address O/P Group
020.0 199
021.0 199
022.0 199
023.0 199

Use the number buttons to change the value of the O/P Group setting.
By default, all Loop Output devices are assigned to Output Group 199.
For detailed information and guidance on the programming and use of Output Groups, refer to Section 3.3.8.

3.3.2.9 Additional Info


This parameter shows additional information, if available, for this device. For example, the following display
shows the Apollo detector series types:
[Loop 1 Devices] <More>
Address Additional Info
001.0 Disco
002.0 XP95
003.0 Disco
004.0 Disco

For further information on this option, refer to Appendix 5 – Apollo Information and Appendix 6 – Hochiki Esp
Information.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 28


UK Security Panels Alarmhelp.net

3.3.2.10 Detector Testing


Individual detectors can be tested to check the chamber response and illuminate the detector LED.
While the address field is highlighted, press the ÏÐ buttons to scroll through the list of devices to the desired
detector (or key in the address, and then press the  button).
A menu will appear to confirm that you want “Test This Detector”.
Press the  button to confirm or press the ‘Esc’ button to cancel.
Once selected, commands are sent to the detector to turn on the detector LED and put the chamber into test. The
“Test” LED lights up and the panel display returns to the list of devices.
After a few seconds the analogue signal will be seen to rise. If the detector is then left in the test condition, the
Detector State will change to a “Fire Test” status.
The test is cancelled as soon as the display is scrolled up or down or when the ‘View Devices’ option is exited.

3.3.3 Loops - Auto Learn

3.3.3.1 Normal Procedure / Initial learn


The panel can automatically learn the presence or absence of devices at all addresses connected to the loop. When
the Auto Learn option is selected, the panel starts searching each address on the loop to locate and find all of the
devices connected. A display is shown to indicate the progress of this procedure.
For example:
[Auto Learn Loop 1] HOCHIKI

Address 15 Devices found = 3

When all addresses have been searched, the panel displays a summary screen showing the quantity of devices
found for each type of device.
For example:
[Auto Learn Loop 1] HOCHIKI

Address 127 Devices found = 4


OPT ION MUL TMP MCP SCC I/O ZMU OTHERS
0 1 1 1 1 0 0 0 0

This summary provides a quick check to ensure that the panel has found all of the devices that should be
connected to the loop.
Press the ‘Esc’ button to return to the main Loops Menu.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 29


UK Security Panels Alarmhelp.net

3.3.3.2 Procedure if the Panel finds Devices Missing


When the panel cannot communicate with a device previously programmed into the panel, the Auto Learn process
is suspended and the display shows a pop-up window with options. For example:

KEEP THIS DEVICE .


DELETE THIS DEVICE
KEEP ALL MISSING
DELETE ALL MISSING
! Address 002 DEVICE MISSING

If the missing device is kept (or all missing devices are kept), the panel remembers the programming for these
devices. The panel will report a fault condition until such time as the missing devices are reconnected.
If the missing device is deleted (or all missing devices are deleted), the panel clears all previous programming for
these devices. This includes any sensitivity threshold changes, text assignments, zone assignment, action, etc.
Press the ÏÐ buttons to highlight the required menu option and then press the  button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is deleted and another missing device is subsequently registered, the display will once again
show the pop-up window to keep or delete this device.

3.3.3.3 Procedure if the Panel finds Devices Added


When the panel finds a device not previously learnt and programmed in the panel, the Auto Learn process is
suspended and the display shows a pop-up window with options. For example:

ACCEPT NEW DEVICE .


REJECT NEW DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 NEW DEVICE

If the new device is accepted (or all new devices are accepted), the panel will configure the memory to register
these devices. All data will be configured to initial settings for sensitivity threshold changes, text assignments,
zone assignment, action, etc. for these devices.
If the new device is rejected (or all new devices are rejected), the panel clears all programming for these devices
and will not attempt to communicate with the devices at these addresses.
Press the ÏÐ buttons to highlight the required menu option and then press the  button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is accepted / rejected and another new device is subsequently registered, the display will once
again show the pop-up window to accept or reject this device.

3.3.3.4 Procedure if the Panel finds Devices Changed


When the panel finds a new type of device installed at an address previously learnt and programmed in the panel,
the Auto Learn process is suspended and the display shows a pop-up window with options. For example:

ACCEPT NEW DEVICE .


KEEP OLD DEVICE
ACCEPT ALL NEW DEVICES
REJECT ALL NEW DEVICES
! Address 002 TYPE CHANGE

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 30


UK Security Panels Alarmhelp.net
This situation could arise for example if a heat detector has been installed in place of an optical smoke detector.
If the new device type is accepted (or all new device types are accepted), the panel will configure the memory to
register these devices. All data will be configured to initial settings for sensitivity threshold changes, text
assignments, zone assignment, action, etc. for these devices.
If the new device type is rejected (or all new device types are rejected), the panel remembers the programming for
the original devices. The panel will report a fault condition until such time as the correct device types are
reconnected.
Press the ÏÐ buttons to highlight the required menu option and then press the  button to confirm. The pop-up
window will disappear and the panel will continue with the auto learn process.
If a single device is accepted / rejected and another new device type is subsequently registered, the display will
once again show the pop-up window to accept or reject this device.

3.3.4 Loop – Calibrate


Calibrates Hochiki devices – Note this can take up to several minutes if many detectors & sounder bases are
installed.

