Specification
Specification
PART1
DIVISION 03 - CONCRETE
031000 CONCRETE FORMING AND ACCESSORIES 09
032100 CONCRETE REINFORCEMENT 08
033000 CAST-IN-PLACE CONCRETE 67
033420 SAND CEMENT SCREED 05
033430 SELF-LEVELING SCREED 05
034900 GLASS-FIBER-REINFORCED CONCRETE (GRC) 13
037100 MASS CONCRETE 08
DIVISION 04 – MASONRY
042200 CONCRETE UNIT MASONRY 16
042250 LIGHT WEIGHT CONCRETE MASONRY 07
044200 EXTERIOR STONE CLADDING 16
DIVISION 05 – METALS
055000 METAL FABRICATIONS 14
055130 METAL LADDERS 03
055213 PIPE AND TUBE RAILINGS 12
057300 DECORATIVE METAL RAILINGS 16
057313 GLAZED DECORATIVE METAL RAILINGS 12
PART 2
DIVISION 08 – OPENINGS
081113 HOLLOW METAL DOORS AND FRAMES 13
081416 FLUSH WOOD DOORS 08
084213 ALUMINUM-FRAMED ENTRANCES 13
084413 GLAZED ALUMINUM CURTAIN WALLS 17
085113 ALUMINUM WINDOWS 09
086300 METAL FRAME SKYLIGHT 10
087100 DOOR HARDWARE 18
088000 GLAZING 16
088300 MIRRORS 07
089119 FIXED LOUVERS 08
DIVISION 09 – FINISHES
092400 CEMENT PLASTERING 10
092900 GYPSUM BOARD 18
093013 CERAMIC TILING 17
093033 STONE TILING 11
095123 ACOUSTICAL TILE CEILINGS 13
095133 ACOUSTICAL METAL PAN CEILINGS 10
096516 RESILIENT SHEET FLOORING 08
096536 STATIC-CONTROL RESILIENT FLOORING 08
096723 RESINOUS FLOORING 07
096766 FLUID APPLIED ATHLETIC FLOORING 06
096813 TILE CARPETING 08
096816 SHEET CARPETING 07
097200 WALL COVERING 07
099113 EXTERIOR PAINTING 11
099123 INTERIOR PAINTING 16
DIVISION 10 – SPECIALTIES
102113.17 PHENOLIC-CORE TOILET COMPARTMENTS 06
102800 TOILET BATH AND LAUNDRY ACCESSORIES 06
104413 FIRE PROTECTION CABINETS 07
104416 PORTABLE FIRE EXTINGUISHERS 05
DIVISION 11 – EQUIPMENT
116800 PLAY FIELD EQUIPMENT AND STRUCTURES 05
DIVISION 12 – FURNISHINGS
129300 SITE FURNISHINGS 07
PART 3
DIVISION 22 – PLUMBING
220000 PLUMBING GENERAL PROVISIONS 41
220500 COMMON WORK RESULTS FOR PLUMBING 12
220513 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT 05
220516 EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING 07
220519 METERS AND GUAGES FOR PLUMBING PIPING 07
220523 GENERAL-DUTY VALVES FOR PLUMBING PIPING 13
220529 HANGERS AND SUPPORTS FOR PLUMPING PIPING AND 11
EQUIPMENT
220548 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING 09
AND EQUIPMENT
220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT 09
220719 PLUMBING PIPING INSULATION 12
221116 DOMESTIC WATER PIPING 17
221119 DOMESTIC WATER PIPING SPECIALTIES 12
221123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS 10
221123.14 IRRIGATION WATER PUMPS 08
221224 WATER STORAGE TANKS 06
221316 SANITARY WASTE AND VENT PIPING 10
221319 SANITARY WASTE PIPING SPECIALTIES 14
221329 SANITARY SEWERAGE PUMPS 08
221413 FACILITY STORM DRAINAGE PIPING 08
221423 STORM DRAINAGE PIPING SPECIALTIES 07
223200 DOMESTIC WATER FILTRATION EQUIPMENT 11
223600 SWIMMING POOL 27
224000 PLUMBING FIXTURES 11
PART 4
DIVISION 26 – ELECTRICAL
260500 COMMON WORK RESULTS FOR ELECTRICAL 12
260513 MEDIUM VOLTAGE CABLES 10
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND 16
CABLES
260526 GROUNDING & BOUNDING OF ELECTRICAL SYSTEMS 09
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 06
260533 RACEWAYS AND ACCESSORIES 09
260536 CABLE TRAYS FOR ELECTRICAL SYSTEMS 13
260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL 10
SYSTEMS
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS 09
260573.13 SHORT-CIRCUIT STUDIES 06
260573.16 COORDINATION STUDIES 10
260923 LIGHTING CONTROL DEVICES 11
260926 LIGHTING CONTROL PANELBOARDS 15
261326 MEDIUM-VOLTAGE, METAL-CLAD SWITCHGEAR 29
262040 LIGHTING FIXTURES AND ACCESSORIES 12
262200 LOW-VOLTAGE TRANSFORMERS 12
262413 SWITCHBOARDS 29
262416 PANELBOARDS 08
262419 MOTOR CONTROL CENTERS 22
262500 LOW VOLTAGE ENCLOSED BUS ASSEMBLIES 12
262713 ELECTRICITY METERING 07
262726 WIRING DEVICES 09
262923 VARIABLE-FREQUENCY MOTOR CONTROLLERS 13
263213 ENGINE GENERATOR 20
263323.13 CENTRAL BATTERY EQUIPMENT FOR EMERGENCY LIGHTING 25
263353 STATIC UNINTERRUPTIBLE POWER SUPPLY 22
263533 POWER FACTOR CORRECTION EQUIPMENT 07
263600 TRANSFER SWITCHES 11
264113 LIGHTNING PROTECTION FOR STRUCTURES 06
265119 LED INTERIOR LIGHTING 20
PART 5
DIVISION 31 – EARTHWORK
313116 TERMITE CONTROL 04
PART 1 - GENERAL
A. The Qatar construction specification (QCS 2014) shall form the basis of the project specification. The
technical specification is supplemental to QCS (latest revision) and should be read in conjunction
with QCS and all other contract documents. In case of contradiction or discrepancy between QCS
and technical specifications, CONTRACTOR shall incorporate whichever is more stringent.
B. The scope of works for all mechanical works and systems comprises engineering, supply,
delivery, installation, testing and commissioning, handover, training, maintenance and
warranty as described or reasonably implied in the Contract. Contractor is obliged to
provide fully functioning works and systems in conformance with the requirements of the
Contract. In the event certain items are not fully described or indicated in the Contract,
but deemed essential by the Engineer (in all reasonableness) for the performance of the
works and systems then the provision of such items shall form part of Contractor’s scope
of works at no additional cost to Employer.
C. All cold water draw-off points / taps will be supplied from domestic water storage tank and
entered to the plate heat Exchanger supplied from Chilled water system for the domestic
water cooling purpose. The cold water draw-off taps water temperature to be maintained
at 280C.
