Guidelines For UPS Battery Room - PDF - V2.0
Guidelines For UPS Battery Room - PDF - V2.0
1 Battery Overview
There are primarily three kinds of batteries used in UPSs—vented lead acid (VLA) (also
called flooded-cell),valve-regulated lead-acid (VRLA), and sealed or maintenance-free lithium-
ion batteries.VRLA batteries usually have lower up-front costs but have a shorter lifetime of
around five years.Flooded-cell batteries require more maintenance but have a longer lifetime,
up to 20 years.Lithium-ion batteries are smaller and lighter than the above types and have
changed the traditional status quo for UPS use.Costs are like VRLA, and new energy storage
applications with UPS systems, such as gridsharing and peak shaving, are now viable.These new
capabilities provide more than just backup time and can now contribute to significant cost
savings for the user in their day-to-day operations.
2 Lead-Acid Batteries
Lead-acid batteries are the most widely used electrical energy storage, primarily for
uninterrupted power supply (UPS) equipment and emergency power system (inverters). Lead-
acid batteries release hydrogen gas that is potentially explosive.The battery rooms must be
adequately ventilated to prohibit the build-up of hydrogen gas.The hydrogen generation is
relatively small during normal operation.However, significant hydrogen can be produced during
rapid and deep discharge of the battery.
2.1 Types Of Lead-Acid Batteries
2.1.1 Vented Lead-acid (VLA) Batteries
Vented Lead-acid Batteries are commonly called “flooded” or “wet cell” batteries. VLA is
an exceptionally reliable design, so failures are uncommon until halfway of their 20-year pro-
rated life. The most common failure mode is a short circuit and even that is not an emergency,
as long as the fault is localized. However, there are downsides to flooded-cell batteries. VLA
batteries require more maintenance,safety and space. VLA batteries have thick lead-based
plates that are submersed in an acid electrolyte. The electrolyte depletes over time so distilled
water must be added periodically. Also, hydrogen is produced during charging. The hydrogen is
evacuated through vents. Hydrogen is highly flammable and explosive, so these batteries must
be installed in a ventilated room. OLSEH mandates 6 air-changes per hour in the battery room.
2.1.2 Recombinant Valve-Regulated Lead-acid (VRLA)Batteries
VRLA batteries are sealed, usually within polypropylene plastic, so there is no sloshing
acid that can leak or drip when inverted or handled roughly.The term “valve-regulated” refers
to the method of gas release.If the gas pressure becomes too great inside the battery, the valve
will vent when it reaches a certain pressure.
Recombinant cells have a starved or gelled electrolyte.The oxygen generated from the
positive electrode during charging diffuses to the negative electrode producing water:
Pb + H2SO4 + ½O2 → PbSO4 + H2O
The recombinationreaction suppresses hydrogen evolution at the negative electrode,
thereby allowing the cell to be sealed.In practice, the recombination efficiency is not 100% and
a pressure relief valve regulates the internal pressure at a relatively low value, generally below
10 psig.
2.2 Comparison between flooded and sealed batteries
The diagram below shows a comparison between vented battery gassing and VRLA
battery recombination.
3 Lithium-Ion Batteries
Lithium batteries have significant benefits over lead-acid batteries for UPS, for
example,smallsize, light weight, high cycle-count (charge-discharge cycles), faster recharge
times, and built-in battery management (not just monitoring). The technology is
underactivedevelopment due to the demand fromheavy-duty sectors like e-mobility.
4 Battery Hazards
5 Battery Safety
5.1 Prevent thermal runaway
a. Proper Storage Temperature: Always store batteries at safe temperatures.The ideal
storage temperature for most lithium-ion batteries is between 40-70 degrees
Fahrenheit (5-20 degrees Celsius).However, this can differ based on the battery and
manufacturer, so consult the label for your specific battery.
b. Proper Ventilation: One of the easiest ways to maintain a safe operating temperature is
properly ventilation.All the electronics needed to manage your battery system, plus the
batteries themselves, produce heat.The heat generated by the batteries and electronics
must be dissipated.
c. Replace Old Batteries:Old battery must be replacedbefore end-of-life.If you have an old
battery that has been uncharged or undercharged, it may have built up gasses within
the casing, which can easily cause an explosion.If you see a deformed or “bubbled”
battery, do not attempt to charge it.Properly dispose of and replace any deformed
batteries.
Storage area Separate storage area Separate storage area Separate storage
(cabin) required not required area not required
Ventilation Forced ventilation for Room/lab should be Room/lab should be
the separate cabin is adequately ventilated adequately
required ventilated
Ideal temperature 25 C 25 C 25 C
Flammable Gas 20 Ft clearance 20 Ft clearance 20 Ft clearance
cylinders/pipelines distance required distance required distance required
Housekeeping Dust accumulation Dust accumulation Dust accumulation
should be prevented should be prevented should be prevented
PPE required for Electrical safety shoes Electrical safety shoes Electrical safety
accessing the & acid resistant gloves are required shoes are required
storage area are required
Sign boards Entry restricted; Electrical hazard Electrical hazard
required Electrical hazard
Dust accumulation
Poor housekeeping near battery
storage area.
Wash basin near the battery storage
area
[2] Bro, P. and Levy, S., 2006. Battery Hazards and Accident Prevention. New York, NY: Springer.
[3] Exide's Do's and Don'ts for Sealed Maintenance Free Batteries, 2022
[4] The large UPS battery handbook, EATON
[5] Technical Bulletin, 41-2128, Charging Valve Regulated Lead Acid Batteries, C&D Technologies
8 Appendix
8.1 Typical Layouts of a Battery & UPS Room
Below if sample layout of the battery room in a lab. The layout is exemplary. It does not include
dimensions because details will be different for each lab.
8.1.1 For Vented Lead-acid Batteries