Techinical - Specification - 15kv-Distribution Transfrormer
Techinical - Specification - 15kv-Distribution Transfrormer
1. Scope
1.1. This specification covers the design, manufacture, testing, supply, delivery of three phase
polemounted Hermetically sealed outdoor Distribution Transformers with natural or air
cooling.
1.2. The transformers shall be suitable for Operation in outdoor exposed locations.
1.4. The transformer shall conform in all respects to the highest standards of engineering,
design, workmanship of this specification and the latest revisions of IEC standards at the
time of offer and the purchase will have full right to reject any work or material which are
not in full accordance therewith. The offered equipment shall be complete with all
components necessary for effective and trouble-free operation. Such components shall be
deemed to be within the scope of the bidder’s supply irrespective of whether those are
specifically mentioned or not.
1.5. This Specification may not include all the necessary provisions of the contract
2. System Parameters & Service Conditions
The transformers to be supplied shall be suitable for satisfactory continuous operation under the
following climatic conditions:
S. N Item Parameter
Minimum -50c
Maximum 500c
6 Wind Velocity:
Relevant
StandardIdentifications Title
IEC 60071 Insulation co-ordination
IEC 60076 Power Transformers
IEC60137 Insulating bushings for alternating voltages above 1000 V
IEC 60214 On-Load Tap Changers
IEC 60296 Specification for unused mineral insulating oils for
transformers and switchgear
IEC 60317-0-1-2013 Specifications for particular types of winding wires-Part 0:
General Requirements-Section 1: Enameled round Copper
wire
IEC 60354 Loading guide for oil-immersed power transformers
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC60551 Determination of Transformer and reactor sound level
IEC 60554-3-1 Specification for cellulosic paper for electrical purposes-Part
3: Specifications for individual materials, sheet 1- General
purpose electrical paper.
IEC 60567 Guide for sampling of gases and oil from oil filled electrical
equipment and analysis of free and dissolved gases
In the event of direct conflict between various order documents, the precedence of authority of
documents shall be as follows –
4.1.2 The transformers shall be capable of operating continuously with rated power, and
at30 °C averageyearly temperature and at 50 °C maximum yearly temperature of the
external cooling medium, theirspecified temperature rise limits, i.e., the maximum
permissible temperature rise of the oil (top oil) shall not exceed 50° C, the average
temperature rise of the winding is to be limited to 55°C, and the winding hot spot
temperature rise shall not exceed 68°C as per IEC60076-2.
If the annual temperature varies from 20°C, we will apply correction factors as per
IEC60076-2 Clause 6.3.2 (Table 2).
4.1.3 The transformers shall be capable of withstanding external short circuits for at least
3 seconds following application of loading conditions specified in IEC 60076-7. The
transformer shall have a minimum insulation life of 20.55 years and service life at least
25 years
4.1.4 Neutral points shall be brought out on a bushing to enable LV transformer earthing.
4.1.5 All specific schedules of guaranteed characteristics are stipulated in the technical
schedule. The transformers shall be designed and tendered in full compliance with all
further applicable sections, articles and drawings of the Specification. Furthermore,
each transformer shall comply with the stipulations mentioned hereunder.
4.1.6 All outdoor apparatus, including bushing insulators with their mountings, shall be
designed so as to avoid any accumulation of water.
4.1.7 The transformers of ratings 25kVA, 50kVA, 100kVA, 200kVA, 315kVA and 400KVA
shall be pole mounted type
The transformers shall be core typeoil immersed ONAN cooled, for outdoor application,
designed for continuous operation in the prevailing site conditions.
The design shall be based on site and service conditions as specified in this specification.
The design of the magnetic circuit shall be of non-ageing, Cold Rolled Grain Oriented
(CRGO) Silicon steel of minimum of M3Grade (Nominal thickness of 0.23mm and
maximum total loss at 1.7T to be 0.85w/Kg or better as per IEC 60404-8-7) high
permeability without burrs and such as to avoid static discharges, development of
short circuit paths within itself or to the earthed clamping structure and production of
flux components at right angles to the plane of laminations which may cause local
heating.