3.3.5 Loop – Driver


Displays loop output and input voltages and loop loading.
A diagnostic display with automatic scanning of the loop to find devices with minimum and maximum
communication pulse heights is available (for loop drivers manufactured after October 2002).

3.3.6 Zones
The Commission Zones option lists all the zones in use by the panel and allows the zone text description to be
changed.
[Commission Zones]
Zone Location
0001 BASEMENT WEST
0002 RECEPTION
0015 EAST WING
0018 TOWER BLOCK

To change the location text assigned to the Zone, press the  button when the Zone Location Text is highlighted.
Refer to Section 3.1.4 for guidance on how to change text descriptions.
To select a different zone, either use the scroll up/down keys, or just type in the number of the required zone,
followed by the  button. Note that only zones in use are displayed.

3.3.7 Exit
To exit the Commission Mode and return the panel to normal operation (ie level 2), select the “Exit” option. The
display will prompt for confirmation of the level 3 password. For example:
[Commission Menu 1]
Please Enter Your Password

Next Menu

If the password is incorrect (this will be indicated) or if the password is not entered within 5-seconds, the display
will revert to the Commission Level Menu and level-2 will not be entered.
After commissioning, the panel must always be returned to level 2 (or level 1) to give normal fire coverage.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 31


UK Security Panels Alarmhelp.net

3.3.8 Outputs
The “Cause and Effect” programming is a schedule of actions that will turn on one or more outputs dependant on
a set of input events.

The Outputs Option provides the means to create simple or complex “cause and effect” programming within the
panel. Delays can be introduced to allow a phased evacuation of a building (Note this is different to an
“Investigation Delay” which is detailed in section 3.3.9) .
This section describes the settings and options in detail for each parameter. Refer to Appendix 4 – Cause and
Effect Programming Example for a description of how to program a typical requirement.
More complex “Cause and Effect” programming may be undertaken using the PC Configuration tool.

When the OUTPUTS Option is selected, the display shows the cause and effect programming for Output Group 1.
For example:

[Output Group 1] [ 3.9% Mem used]


ZONE GROUP CAUSE STYLE=Delay->MODE
1 1 ANY FIRE 00 - On
2 1 ANY FIRE 00 - On
3 1 ANY FIRE 00 - On
4 1 ANY FIRE 00 - On

To simplify the cause & effect programming, one or more outputs that will respond in the same way when the
same set of input events occurs can be grouped together. This association of outputs is called an Output Group.
The panel can support up to 200 of these Output Groups.

To select a different Output Group, highlight any group number and then enter the number of the output group
required using the number buttons. The display always shows the Output Group is shown in the top left corner.
Press the ÏÐ buttons to scroll through the list of zones.
Press theÍÎ buttons to select the fields for a particular zone.
Press the  button to select a particular field option to change its setting.

3.3.8.1 Default Output Settings


On initial installation, or after clearing the configuration memory, all outputs are assigned to specific Output
Groups and will turn on immediately a single fire alarm occurs in any zone (any fault condition for the fault
relay). The default assignments are as follows:

Output Device Output Group Cause and Effect


On-board Sounder A 1 Any fire in any zone – no delay
On-board Sounder B 2 Any fire in any zone – no delay
On-board Sounder C * 3 Any fire in any zone – no delay
On-board Sounder D* 4 Any fire in any zone – no delay
On-board Relay 1 200 Any fault in any zone – no delay
On-board Relay 2 199 Any fire in any zone – no delay
On-board Open Collectors 199 Any fire in any zone – no delay
All Loop Output Devices 199 Any fire in any zone – no delay
* Mx4400 only

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 32


UK Security Panels Alarmhelp.net

3.3.8.2 Cause
Each Output Group can be programmed to respond in a unique way to events from each individual zone. An input
event may be a fire alarm condition or it may be a fault, disablement or other condition. A combination of criteria
may also be applied to each zone.

The Cause field determines what type of input event (or a combination of input events) will generate an output
response for the selected input zone.

To inspect or change the Cause, press the Î button to highlight the cause option. For example:
[Output Group 1] [ 3.9% Mem used]
ZONE CAUSE STYLE=Delay->MODE Wait
1 ANY FIRE 00 - On
2 ANY FIRE+ 00 - On
3 ANY FIRE 00 - On
4 ANY FIRE 00 - On

Press the  button to change the setting and a pop-up window will appear showing the options available. For
example:

[FIRE ] [D/K FIRE] [ALARM][PRE-ALARM]


 - - -
[FAULT] [I/P DISABLE][TEST ][ CONTROL ]
- - - -

Press theÍÏÐÎ buttons to highlight the required menu option and then press the  to change its setting. An
input action type is enabled when a ‘’ is shown beneath the option. It is permitted to select multiple input types
in which case a combination of input events will result in an output action. If there is a combination of input
events, the CAUSE display above shows this extended programming by adding a ‘+’ to the text. For example,
Zone 2 above shows that the basic event is ANY FIRE + other criteria.
Press the ‘Esc’ button to return to the previous display.

The definition for each cause is as follows:


Fire Any single fire.
Double Knock (D/K) Coincidence of 2 or more fire detectors or a single manual call point in the same zone.
Alarm Activation of an input device programmed with an ‘Alarm’ action.
Pre-Alarm A device in a pre-alarm condition.
Fault Any device entering a fault condition.
Input Disabled Whenever an input device is disabled.
Output Disabled Whenever an output device / circuit is disabled.

