Finder 4
Finder 4
(DI) Interval
B Apply power to timer. Output contacts transfer
immediately. After the preset time has elapsed, contacts
1 2 3 4 5
reset.
*
(CE) On- and off-delay with control signal
Power is permenently applied to the timer. Closing the
Signal Switch (S) initiates the preset delay, after which
* With DC supply, 1 2 3 4 5
time the output contacts transfer. Opening the Signal
positive polarity has
switch initiates the same preset delay, after which time
to be conneted to B1,
the output contacts reset.
terminal (according to
EN 60204-1).
(DE) Interval with control signal on
Power is permenently applied to the timer. On momentary
or maintained closure of Signal Switch (S), the output
1 2 3 4 5
contacts transfer, and remain so for the duration of the
preset delay, after which they reset.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
** A voltage other than the supply voltage can be applied to the command Start (B1), example:
A1 - A2 = 24 V AC
IX-2021, www.findernet.com
B1 - A2 = 12 V DC
26
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
27
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Main features
Push-in terminals
The push-in terminals permit the quick connection of solid wires or ferrules by their simple insertion into the terminal (A).
It is possible to open the terminal to extract the wire by first pushing down on the push-button using a screwdriver (C).
For stranded cable it is necessary first to open the terminal using the push button, both for the extraction (C) and insertion (B).
It is possible at any time to check the connection via the test aperture, using a 2 mm diameter test probe (D).
A B C D
IX-2021, www.findernet.com
28
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
.9073 (5A - 24 V DC) Interface Module Code Input voltage Relay Socket
.8273 (0.75 A - 230 V AC) MasterTIMER HazLoc
39.90.0.012.8273 12 V AC/DC 34.81.7.012.8240 93.69.0.024.7
.xxxx 39.90.0.024.8273 24 V AC/DC 34.81.7.024.8240 93.69.0.024.7
.9024 39.90.0.012.9073 12 V AC/DC 34.81.7.012.9024 93.69.0.024.7
.8240 39.90.0.024.9073 24 V AC/DC 34.81.7.024.9024 93.69.0.024.7
31
39 39 SERIES
SERIES Relay interface modules 0.1 - 2 - 6 A
Accessories
Output fuse module for 39.31/30/81/80/61/60/91/90 types 093.63 093.63.0.024 093.63.8.230
- For 5 x 20 mm fuses up to 6 A, 250 V
- Type 093.63 - Easy visibility of the fuse condition through the window
- Type 093.63.0.024 - (6…24)V AC/DC with LED fuse status indicator
- Type 093.63.8.230 - (110…240)V AC with LED fuse status indicator
- Quick connection to socket
093.63
B Approvals
Notes
Safety: Because the output circuit can be reinstated (point 3 below), even with the fuse removed, it is important not to
(according to type):
consider the removal of the fuse as a “safety disconnect”. Always isolate elsewhere before working on the circuit.
UL: According to UL508A, the fuse module cannot be installed in power circuits (in which it is mandatory that a fuse certified
according to UL category JDDZ be fitted). However, where the MasterInterface is connected as an output interface to a PLC
no such restrictions apply, and the fuse module can be usefully employed.
Type 093.63 Type 093.63.0.24 / 093.63.8.230
093.63.0.024
093.63.8.230
1. In order to use a fuse module, it is enough to remove the “bridging” module and replace it by the fuse module. The fuse is
positioned electrically in series with the common output terminal of the interface module (11 for EMR versions, 13+ for SSR
versions, 15 for EMR timer, 15+ for SSR timer). .
2. If the fuse module is extracted (for example; because the fuse element has blown) the output circuit will be locked open, as
this will generally be the “safe option”.
3. In order to reinstate the output circuit it is necessary to either re-insert the fuse module (complete with functional fuse), or,
alternatively, the “bridging” module.
IX-2021, www.findernet.com
32
39 SERIES 39
Relay interface modules 0.1 - 2 - 6 A SERIES
Accessories
16-way jumper link 093.16 (blue) 093.16.0 (black) 093.16.1 (red)
Rated values 36 A* - 250 V
093.16 Possibility of multiple connection, side by side
* Maximum rating of the jumper link. Each individual pole shall not exceed the 6 A limit of the interface to which it is connected.
093.16.0
B
093.16.1
Approvals
(according to type):
093.60
2. Leaving the ribs in place provides 6.2 mm separation. Simply cutting (with scissors) the relevant segment(s) permits the
interconnection across the separator of 2 different groups of interface relays, using the standard jumper link.
093.48
IX-2021, www.findernet.com
Sheet of marker tags (CEMBRE Thermal transfer printers) ,48 tags, 6 x 12 mm 060.48
060.48
33
39 39 SERIES
SERIES Timed interface modules
Accessories
Terminal doubler (for Push-in sockets only) 093.62
Total load 6 A - 300 V
Solid and stranded cable
2
Max. wire size mm 2 x 1.5
AWG 2 x 16
B
MasterADAPTER 093.68.14.1
The MasterADAPTER permits the easy connection of A1/A2 terminals of up to 8 MasterINTERFACE modules to PLC outputs
via a 14-Pole ribbon cable, plus simple 2-wire power supply connection ATEX Version.