Each lamination shall be insulated with high quality insulation coating. The core and
its Clamping plates shall form a rigid unit structure, which shall maintain its form and
position under the severe stresses encountered during shipment, installation and short
circuits.
4.3.2 The flux density
The flux density at any point of the magnetic circuit when the transformer is
connected on tap No. 3 and operating at normal voltage and frequency shall be stated
and shall notexceed 1.7 Tesla.
All parts of the cores shall be of robust design capable of withstandingany shocks to
which they may be subjected during lifting, transport installation and service.
All structural members of the assembled cores shall be of steel. All castings shall be
fettled and structural steel adequately cleaned and painted before being built into the
structure any non-magnetic or high resistance alloy used shall be subject to approval.
Adequate fitments shall be provided to enable the core and windings to be lifted out
of the transformer tank.
The supportingframeworkof the cores shall be designed soas toavoid the presenceof
pockets which wouldpreventcomplete emptyingof the tank throughthe drain
valveorcause trapping of air during filling.
The framework and core bolts shall be effectively insulated from the core so as to
reduce circulating currents to a minimum.
4.4 Windings
4.4.1 General
The HV and LV windings shall be made of continuous smooth high-grade electrolytic
copper as per IEC 60317. The characteristics of copper required shall be as per IEC
60076-5. The Purchaser will inspect the quality of copper material used: size of
copper, number of turns, weight of copper and density…etc.
The three medium voltage windings of the transformer shall be identical in order to
allow interchangeability.
Terminals of all windings shall be brought out of the tank through Bushings for
external connections.
The windings Shall be uniformly insulated and the LV neutral points Shall be
insulated for full voltage.
The completed core and coil assemble shall be dried in vacuum at not more than
0.5mm of mercury absolute pressure and shall be immediately impregnated with oil
after the drying process to ensure the elimination of air and moisture within the
insulation. Vacuum may be applied in either vacuum over or in the transformer tank.
The stacks of windings shall receive adequate shrinkage treatment before final
assembly.
All leads or bars from the windings shall be brought out of the tank through bushings
for connection shall be rigidly supported. Stresses on coils and connections must be
avoided.
The coil clamping arrangement and the finished dimensions of any oil ducts shall be
such that they will notimpedethe free circulationof oil through theducts.
Any metal pieces in contact with end rings shall be so designedand secured that they
do not weaken the electrical or the mechanicalproperties of the rings.
If the transformer winding is built up of sections or disc coils separated by spacers the
clamping arrangements shall besuch that equal pressure is appliedto all columns of
spacers. All suchspacers shall besecurelylocated, shall be ofsuitablematerialand shall
receiveadequate shrinkage treatmentbefore assembly.
Technical data of the Medium Voltage windings (dimensions, number of turns, thicknessand
type of wire, etc..) shall be supplied to Employer for purposes of windings repair, inPurchaser's
workshops.
The data shall be submitted together with the offer, or when submittingdocuments for prototype
approval.
There shall be double layer enamel insulation for the copper winding conductor. The
insulation shall be of class A with temperature class of 105oC as per IEC 60085.
Grade K- Diamond dotted Press Paper(Thermopox): isa press paper with qualities to
improve the mechanical strength of oil immersed transformer windings without reducing
partial discharge levels in accordance with IEC standards 60641-2 and 60243-1
Crepe Paper: Crepe Papers shall be of type 3.2-130-100F or better in accordance with IEC
60554-3-3. It shall have high elongation insulating properties useful for joining and forming
tapping leads of transformers. They shall have low dissipation factor suitable for high
voltage bushings of transformers, wire wrapping, and shielded rings placed within end
sections of Power transformer windings. Crepe papers shall be made from high quality
electrical grade Kraft base papers (100% sulphate wood pulp). The technical characteristics
of the paper according to IEC standards 60554-2 and 60243-1.
4.6 MV Bushings
4.6.1 General design
Bushings shall be outdoor type, easily replaceable and shall be located on the
top.Bushing Material Shall be Porcelain material. Cemented in type bushing shall not
be accepted.The Bushing Shall be manufactured and tested in accordance with IEC
60137 and DIN 42530, DIN 42532, DIN 42534 and DIN42539.