Coincidence Detection.

The operation of the Coincidence Detection (Double Knock) feature is on a per zone
basis.
Section 7.12

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 33


UK Security Panels Alarmhelp.net

3.3.8.3 Style
The way in which an output turns on in response to a particular input event can be programmed. For example, an
output may turn on immediately, it may turn on after a delay or it may pulse for a set time and then turn on. This
method of operation is called a Style. A style may have up to three different methods of operation. For example,
DelayÎ Mode, WaitÎ Mode, WaitÎ Mode.

Style 00 is fixed to turn on immediately an input event occurs.


Style 01 defaults to pulse immediately an input event occurs.
Styles 02 to 20 are programmable (02 to 10 on Mx4100).

Press theÎ button to step on to the style field. Change the setting using number entry to select the required output
style. If the style is already programmed elsewhere, the relevant style parameters are automatically entered into
the appropriate fields.

3.3.8.3.1 Delay
The delay field is the time from qualification of the input event to something happening at the output. The delay
time can be set in intervals of 1 second up to a maximum of 250 seconds.
Press theÎ button to step on to the delay field and change the setting using number entry.

3.3.8.3.2 Mode
The mode field defines the method of operation of the output when it is first activated. This can be ON or PULSE.
Press theÎ button to step on to the delay field and change the setting using the  button.

3.3.8.3.3 Wait
The wait field is the time from first activation of the output to the next operational condition (mode) of the output.
For example, the output could initially be delayed for 20 seconds and turn on in a pulsing mode. After a wait of a
further 30 seconds it can be programmed to turn on differently such as ON. The wait time can be set in intervals
of 1 second up to a maximum of 250 seconds.
Press theÎ button to step on to the wait field and change the setting using number entry.

3.3.8.4 Copying Output Settings to Multiple Zones


To save time in the entry of similar Output Group Settings for each zone, it is possible to copy information
programmed for a particular zone to subsequent zones.
Press the Í button to highlight the required zone number and then press the  button. The display shows a pop-
up window prompting for the number of the zone to which to copy the information.
Use the number entry to select the required zone number. The Output Group programming for all of the zones
from the currently selected zone to the zone number entered will be programmed with the same information as the
currently selected zone.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 34


UK Security Panels Alarmhelp.net

3.3.9 Investigation Delays


In addition to the “Cause and Effect” programming described above, the panels also support an “Investigation
Delay Mode” which allows time for a building supervisor to investigate fire signals before turning outputs on.
This mode can only be configured from the PC software.
There are two parts to this delay. The first stage is set relatively short. If the building supervisor does not
acknowledge the fire signal within the first stage, the delayed outputs will turn on. The second stage gives a
longer period to investigate the fire signal. This delay can be cancelled at any time by pressing the EVACUATE
button, or any nominated input devices (by default, all call points cancel this mode).
Each input and output device can be individually programmed to use the investigation delay from the PC
configuration software, together with the times appropriate to each stage of the delay. The user manual gives
details of how the building occupier can turn the investigation delay feature on or off.

Delays to Outputs.

It must be possible to override the operation of any delays at Level 1. Refer to Section
3.3.9.1 for information on overriding delays.
Section 7.11
For compliance, the maximum total delay permitted is 10 minutes.

3.3.9.1 Overriding Delays at Level 1


A facility to override any programmed delays and immediately activate the sounder circuits should be provided at
Level 1. It is possible to override the delay using the panel controls (see the user manual for details). This can also
be achieved from an input device that is programmed to turn on all outputs immediately..

3.3.10 Time and Date


This function allows the time and date in the panel to be changed. On entry to the function, the display shows the
current time and date with confirmation of the day of the week on the bottom line. For example:
[SET TIME/DATE]

TIME = 15:28
DATE = 15/04/02 MON 15 APR 2002

To change the settings, use the ÏÐ buttons to highlight the required option. Directly enter the new time or date
using the number buttons. As soon as a number button is pressed, the display will clear the current setting and
show the new value as it is entered. For example:

[SET TIME/DATE]

TIME = 1-:--
DATE = 15/04/02 MON 15 APR 2002

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 35


UK Security Panels Alarmhelp.net

3.3.11 View Options


The View Menu Options are identical to those available during Level-2 operation.
For further information on the View Options and the information that is presented, refer to the User Manual
(Document No. 680-015).

3.3.12 Passwords
The panel provides up to 10 User Level-2 passwords and 2 Level-3 passwords. All of the passwords can be
changed.
On entry to the function, the display shows a list of the passwords. For example:
Password Access level User ID
15633 2 01
9988 2 02
13344 2 03
10000 2 04
10000 2 05

To change a password, use the ÏÐ buttons to highlight the required password and then enter the new password
using the number buttons. When the password is correct, press the  button to confirm.

Level-3 Passwords.
Care should be taken when changing the Level-3 password. If this new number is lost, it is not
possible to enter commission mode functions.
Refer to 6.1 for further information.