Technical data
Rated current (per signal path) A 1
Minimum required supply power W 3
Nominal voltage (UN) V DC 24
093.68.14.1 Operating range (0.8…1.1)UN
Approvals
Control logic Positive switching (to A1)
(according to type):
Power supply status indication Green LED
Ambient temperature range °C –40…+70
Terminals for 24 V control logic
Type of connector 14 pole, according to IEC 60603-13
ATEX version II 3G Ex nA IIC Gc
Terminals for 24 V power supply
Wire strip length mm 9.5
Screw torque Nm 0.5
Max. wire size
solid wire mm2 1 x 4 / 2 x 1.5
AWG 1 x 12 / 2 x 16
Connected MasterADAPTER stranded wire mm2 1 x 2.5 / 2 x 1.5
AWG 1 x 14 / 2 x 16
Wiring diagram
IX-2021, www.findernet.com
34
39 SERIES 39
Timed interface modules SERIES
Accessories
PLC cable 093.00020
Lenght mt 2
Operating voltage V 35
Nominal current per wire A 0.7
N° of poles 14
Ambient temperature range °C –40…+50 B
Wire size mm2 0.2
AWG 24
Blue/Red
Blu/Rosso 12 10
White/Green
Bianco/Verde 13
Brown/Green
Marrone/Verde 14
20
Useful length:
Lunghezza L +/–L+/-
utile: 1% 1%
093000XX-ASS
10
20
10
40
IX-2021, www.findernet.com
Relay Interface
Modules 8 - 10 -16 A
Control panels
Carousel
warehouses
Medical and
dentistry
Shipyards
Elevators
and liſts
Building
automation
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
48 48 SERIES
SERIES Relay interface modules 10 A
Type 48.P3
- 1 CO 10 A
- Push-in terminals
Type 48.31
- 1 CO 10 A
B - Screw terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 1 CO 10 A • 1 CO 10 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P3 48.31
Push-in terminal Screw terminal
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
4
48 SERIES 48
Relay interface modules 8 A SERIES
Type 48.P5
- 2 CO 8 A
- Push-in terminals
Type 48.52
- 2 CO 8 A
- Screw terminals
B
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 2 CO 8 A • 2 CO 8 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P5 48.52
Push-in terminal Screw terminal
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
5
48 48 SERIES
SERIES Relay interface modules 16 A
Type 48.P6
- 1 CO 16 A
- Push-in terminals
Type 48.61
- 1 CO 16 A
B - Screw terminals
• AC coils or DC sensitive coils
• Supply status indication and EMC coil • 1 CO 16 A • 1 CO 16 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material available
48.P6 48.61
Push-in terminal Screw terminal
* For currents > 10 A, contact terminals * For currents > 10 A, contact terminals
must be connected in parallel must be connected in parallel
For outline drawing see page 11 (21 with 11, 24 with 14, 22 with 12). (21 with 11, 24 with 14, 22 with 12).
Contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT)
Rated current/Maximum peak current A 16*/30 16*/30
Rated voltage/
Maximum switching voltage V AC 250/400 250/400
Rated load AC1 VA 4000 4000
Rated load AC15 (230 V AC) VA 750 750
Single phase motor rating (230 V AC) kW 0.55 0.55
Breaking capacity DC1: 30/110/220 V A 16/0.3/0.12 16/0.3/0.12
Minimum switching load mW (V/mA) 500 (10/5) 500 (10/5)
Standard contact material AgCdO AgCdO
Coil specification
Nominal voltage (UN) V AC (50/60 Hz) 12 - 24 - 110 - 120 - 230 12 - 24 - 110 - 120 - 230
V DC 12 - 24 - 125 12 - 24 - 125
Rated power AC/sens. DC VA (50 Hz)/W 1.2/0.5 1.2/0.5
Operating range AC (0.8…1.1)UN (0.8…1.1)UN
sens. DC (0.8…1.5)UN (0.8…1.5)UN
Holding voltage AC/DC 0.8 UN / 0.4 UN 0.8 UN / 0.4 UN
Must drop-out voltage AC/DC 0.2 UN / 0.1 UN 0.2 UN / 0.1 UN
Technical data
Mechanical life cycles 10 · 106 10 · 106
3
Electrical life at rated load AC1 cycles 100 · 10 100 · 103
Operate/release time ms 7/4 (AC) - 12/12 (DC) 7/4 (AC) - 12/12 (DC)
Insulation between coil
and contacts (1.2/50 µs) kV 6 (8 mm) 6 (8 mm)
XII-2020, www.findernet.com
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
6
48 SERIES 48
Relay interface modules 10 A SERIES
Type 48.P8
- 2 CO 10 A
- Push-in terminals
Type 48.62
- 2 CO 10 A
- Screw terminals
B
• DC sensitive coils
• Supply status indication and EMC coil • 2 CO 10 A • 2 CO 10 A
suppression module as standard • Push-in terminals • Screw terminals
• Identification label
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
• Cadmium-free contact material
48.P8 48.62
Push-in terminal Screw terminal
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
7
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Ordering information
Example: 48 series, 35 mm rail (EN 60715) mount, Push-in terminal relay interface module, 2 CO 8 A contacts, 24 V sensitive DC coil, green LED + diode,
99.02 coil indication.
A B C D
4 8 . P 5 . 7 . 0 2 4 . 0 0 5 0
B Series A: Contact material D: Special versions
0 = Standard AgNi for 0 = Standard
Type 48.P3/P5/P8/31/52/62 7 = Standard (for 48.12/48.P2 only)
Screw terminal AgCdO, Standard
1 = 35 mm rail (EN 60715) mount, for 48.P6/61 C: Options
forcibly guided contacts relay 4 = AgSnO2, for 48.P6/P8/ 0 = Standard (for 48.12/48.P2 only)
3 = 35 mm rail (EN 60715) mount 61/62 only 5 = Standard for DC:
5 = 35 mm rail (EN 60715) mount 5 = AgNi + Au, for 48.12/P2 green LED + diode (polarity +A1)
6 = 35 mm rail (EN 60715) mount and 48.P3/P5/31/52 only 6 = Standard for AC and 48.32:
Push-in terminal Standard for 48.32 green LED + Varistor
P = 35 mm rail (EN 60715) mount
B: Contact circuit
Type 0 = CO (nPDT)
Screw terminal
1 = for 48.31, 1 pole, 10 A
48.61, 1 pole, 16 A
2 = for 48.12/48.32 (DC only), 48.52, 2 poles, 8 A
48.62 (DC only), 2 poles, 10 A
Push-in terminal Selecting features and options: only combinations in the same row are possible.