MV bushings shall be rated to withstand the highest system voltage and the
maximum fault current of the windings when connected to the 15kV network and
for the same period of time.
It shall be possible to change the bushings without removing the transformer lid.
Each bushing shall be marked with the name of the manufacturer and type. The
marking shall be visible after assembly of the fittings.
4.6.2 The bushings shall be equipped with line clamps suitable for the connection of
aluminum (up to 240mm2) orcopper (up to 120mm2) conductors of medium voltage
line. The clamps shall be complete with necessary screws, washers and nuts.
Clearance
Voltage Phase to Phase Phase to Earth and Phase to Neutral Creepage Distance
The outer creepage distance for outdoor bushings shall not be less than 31mm/kV.
The insulation levels of the bushings shall conform to the given in the technical
schedule.
System Distance between
Voltage Current Creepage Bushings Centers
(KV) Porcelain Type (A) Distance (mm)
15KV 30NF DIN 42532 630 525 280
30NF DIN 42533 Or
33KV 52/1000 DIN 42534 630 1080 480
The Bidder shall submit to the Purchaser Type tests reports of medium voltage bushings,
for approval of the bushings in the proposed transformers. The type tests shall be
performed according to the latest published International Standard IEC 60137 and shall
include the following type tests:
Wet power-frequency voltage withstand test
Dry lightning impulse voltage withstand test
Temperature-rise test
Verification of thermal short-time current withstand test
Cantilever load withstand test
Verification of dimensions
The MV Rod diameter shall be greater than or Equal to M20 depending the current.
4.7 LV Bushings
The position of each LV bushing shall be permanently and legibly marked on the tank or
lid with a label corresponding to the rating plate designation. The LV neutral connection
shall have a permanent, special marking, different from the phase connections.
The LV Rod diameter shall be greater than or Equal to M20 depending the current.
The Transformer shall be capable of carrying its normal rating continuously at any tap
without undue stress and Overheating.
All transformers shall be capable of withstanding for three seconds without damage any
external short-circuit.
Any wiring liable to come in contact with oil shall have suitable oil resisting insulation.
The ends of stranded conductors shall be treated to prevent creepage of oil inside the
wire. There shall be no possibility of oil entering connection boxes for cables or wiring.
Unless otherwise approved high temperature, insulation shall be provided on all wiring
when this comes into contact with the transformer tank.
Where the use of conduits is agreed the runs shall be laid with suitable falls and the
lowest parts of the run shall be external to the kiosks or boxes. All conduit-runs shall be
adequately drained and ventilated. Conduits shall not be run at or below ground level.
The external cabling on transformers shall be armored or alternatively protected from
mechanical damage in an approved manner.
Rated short
duration power Rated lightning
Highest voltage frequency impulses
System for equipment withstand voltage, withstand voltage,
Voltage(kV) Um kV (rms.) kV(rms.) kV (peak.)
15 24 50 125
4.13.3 Rated Power
The rated output at +50°C maximum ambient temperature shall be one of the preferred
ratings 25, 50, 100, 200, 315 and 400Rated Voltage
T
h
e
((15/0.4 (Phase to Phase)) KV
Three-phase 4 wire LV
t
((15/.22)(Phase to Neutral)) KV
r
ansformers are required to operate from the 15kV network as follows:
All secondary voltage ratings shall be at full load current at nominal tap.
4.13.4 Vector Group
The vector group of the three-phase transformers shall be Dyn5.
4.13.5 Impedance Voltage
The Percentage impedance of transformer at 75oC shall be as stated in the following
table as per IEC 60076-5. The tolerance will be +/-10% at principal tapping and +/-
15% at any other tapping of the pair
KVA
Rating 25 50 100 200 315 400
% Impedance for15kV 4 4 4 4 4 4
The MV windings shall be provided with an off-load tap changer providing 5 positions
and each step shall be 2.5%. The tap settings shall be 5% +2.5%, 0%, -2.5%, -5%, for
three phase transformers.
The off-load tap changer shall have an externally operated mechanism for manual
operation. The selector switch shall be gang-operated by an accessible single handle
from the ground at convenient floor height Tap positions shall be clearly identified. The
operating mechanism shall have an effective locking device for locking the tap changer
in any desired position. All transformers shall be capable of
operationcontinuouslywithout injurious sheathingwhen operatingon any tappingposition
and at 150% continuous loading andover-voltage surges.