The factory default level 3 password is 7654

3.3.13 Panel
The Panel Menu Option shows a list of the internal panel circuits and provides a means to change their default
configuration settings.
Only use this menu if changes are to be made to the default settings for the panel’s internal circuits. Use the
VIEW-PANEL Menu Option to view the state and operating condition of each circuit.
The display shows for example:
More>
Address State Type Value
>001.0 Normal VOLTAGE 5.6V
001.1 Normal VOLTAGE 5.6V
002.0 Normal CURRENT 0mA
002.1 Normal CURRENT 0mA

Use the ÏÐ buttons to scroll through the circuits. Use the ÍÎ buttons to view additional information. The zone
and Output Group Assignments can be modified if required.
For further information on the View – Panel Options and the information that is presented, refer to the User
Manual (Document No. 680-015).

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 36


UK Security Panels Alarmhelp.net

3.3.14 PC Config
The PC Link Option enables the connection of the PC Configuration Tool for retrieving configuration data from
the panel and programming configuration data from a file on the PC.
For further information, refer to the Manual supplied with the PC Configuration Tool.

3.3.15 Setup
The Setup Options Menu enables the configuration of panel generic operating parameters. When the option is
selected, the display shows a list of the available parameters. For example:
[Setup]

THIS NETWORK NODE : . 0 .


NEXT NETWORK NODE : 0
PANEL ZONE : 100
SERVICE NUMBER : 01234 567890

Use the ÏÐ buttons to scroll through the list of options. The following will then be shown:
[Setup]

SERVICE DUE DATE : 01 JAN 2011 10:00


TRACE LOGGING MODE : STANDARD More>
DETECTOR BLINKING : NONE
COMPANY LCD LOGO : 

3.3.15.1 Network
This Network node is set to 0 for a standard non- networked panel. For panels in a networked application please
refer to the Network document, reference: 680-027.

3.3.15.2 Panel Zone


By default all the panel inputs are assigned to the Panel Zone. Alternatively the PC configuration program allows
individual inputs to have different zones if required.

3.3.15.3 Service Number


The Service Number is the telephone number that is shown on the status display whenever a fault condition
occurs. To change the number, press the  button when the option is highlighted. The number is entered using the
text entry facility, refer to Section 3.1.4 for guidance on how to enter text.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 37


UK Security Panels Alarmhelp.net

3.3.15.4 Service Due Date


The next service (over)due date can be entered into the panel memory. When this date is reached, the panel will
enter a fault condition to alert the site operator that a service visit is overdue. To change the due date, press the 
button when the option is highlighted. The display prompts for entry of the next service date. For example:
[NEXT SERVICE DUE]

TIME = 12:00
DATE = 24/04/02

Use the ÏÐ buttons to select between the time and date. Use the number buttons to enter the required time or
date.
As soon as a new service date is entered, the panel will cancel any Service Due Fault condition.

3.3.15.5 Trace Logging Mode


The Trace Logging Option determines what type of information and to what level is stored in the Event Log.
There are three options:
STANDARD = the normal operating mode logging fire alarm, fault and warning conditions as they occur.
STANDARD + = an extended version of the standard operating mode where the removal of fault and warning
conditions are also logged.
DIAGNOSTIC = a full diagnostic trace of all conditions with greater depth to aid diagnosis of fault conditions.
To change the option, press the  button.
To erase the event log, press the Î button to view the additional command option as follows:
[Setup]

TRACE LOGGING MODE : Wipe Event Log


DETECTOR BLINKING :
COMPANY LCD LOGO :
PROGRAM ID :

Press the  button and the display will show that the event log is being erased by display the message
“WORKING…”. After the event log is erased, the display reverts to the Set-up Options screen.

3.3.15.6 Detector Blinking


The Detector Blinking option determines whether the LED indicators on the devices will blink whenever the
panel polls the device. To change the operation, press the  button. The display presents a list of options. For
example:
[Setup]
INDIVIDUAL
ALL
NONE

Use the ÏÐ buttons to scroll through the list of options and press the  button to confirm the selection.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 38


UK Security Panels Alarmhelp.net
The device LED indicators will not blink if NONE is chosen or will blink if ALL is chosen. Note that only certain
devices, such as Apollo Discovery, support this feature.
If a device, such as a Discovery device, is changed it may be necessary to select and reconfirm the blinking
command so that the new device will blink its LED.
The INDIVIDUAL option should be chosen when it is required that only certain devices should blink their LED.
The devices that shall blink their LED can only be programmed using the PC Configuration Tool.

3.3.15.7 Company LCD Logo


This parameter determines whether the Company Logo is shown on the display during normal operation. To
change the setting, press the  button. The status changes from  to X and vice versa.

3.3.15.8 Program ID
The display shows the part number and version of the software installed in the panel. Press the Î button to see
the program checksum (8 digits)

3.3.15.9 Config Data


The Config Data option shows the loop protocol selected and the checksum for the configuration data. A note of
this number can be taken and then checked on the next service visit to see if any changes have been made to the
configuration data.
In addition, there is an option to erase the Config Data.
To view the Config Data Checksum, press the Î button. The display then shows:
[Setup]

CONFIG DATA :APOLLO More>

To change the protocol, press the  button. A pop up window is shown with the following options

. KEEP PROTOCOL .
! CHANGE LOOP PROTOCOL !