2 = for 48.P2 (DC only), 2 pole, 8 A Preferred selections for best availability are shown in bold.
3 = for 48.P3, 1 pole, 10 A
5 = for 48.P5, 2 pole, 8 A
Type Coil version A B C D
6 = for 48.P6, 1 pole, 16 A
8 = for 48.P8 (DC only), 2 pole, 10 A 48.12/48.P2 DC 5 0 0 7
48.32 DC 5 0 6 0
Coil version
7 = Sensitive DC 48.P3/P5/31/52 AC 0-5 0 6 0
8 = AC (50/60 Hz) 48.P3/P5/31/52 Sensitive DC 0-5 0 5 0
9 = DC (for 48.12/48.P2 only) 48.P6/61 AC 0-4 0 6 0
Coil voltage 48.P6/61 Sensitive DC 0-4 0 5 0
See coil specifications 48.P8/62 Sensitive DC 0-4 0 5 0
Technical data
Insulation 48.12/P2/31/32/61/P3/P6 48.52/P5 48.12/31/61/62/P3/P6/P8
Insulation according to EN 61810-1 insulation rated voltage V 250 250 400
rated impulse withstand voltage kV 4 4 4
pollution degree 3 2 2
overvoltage category III III III
Insulation between coil and contacts (1.2/50 µs) kV 6 (8 mm)
Dielectric strength between open contacts V AC 1000; 1500 (48.12/P2/32)
Dielectric strength between adjacent contacts V AC 2000 (48.P5/52); 2500 (48.P8/62) 3000 (48.12/P2/32)
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV (1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/5; 2/10 (48.12/P2/32)
Vibration resistance (10…200)Hz: NO/NC g 20/5 (for 1 pole) 15/3; 20/6 (48.12/P2/32) for 2 pole
Power lost to the environment without contact current W 0.7
with rated current W 1.2 (48.12/P2/31/32/P3) 2 (48.52/P5/61/62/P6/P8)
Wire strip length mm 8
Screw torque (only for 48.12/31/32/52/61/81) Nm 0.5
Min. wire size Screw terminal Push-in terminal
solid cable stranded cable solid cable stranded cable
XII-2020, www.findernet.com
8
48 SERIES 48
Relay interface modules 8 - 10 - 16 A SERIES
Contact specification
F 48 - Electrical life (AC) v contact current F 48 - Electrical life (AC) v contact current
Types 48.P3/P6/31/61 Types 48.P8/62
Cycles
Inductive load AC15
8 12
F 48 - Electrical life (AC) v contact current F 48 - Electrical life (AC) v contact current
Types 48.P5/52 Type 48.12/P2/32
Cycles
Inductive load- cosϕ = 0.4
2 contacts in series
2 contacts in series
single contact
single contact
values under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
DC voltage (V)
Note: the release time for the load will be increased.
9
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Coil specifications
* Umin = 0.8 UN for 48.61, 48.62, 48.P6, 48.P8 120 8.120 96 132 11.8
230 8.230 184 253 7.0
R 48 - DC coil operating range v ambient temperature R 48 - AC coil operating range v ambient temperature
48.P3/P5/31/52
48.P6/P8/61/62 1
48.P6/P8/61/62
2 2
48.P3/P5/31/52
10
48 SERIES 48
Relay interface modules 8 - 10 - 16 A SERIES
Outline drawings
64.5
15.8 25.9 17.5 17.5
21.6
78.6
35.4
25.5
32
35.5
29.5
30.4
11
48 48 SERIES
SERIES Relay interface modules 8 - 10 - 16 A
Accessories
8-way jumper link for type 48.P3/P5/P6/P8 097.58
Rated values 10 A - 250 V
097.58
B
2-way jumper link for type 48.P3/P5/P6/P8 097.52
Rated values 10 A - 250 V
097.52
097.42
097.00
PEAN
8-way jumper link for screw terminal version 095.18 (blue) 095.18.0 (black)
O
EUR
N
T Rated values 10 A - 250 V
T E
EUR
P A O
PEAN
095.18
060.48
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
4 8 . P 5 . 7 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
Relay interface
modules 8 - 10 - 16 A
Escalators
Road / tunnel
lighting
Hoists and
cranes
Carousel
warehouses
Control panels
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C ≤ 12 A: –40…+70/>12 A: –40…+50 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
4
4C SERIES 4C
Relay interface modules 8 to 16 A SERIES
Ordering information
Example: 4C series, 35 mm rail (EN 60715) mount, Push-in terminal relay interface module, 1 CO 10 A contacts, 24 V DC coil, green LED + diode.
A B C D
4 C . P 1 . 9 . 0 2 4 . 0 0 5 0
Series A: Contact material
0 = AgNi
D: Special versions
0 = Standard
B
Type 4 = AgSnO2
0 = 35 mm rail (EN 60715) mount 5 = AgNi + Au C: Options
screw terminal socket 5 = Standard for DC:
P = 35 mm rail (EN 60715) mount B: Contact circuit green LED + diode (polarity +A1)
Push-in terminal socket 0 = CO (nPDT) 6 = Standard for AC:
green LED + Varistor
No. of poles
1 = 1 pole, 10/16 A
2 = 2 pole, 8 A
Coil version
8 = AC (50/60 Hz) Selecting features and options: only combinations in the same row are possible.
9 = DC Preferred selections for best availability are shown in bold.