D. Domestic hot water draw-off points / taps will be supplied via a hot water storage tank
supplied from LTHW Boiler system for the domestic water heating purpose. The hot
water storage tank secondary outlet temperature to be maintained at 600C.
E. The minimum and maximum residual pressures for hot and cold water faucets shall be as
under:
i. Guest washrooms: Min.: 1.5 bars, Max.: 5.5 bars and the optimum: 2.0 bars.
ii. Residential Suites washrooms: Min.: 1.5 bars, Max.: 2.8 bars and the optimum: 2.0 bars.
iii. Public Washrooms: Min.: 2.0 bars, Max.: 5.5 bars and the optimum: 3.0 bars.
iv. Hose Bibbs: Min.: 3.5 bars, Max.: 4.5 bars and the optimum: 4.0 bars.
v. Kitchen sink, cleaner sink and janitor sink: Min.: 3.5 bars, Max.: 4.5 bars and the
optimum: 4.0 bars.
F. The maximum flow rate for hot and cold water faucet shall be as prescribed in the Section
224000 “PLUMBING FIXTURES”
G. Inlet pressure for the Sub-meter of water supply shall not exceed 2.8 bars as recommended
by Kahramaa.
H. Where reverse flow along the cold feed is prevented, provide an expansion vessel in
accordance with BS 6144 to accommodate expansion water. This vessel shall be sized in
accordance with the volume of water heated and the water temperature rise so as to limit
the pressure to the maximum working pressure for the system. The expansion vessel shall
accommodate an expansion equal to 4% of the total volume of water heated. Any
discharge from relief valves shall be readily visible and disposed of safety.
I. The contractor is responsible to connect drainage line (soil/waste) and water line (including
isolation valves) to any equipment as per final equipment/furniture layout whatever
showing in the design drawings or not without any variation in time and cost.
J. Contractor shall be responsible to co-ordinate the equipment and services and shall produce
properly coordinated shop drawings to demonstrate the installation comply with the
performance requirement with shop drawing, calculations and details.
K. Shop drawings shall take into account actual measurement and setting out dimensions/levels
obtained and determined by Contractor on site, actual equipment/material used, actual
routing of services, co-ordination with all installation, and site conditions/constraints.
L. The installation, materials and all components shall comply with all statutory instruction and
regulations current at the time of tender whether so detailed or not, and shall confirm in
all respects with the following:
8. Should any conflict arise between the codes and standard mentioned above,
regulations issued by the State of Qatar shall take precedence.
9. Other electromechanical codes and standards:
M. Where there is conflict between any local authority or codes requirements and the drawings
or specifications, requirements of local authorities & codes shall govern without any
additional cost and/or time.
O. Plumbing provisions/connections shall be provided as per the final ID and kitchen specialist
design without any variation in time/cost.
P. The contractor shall provide all valves, fitting and equipment for all plumbing system
whatever shown in the design document or not and provide complete solutions for the
systems for proper operation and high efficient system as per codes and standers and
manufacturer recommendation/perquisites.
Q. The contractor shall check the equipment location including but not limited to (pumps,
boilers, calorifiers, heat exchanger, etc..) and provide complete selection and solutions
before ordering any equipment.
R. Final design of specialty system shall be provided in complete design and calculation from
system specialist to obtain engineer approval before ordering any component. Required
components and changing in the design (if any) for code and regulation compliance, high
efficient and proper operation shall be provided for engineer approval without any
additional cost and/or time.
S. GSAS requirement
1. The contractor shall submit all required document and calculations which required for
the GSAS 3 stars
2. All equipment and systems selection shall complied with the requirements of GSAS 3
stars
3. The mentioned power in the schedule of equipment are the maximum value and the
contractor shall select any equipment with high efficiency which meet the GSAS 3
stars and in any case the contractor/ manufacturer are obliged to comply without
variations in time/cost.
4. The motor for the air handling units/ fan coil units can be EC type to comply with
GSAS if needed
5. The contractor shall not procure any equipment unless assuring the compliance with
the GSAS 3 stars
1. Liaison with the local supply Authority to obtain and coordinate provision of
discharge points to city sewer drainage system.
2. Complete domestic water supply system including domestic water storage tanks,
domestic water booster pumps and associated accessories.
3. Complete hot water supply system including Individual electric hot water heaters as
per design drawings complete with water distribution pipe-work and associated
accessories.
4. Complete storm water removal pipe-work system and associated accessories.
5. Complete two pipes sewerage system (sewerage and waste water) and associated
accessories.
6. Supply and Installation of all sanitary wares and fittings including flush valves, auto-
sensors, WCs, urinals, water taps, bidets, wash basins, mop sinks and sinks.
7. Power supply wiring and control cabling works for plumbing and sanitary fixture
automatic sensors/devices.
8. All associated electrical works.
9. All associated automatic control works.
10. All associated interfacing works with M&E Services including electrical, fire alarm
and protection, air conditioning and mechanical ventilation, etc.
A. Comply with current applicable codes, ordinances, and regulations of the authority or
authorities having jurisdiction, the rules, regulations and requirements of the utility
companies/authorities serving the project and Employer’s insurance underwriter.
B. Approval or acceptance by the Engineer shall not relieve Contractor of his responsibilities
under the Contract for the quality of materials and the standard of workmanship in the
works.
C. No work shall be covered up or put out of view without the agreement of the Engineer.
Contractor shall provide/allow the Engineer full opportunity for the examination and
measurement of any work which is about to be covered or put out of view. Upon request
by the Engineer, the Contractor shall expose their Works and allow/provide access to the
Engineer to inspect any part of the works during the course of the manufacturing or site
installation/erection.
D. When requested by the Engineer, the Contractor shall submit evidence including written
certificates and full testing reports from approved/recognized testing organization
certifying that his proposed equipment or material has been tested and conform to the
specified standard
E. Contractor should submit a time Schedule of all project Construction stages and critical
milestones from builders works to the Engineer’s takeover including the Local Authorities
approval. Takeover of the project shall not exceed the project deadline.
F. Contractor, prior to the commencement of the Works , Testing and Commissioning, shall
submit for the Engineer’s approval comprehensive QA/QC programme for the installation
pre commissioning and testing and commissioning which shall include, but not be limited
to the following:
G. All equipment, material and items incorporated in the Works under this Contract are to be
new and of top class quality.
I. The use of electrically dissimilar metals in contact with each other shall be avoided. If this is
not possible, the contact surfaces of the two (2) metals shall be insulated from each other
by an approved method.
K. All instrumentation and equipment required for inspection, testing and commissioning shall
be calibrated and maintained by the Contractor. The Contractor shall submit all valid
calibration records from manufacturer and/or recognized laboratories and testing
authorities before the use of such instrumentation and equipment.