Use the ÏÐ buttons to select the required options and press the  button to confirm the selection.
Selecting “CHANGE LOOP PROTOCOL” will toggle to the alternative loop protocol available (ie:
Apollo/Hochiki)

Changing between protocols will automatically erase all loop devices from the configuration
memory.
Perform an “Auto-Learn” or use the PC Config Tool to re-define the devices connected to the
loop.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 39


UK Security Panels Alarmhelp.net

4 EN54 Optional Features


In addition to the mandatory requirements of EN54 Part 2, the Control and Inidcating
Equipment (C.I.E) supports the following optional features :-

Fault Signals from Points.

The C.I.E is able to receive and process fault signals from points. These are indicated
on a per zone basis. Refer to the User Manual for further information.
Section 8.3

Outputs to Fire Alarm Devices.

The C.I.E has provision for connection to Fire Alarm Devices. It is possible to Silence
and Resound the alarms at Level 2. Refer to the User Manual for further information.
Section 7.8

Delays to Outputs.

The C.I.E has provision for Output and Investigation Delays. Refer to Section 3.3.8
for further information
Section 7.11

Coincidence Detection.

The C.I.E has provision for Coincidence Detection. Refer to Section 3.3.8 for further
information.
Section 7.12

Disablement of Points.

The C.I.E has provision for enabling and disabling signals from points. Refer to the
User Manual for further information.
Section 9.5

Test Condition.

The C.I.E has provision for testing the installation on a per zone basis. Refer to the
User Manual for further information.
Section 10

Standardised Input/Output interface

Standardised I/O interfaces are supported over the Ad-Net Network.


Section 11

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 40


UK Security Panels Alarmhelp.net

5 Service and Maintenance


5.1 Maintenance Schedule
This equipment sould be maintained in accordance with the regulations and codes appropriate to the country and
location of installation. The following is recommended if no other regulations apply.

5.1.1 Daily Actions


The site operator / user should perform the following checks and actions:
a) The panel indicates normal operation. If any faults exist, these should be recorded in a logbook.
b) Any recorded faults have received attention and have been signed off.

5.1.2 Monthly Actions


The site operator / user should perform the following checks and actions:
a) Any stand-by generators should be started and fuel levels checked.
b) Operate at least one call point or detector (from different zones each month) and check that the panel enters a
fire alarm condition and that the appropriate / programmed alarm or warning devices are sounded / operated.
Where permissible, this should include any links to the fire brigade or remote centre.
c) Check that all outstanding faults have been recorded and have received attention.

5.1.3 Quarterly Actions


The service / maintenance contractor should perform the following checks and actions:
a) Check that all entries in the logbook have been addressed, check the event log in the panel and take the
necessary remedial actions.
b) Visually inspect the panel for any moisture ingress or other deterioration, check all battery connections and
test / check the alarm, fault and other functions of the panel operation.
c) Ascertain if any building or structural alterations have been carried out that would affect the siting of call
points or detectors. If so, perform a visual inspection.
d) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.

5.1.4 Annual Actions


The service / maintenance contractor should perform the following checks and actions:
a) Perform the checks as recommended above in the daily, monthly and quarterly schedules.
b) Perform a complete “Walk Test” of the system to check that each call point and detector is operating to its
manufacturers’ specification.
c) Visually inspect all cable fittings. Check that the equipment is undamaged and that the conditions of
installation have not changed such that they fall outside of the equipment specifications.
d) Inspect and test all batteries and replace as required – refer to Section 5.2 for recommended replacement
schedule.
e) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 41


UK Security Panels Alarmhelp.net

5.2 Replacement of Components


In general, all of the components parts used in the construction of the panel have been selected for long life and
reliability.
However, certain components may require to be changed on a regular service basis. The details of these are as
follows:

5.2.1 Batteries
For battery installation, see section 2.4.2
Respect the Environment.
Batteries must be disposed of responsibly and in accordance with any local regulations.

5.2.1.1 Standby Batteries


Expected Life - 3-5 years at an ambient temperature of 20°C
Replacement Schedule - As above. However, note that the expected battery life is shortened
by increase in ambient temperature. The life reduces by 50% for
every 10°C rise above ambient. Refer to battery manufacturer for
further information.
Manufacturer / Part Numbers - YUASA POWERSONIC
4AH NP4-12 5AH PS-1250-F1
7AH NP7-12 7AH PS-1270
12AH NP12-12 12AH PS-12100-F1
17AH NP18-12 18AH PS-12180-NB
24AH NP24-12B 26AH PS-12260-NB
Batteries connected in parallel 48AH (2 x NP24-12B) 48AH (2 x PS-1260-NB)*
*Note rated as 24AH/battery
For optimum performance and charge retention, Yuasa recommend that batteries are ‘top-charged’
STOP prior to installation.
For batteries up to 6 months old from date of manufacture, charge at 2.4V per cell (i.e. 14.4V per
battery) for 20 hours prior to installing the batteries.
It is not recommended to use batteries that are older than 6 months from the date of manufacture on
a new installation.
It is quite normal for lead-acid batteries to vent hydrogen when being charged.
The panel is adequately ventilated to dissipate this hydrogen. DO NOT seal the enclosure or install
in a sealed enclosure or cavity.

5.2.1.2 Lithium Battery

WARNING – A lithium battery is used for data retention and for the real time clock.
Replace only with the same type or authorised equivalent. This battery is not rechargeable.