Technical data
Insulation
Insulation according to EN 61810-1 insulation rated voltage V 250 440
rated impulse withstand voltage kV 4 4
pollution degree 3 2
overvoltage category III III
Insulation between coil and contacts (1.2/50 μs) kV 6 (8 mm)
Dielectric strength between open contacts V AC 1000
Dielectric strength between adjacent contacts V AC 2000
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV (1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/6 (4C.01/P1) 1/4 (4C.02/P2)
Vibration resistance (10…150)Hz: NO/NC g 20/12
Power lost to the environment without contact current W 0.6
with rated current W 1.6 (4C.01/P1) 2 (4C.02/P2)
Terminals 4C.01/4C.02 4C.P1/4C.P2
Wire strip length mm 8 8
Screw torque Nm 0.8 —
Min. wire size solid cable stranded cable solid cable stranded cable
2
mm 0.5 0.5 0.5 0.5
AWG 21 21 21 21
XII-2018, www.findernet.com
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x 16 / 1 x 14 2 x 16 / 1 x 14
5
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Contact specification
F 4C - Electrical life (AC) v contact current F 4C - Electrical life (AC) v contact current
Types 4C.02/P2 Types 4C.01/P1
Cycles
limit for 4C.P1
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage consumption voltage consumption
UN Umin Umax R I at UN UN Umin Umax R I at UN
V V V Ω mA V V V Ω mA
12 9.012 8.8 13.2 300 40 12 8.012 9.6 13.2 80 90
24 9.024 17.5 26.4 1200 20 24 8.024 19.2 26.4 320 45
125 9.125 91.2 138 32000 3.9 110 8.110 88 121 6900 9.4
120 8.120 96 132 9000 8.4
230 8.230 184 253 28000 5
R 4C - DC coil operating range v ambient temperature R 4C - AC coil operating range v ambient temperature
XII-2018, www.findernet.com
6
4C SERIES 4C
Relay interface modules 8 to 16 A SERIES
Outline drawings B
Accessories
8-way jumper link for type 4C.P1 and 4C.P2 097.58
Rated values 10 A - 250 V
097.58
097.52
097.42
XII-2018, www.findernet.com
7
4C 4C SERIES
SERIES Relay interface modules 8 to 16 A
Accessories
Marker tag holder for type 4C.P1/P2/01/02 097.00
097.00
PEAN
8-way jumper link for 4C.01 and 4C.02 095.18 (blue)
O
EUR
T
B T E
N Rated values 10 A - 250 V
EUR
P A O
PEAN
095.18
060.48
Packaging codes
How to code and identify retaining clip and packaging options for relay interface module.
Example:
4 C . P 1 . 9 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
XII-2018, www.findernet.com
Relay interface
modules 6 - 7 - 10 A
Control panels
Packaging
machines
Shipyards
Textile
machines
Carousel
warehouses
Wood-processing
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
58 SERIES 58
Relay interface modules 7 - 10 A SERIES
Type 58.P3
- 3 CO 10 A
- Push-in terminals
Type 58.P4
- 4 CO 7 A
- Push-in terminals
B
• AC coils or DC coils
• Supply status indication and EMC coil • 3 CO 10 A • 4 CO 7 A
suppression module as standard
• Push-in terminals • Push-in terminals
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• Atex compliant (Ex ec nC) option available
• HazLoc Class I Div. 2 Groups A, B, C, D - T5
option available
• 35 mm rail (EN 60715) mounting
58.P3 / 58.P4
Push-in terminals
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range °C –40…+70 –40…+70
Protection category IP 20 IP 20
Approvals relay (according to type)
3
58 58 SERIES
SERIES Relay interface modules 7 - 10 A
Type 58.32
- 2 CO 10 A
- Screw terminals
Type 58.33
- 3 CO 10 A
B - Screw terminals
Type 58.34
- 4 CO 7 A
• 2 CO 10 A • 3 CO 10 A • 4 CO 7 A
- Screw terminals
• Screw terminals • Screw terminals • Screw terminals
• AC coils or DC coils
• Supply status indication and EMC coil
suppression module as standard
• Identification label
• Cadmium Free contacts
• UL Listing (certain relay/socket combinations)
• 35 mm rail (EN 60715) mounting
58.32 / 58.33 / 58.34
Screw terminals
Dielectric strength
between open contacts V AC 1000 1000 1000
Ambient temperature range °C –40…+70 –40…+70 –40…+70
Protection category IP 20 IP 20 IP 20
Approvals relay (according to type)
4
58 SERIES 58
Relay interface modules 6 - 10 A SERIES
Dielectric strength
between open contacts V AC 1000 1000
Ambient temperature range* °C –40…+70* –40…+70*
Protection category IP 20 IP 20
Approvals relay (according to type) HazLoc
5
58 58 SERIES
SERIES Relay interface modules 6 - 7 - 10 A
Ordering information
Example: 58 series, 35 mm rail (EN 60715) mounting, Push-in terminals interface module, 4 CO, 24 V DC coil, green LED + diode.
A B C D
5 8 . P 4 . 9 . 0 2 4 . 0 0 5 0
No. of poles
2 = 2 pole, 10 A
3 = 3 pole, 10 A
4 = 4 pole, 7 A
Selecting features and options: only combinations in the same row are possible.
Coil version
Preferred selections for best availability are shown in bold.
8 = AC (50/60 Hz)
9 = DC Type Coil version A B C D
58.P3/P4/32/33/34 AC 0-5 0 6 0
Coil voltage
See coil specifications 58.P3/P4/32/33/34 DC 0-5 0 5 0
A B C D
5 8 . 3 4 . 8 . 1 2 0 . 0 0 4 9
Series A: Contact material D: Special versions
0 = AgNi Standard 8 = Atex (Ex ec nC) and HazLoc Class I
Type 2 = AgCdO Div. 2 compliant without mechanical
3 = Screw terminals 5 = AgNi + Au indicator
35 mm rail (EN 60715) mount 9 = Atex (Ex ec nC) and HazLoc Class I
P = Push-in terminals B: Contact circuit Div. 2 compliant with mechanical
35 mm rail (EN 60715) mount 0 = CO (nPDT) indicator
Coil voltage Selecting features and options: only combinations in the same row are possible.