L. Necessary Steel platforms and proper walkway bridges shall be provided for maintenance
purpose
1.4 WARRANTIES
A. The Contractor shall warrant that the capacity, rating or duty of all equipment used in the
installation shall not be less than the performance specified on the Drawing or in the
Specification when operating under the specified conditions and in accordance with the
equipment manufacturer’s instructions. Any equipment/system not meeting this
requirement shall be rejected.
C. Warranty Certificate by both Contractor and specialist (wherever applicable) shall be issued
prior takeover Certificate.
D. During the warranty period, perform the periodic routine and preventive maintenance as per
the Equipment Manufacturer’s requirement to verify its proper operation.
E. Warranty period:
1. In General: 400 days commenced from date of takeover Certificate or (as per contract)
for all plumbing systems’ whole installation.
2. For Equipment and special systems: as prescribed in relevant sections for each
Equipment / special systems and / or as per the Contract.
2. Any other products not listed in vendor list subject to the ENGINEER and DESIGNER
approval.
1. The following equipment shall be tested at the supplier’s manufacturing facilities in the
presence of the consultant and client representatives:
a. boilers
b. Calorifiers
c. Pumps
2. The contractor shall submit for consultant’s approval, the test procedure for performance
tests at least 4 weeks prior to witness testing.
3. Notice of witness testing shall be given at least 6 weeks prior to the actual test.
4. Contractor shall bear all costs for performance testing of each equipment, inclusive of
business class air fare for 4 persons with their boarding and lodging expenses and local
transport.
5. In case of failure of any tests, retesting shall be required and the above conditions shall be
applicable.
A. Equipment tests will considered as accepted only when the values being tested are equal to
the design parameters and or within the allowable limits / tolerances ±10% .
A. Immediately answering the breakdown calls, the Contractor shall attend to such calls within
a maximum time limit of three hours during Night and Two hours during Daytime of
receiving such Calls.
B. During the defects warranty period, the Contractor shall at his own cost repair all faults or
defects in the works which in the opinion of the Engineer are due to faulty materials and
workmanship.
C. If the Contractor fails to remedy such faults and or defects within a reasonable time, the
Employer may deploy other Contractor to do such work under the expenses of the contractor
and without prejudice to such other rights as the Employer may have under the Contract.
A. During the course of the Contract, the Contractor shall keep progressive record drawings of
all installation works.
B. As-built drawings shall be submitted prior to the issue of Taking over Certificate by the
Engineer.
C. As-fitted schematic system diagrams, properly framed, shall also be provided and mounted
on the wall inside each plant room.
D. The As-Built drawings must be checked and verified by the Contractor prior submission to
the Engineer for final Confirmation and Approval.
E. Prior to close any of false ceilings, the Partial As-built drawing for the Particular area should
be arranged by the Contractor and accepted by the Engineer.
A. The Operation and Maintenance Instruction manual shall be in A4 size paper and be bound
in rigid covers covered and engraved with lettering giving the Employer’s name, project
name, the Engineer’s name.
B. Final draft manuals must be submitted for the Engineer’s review before Taking Over
Certificate is issued. After acceptance by the Engineer, the Contractor shall submit five (5)
sets and a soft copy of this manual for record before Taking Over certificate is issued.
C. Separate Binders shall be provided as each services for the following Systems:
D. In general, each manual shall consist, but not be limited to the following section:
1. General
a. This section shall include the purpose of the manual and brief description of the
manual directory.
2. System Description
3. Technical Specification
a. This section shall include the technical descriptions and functions of all
equipment and components and shall include:
4. Maintenance
a. This section shall include the required operating, Troubleshooting and Routine
maintenance procedures of all the equipment. This shall include the following
as a minimum:
5. Safety
6. Directory of Suppliers
a. This section shall list the name of suppliers and agents of each type of
equipment, materials and accessories. Correspondence address, telephone
number, fax number and E-mail address shall be included.
7. List of Spares
a. This section shall list all the spares, consumable materials, and maintenance
tools that will be maintained and kept to ensure continued satisfactory operation
of the equipment and systems.
a. This section shall contain a full list of all “as-built” and “as-manufactured”
drawings.
A. Contractor’s obligations for the production of Shop Drawings shall, in addition to other
requirements specified elsewhere in the Contract Documents, include the following:
B. The Contractor shall be responsible and liable for the preparation of all Shop Drawings
necessary or required under the Specifications and/or for the construction of the Works. The
Shop Drawings prepared by the Contractor shall be based on the Contract Document. These
Shop Drawings shall be subject to the approval of the Engineer.
C. During the course of the Contract, The Contractor shall produce and commence submission
of detailed shop drawings sufficiently early for the Engineer’s review. These shop drawings
shall be submitted progressively in accordance with the construction programme. Clearance
or approval of any such drawings by the Engineer shall not relieve the Contractor from any
specified performance or material requirements, nor nullify the Engineer’s right to reject
unsatisfactory works on the site.
D. Installation works carried out by the Contractor before the relevant shop drawings submitted
and approved by the Engineer are at the Contractor’s own risk.
E. Shop drawings shall show at least the following general categories of information:
F. In preparing the Shop Drawings, the Contractor shall provide all construction-related
engineering input and undertake construction co-ordination, inter-facing, cross-checking,
sequencing and construction detailing subject to the absolute approval of the Engineer.
H. Shop drawings produced shall be properly co-ordinated with the works of all installation.
Where required for proper co-ordination and to achieve required headroom, The Contractor
shall make modification of services layout/routing, duct aspect ratios, pipe-work gradient,
etc. (from those shown on the Contract Drawings) and reflect all these on the shop drawings
for he Engineer’s approval.
I. The Contractor shall co-ordinate and provides on time the details of builders works required
to e incorporated into the construction works. For builder’s work information has already
been given on the Drawings or the Contract drawings, Such information is to be checked by
the contractor to ensure suitability and sufficiency for his works.
J. The Engineer’s comments and corrections made on shop drawings shall not relieve the
Contractor of his contractual responsibilities to comply with requirements of the
Specification and Local Authorities regulations.
L. In preparing the Shop Drawings, the Contractor shall co-ordinate the information in the
Contract, engineering the installation and demonstrates the installation adequacy,
practicality, suitability, compliance of any statutory requirements and integrity of other
information in the Contract Documents. The Contractor shall not be entitled to any increase
whatsoever to the Contract Sum for the Works or any extension of time to complete the
Works.
M. In preparing the shop Drawings, the Contractor shall take full account of the latest structural
and architectural drawings and any relevant drawings by other Contractors. The Contractor
shall make any adjustments to services equipment and layout necessary to comply with
variations included upon the structural and architectural drawings and any design costs
associated with such variations shall be included as an integral part of the Contract Works.
N. The shop Drawings shall be stamped and signed by specialist contractor / supplier (wherever
applicable) prior to submit for the Engineer’s review and approval.
O. The Contractor shall submit three /3 set of Hard copies (prints) and One/1 AutoCad copy on
CD for each shop drawings submitted for the Engineer’s review and approval.