4.15 Losses
The bid shall be accompanied with Type test reports (Short circuit test and Impulse test)
conducted at independent third-party testing Laboratories for the offered
transformersincluding the surge arrestorwithin five years from the date of the bid.Type
tests shall be conducted on the Transformers of identical design to prove that the
offered transformers satisfy all the design requirements set out in this specification.
In case of any doubts, Ethiopian Electric Utility (EEU) reserves the right to verify
the original type test reports of the independent third-party testing Laboratory or ask the
supplier to conduct the type tests at an independent third-party independent testing
laboratory which is approved by EEU Type test without ADDITIONAL COST to the
employer (EEU)
The maximum Load losses and No-Load losses at rated load and conditions shall be
as given below:
The above losses are the maximum allowable and there should not be any positive
tolerance.Bids with higher losses than the above specified values would be treated as
non-responsive and will be rejected automatically.
Bidders are required to submit their guaranteed No losses and Load losses(at 75oC)
for each proposed transformer type.
However, the manufacturer/Supplier can offer losses less than the above stated values.
The utility will evaluate offers with losses lower than the maximum allowable losses on
total owning cost basis in accordance with IEC 60076-20-2017 Appendix A.
In comparing Bidder’s proposal and for Penalty losses will be capitalized at the rates
given Below:
If the Bid currency is other than US$ the exchange rate at the time of bid submission
will be used.
If, on delivery, the tested losses exceed the guaranteed losses up to 20% then losses in
excess of the guaranteed valuesshall be capitalized at the evaluation rate and the amount
deducted from the contract price. If the measured value of loss is above 20% of the
quoted value, the purchaser shall reject the transformer.
There will be no credit for losses less than the guaranteed value other than for
evaluation purposes.
4.16 Transformer Tanks
4.16.1 Tank with Accessories
The tank Shall be of Hermetically Sealed Construction. The transformer top cover shall
be bolted type and fitted with neoprene bonded cork gasket suitable for temperatures as
specified in this specification.
The top cover of the tank shall be slightly sloping to drain rain water.
The tank shall be designed for natural cooling (ONAN) with corrugated walls.
The main tank body shall be pressure tested and a certificate issued/signed by ISO/IEC
17025 Accredited Laboratory ascertaining the soundness of all welded joints in
accordance with relevant ISO standards. A copy of certificate shall be supplied. Tanks
with corrugations shall be tested for leakage test at a pressure of 0.25kg/cm² measured
at the bottom of the tank.Cooling fins shall be welded with round stiffening rods to
prevent vibration during operation of the transformers.
The tank design shall be such that the core coil assembly can be lifted freely.
Lifting lugs shall be available for lifting the core and coils out of the tank. The hooks
that will be used for anchoring the core shall be so located as not to foul with the core
coil assembly.
Gaskets used shall be oil resistant and made of such a material that no serious
deterioration occurs under service conditions. Rubber gaskets used for flange
connections of the various oil compartments shall be laid in grooves. Gaskets of
neoprene and/or such material which can be easily damaged by over-pressing (e.g., any
kind of impregnated/ bonded cork) are not acceptable. Use of hemp as gasket material
is also prohibited.
The smaller parts such as brackets, etc. shall be hot-dip galvanized. Fasteners mounted
on hot-dip galvanized or ready painted part shall be galvanized or made of stainless-steel
ISO class F1 or A2.
All steel surfaces shall be sand blasted in accordance with DIN 55928 Part 4 and shall
then be painted in the following sequences.
Layer
Coatings Kind Thickness
One (1) primer two-component epoxy zinc phosphate 60µm
coat
One (1) Two-component epoxy micaceous 60µm
intermediate coat iron oxide
One top coat (1) Two-component polyurethane 40µm
Total coatingsthickness (dry film) 160µm
The final coat of painting shall be of pore free and homogeneous quality and shall be of
a uniform shade of code RAL 7032(silica grey) paint for the outside surfaces.
Manufactures are free to select the inner transformer paint color.