Expected Shelf Life - > 10 years


Replacement Schedule - 10 years for panels in continuous service
10 years for spares (i.e. when the panel / board is not powered)
Replace if the battery voltage falls below 2.6 volts.
Manufacturer / Part Number - CR2032

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 42


UK Security Panels Alarmhelp.net

5.2.2 Liquid Crystal Display


Expected Life - > 10 years
Replacement Schedule - When the display becomes difficult to read. The display contrast will
gradually fade with time.
Manufacturer / Part Number - Replace the complete display / keyboard assembly. Spare part
number MXS 004.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 43


UK Security Panels Alarmhelp.net

6 Appendices
6.1 Appendix 1 – Forgotten Level 3 Password

Should the Level-3 password be forgotten, contact Customer Support to obtain a temporary permit number to
regain access to the panel programming functions.
Customer Support will require a decryption key displayed by the panel. To obtain this number, attempt to gain
access to the Level-3 Programming Functions entering “1” when prompted for the password. As soon as the
“Password Invalid” message is shown, press the “0” button and the display will show a decryption key. Make a
note of the first part of this number.
For example:
[Level 2 Menu]

Please Enter Your Password


214728378

Customer Support will provide a temporary permit number that you can enter when prompted for the Level-3
password. As soon as access has been regained to the Level-3 Programming Functions, select the Passwords
Menu Option and check / change the Level-3 password. (Refer to Section 3.3.12 for further information).

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 44


UK Security Panels Alarmhelp.net

6.2 Appendix 2 – Recommended Cables

Detector Loop & Sounder Circuits

Manufacturer Cable Type


AEI Firetec Multicore Ref. F1C1 (1.0mm2)
AEI Firetec Multicore Ref. F1C1.5 (1.5mm2)
AEI Firetec Multicore Ref. F1C2.5 (2.5mm2)
AEI Firetec Armoured Ref. F1C1 (1.0mm2)
AEI Firetec Armoured Ref. F1C1.5 (1.5mm2)
AEI Firetec Armoured Ref. F1C2.5 (2.5mm2)
AEI Mineral Insulated Copper Cable (1.0mm2)
AEI Mineral Insulated Copper Cable (1.5mm2)
AEI Mineral Insulated Copper Cable (2.5mm2)
BICC Mineral Insulated Twin Twisted CCM2T1RG (1.0mm2)
BICC Mineral Insulated Twin Twisted CCM2T1.5RG (1.5mm2)
CALFLEX Calflam CWZ (2.5mm2)
DRAKA Firetuf (OHLS) FTZ (1.0mm2)
DRAKA Firetuf (OHLS) FTZ (2.5mm2)
HUBER & SUHNER Radox FRBS/M1x2x1.5 (1.5mm2)
HUBER & SUHNER Radox FRBS/M1x2x2.5 (2.5mm2)
PIRELLI FP200 Gold (1.0mm2)
PIRELLI FP200 Gold (1.5mm2)
PIRELLI FP200 Gold (2.5mm2)

With the above cables, loops can be up to 2Km in length, however care must be taken when designing the system
to take into account the maximum loop loading. The voltage drop (load current x cable resistance) over the cable
always needs to be taken into account to ensure the devices receive an adequate supply voltage ( refer to the
Apollo/ Hochiki data sheets and LoopCalculators for further information on calculating loop loading, cable cross
sectional area and loop distance).

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 45


UK Security Panels Alarmhelp.net

6.3 Appendix 3 – Battery Standby Calculation Chart

Use the following charts and associated notes to calculate the size of the batteries required to ensure operation of
the installation in the event of AC Mains power failure.

6.3.1 Mx-4100
Quiescent Load Fire Alarm Load
Equipment I (A) x Total I (A) x Total
Mx-4100 0.115 1.0 = 0.115 0.225 1.0 = 0.225
Auxiliary Supply Output 1.0 = 1.0 =
1 2
Sensor / Loop Current 1.25 = 1.25 =
Sounder Output A 1.0 =
Sounder Output B 1.0 =
Total ΣQuiescent Load ΣAlarm Load
x 24 hr = AHr x 0.5 hr = AHr
§ (carry forward) + Ahr
Total Load (Quiescent + Alarm) = AHr
x 1.23 (Battery Derating factor) = AHr

1
Use the detector manufacturers’ technical information to calculate the load on the loop for both the quiescent
condition and fire alarm condition for all loop devices. By default, a maximum of 5 detector / call point LED
indicators will be turned on in a fire alarm condition. (This number can be changed via the PC Programming
Tool).
2
The calculated loop loading must be multiplied by a factor of 1.25 to calculate the actual current draw from the
batteries. This is to take into account voltage conversion and conversion efficiency in generating the supply for
the loop.
3
The total load calculated must be multiplied by a derating factor of 1.2 to allow for changes in battery efficiency
over time.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 46


UK Security Panels Alarmhelp.net

6.3.2 Mx-4400 & Mx-4200


Quiescent Load Fire Alarm Load
Equipment I (A) x Total I (A) x Total
Mx-4400/Mx4200 0.083 1.0 = 0.083 0.178 1.0 = 0.178
Auxiliary Supply Output 1.0 = 1.0 =
Loop Driver 0.042 1.0 = 0.042 1.0 =
1
Loop 1 2
Sensor / Loop Current 1.25 = 1.25 =
Loop Driver 0.042 1.0 = 0.042 1.0 =
Loop 2
Sensor / Loop Current 1.25 = 1.25 =
Loop Driver 0.042 1.0 = 0.042 1.0 =
Loop 3*
Sensor / Loop Current 1.25 = 1.25 =
Loop Driver 0.042 1.0 = 0.042 1.0 =
Loop 4*
Sensor / Loop Current 1.25 = 1.25 =
Sounder Output A 1.0 =
Sounder Output B 1.0 =
Sounder Output C* 1.0 =
Sounder Output D* 1.0 =
Total ΣQuiescent Load ΣAlarm Load
x 24 hr = AHr x 0.5 hr = AHr
§ (carry forward) + Ahr
Total Load (Quiescent + Alarm) = AHr
3
x 1.2 (Battery Derating factor) = AHr