P. All modification, alteration on the new revision drawings to incorporate the Engineer’s
previous comments shall be clouded.
Q. Indicate the following on the lower right hand corner of each shop drawing:
1. The submittal identification number;
2. Title of the sheet or brochure;
3. Name and location of the project;
4. Names of the Project Manager, Architect, Consultant, Contractor, subcontractor,
manufacturer, supplier and vendor.
5. The date of the submittal and the date of each correction.
6. Version and Revision.
7. Number all pages and drawings in product data Brochures consecutively from
beginning to end.
A. The Contractor shall submit co-ordinated installation drawings, showing the services that
form the Contract and co-ordinated with all other trades.
B. Drawings shall show all critical dimensions, including dimensions for pipework, ductwork,
plant and equipment.
D. For each room or area of the building containing mechanical, Electrical and public health
equipment, submit the following:
1. Floor Plans: Plan and elevation layout drawings indicating the equipment in the exact
location in which it is intended to be installed. These plans shall be of a scale not less
than 1:20. They shall be prepared in the following manner.
a. Illustrate all mechanical equipment proposed to be contained therein. Include
top and bottom elevations of all mechanical equipment. The drawings shall be
prepared utilising the dimensions contained in the individual equipment
submittals. Indicate code and manufacturer’s required clearances.
b. Illustrate all other equipment therein such as pipework, ductwork, diffusers,
terminal units, structural elements, etc.
c. Indicate the operating weight of each piece of equipment.
d. Illustrate concrete plinths.
e. Indicate maximum normal allowable operating temperature for each piece of
equipment (as per each respective manufacturer’s recommendation).
F. In preparing the Co-ordinated Installation Drawings, the Contractor shall take full account of
the latest structural and architectural drawings and any relevant drawings by other
Contractors. The Contractor shall make any adjustments to services equipment and layout
necessary to comply with variations included upon the structural and architectural drawings
and any design costs associated with such variations shall be included as an integral part of
the Contract Works.
G. The Contractor shall be responsible for preparing all working detail and fabrication drawings
as necessary for the execution of the works.
H. Drawings shall be in the latest release of AutoCAD. The contractor shall obtain from the
Architect a complete set of construction drawings in AutoCAD format including current
building backgrounds. The Contractor shall base coordinated installation drawings on the
Construction drawings and any amendments.
I. Provide dimensioned drawings in plan and elevation showing required all cast in place
brackets, unistrut etc.
J. The Contractor shall submit three /3 set of Coloured Hard copies (prints) and One/1
AutoCad copy on CD for each coordinated drawings submitted for the Engineer’s review
and approval.
K. All modification, alteration on the new revision drawings to incorporate the Engineer’s
previous comments shall be clouded.
L. Indicate the following on the lower right hand corner of each shop drawing:
1. The submittal identification number;
2. Title of the sheet or brochure;
3. Name and location of the project;
A. Submit co-ordinated installation drawings, manufacturer’s shop drawings, and product data
sheets, materials with physical samples and test reports as specified.
2. Within one month after notice to proceed by the Project Manager, submit a
complete typed list of all equipment manufacturers and material suppliers for
the equipment proposed for this project, as well as names of all subcontractors.
3. Within one month after notice to proceed by the Project Manager, prepare an
index of all submittals for the project. Include a submittal identification number,
a cross-reference to the Specification sections or Drawing number, and an item
description. Prefix the submittal identification number by the Specification
sections to which they apply. Indicate on each submittal, the submittal
identification number in addition to the other data specified.
4. After the Contract is awarded, obtain complete shop drawings, product data
and samples from the manufacturers, supplier’s vendors, and all subcontractors,
for all materials and equipment as specified. Submit data and details of such
materials and equipment for review. Prior to submission, certify that the shop
drawings, product data and samples are in compliance with the Contract
Documents. Check all materials and equipment upon their arrival on the job site
and verify their compliance with the Contract Documents. Modify any work,
which proceeds prior to receiving accepted shop drawings as required to
comply with the Contract Documents and the shop drawings.
5. A minimum period of Fifteen /15 days from the date of receiving the
submittal and / or as per the Contract documents, exclusive of transmittal time,
will be required in the Consultant’s office each time a shop drawing, product
data and/or samples are submitted for review. A minimum of Twenty one /21
days from the date of receiving the submittal and / or as per the contract
documents required for review the Operation and Maintenance Manuals.
6. Submit three prints / hard copies (prints) and one AutoCad on CD of all
drawings. Submit three copies of manufacturer’s product submittals.
B. Review of submittals is for general compliance with the design concept and Contract
Documents. Comments or absence of comments shall not relieve the Contractor from
compliance with the Contract Documentations. The Contractor remains solely responsible
for details and accuracy, for confirming and for co-coordinating the work with that of other
trades. The Contractor is not relieved of the responsibility for dimensions or errors that may
be contained on submissions, or for deviations from the requirements of the Contract
Documentations.
D. All modification, alteration on the new revision drawings to incorporate the Engineer’s
previous comments shall be clouded.
3. Include dimensional data for roughing in and installation and technical data
sufficient to verify that equipment meets the requirements of the Contract
Documents. Include wiring, piping and service connection data.
5. Unless the above information is included, the submittal will be returned for
re-submission. Re-submittals of product data or brochures shall include a cover
letter summarizing the corrections made in response to the review comments.
F. Maintain a complete set of reviewed and stamped shop drawings and product data on site.
G. For Material and Equipment submittals, the Contractor shall provide full compliance
statement to the Specifications. Full Comparison between the proposed and specified itemes
in case of the material deviates from the specified. At any Case, the proposed item/(s) shall
be higher quality and / or equal to the specified item/(s).
H. Indicate the following on the lower right hand corner of each shop drawing and on the front
cover of each product data brochure cover:
vii- Number all pages and drawings in product data Brochures consecutively
from beginning to end.
A. The Contractor shall complete the mechanical and electrical installation to meet the entire
performance requirement in this document. All necessary changes and adjustments of the
mechanical and electrical system to take into account of the Contractor’s actually equipment
offered and service layout shop drawings, to meet the Acoustic Performance Requirements
shall be included in the Contract. Equipment used shall also meet the maximum sound power
level specified in the contract.
1. Pump sets on the rooftop or in plant rooms below or over critical areas of NC 40 or
better shall be installed on inertia blocks isolated with minimum 75mm static
deflection un-housed spring-neoprene in-series isolators, with non-skid neoprene pads.
Pipe supports on the rooftop and in the plant rooms shall be isolated with minimum
63mm static deflection spring neoprene in-series isolators.
2. Pump sets in other areas shall be isolated with minimum 50mm static deflection un-
housed spring-neoprene in-series isolators, with non-skid neoprene pads. Pipe
supports shall be isolated with minimum 25mm static deflection spring-neoprene in-
series isolators
3. The weight of the inertia block shall be 1.5 times the weight of the pump set. The
inertia weight design should consider water and pipe weight carried by each pump set.
