Elect 2
Elect 2
i 1 p SIZE OF PVC
CKT. LOAD DESCRIPTION VA LOAD VOLTS AMPERE CKT. BREAKER SIZE & TYPE OF COPPER CONDUCTOR
CONDUIT SERVICE ENTRANCE
h
FIRE EXIT 1 LIGHTING, 14PCS X 25W/PC 350 230 1.52 15 A 2-2.0MM² THHN + 1-2.0MM² THHN GROUND WIRE 20mm DIA.
c k PANEL BOARD
c
Sghi
J
2 LIGHTING, 11PCS X 25W/PC 275 230 1.2 15 A 2-2.0MM² THHN + 1-2.0MM² THHN GROUND WIRE 20mm DIA.
Sj Sk l CONV. OUTLET, 1500W/CKT 1500 230 6.52 20 A 20mm DIA.
b Sl 3 2-3.5MM² THHN + 1-3.5MM² THHN GROUND WIRE CIRCUIT BREAKER
FIRE EXIT
h LP Snop
4 CONV. OUTLET, 1500W/CKT 1500 230 6.52 20 A 2-3.5MM² THHN + 1-3.5MM² THHN GROUND WIRE 20mm DIA.
1 CIRCUIT HOMERUN
n p 5 SPARE 1000 230 4.35 20 A 20mm DIA.
d 2-3.5MM² THHN + 1-3.5MM² THHN GROUND WIRE
a a
6 SPARE 1000 230 4.35 20 A 2-3.5MM² THHN + 1-3.5MM² THHN GROUND WIRE 20mm DIA. LIGHTING OUTLET
g Sabc Sdef
TOTAL
Sm 5625 230 40 A 2-8.0MM² THHN + 1-5.5MM² THHN GROUND WIRE 20mm DIA.
2 S(3W) 3-WAY SWITCH
g f e f e m
FIRE EXIT SERVICE-ENTRANCE & FEEDER CALCULATION FOR PANEL BOARD:
o DUPLEX CONVENIENCE OUTLET
p VA LOAD = 350+275+1500+1500+1000+1000 = 5625 VA
I T = 5625 VA / 230 V x 0.80 DEMAND FACTOR = 19.57 A DUPLEX CONVENIENCE OUTLET,
o USE: 2-8.0MM² THHN + 1-5.5MM² THHN CU. IN 20 MM DIA. PVC WITH 40AT CIRCUIT BREAKER PROTECTION WP WEATHER -PROOF
FIRE EXIT
SPECIAL-PURPOSE OUTLET
LIGHTING LAYOUT PLAN USE: 2-8.0MM² THHN CU. FOR MAIN FEEDER
(AIRCON OR ELECTRIC RANGE)
SCALE 1:60 M 230V, 1-PH, 60-HZ + 1-5.5MM² THHN CU. FOR GROUNDING ELECTRODE CONDUCTOR
SPST SWITCH (LETTER INDICATE
S IDENTIFICATION & QYT. OF SWITCHES)
M
SERVICE DISCONNECT
SERVICE-ENTRANCE GROUND
PANEL BOARD
SPECIFICATIONS & GENERAL NOTES:
FIRE EXTINGUISHER
WP 1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE
PHILIPPINE ELECTRICAL CODE (PEC), GUIDELINES & REGULATIONS OF THE OFFICE OF THE BUILDING
WP FIRE EXIT OFFICIAL (OBO/EE), AND SERVICE-ENTRANCE REQUIREMENT OF THE ELECTRIC POWER UTILITY COMPANY
3 L.O. L.O. (ANTECO).
2. ELECTRIC SERVICE TO THE BUILDING SHALL BE 230-VOLT, 60-HERTZ, SINGLE-PHASE, 2- WIRE.
4
3. TYPE OF WIRING SHALL BE RSC, EMT, OR PVC CONDUIT FOR SERVICE ENTRANCE AND PVC CONDUIT
FIRE EXIT
11. ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL
ENGINEER (PEE/REE) OR A REGISTERED MASTER ELECTRICIAN (RME).
PRC NO : 0003605
PREPARED BY: PROJECT TITLE: APPROVED BY: SHEET CONTENT: REVISION: SHEET NO:
DATE ISSUED : 01/04/2023