2019 Ampacity-Calculations
2019 Ampacity-Calculations
90º for
DERATING
Copyright 1999-2019 Dan Dudley
NEC 2014 Article 110.14
(C) Temperature Limitations. The temperature
rating associated with the ampacity of a conductor shall
be selected and coordinated so as not to exceed the
lowest temperature rating of any connected termination,
conductor, or device. Conductors with temperature
ratings higher than specified for terminations shall be
permitted to be used for ampacity adjustment,
correction, or both.
(a) Termination provisions of equipment for circuits rated 100 amperes or less, or marked for 14 AWG
through 1 AWG conductors, shall be used only for one of the following:
(2) Conductors with higher temperature ratings, provided the ampacity of such conductors is determined based
on the 60°C (140°F) ampacity of the conductor size used.
(3) Conductors with higher temperature ratings if the equipment is listed and identified for use with such
conductors.
(4) For motors marked with design letters B, C, or D, conductors having an insulation rating of 75°C (167°F) or
higher shall be permitted to be used, provided the ampacity
of such conductors does not exceed the 75°C (167°F) ampacity.
(2) Conductors with higher temperature ratings, provided the ampacity of such
conductors does not exceed the 75°C (167°F) ampacity of the conductor size
used, or up to their ampacity if the equipment is listed and identified for use with
such conductors
• Grounded Conductor
– Carries unbalanced load
– Is not counted if it only carries the
unbalanced load.
– Must be counted as a current carrying
conductor if load consists of flourescent
lighting or other harmonic loads.
Copyright 1999-2019 Dan Dudley
Ampacity Calculations #1
What is the Maximum allowed ampacity for
a single #2 THHN Conductor installed in a
circuit.
Step 1. 110.14(c) (#14 thru #1)
Step 2. Table 310.15(B)(16) (60°C Column)
Step 3. Read Ampacity
95 Amps
Copyright 1999-2019 Dan Dudley
Ampacity Calculations #2
What is the Maximum allowed ampacity for
a single #2 THHN Conductor not installed in
a circuit.
Step 1. Table 310.15(B)(16) (90°C Column)
Step 3. Read Ampacity
130 Amps
Copyright 1999-2019 Dan Dudley
Ampacity Calculations #3
What is the Maximum allowed ampacity for a
single # 500 Kcmil THHN Conductor installed
in a circuit with both 75° and 90° lugs.
Step 1. 110.14(c) (Larger than #1)
Step 2. Table 310.15(B)(16) (75°C Column)
Step 3. Read Ampacity
380 Amps
Copyright 1999-2019 Dan Dudley
Copyright 1999-2019 Dan Dudley
Adjustment Factors
#4/0 THHN
Copyright 1999-2019 Dan Dudley
Ampacity Test Questions
30 Minutes