4. The water tanks shall be isolated on minimum 50mm static deflection spring-neoprene
in series restraint isolators.
PART 2 - PRODUCTS
A. Provide products and materials that are new, clean, free of defects, and free of damage and
corrosion.
B. Products and materials shall not contain asbestos, Polychlorinated Biphenyls (PCB), or any
other material which is considered hazardous by the authority having jurisdiction.
C. Replace materials of less than specified quality and relocate work incorrectly installed as
directed by the Engineer.
F. Maintain uniformity of manufacturer for equipment used in similar application and sizes.
I. Equipment capacities, ratings, etc, are scheduled or specified for job site operating
conditions. Equipment sensitive to altitude shall be de-rated with the method of de-rating
identified on the submittals.
J. Energy consuming equipment shall meet local energy ordinances and by-laws.
B. All external equipment included air-conditioning units on roof shall be specially graded
against corrosive environment.
C. This outdoor weatherproof requirement shall also apply to services installed in close
proximity of external openings and louvers.
A. For all Mechanical and Electrical panels outside plant rooms and at exposed locations such
as car park, services area, public space, etc. shall be provided with a lockable front door.
A. The capacities of all plant and equipment described in the Contract are minimum capacities
and the Contractor shall take into account of the offered equipment capacities to meet the
performance requirement in the Contract and actual installation requirements.
B. Physical sizes of all plant and equipment shall suit the space allocated, taking into account
the requirement for access and proper maintenance.
C. Any proposal to deviate from the Specification and Drawings is subject to the Engineer’s
approval at his sole discretion. Upon approval, any necessary changes to Engineering and
installation as a result of these deviations shall be the responsibility of the Contractor.
D. Proposed equipment shall be submitted for approval by the Engineer before ordering is
placed. All necessary information requested by the Engineer for the review of the proposal
shall be submitted.
A. The Contractor to liaise with the Engineer to determine the recommended lists of spare parts
for three years operation and maintenance covering all systems and sub-systems of the
specification. This list will be subject to the Engineer’s discretion; by which the Contractor is
committed to order these spare parts in part or in whole at any time up to the issue of the
Performance Certificate without any cost escalation.
B. All spare parts and maintenance equipment shall be provided in original packing, clearly
identified and labeled. Provide complete schedules of spare parts and maintenance
equipment clearly cross-referenced with the “Record Drawings” and maintenance
instructions and manuals.
C. All spare parts and maintenance equipment shall be as recommended by the equipment
manufacturer and or at least as detailed specifically in other related sections. List of spare
parts . List of spare parts shall be subject to the final approval of the Engineer.
D. Spare Parts as mentioned in “E” above shall be supplied and handed-over by the Contractor
under his expenses without additional cost to the Employer prior Take over Certificate.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc. requiring
maintenance and replacement.
2.6 SAMPLE
A. Contractor must submit Material Inspection Request for the Engineer’s inspection and
approval upon received material on site.
B. All materials shall be delivered as brand new without any marking of corrosion any not
affected by the transportation and / or by the maneuvering.
D. If the delivered material contains Stainless Steel material such as tank internal ladders, lifting
chain, etc, the SS grade certificate shall be provided.
E. If the delivered material hot dipped galvanized coated such as buddle flanges, tank external
ladders, etc, the mill certificate shall be provided.
F. All delivered meters shall have a valid due calibration Certificate from the manufacturer.
G. All delivered materials and Equipment shall be stored as per the normal practice, standards
as well as Manufacturer’s recommendations.
H. All delivered materials and equipment shall have a delivery note or purchasing order from
the supplier. If the material supplier is not in Qatar, Domestic dealer warranty certificate
shall be provided.
I. Date of delivered Equipment and instruments on site shall be within One year after the
Equipment / instrument production year.
J. All delivered Equipment shall have its own manufactured name plate shows all pertinent and
necessary data. Tagging preferably needs to be provided also.
K. In addition to the above, refer to the blow section for “PROTECTION OF MATERIALS,
PERSONNEL AND PROPERTY”.
PART 3 - EXECUTION
A. Contract documents establish scope, materials and quality but are not detailed installation
instruction.
B. Coordinate work with related trades and furnish, in writing, any information necessary to
permit the work of related trades to be installed satisfactorily and with the least possible
conflict or delay.
C. The drawings show the general arrangement of equipment and appurtenances. Follow these
drawings as closely as the actual construction and the work of other divisions will permit.
Provide off-sets, fittings, and accessories which may be required but not shown on the
drawings. Investigate the site, and review drawings of other divisions to determine
conditions affecting the work, and provide such work and accessories as may be required to
accommodate such conditions.
D. The locations of thermostats, switches, panels and other equipment indicated on the
drawings are approximately correct. Exercise particular caution with reference to the location
of panels, thermostats, switches, etc., and have the precise and definite locations accepted by
the Engineer before proceeding with the installation.
E. The drawings show only the general run of services and approximate location of equipment,
outlets, panels, etc. Any significant changes in location of equipment, outlets, panels, etc.
necessary in order to meet field conditions shall be brought to the determine attention of the
Engineer for review before such alterations are made. Modifications shall be made at no
additional cost to the Contract.
F. Carefully check space requirements with other division works to ensure that equipment can
be installed in the space allotted.
G. Wherever work interconnects with work amongst different installation, coordinate with MEP
Services to insure that they have the information necessary so that the Contractor may
properly install the necessary connections and equipment. Identify items requiring access in
order that the Ceiling Trade will know where to install access doors and panels.
H. Consult amongst installation so that, wherever possible, motor controls and distribution
equipment are of the same manufacturer and / or Other Manufactures Authorized by /
accepted to the Equipment’s Manufacturers.
I. Furnish and set sleeves for passage of risers through structural masonry and concrete walls
and floors and elsewhere as required for the proper protection of each riser passing through
building surfaces.
J. Provide fire stopping around all pipes, conduits, ducts, sleeves, etc, which pass through fire
compartments.
K. Provide required supports and hangers for equipment suitably so as not to exceed allowable
loading of structures.
L. Wherever the work is of sufficient complexity, prepare additional detail drawings to scale to
coordinate the work with the work of MEP Services. Detailed work shall be clearly
identified on the drawings as to the area to which it applies. Submit these drawings to the
Engineer for review. At completion include a set of these drawings with each set of record
drawings.
M. Coordinate with the local utility companies/authorities for their requirements for service
connections and provide all necessary provisions, grounding, materials, equipment, labor,
testing, and appurtenances.
N. Before commencing works, examine adjoining works on which this work is in any way
affected and report conditions which prevent performance of the works. Become thoroughly
familiar with actual existing conditions to which connections must be made or which must
be changed or altered.
O. The Contractor is responsible to any modifications required due to service not properly
coordinated.
A. Provide excavation for the work of the specified installation, if required or necessary.
Excavate all material encountered, to the depths indicated on the drawings or as required.