See coil specifications
Type Coil version A B C D
58.3x AC/DC 0-2-5 0 4-5-6-7 8-9
58.Px AC/DC 0-2-5 0 0 8-9
III-2020, www.findernet.com
6
58 SERIES 58
Relay interface modules 6 - 7 - 10 A SERIES
Technical data
Insulation
Insulation according to EN 61810-1 insulation rated voltage V 400 (2-3 pole) 250 (4 pole)
rated impulse withstand voltage kV 3.6 (2-3 pole) 2.5 (4 pole)
pollution degree 2 2
overvoltage category III II
Insulation between coil and contacts (1.2/50 μs) kV 3.6
Dielectric strength between open contacts V AC 1000 B
Dielectric strength between adjacent contacts V AC 2000 (58.32,58.33, 58.P3) 1550 (58.34, 58.P4)
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV (1.2/50 µs) 4
Other data
Bounce time: NO/NC ms
1/3
Vibration resistance (10…55)Hz: NO/NC g
6/6
Power lost to the environment without contact current W
1
with rated current W
3 (58.32, 58.34, 58.P4) 4 (58.P3, 58.33)
58.32/33/34 (screw terminals) 58.P3/P4 (Push-in terminals)
Wire strip length mm 8 8
Screw torque Nm 0.5 —
Min. wire size solid cable stranded cable solid cable stranded cable
mm2 0.5 0.5 0.5 0.5
AWG 21 21 21 21
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 2.5 2 x 1.5 / 1 x 2.5 2 x 1.5 / 1 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 14 2 x 16 / 1 x 14 2 x 16 / 1 x 14
Ex nC
Sealed device (type of protection for category 3G)
IIC
Gas group
Gc
Equipment Protection Level
III-2020, www.findernet.com
–40 °C ≤ Ta ≤ +70 °C
Ambient temperature
EPTI 15 ATEX 0195 U
EPTI: laboratory which issues the CE type certificate
15: year of issue of certificate
0195: number of CE type certificate
U: ATEX component
7
58 58 SERIES
SERIES Relay interface modules 6 - 7 - 10 A
58.P2.x.xxx 10 7 9 9
58.P4.x.xxx 6 5 5 5
III-2020, www.findernet.com
8
58 SERIES 58
Relay interface modules 7 - 10 A SERIES
Contact specification
F 58 - Electrical life (AC) v contact current F 58 - Electrical life (AC) v contact current
2 & 3 pole relays 4 pole relay
Cycles
Inductive load - cosφ = 0.4
Resistive load - cosφ = 1
Inductive load - cosφ = 0.4
DC voltage (V)
Coil specifications
DC coil data AC coil data
Nominal Coil code Operating range Resistance Rated coil Nominal Coil code Operating range Resistance Rated coil
voltage absorption voltage absorption
UN Umin Umax R I at UN UN Umin Umax R I at UN (50 Hz)
V V V Ω mA V V V Ω mA
12 9.012 9.6 13.2 140 86 12 8.012 9.6 13.2 50 97
24 9.024 19.2 26.4 600 40 24 8.024 19.2 26.4 190 53
48 9.048 38.4 52.8 2400 20 48 8.048 38.4 52.8 770 25
125 9.125 100 138 17300 7.2 110 8.110 88 121 4000 12.5
120 8.120 96 132 4700 12
230 8.230 184 253 17000 6
R 58 - DC coil operating range v ambient temperature R 58 - AC coil operating range v ambient temperature
1
1
2 2
III-2020, www.findernet.com
9
58 58 SERIES
SERIES Relay interface modules 7 - 10 A
B Outline drawings
Type 58.32 Type 58.33
Screw terminals Screw terminals
Type 58.34
Screw terminals
10
58 SERIES 58
Relay interface modules 7 - 10 A SERIES
Accessories
2-way jumper link for type 58.P3 and 58.P4 094.52.1
Rated values 10 A - 250 V
094.52.1
B
097.52
Marker tag holder for type 58.P3, 58.P4, 58.32, 58.33 and 58.34 097.00
097.00
PEAN
6-way jumper link for type 58.32, 58.33, 58.34 094.06 (blue) 094.06.0 (black)
O
EUR
N
T Rated values 10 A - 250 V
T E
EUR
P A O
PEAN
094.06
PEAN
6-way jumper link for type 58.P3 and 58.P4 094.56 (blue)
O
EUR
N
T Rated values 10 A - 250 V
T E
EUR
P A O
PEAN
094.56
060.48
Packaging codes
How to code and identify retaining clip and packaging options for sockets.
Example:
5 8 . P 4 . 9 . 0 2 4 . 0 0 5 0 S P A
A Standard packaging
B Blister packaging
Versions only
Panels for
electrical
distribution
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Wiring diagram
DC (0.8…1.1)UN
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
3
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Wiring diagram
DC (0.8…1.1)UN
Technical data
Ambient temperature range °C –20…+50
Protection category IP 20
Approvals (according to type)
4
19 SERIES 19
Relay actuators & Status indicating modules SERIES
5
19 19 SERIES
SERIES Relay actuators & Status indicating modules
6
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Ordering information
Example: 19 series Auto/Off/On override module, 1 CO (SPDT) 10 A contact, 24 V AC/DC supply.