If any hot dipped galvanized parts are provided the same painting method shall be
applied, however instead of two primer coats one adhesive coat and one base coat shall
be applied. In this case the mean thickness of galvanizing shall be 70 µm. Mechanical
damage shall be repaired at site with original paint as above.
4.16.6 Filling Valves
A filling stub with an inner diameter of at least 25-mm shall be placed at the top of the
cover.
Each transformer shall be supplied with standard insulating oil conforming to the
requirements of IEC 60156 and the oil shall have a high dielectric strength (breakdown
voltage >70KV).
The type of insulating liquid, e.g., “Mineral oil-based insulating oil pursuant to DIN
VDE 0370”/relevant IEC is to be indicated on the rating plate of eachtransformer.
4.18 Lightning/SurgeArrester
Each Transformer Shall be complete with lightning/Surgearrestor mounted on brackets
(one per phase) fitted under the HV bushings with galvanized iron earth strip of at least
25mmX4mm connected to the body of the transformer with necessary fixing
arrangements suitable to allow for physical disconnection of operated surge arrester.
The fixing arrangement for the surge arresters shall be universal type to accept a wide
range of Lightning/Surgearresters and shall be subject to approval by Ethiopian Electric
Utility before manufacture.
All ferrous parts of mounting brackets shall be protected against corrosion by the hot
dip galvanizing to ISO 1461.
The bid shall be accompanied with Type test reports conducted at independent third-
party testing Laboratories for the offered Lightning Arrester within five years from the
date of the bid.
4.19 Undercarriage
The following undercarriage shall be provided as specified in the technical schedules.
A grounding sign shall be put next to the grounding screw. The marking shall be
stamped and red color painted on tin plates which shall be fastened with transformer.
1) Rating and diagram plates bearing the data specified in the appropriate IEC
recommendations.
2) Oil filling and drain valves. It shall only be possible to open these valves with a special
key/spanner todiscouragetampering.
3) Tank earthing terminal. M12 size screws -2 Nos. one on the tank cover and another on
the base frame suitable for copper earthing wires.
5) Oil level indicator: This shall be readable by an operator standing at ground level at
distance of up to 5 meters away from the transformer. It shall have maximum and
minimum oil level markings which shall fall within range.
8) Pressure relief Device: The pressure relief device shall have a flow rate of 16.5 litres/sec
at 100KN/sqm operating pressure shall be 40KN/m2
9) Top oil thermometer
15) Galvanized steel plates (for installation of lightning/Surge arresters and fuses)
5. Inspection andTesting
The tests shall be performed in accordance with the latest published recommendations of the
IEC 60076 and this specification by and at the expense of the manufacturer.
For Medium Voltage Bushing tests, please refer clause 4.6.6
The pertinent professionals shall be given access to the Manufacturing Works (Factory) at all
reasonable times for the purpose of inspection of the manufacturing and testing facilities
available in addition to inspection of the equipment.
The tests will be divided into the following categories:
1. Type Tests,
3. Acceptance Tests.
Prior to the tests the supplier shall submit an outline of the procedures and tests in its plans, to
demonstrate fulfilment of the requirements specified in subsequent sections of the detailed
technical specification.
Before regular manufacturing commences, samples of the equipment i.e. The transformers shall
be made available for testing to ensure compliance with the design.
The Buyer reserves the right to call for type tests on the equipment at the Supplier’s expense, on
samples selected at random at the Manufacturer's Works and witness these testsat an approved
independent third-party standard Laboratory. Failure to meet the conditions of test could result
in the rejection of a complete batch of equipment’s.
The Buyer will have the authority to delay delivery of any items of equipment, which have not
been tested and approved in accordance with the Contract.
The Supplier shall report on progress and will compare the Supplier’s production program with
actual progress and shall report in a timely manner to the Employer the reason for any delays.
The Supplier shall submit copies of the Routine test reports of the equipment/ material along
with the inspection offer.
The inspection and acceptance tests shall be carried out in accordance with the provisions in the
applicable standard, supplemented by the specific requirements indicated in the technical
specifications free of cost to the Employer.
At least 15 days’ notice of the date, time and place of all tests shall be given to the Buyer so that
arrangements can be made to have the test witnessed.