Remove from the site excavated materials not required or suitable for backfill. Provide
grading as may be necessary to prevent surface water from flowing into trenches or other
excavations. Remove any water which accumulates. Provide sheeting and shoring as may be
necessary for the protection of the work and for the safety of personnel.
B. Provide trenches of widths necessary for the proper execution of the work. Grade bottom of
the trenches accurately to provide uniform bearing and support the work on undisturbed soil
at every point along its entire length. Except where rock is encountered, do not excavate
below the depths indicated. Where rock excavations are required, excavate rock to a
minimum over depth of 100 mm below the trench depths indicated on the drawings or
required. Backfill over depths in the rock excavation and unauthorized over depths with
loose, granular, moist earth, thoroughly machine tamped to a compaction level of at least
95% to standard proctor density or 75% relative density or as specified by the Engineer.
Wherever unstable soil that is incapable of properly supporting the work is encountered in
the bottom of the trench, remove soil to a depth required and backfill the trench to the proper
grade with coarse sand, fine gravel or other suitable material.
C. Excavate trenches for utilities that will provide the following minimum depths of cover from
existing grade or from indicated finished grade as required by local authorities.
D. Trenches should not be placed within 3 meters of foundation or soil surfaces which must be
resist horizontal forces.
E. Do not backfill until all required tests have been performed and installation observed by
Engineer. Comply with the requirements of other sections of the specifications. Backfill shall
consist of non-expansive soil with limited porosity. Deposit in 150 mm layers and
thoroughly and carefully tamp until the work has a cover of not less than 300 mm. Backfill
and tamp remainder of trench at 300 mm intervals until complete. Uniformly grade the
finished surface.
F. Piping shall not be buried at less than 900mm below finished grade for protection against
mechanical damages; otherwise, piping shall be surrounded with grade OPC 20 Concrete.
Concrete encasement shall be applied as per QCS-2014, section 08, part 04 “ Concrete
protection to pipe”.
G. Except where the method of jointing and normal trench backfill are adequate to prevent
longitudinal movement , Grade C 20 Concrete thrust blocks cast in Concrete with
undisturbed ground shall be constructed at every changing of direction, Junctions and blank-
end. In Case of Hub – Spigot type connection, the Thrust blocks shall be provided at both
sides.
H. Any Additional excavation required to accommodate thrust blocks shall be carried-out after
the bend or branch is in position and the thrust face shall be trimmed back to remove all
loose or weathered material immediately prior to concreting.
A. All Buried Metallic Piping shall have a corrosion resistance such as provided in ductile iron
piping. Anti-corrosive protection for other metallic buried piping shall be applied to the
piping and pipe fitting in according to QCS-2014, Section 08, part 04 “ Corrosion Protection
of Ferrous Pipelines”.
A. General:
1. Access is required to drainage installations for testing, inspection, maintenance and
debris removal.
2. Every drain Length should be Accessible for maintenance and rodding / jet without
the need to enter the building. Access shall be provided at the head of each run if drain
and at every change in the flow direction, gradient and diameter.
3. All floor clean out shall be covered as specified.
4. Refer to the respective Specification Division 22, section 221319 “Cleanouts”.
B. Piping In Trenches:
1. Access is required to drainage installations at every 20 meter span of horizontal
running.
2. Access is required to the building drainage installations close to the Municipality
discharge.
3. Access Panel with suitable size and proper height shall be provided in the bathtub wall
for accessing the Cleaning eye of bathtub ‘P’ trap.
4. Access is required to drainage installations at every 20 meter span of horizontal
running.
A. The Contractor Must Provide a proper Access way for inspection, testing, Maintenance and
further Replacement of the Equipment, valves and instrumentations. All plantroom
Equipment, instrumentations, Valves including float ball valve and Its MEP services
Equipment must be Accessible / serviceable.
B. When the pipe Line obstructing the access way , Standard Fabricated Way Bridges and / or
platforms along with steps and Protection Guard Rails must be installed over on the piping /
valves in the following:
1. Piping line along with valves run on the floor obstructing the access way.
2. Piping line along with valves leveled within 1000 mm AFFL obstructing the access way.
C. Standard Fabricated steel Platform along with access ladders and Protection Guardrails Must
be provided to access the valves for its operation and further maintenance if the distance
from the valves to false Ceiling Exceeds 2500 mm.
D. Size of the access panel to access the valves on the false ceiling should be arranged and
coordinated with the Architect. All valves shall be accessible / serviceable for inspection,
testing and further Maintenance.
A. Catwalk to maintenance platform shall be provided with railings and guards designed for
safe movement of personnel in a restricted space including provision for gaining access and
to accommodate maintenance personnel.
B. Hand railing and guards shall be designed by the Contractor and provided by the Contractor
for all concrete tanks to allow safe movement of personnel.
C. Permanent I-beams, sliding eyes hocks / bolts, SS 316 lifting chains, etc. shall be provided
by the Contractor over major equipment which requires lifting for overhaul and maintenance.
D. Waterproof power sockets required for servicing shall be provided by the Contractor. The
number and locations shall be proposed by the Contractor and approved by the Engineer.
Power supply to these sockets shall be taken from control panel of the submersible pump.
E. The design of all permanent work platform, hand rails, etc. shall be submitted to the
Engineer for approval. The loading and fixing method of lifting facilitate shall also be
submitted to the Engineer for approval and checking within 4 weeks on award of Contract or
receipt of letter of intent.
A. The top of each riser shall be fitted with a 25 mm automatic air release valve, brass
construction, with internal solid rubber ball and / or as specified.
B. Automatic Air Release Valve shall be provided with Isolating Valve for further
Replacement.
C. Automatic Air Release valve along with its isolating valve shall be provided at accessible
location. Means of access shall be provided.
A. Unless specified otherwise, puddle flanges in water tanks for casting into the concrete tank
structure shall be PN-16 pipe same material of network piping, with PN-16 flanges to B.S.
4504 : Part 1 : latest edition both coated by a good quality Hot dipped Galvanized to ASTM
A153:latest edition to be provided.
B. All Puddle flanges, piping, washers, nuts and bolts provided inside the tank for tank filling
line , etc shall be coated by hot dipped galvanized conform to ASTM A153.
C. At least One Spare Puddle flange of each size shall be provided for each tank / compartment.
D. All Puddle flanges shall be protruded from the tank in the plantroom side with minimum of
150mm.
E. All Puddle flanges for tank suction piping and incoming tank filling line /(s) shall be
protruded from the tank inside the tank side with minimum 150mm.
A. Where cutting, channeling, chasing or drilling of floors, walls, partitions, ceilings or other
surfaces is necessary for the proper installation, support or anchorage of conduit or other
equipment, layout the work carefully in advance. Repair any damage to the building, piping,
equipment or defaced finish plaster, woodwork, metalwork, etc., using skilled trade people
of the trades required at no additional cost to the Contract.