1 9 . 2 1 . 0 . 0 2 4 . 0 0 0 0
Series Contact circuit
Type
0 = Standard B
21 = Auto/Off/On output module, 11.2 mm 3 = NO (19.6K)
50 = Analogue override module (0…10)V
91 = Power relay module Contact material
6K = KNX actuator, 6 poles 16 A 0 = Standard for 19.21, 19.50
4 = Standard for 19.91, 19.6K
Supply version
0 = AC (50/60 Hz)/DC
9 = DC
Supply voltage
012 = 12 V
024 = 24 V Codes / Module width
030 = KNX Bus 19.21.0.024.0000/11.2 mm
19.50.0.024.0000/17.5 mm
19.91.9.012.4000/17.5 mm
19.91.9.024.4000/17.5 mm
19.6K.9.030.4300/70 mm
Technical data
Insulation 19.21 19.50 19.91
Dielectric strength (V AC) between supply and contacts 3000 — 4000
between open contacts 1000 — 1000
between supply and feedback output 2000 1500 —
EMC specifications
Type of test Reference standard 19.21/91 19.50
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radiated electromagnetic field (80…1000 MHz) EN 61000-4-3 30 V/m
Fast transients (burst) (5-50 ns, 5 kHz) EN 61000-4-4 4 kV
Voltage pulses (1.2/50 µs) common mode EN 61000-4-5 2 kV 1 kV
on supply terminals differential mode EN 61000-4-5 1 kV 0.5 kV
Terminals 19.21/6K 19.50/91
Screw torque Nm 0.5 0.8
Max. wire size solid cable stranded cable solid cable stranded cable
mm2 1 x 6 / 2 x 2.5 1 x 4 / 2 x 1.5 1x6/2x4 1 x 4 / 2 x 2.5
AWG 1 x 10 / 2 x 14 1 x 12 / 2 x 16 1 x 10 / 2 x 12 1 x 12 / 2 x 14
Wire strip length mm 7 9
VII-2019, www.findernet.com
7
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Type 19.50
In selector position A (Automatic) the (0…10)V controller variable is transferred via Yin - A2 and Yout to the end process.
In selector position H (Hand) the (0…10)V value set by the regulator is transferred via Yout to the end process.
Type 19.6K
VII-2019, www.findernet.com
8
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Outline drawings
Type 19.21 Type 19.50
Screw terminal Screw terminal
9
19 19 SERIES
SERIES Relay actuators & Status indicating modules
Accessories
Sheet of marker tags (CEMBRE Thermal transfer printers) for 19.21/50/91/6K types, (48 tags) 6 x 12 mm 060.48
060.48
B
Identification tag, for 19.50 types, plastic, 1 tag, 17 x 25.5 mm 019.01
019.01
Adaptor for panel mounting, for 19.21/50/91 types, plastic, 17.5 mm wide 020.01
020.01
VII-2019, www.findernet.com
10
19 SERIES 19
Relay actuators & Status indicating modules SERIES
Application notes
Intervention Modules
The demand for security apparatus, heating, air conditioning or
efficient energy use in offices, hotels, and private homes or in
industrial space is growing constantly, leading to the installation of
increasingly complex electronic systems. But what happens if these
systems malfunction and a qualified service technician will only be
available in a few hours, or even days?
B
With the use of carefully installed intervention modules, a trained
caretaker or security guard can be in a position to recognize
interruptions in service, and by manual intervention perform the
necessary override actions to maintain system operation until a repair
can be effected.
guided contacts 8 A
Escalators
Medical and
dentistry
Hospitals
Carousel
warehouses
Elevators
and lifts
Disabled lift
Wood-
processing
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT II RT II
Approvals (according to type)
3
50 50 SERIES
SERIES Forcibly guided contacts relay 8 A
3 NO + 1 NC
Ø1.3
7.6
Dielectric strength
between open contacts V AC 1500 1500
Ambient temperature range °C –40…+70 –40…+70
Environmental protection RT III RT III
Approvals (according to type)
4
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
Ordering information
Example: 50 series forcibly guided contacts, 2 CO (DPDT) 8 A contacts, 24 V DC coil.