Notes: * Only used on the Mx-4400

1
Use the detector manufacturers’ technical information to calculate the load on the loop for both the quiescent
condition and fire alarm condition for all loop devices. By default, a maximum of 5 detector / call point LED
indicators will be turned on in a fire alarm condition. (This number can be changed via the PC Programming
Tool).
2
The calculated loop loading must be multiplied by a factor of 1.25 to calculate the actual current draw from the
batteries. This is to take into account voltage conversion and conversion efficiency in generating the supply for
the loop.
3
The total load calculated must be multiplied by a derating factor of 1.2 to allow for changes in battery efficiency
over time.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 47


UK Security Panels Alarmhelp.net

6.4 Appendix 4 – Cause and Effect Programming Example

6.4.1 Introduction
By default, all sounders and output devices will turn on immediately as soon as a fire is detected anywhere in the
system. For example:
Cause Effect
Any Fire, Anywhere. Î ALL Output Devices will Turn ON

Quite often an installation will require a more complex “Cause and Effect” solution. Consider a multiple story
building where phased evacuation is required when a fire occurs on a particular floor. For example:
Cause Effect
Any Fire on Floor 7 Î Sounders on Floor 6 will DELAY for 30 seconds, then start
(From Zones 22, 23 or 24) PULSING. After 2 minutes turn ON
Î Sounders on Floor 7 will Turn ON
Î Sounders on Floor 8 will DELAY for 30 seconds, then start
PULSING. After 2 minutes turn ON

6.4.2 Output Groups


There may be several sounders on each floor. These can be grouped together using the Output Groups so that a
single group number can easily reference all sounders on a particular floor in the panel. For example:
Sounders Output Group
Assign All Sounders of Floor 6 Î Output Group 6
Assign All Sounders of Floor 7 Î Output Group 7
Assign All Sounders of Floor 8 Î Output Group 8

Refer to Section 3.3.2.8 for how to assign the output group to a loop output device. Refer to Section 3.3.13 for
how to assign the output group to an internal panel circuit.

6.4.3 Styles
In the example, there are two ways in which the sounders should ring. These two operational characteristics can
be defined as Styles in the panel. For example:
The first Style is that the sounders should turn on immediately a fire is recognised in Zone 22 or in Zone 23 or in
Zone 24. The panel contains a default Style (Style 00) for this method of operation.
The second Style is that the sounders should stay silent for 30 seconds and then start pulsing. After 2 minutes of
pulsing, they should then turn on. This is a little more complex but is easy to program. In the following
description, a new Style (Style 2) will be defined for this purpose.
It is quite likely that Style 2 will be used extensively in the cause and effect programming for the rest of the
building. For example, a fire on Floor 8 may also require the sounders on Floors 7 and 8 to operate in this manner.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 48


UK Security Panels Alarmhelp.net

6.4.4 Output Group Programming


To achieve the above cause and effect requirements, the three different Output Groups would be programmed and
indicated on the panel as in the following display examples:
Output Group 6 – Sounders on Floor 6:
[Output Group 6] [ 3.9% Mem used] [STYLE 02 ]

ZONE GROUP CAUSE STYLE=Delay->MODE Wait MODE Wait MODE


22 6 ANY FIRE 02 30s Pulse 120s On
23 6 ANY FIRE 02 30s Pulse 120s On
24 6 ANY FIRE 02 30s Pulse 120s On
More>

Output Group 7 – Sounders on Floor 7:


[Output Group 7] [ 3.9% Mem used] [STYLE 00 ]

ZONE GROUP CAUSE STYLE=Delay->MODE Wait MODE Wait MODE


22 7 ANY FIRE 00 - On
23 7 ANY FIRE 00 - On
24 7 ANY FIRE 00 - On
More>

Output Group 8 – Sounders on Floor 8:


[Output Group 8] [ 3.9% Mem used] [STYLE 02 ]

ZONE GROUP CAUSE STYLE=Delay->MODE Wait MODE Wait MODE


22 8 ANY FIRE 02 30s Pulse 120s On
23 8 ANY FIRE 02 30s Pulse 120s On
24 8 ANY FIRE 02 30s Pulse 120s On
More>

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 49


UK Security Panels Alarmhelp.net

6.5 Appendix 5 – Apollo Information


Special Discovery specific features are available from the “Additional Info” field of the Loop View/Edit display.
It is then possible to view the internal Drift, perform a rapid compensation or access any of the internal Discovery
EEPROM memory locations. Press the  button and a pop-up window is shown presenting a list of options.
For example:
[Loop 1 Devices] <More>

VIEW DRIFT
RAPID COMPENSATION
VIEW EEPROM

Press the ÏÐ buttons to highlight the required menu option and then press the  button to confirm.