B. Provide slots, chases, openings and recesses through floors, walls, ceilings, and roofs as
required. Where these openings are not provided, provide cutting and patching to
accommodate penetrations at no additional cost to the Contract.
1. All penetrations through the building fabric subject to suction or pressurization shall
be sealed airtight.
B. Holes in Roof
1. Roof penetrations for passage of conduits or circular PVC and PVC Cables shall be
sealed watertight using a flexible polypropylene conical sleeve manufacturer or XLPE
Cables to seal the cable to the roof structure, regardless of the roof profile.
2. All sharp metal edges, which may come in contact with the cable, shall be suitably
bushed.
1. Where services penetrate any fire rated barrier, the Contractor shall seal the
penetration with the use of an appropriate material to ensure the integrity of the fire
barrier.
2. The Contractor shall seal the cable enclosures through fire rated barriers to ensure the
integrity and rating of the fire barrier.
3. All Fire Rated Penetrations Must be sealed with proper Material accepting to the
Authorities Having Jurisdictions. Stickers with Authorized person’s (accepted by the
Authorities Having Jurisdictions) signature Must be provided at every Fire Rated
Penetrations.
D. Acoustic Penetrations
1. Where services penetrate acoustic barriers, sealant shall be supplied and installed to
maintain the acoustic separation at least equal to the barrier penetration.
A. Where Pipe penetrates any wall, the Contractor shall install Metallic Pipe sleeve with
100mm protrusion from both sides. One pipe size higher than pipe shall be provided for pipe
sleeve. Refer to the related specification Division 22, section 220500 “Sleeves” and “piping
System – common Requirements.
B. Pipe Sleeve not required to be installed for the new coring in slabs and beams.
A. Verify exact locations and mounting heights with the Engineer before installation.
3.13 SUPPORTS
A. The pipework shall be supported, anchored and guided in order to preclude failure or
deformation. The Contractor shall construct and install hangers, supports, anchors, guides
and accessories as necessary to the approval of the Engineer. Supports shall be designed to
support the weight of the pipe, the weight of fluid with suitable Factor of safety.
B. Comply with the Requirement prescribed on the Division 22, section 220529 “HANGERS
AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT”.
C. Support work in accordance with the best industry practice. Provide supports, hangers,
auxiliary structural members and supplemental hardware required for support of the work.
D. Provide supporting frames or racks extending from floor slab to ceiling slab for work
indicated as being supported from walls where the walls are incapable of supporting the
weight. In particular, provide such frames or racks in electric closets and equipment room.
E. Provide supporting frames or racks for equipment, which is installed in a free standing
position.
F. Supporting frames or racks shall be of standard angle, standard channel or specialty support
system steel members, rigidly bolted or welded together and adequately braced to form a
substantial structure. Racks shall be of ample size to assure a workmanlike arrangement of
all equipment mounted on them.
G. Adequate support of equipment (including outlet, pull and junction boxes and fittings) shall
not depend on ducts, pipe, electric conduits, raceways, or cables for support.
H. Equipment shall not rest on or depend for support on suspended ceiling media (tiles, lath,
plaster, as well as splines, runners, bars and the like in the plane of the ceiling). Provide
independent support of equipment. Do not attach to supports provided for ductwork, piping
or work of MEP Services.
I. Provide required supports and hangers for equipment so that loading will not exceed
allowable loading of structure. Equipment and supports shall not come in contact with work
of MEP Services.
J. Standard Fabricated Rigid / Anchored Angle or Channel Support Should be Provided at the
pipe line when the distance from slab soffit to piping exceeds 1.5m as under:
a. For Piping up to 3 inches: Standard Fabricated Angle Anchored support with
cross stiffness.
b. For Piping from 4 inches and above: Standard Fabricated Channel Anchored
Support.
K. In addition to the hanger support, Standard Fabricated Rigid / Anchored Angle or Channel
Support Should be Provided for the extreme lengthy Horizontal pipe Line running at every
20 meter span as under:
a. For Piping up to 3 inches: Standard Fabricated Angle Anchored support with
cross stiffness.
b. For Piping from 4 inches and above: Standard Fabricated Channel Anchored
Support.
B. Where weight applied to the attachment points is 45 kg or less, conform to the following as a
minimum:
C. Where weight applied to the building attachment points exceeds 45 kg, and less than or
Equal to 135 kg,, conform to the following as a minimum:
1. At concrete slabs provide suitable steel fishplates on top with through bolts. Fishplate
assemblies shall be chased in and grouted flush with the top slabs screed line, where
no fill is to be applied.
2. At steel decking or sub-floor for all fastenings, provide through bolts and threaded
rods. The tops of bolts and rods shall be set at least 25 mm below the top fill screed
line and grouted in. Suitable washers shall be used under bolt heads or nuts. In cases
where the decking or sub-floor manufacturer produces specialty hangers to work with
his decking or sub-floor such hangers shall be provided.
D. Where weight applied to building attachment points exceeds 135 kg, coordinate with and
obtain the approval of Engineer and conform to the following as a minimum:
1. Provide suitable auxiliary channel or angle iron bridging between building structural
steel elements to establish fastening points. Bridging members shall be suitably
welded or clamped to building steel. Provide threaded rods or bolts to attach to
bridging members.
E. For items which are shown as being ceiling mounted at locations where fastening to the
building construction element above is not possible, provide suitable auxiliary channel or
angle iron bridging tying to the building structural elements.
F. Wall mounted equipment may be directly secured to wall by means of steel bolts. Groups or
arrays of equipment may be mounted on adequately sized steel angles, channels, or bars.
A. Identify equipment, piping and Valves with permanently attached black phenolic nameplates
with 13 mm high white engraved lettering. Identification shall include equipment name or
load served as appropriate. Nameplates shall be attached with cadmium plated screws; peel
and stick tape or glue on type nameplates are unacceptable.
C. Services runs shall be properly identified as per the requirements in the Contract.
A. In all public areas, tenant areas, and similar locations within the project, the inclusion or
installation of any equipment or assembly which bears on any surface any name, trademark,
or other insignia which is intended to identify the manufacturer, the vendor, or other
source(s) from which such object has been obtained, is prohibited.
B. Required test lab certification labels shall not be removed nor shall identification specifically
required under the various technical sections of the Specifications be removed.
A. Provide concrete pads under all floor mounted Mechanical equipment. Equipment pads shall
conform to the shape of the piece of equipment it serves with a minimum 25 mm margin
around the equipment 28 day, 175 kg/cm2 concrete reinforced with 150 mm x 150 mm
welded wire mesh. Trowel tops and sides of pad to smooth finishes, equal to those of the
floors, with all external corners bull nosed to a 20 mm radius. Shop drawings stamped
UNALTERED shall be used for dimensional guidance in sizing pads.
B. Provide galvanized anchor bolts for all equipment placed on concrete equipment pads, inertia
blocks, or on concrete slabs. Provide bolts of the size and number recommended by the
manufacturer of the equipment and locate by means of suitable templates. Equipment
installed on vibration isolators shall be secured to the isolator. Secure the isolator to the
floor, pad, or support as recommended by the vibration isolation manufacturer.