A B C D
5 0 . 1 2 . 9 . 0 2 4 . 5 0 0 0
Series A: Contact material D: Special versions
1 = AgNi (50.12) 0 = Flux proof (RT II)
Type 4 = AgSnO2 (50.14) 0 = Wash tight (RT III), 50.14, 50.16
1 = PCB 5 = AgNi + Au (50.12) C: Options
5 = AgSnO2 + Au (50.16) 0 = CO (nPDT)
No. of poles 1 = 1 NC (SPST-NC)
2 = 2 pole 8 A B: Contact circuit 2 = 2 NC (DPST-NC)
C
4 = 4 pole 8 A 0 = CO (nPDT) 3 = 3 NC (3PST-NC)
6 = 6 pole 8 A 2 = 2 NO (DPST-NO)
3 = 3 NO (3PST-NO)
Coil version 4 = 4 NO (4PST-NO)
9 = DC 5 = 5 NO (5PST-NO)
Coil voltage
See coil specifications
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250 400
Pollution degree 3 2
Insulation between coil and contact set
Type of insulation Reinforced (8 mm)
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
Type of insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength (50.12, 50.16) V AC 3000
Dielectric strength (50.14) V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1500/2.5
Insulation between coil terminals
Rated impulse voltage (surge) differential mode
(according to EN 61000-4-5) kV (1.2/50 µs) 2
Other data
Bounce time: NO/NC ms 2/10
Vibration resistance (10…200)Hz: NO/NC g 20/6
Shock resistance NO/NC g 20/5
Power lost to the environment without contact current W 0.7
with rated current W 1.2
Recommended distance between relays mounted on PCB mm ≥ 5
X-2019, www.findernet.com
5
50 50 SERIES
SERIES Forcibly guided contacts relay 8 A
Contact specification
F 50 - Electrical life (AC) v contact current (type 50.12) H 50 - Maximum DC1 breaking capacity (type 50.12)
C
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Coil specifications
R 50 - DC coil operating range v ambient temperature
DC coil data (type 50.12) Standard coil (type 50.12)
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
5 9.005 3.8 6 35 143
6 9.006 4.5 7.2 50 120
12 9.012 9 14.4 205 58.5
24 9.024 18 28.8 820 29.3
48 9.048 36 57.6 3280 14.4
60 9.060 45 72 5140 11.7
110 9.110 82.5 131 17250 6.4
125 9.125 93.7 150 22300 5.6
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
DC coil data (type 50.14/16)
Nominal Coil Operating range Resistance Rated coil
voltage code consumption
UN Umin Umax R I at UN
V V V Ω mA
12 9.012 9 14.4 180 66.6
X-2019, www.findernet.com
6
50 SERIES 50
Forcibly guided contacts relay 8 A SERIES
Contact specification
F 50 - Electrical life (AC) v contact current (type 50.14) H 50 - Maximum DC1 breaking capacity (type 50.14)
2 4 6 8
C
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
F 50 - Electrical life (AC) v contact current (type 50.16) H 50 - Maximum DC1 breaking capacity (type 50.16)
2 4 6 8
DC voltage (V)
• When switching a resistive load (DC1) having voltage and current values
under the curve, an electrical life of ≥ 100 · 103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the
load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
Outline drawings
Types 50.12…1000/50.12…5000 Type 50.14 Type 50.16
X-2019, www.findernet.com
forcibly guided
contacts 6 - 10 A
Chemical and
petrolchemical
Wood-
processing
machines
Carousel
warehouses
Escalators
Elevators
and liſts
Process
Industry
Automatic
car-washes
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
7S SERIES 7S
Modular relays with forcibly guided contacts 6 A SERIES
3
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 10 A
Screw terminal
4
7S SERIES 7S
Modular relays with forcibly guided contacts 6 A SERIES
5
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Ordering information
Example: 7S series Modular relay with forcibly guided contacts, 6 contact (4 NO + 2 NC) 6 A, supply voltage 24 V DC.
7 S . 1 6 . 9 . 0 2 4 . 5 4 2 0
Series Special versions
Type 0 = Standard
1 = 22.5 mm wide, screwless terminals 1 = NO auxliary contact
2 = 17.5 mm wide, screw terminals NO and NC contatcs
3 = 22.5 mm wide, screw terminals 11 = 1 NO + 1 NC (SPST-NO + SPST-NC)
4 = 22.5 mm wide, screwless terminals 21 = 2 NO + 1 NC (DPST-NO+SPST-NC)
C 6 = 22.5 mm wide, screw terminals 22 = 2 NO + 2 NC (DPST-NO + DPST-NC)
Output 31 = 3 NO + 1 NC (3PST-NO + SPST-NC)
2 = 2 contacts 42 = 4 NO + 2 NC (4PST-NO + DPST-NC)
3 = 3 contacts 51 = 5 NO + 1 NC (4PST-NO + SPST-NC)
4 = 4 contacts Contact material
6 = 6 contacts 0 = AgNi +Au (7S.23) only
Supply version 0 = AgSnO2 & AgNi + Au
8 = AC (50 /60 Hz) (7S.43/63) only
9 = DC 4 = AgSnO2 (7S.14/34) only
Supply voltage 5 = AgNi +Au (7S.12/32) only
See page 10 5 = AgSnO2 + Au (7S.16/36) only
Codes, Preferred selections for best availability are shown in bold.
7S.12.9.012.5110 7S.14.9.012.4220 7S.16.9.012.5420
7S.12.9.024.5110 7S.14.9.012.4310 7S.16.9.024.5420
7S.12.8.120.5110 7S.14.9.024.4220 7S.16.9.110.5420
7S.12.8.230.5110 7S.14.9.024.4310 7S.16.8.120.5420
7S.14.9.110.4220 7S.16.8.230.5420
7S.32.9.012.5110 7S.14.9.110.4310
7S.32.9.024.5110 7S.14.8.120.4220 7S.36.9.012.5420
7S.32.8.120.5110 7S.14.8.120.4310 7S.36.9.024.5420
7S.32.8.230.5110 7S.14.8.230.4220 7S.36.9.024.5510
7S.14.8.230.4310 7S.36.9.110.5420
7S.43.9.012.0211 7S.36.8.120.5420
7S.43.9.024.0211 7S.34.9.012.4220 7S.36.8.230.5420
7S.43.9.048.0211 7S.34.9.012.4310
7S.43.9.110.0211 7S.34.9.024.4220 7S.23.9.012.0210
7S.34.9.024.4310 7S.23.9.024.0210
7S.63.9.012.0211 7S.34.9.110.4220 7S.23.9.048.0210
7S.63.9.024.0211 7S.34.9.110.4310 7S.23.9.110.0210
7S.63.9.048.0211 7S.34.8.120.4220
7S.63.9.110.0211 7S.34.8.120.4310
7S.34.8.230.4220
7S.34.8.230.4310
IX-2021, www.findernet.com
6
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system V AC 230/400
Rated insulation voltage V AC 250
Pollution degree 2
Insulation between coil and contact set
Type of Insulation Reinforced
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 6
Dielectric strength V AC 4000
Insulation between adjacent contacts
C
Type of Insulation Basic
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength V AC 2500
Insulation between open contacts
Type of disconnection Micro-disconnection
Dielectric strength V AC/kV (1.2/50 µs) 1500/2.5
7
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Contact specifications
Contact diagrams
7S.12/7S.32 7S.14/34....4220 7S.14....4310 7S.16/36....5420 7S.16/36....5510
12 34
11 33
11 12
43
C
54 33 34
7S.23 7S.43/7S.63
23 47
24 48
11 33 23
47 48
12 34 24
F 7S12 - Electrical life (AC) v contact current - 7S.12 H 7S12* - Maximum DC breaking capacity - 7S.12
Resistive load
Corrente DC (A)
Tensione DC (V)
F 7S14 - Electrical life (AC) v contact current - 7S.14/34 H 7S14* - Maximum DC breaking capacity - 7S.14/34
IX-2021, www.findernet.com
2 4 6 8
Tensione DC (V)
* When switching a load having voltage and current values under the
curve, an electrical life of ≥ 100 · 103 can be expected.
