MULTI V Indoor Unit Ceiling Concealed Duct (High Static)

2. Specifications
Type Ceiling Concealed Duct (High Static)
Model Unit ARNU48GM3B4 ARNU54GM3B4
kW 14.1 15.8
Cooling Capacity kcal/h 12,100 13,600
Btu/h 48,100 54,000
kW 15.9 18.0
Heating Capacity kcal/h 13,600 15,500
Btu/h 54,200 61,400
Power Input (H / M / L) W 172 / 105 / 65 260 / 215 / 172
Casing Galvanized Steel Plate Galvanized Steel Plate
Dimensions mm 1250 × 360 × 700 1250 × 360 × 700
Body
(WxHxD) inch 49-7/32 x 14-3/16 x 27-9/16 49-7/32 x 14-3/16 x 27-9/16
Rows x Columns x FPI 3 x 16 x 18 3 x 16 x 18
Coil
Face Area m² 0.32 0.32
Type Sirocco Fan Sirocco Fan
Motor Output x Number W 500 x 1 500 x 1
Air Flow Rate (H / M / L) m³/min 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0
Fan (Factory set) ft³/min 1413 / 1201 / 989 1766 / 1589 / 1413
External Static Pressure mmAq(Pa) 6(59) 6(59)
Drive Direct Direct
Motor type BLDC BLDC
Temperature Control Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene
Air Filter - -
Safety Device Fuse Fuse
Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8)
Pipe Connections Gas Side mm(inch) Ø15.88(5/8) Ø19.05(3/4)
Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1)
Net Weight kg(lbs) 42.2(93) 42.2(93)
Sound Pressure Levels (H / M / L) dB(A) 39 / 37 / 35 42 / 40 / 39
Sound Power Levels (H / M / L) dB(A) 63 / 60 / 59 65 / 64 / 62
Power Supply Ø, V, Hz 1, 220 - 230 - 240, 50/60 1, 220 - 230 - 240, 50/60
Running Current
Rated A 1.04 - 1.00 - 0.96 1.58 - 1.51 - 1.44
by voltage
Maximum Running Current A 2.50 2.50
Type - R410A / R32 R410A / R32
Additional Charging Amount
Refrigerant kg(each) 0.61 / 0.50 0.61 / 0.50
(CF Value of IDU)
Control - EEV EEV
Transmission cable mm² 1.0~1.5 x 2C 1.0~1.5 x 2C
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the semi-anechoic rooms by ISO 9614 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
5. Refrigerant information (type, additional charging amount, etc.) must be applied by refrigerant type of the combined outdoor unit.
Adapt after checking the specifications of outdoor unit.