In addition to the above requirements, the following requirements shall apply and take
precedence.
Checking of weights, dimensions, fittings, accessories, tank sheet thickness, oil quality,
material, finish and workmanship as per Guaranteed Technical Particulars and contract
drawings.
3) Measurement of short circuit impedance and load loss (IEC60076-1, clause 11.4)
8) Leak testing with pressure for liquid immersed transformers (IEC60076-clause 11.8).
9) Tightness tests and pressure tests for tanks for gas filled transformers (IEC60076-15).
10) Check of core and frame insulation for liquid immersed transformers with core or frame
insulation (IEC60076-clause 11.12).
1) Visual Inspection
3) Voltage ratio measurement and check of polarity or vector group symbol - at all tap
positions. Bushing positions shall have permanent markings at this stage of production.
8) Dielectric test
9) Induced over voltage withstand test -30kV and 66kV for 60 seconds on the 15kV and
33kV windings respectively.
11) Coordination test for LV circuit breaker and HV Fuse links, if applicable.
6. Marking
Each transformer shall be provided with a rating plate showing the information stated in the
IEC standards. The plate shall be in both Amharic and English. The words "Property of
Ethiopian Electric Utility", the EEU logo, the contract number and loan number and a unique
identification number (to be advised by the Employer) shall also be engraved on the rating plate.
1) A rating plate bearing the data specified in IEC 76 or other approved standard.
Indicating the following shall be fixed on the same side as LV bushings,
2) Name of manufacturer,
4) Year of manufacture,
5) Rated power,
6) Rated frequency,
7) Rated voltages,
8) Rated currents,
17) Each bushing shall be marked with the name or trademark of the manufacturer,
18) A diagram plate showing the internal connections and also the voltage vector
relationship of the several windings. In addition, a plan view of the transformer giving
the correct physical relationship of the terminals shall be given. When links are provided
for changing the transformer group symbol and/or ratio, then means shall be provided
for clearly indicating in which mode the transformer is connected. The transformer ratio
shall be indicated for each tap,
20) The above plates shall be ofanodized sheet aluminium OR stainless steel or of other
material capable of withstanding continuous outdoor service and shall all be suitably
mounted to prevent vibration, rattling or corrosion.
7. TRANSPORT
Irrespective of the actual method approved for transport to the individual site, all transformers
shall be suitable for transport with the transformers full of oil unless otherwise approved.
The Supplier shall be responsible for ascertaining the methods and limitationsof transport to site
and designs affected by these factors be subject to agreement.
8. PACKAGING
Each Packaging Shall be clearly marked in Print (Capital Letters) with the following data in each
transformer:
Manufacturer/Supplier Name and Trademark
Ethiopian Electric Utility
Contract No.
Serial No
Transformer size and Weight
Instructions for unloading with a mobile crane and with a fork-lift truck, checking of the
correctlybalanced during the transportation.
Lifting and Tying Points
Each transformer shall be covered by separate transparent Plastic
9. QUALITY PLANS
The bidder shall draw up for each section of the work quality plans which shall be submitted to
the Purchaser for approval at least two weeks prior to the commencement of work on the
particular section. Each quality plan shall set out the activities in a logical sequence and, unless
advised otherwise, shall include the following:
III. WINDINGS
20 HV Windings
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
No Item Unit Requirement Bid Offer
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
III. WINDINGS
20 HV Windings
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
III. WINDINGS
20 HV Windings
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
III. WINDINGS
20 HV Windings
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70
III. WINDINGS
20 HV Windings
VI. BUSHINGS
31 Primary
31.1 Manufacturer
31.2 Rated current A 630
No Item Unit Requirement Bid Offer
31.3 Power frequency Withstand KV 50
31.4 Lightning Impulse Withstand KV 125
31.5 Clearance across insulator mm 280
31.6 Adjustable arcing horns yes/no Yes
31.7 Creepage distance (minimum) mm >525
31.8 Specification of creepage distance IEC 60815-2/2008
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 Rated current A
32.4 Power frequency Withstand KV 3
32.5 Lightning Impulse Withstand KV 8
32.6 Clearance across insulator mm 80
32.7 Creepage distance mm 70