8
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Contact specifications
F 7S16 - Electrical life (AC) v contact current - 7S.16/36 H 7S16* - Maximum DC breaking capacity - 7S.16/36
C
2 4 6 8
DC voltage (V)
F 7S23 - Electrical life (AC) v contact current - 7S.23 H 7S23* - Maximum DC breaking capacity - 7S.23
DC voltage (V)
F 7S43 - Electrical life (AC) v contact current - 7S.43/63 H 7S43* - Maximum DC breaking capacity - 7S.43/63
DC breaking current (A)
Resistive load
Resistive load - cosφ = 1
Inductive load - AC15 Inductive load - DC13
Cycles
2 4 6 8
DC voltage (V)
* When switching a load having voltage and current values under the
curve, an electrical life of ≥ 100 · 103 can be expected.
IX-2021, www.findernet.com
9
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Coil specifications
DC coil data - type 7S.12/32 AC coil data - type 7S.12/32
Nominal Coil Operating range Rated input Rated Nominal Coil Operating range Rated input Rated
voltage code current power voltage code current power
at UN at UN at UN at UN
UN Umin Umax IN UN Umin Umax IN
V V V mA W V V V mA VA/W
12 9.012 9.6 14.4 55 0.7 110…125 8.120 93 138 9.8 1.2/1.1
24 9.024 16.8 30 38.2 0.9 230…240 8.230 195 264 11.8 2.8/1.2
DC coil data - type 7S.14/34 / 7S.16/36 AC coil data - type 7S.14/34 / 7S.16/36
Nominal Coil Operating range Rated input Rated Nominal Coil Operating range Rated input Rated
C voltage code current power voltage code current power
at UN at UN at UN at UN
UN Umin Umax IN UN Umin Umax IN
V V V mA W V V V mA VA/W
12 9.012 9.6 14.4 64.7 0.8 110…125 8.120 93 138 10.2 1.3/1.1
24 9.024 16.8 30 42.2 1 230…240 8.230 195 264 11.8 2.9/1.2
110 9.110 77 138 11.6 1.4
R 7S - DC coil operating range v ambient temperature - R 7S - AC coil operating range v ambient temperature -
7S.12/32 / 7S.23 / 7S.14/34 / 7S.16/36 7S.12/32 / 7S.14/34 / 7S.16/36
10
7S SERIES 7S
Modular relays with forcibly guided contacts 6 - 10 A SERIES
Safety PLC
feedback
output
feedback
Type 7S.43
Safety PLC L
feedback
output
K1
K2
K3
K4
23 47
48
K2 K3
feedback
3
K1 K4
4
IX-2021, www.findernet.com
11
7S 7S SERIES
SERIES Modular relays with forcibly guided contacts 6 - 10 A
Outline drawings
Types 7S.12/14/16/43 Type 7S.23
Screwless terminal Screw terminal
22.5 4.3 96
33.8
59.5
78.8
86.2
30.5
Accessories
Sheet of marker tags, plastic, 48 tags, 6 x 12 mm, for CEMBRE thermal transfer printers 060.48
IX-2021, www.findernet.com
060.48
Drying kilns
Heating and
cooling
Lighting control
in corridors (for
hotels, offices
and hospitals)
Bottling plant
Labelling
machines
Packaging
machines
FINDER reserves the right to alter characteristics at any time without notice. FINDER assumes no liability for damage to persons or property, caused as a result of the incorrect use or application of its products.
77 SERIES 77
Modular Solid State Relays 5 A SERIES
3
77 77 SERIES
SERIES Modular Solid State Relays 7 - 15 A
Simplified Simplified
For outline drawing see page 16 circuit diagram circuit diagram
Output specification
Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO)
Rated current IN/Max. peak current (10 ms) A 15/160 7/60
Rated voltage V DC 24 125
Switching voltage range V DC 16…32 43…140
Rated load DC13 A 5 2.5
DC motor rating kW 0.2 —
Minimum switching current mA 100 50
Typical “OFF-state” leakage current mA 3 6
Max “ON-state” voltage drop
@ 25 °C and IN V 0.06 0.2
Power loss @ IN W 1 1.5
Input specification
Nominal voltage (UN) V DC 6…24 6…24
Rated power W 0.5 0.5
Operating range V DC 4…36 4…36
Must drop-out voltage V DC 3 3
Technical data
Electrical life cycles 10 · 106 10 · 106
Operate/release time ms 0.05/2 0.05/2
Insulation between input
and output (1.2/50 µs) kV 4 4
Ambient temperature °C –20…+70* –20…+70*
Protection category IP 20 IP 20
Approvals (according to type)
VII-2018, www.findernet.com
4
77 SERIES 77
Modular Solid State Relays 15 A SERIES
5
77 77 SERIES
SERIES Modular Solid State Relays 30 A
6
77 SERIES 77
Modular Solid State Relays 30 A SERIES
7
77 77 SERIES
SERIES Hockey puck Solid State Relays 25 - 40 - 50 A