6.5.1 View Drift


The display then shows the Discovery devices that the panel is reading. For example, select the View Drift option
and the display shows:
[Loop 1 Devices] <More>
Address Additional Info
>001.0 Disco Reading..
002.0 XP95
003.0 Disco Reading..
004.0 Disco Reading..

When the reading is complete, the display shows the drift within the device. For example:
[Loop 1 Devices] <More>
Address Additional Info
>001.0 Disco Drift = 16
002.0 XP95
003.0 Disco Drift = 16
004.0 Disco Drift = 16

Refer to Apollo’s literature for an explanation of the drift mechanism and for further information on the expected
values.

6.5.2 Rapid Compensation


Apollo has incorporated a rapid compensation facility into the Discovery devices. If a device is changed during
service it can be quickly adjusted to the present ambient conditions.
Highlight the required “Disco” family device, select RAPID COMPENSATION and then press the  button to
confirm. The panel will now instruct this device to perform a rapid compensation. This will take approximately 30
seconds.

This operation must only be performed with the detector in clean air.
No other operation should be performed on this device during this rapid compensation period.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 50


UK Security Panels Alarmhelp.net

6.5.3 View EEPROM


The panel can read any of the extended memory locations within the Discovery devices.
Highlight any “Disco” family device, select VIEW EEPROM and then press the  button to confirm. The display
will prompt for entry of the required extended memory address. For example:
[Loop 1 Devices] <More>
Address Additional Info

EEPROM ADDRESS=#

Enter the required address using the number buttons and then press the  button to confirm.
The panel will now read the extended memory locations for all Discovery devices on the loop. When complete,
the display will present the information as follows:
[Loop 1 Devices] <More>
Address Additional Info
>001.0 Disco EEP[ 1] = 23
002.0 XP95
003.0 Disco EEP[ 1] = 21
004.0 Disco EEP[ 1] = 22

Refer to Apollo’s literature for an explanation of the extended memory locations and for further information on
the expected values.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 51


UK Security Panels Alarmhelp.net

6.6 Appendix 6 – Hochiki Esp Information


At power up the panel allows a couple of minutes for Hochiki Esp detectors to stabilise. Any detectors that the
panel knows to be present will then be calibrated. The panel displays can be used normally during this time, but
the fire detection response will be slower until all the calibration phases are complete. If devices are inspected
during this period, they may show their state as: -

“Reset” - panel has reset the device at power up, resetting from a fire etc.
“Calibrating” - checking ESP “Zero Point” and “Fire Points”
“Initialising” - loading detection thresholds, sounder volumes etc.

Calibration can be manually initiated any time at access level 3, forcing all the devices on the selected loop to be
calibrated. Transferring new device information from a PC to the panel will also cause the effected devices to be
re-calibrated.

Periodic re-calibration can be performed at levels 1 & 2 under control of one of the 7-day timeclocks. The
timeclock settings are configured from PC program.

6.6.1 Unprocessed Analogue information


For most purposes the “Value” field in the View/Edit menu gives the easiest to read and the most useful
information from a detector as it is scaled and displayed in standard engineering units. It is, however, possible to
see the unprocessed analogue signal (AN) by moving to the Additional Info field.
[Loop 1 Devices] <More>
Address Additional Info
001.0 AN = 85
002.0 AN = 81
003.0 AN = 97
004.0 AN = 83

Press the  button to cycle through and display the stored Calibration Zero-point (ZP) and the Calibration Fire-
point (FP).

6.6.2 CHQ-BS / CHQ-WS Sounders


Unlike standard sounders, these loop-driven sounders can be programmed to give out many different tones and be
individually programmed to adjust the sound output. When programmed from the panel they will default to turn
on at 85dB. Use one of the many tones available from the PC instead of the standard “Pulse” option if any special
ringing is required.
The panel utilises the “group” features of the CHQ-BS/WS, so that when a command is sent to turn one device on,
all other CHQ-BS/WS devices within the same group will turn on at virtually the same time from the same
command (and likewise when they are silenced). Allocate unique “Output Groups” to CHQ-BS/WS devices, with
no other device types using that group.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 52


UK Security Panels Alarmhelp.net

6.7 Appendix 7 – Mx4000 Series Loop Output Drive Capabilty


The following information is applicable per loop. All loops can be loaded to the maximum
(500mA per loop).

Provision has been made to allow for a typical loading of detectors and inputs (30mA).

6.7.1 Hochiki

Volume Number of Loop Powered Sounder Bases


98db 29
or
95db 42
or
94db 47
or
93db 58
or
90db 72
or
88db 104
or
85db 127

6.7.2 Apollo

Volume Number of Loop Powered Sounders


100db 104 Loop Powered Sounders
or
92db 57 Sounder Bases
or
85db 126 Sounder Bases

The number of devices shown is representative for specific loop arrangements. If there is a
STOP mixture of sounder types or sounder volumes on the installation or if the other devices on the
loop take more than 30mA in quiescent or alarm, then calculate the actual current load in
alarm using the current consumption figures quoted in the device data sheets and ensure that
this does not exceed the maximum output for the loop.

Refer to Apollo and Hochiki LoopCalculator for further information on calculating loop
loading, cable cross sectional area and loop distance.

Document Reference 680-014 Rev 07 Author PS RFM4100 Page 53

You might also like