C. Where the equipment is mounted on gypsum board partitions, the mounting screws shall
pass through the gypsum board and securely attach to the partition studs. They shall be
attached to 15 cm square, galvanized metal back-plates which are attached to the gypsum
board with an approved non-flammable adhesive. Toggle bolts installed in gypsum board
partitions are not acceptable.
A. The Contractor shall make necessary provision of providing flexible connector / joints where
services / piping passes through the structural expansion joints as shown on architectural /
structural drawings whatever applicable.
A. Any successive Valves, successive valve and strainer shall be not connected together, a spool
piece of piping shall be provided in between as per practical standards.
B. Any tapping point from the main pipe shall not be tapping directly from the changing of flow
direction. Minimum Clear distance of (3 D) from the changing in the flow direction fitting to
the tapping point shall be maintained. Where D: is the Pipe Diameter.
A. Contractor shall arrange and submit inspection for Mock-up / benchmark installation for all
services / trades prior to proceed with the same further installation.
C. The Contractor may proceed with further installations only when the benchmark has been
approved by the Engineer.
A. Back flushing shall be conducted to all heat exchangers as described in Division 223500
“DOMESTIC WATER HEAT EXCAHNGER”.
A. Prior to handing over and / or prior take over certificate, All Commissioning Set / Double
Regulating Valves in the Primary Circuit (Pipe line from Boilers to calorifiers) shall be
adjusted by the flow as indicated. Commissioning shall be carried-out by Commissioning
agency accepted by the Engineer.
B. Prior to handing over / or prior take over certificate, All Commissioning Set / Double
Regulating Valves in the secondary hot water return Lines shall be adjusted by the flow as
indicated. Commissioning shall be carried-out by Commissioning agency accepted by the
Engineer
A. Di-electric Union shall be installed in between dissimilar Materials even if not shown on the
drawings.
B. Refer to other related section 220500 “COMMON WORK RESULTS FOR PLUMBING –
DIELECTRIC FITTING & PIPING CONNECTIONS”
3.25 UNION
A. Union shall be installed in the threaded joints pipe line for all threaded joint Plantroom
Equipment, valves, strainers, etc for ease further replacement even if not shown on the
drawings. Union shall be same piping material. Refer to other related section 220500
“COMMON WORK RESULTS FOR PLUMBING – PIPING CONNECTIONS”
A. Air admittance valve to be provided for the counter bars’ hand wash sink , drainage piping
when the vent pipe installation is not doable. Air admittance valve shall be as:
A. Provide drayage, hauling, hoisting, shoring and placement in the building of equipment
specified and be responsible for the timely delivery and installation of equipment as required
by the construction schedule. If any item of equipment is received prior to the time it is
required, the Contractor shall be responsible for its proper storage and protection until the
time it is required. Pay for all costs of demurrage or storage.
B. If equipment is not delivered or installed at the project site in a timely manner as required by
the project construction schedule, the Contractor shall be responsible for resulting
disassembly, re-assembly, manufacturer’s supervision, shoring, general construction
modification, delays, overtime cost, etc., at no additional cost to the Contract.
A. Comply with the project construction schedule for the date of final performance and
acceptance testing, and complete work sufficiently in advance of the Contract completion
date to permit the execution of the testing prior to occupancy and Contract closeout.
Complete any adjustments and/or alterations which the final acceptance tests indicate as
necessary for the proper functioning of all equipment prior to the completion date. Refer
Section 15950 and also see individual sections for extend of testing required.
C. Contractor Must arrange the necessary and required testing Devices / instruments / tools with
a valid due calibration along with its Calibration Certificate and all of necessary pertinent
documentations during the testing inspection of the system with the Engineer.
A. The Contractor shall provide power supply points/isolators at certain designated locations
within the development for all mechanical and electrical installations as indicated on the
drawings. It is the responsibility of the Contractor to coordinate and make connections to
these power supply points/isolators and to provide all the necessary ‘down-stream’ power
supply distribution board/network to the mechanical system’s control panels, equipment,
sensors, field devices, etc.
A. The Contractor shall include the supply and installation of a custom-built control console of
proprietary make in the Command Centre, Security Room to integrate all control panels,
mimic panels, and central equipment of the following systems:
B. The proposed manufacturer detail of the Integrated Control Console shall be submitted to the
Engineer for approval before manufacturing commences. All necessary interfacing works
with other mechanical and electrical systems shall be included.
A. All material and goods shall be delivered to the site in new condition, properly packed and
protected against damage due to handling, adverse weather or other circumstances, and be
kept in packing case or under protective covering until required for use.
B. Any items suffering damage in transit or on site shall be rejected and replaced without extra
cost and time to the Contract.
C. In the case of equipment and materials which originate from other countries and/or different
climatic conditions, all such equipment and material shall be adequately and securely packed
for safe transportation with due regard to the climatic conditions encountered in transit and
arrival.
D. The Contractor shall be entirely responsible for all apparatus, equipment and materials
furnished by him in connection with his works, and special care shall be taken to protect all
parts thereof in such a manner as may be necessary or as directed.
E. Protection shall include covers, crating, sheds, stores or other means to protect the apparatus,
equipment and materials from the weather, water damage and corrosion, and to prevent dirt,
grit, plaster or other foreign substances from entering the working parts of machinery or
equipment. Special care shall be taken to keep all opening of pipes, ducts, etc. closed while
in storage or during the course of delivery and erection/installation.
F. The Contractor shall take precautions to avoid unnecessary damage among the M&E
installation.
G. All precautions shall be taken for the safety of personnel on site. The Contractor shall also
conform to the general regulations governing personnel on the site and must keep to the
working space allocated for their use.
H. Fire Extinguishers, Emergency evacuation plans, Voice Evacuation System and other
necessary site safeties shall be provided temporary by the Contractor under his expenses
during all of the Construction phases until the date of take-over Certificate.
A. General
1. The Contractor shall provide all necessary provisions for interfacing amongst
installation, services, and equipment. All necessary sensors, current/voltage
transformers, voltage-free contacts, relays, auxiliary contacts, terminals, transducers,
etc. for interfacing works shall be provided by the Contractor.
2. All control/monitoring wiring from sensors, equipment, and components for the
interfacing shall be terminated at a separate interfacing compartment located at the
respective equipment/system’s switchboard or control panel. The interfacing
compartment shall be completed with all necessary connectors, terminals, and with
proper identifications to allow interfacing works to be easily carried out. The
compartment shall clearly indicate “Extra Low Voltage Cable Only. No Power Cable
Connection”. Where there is no equipment/system switchboard or control panel
involved, the Contractor shall provide separate interfacing panels with provisions
same as the interfacing compartment as described above. The locations of the
switchboard/control panels and the interfacing panels shall be properly coordinated.
3. For every control panel and each module of the switchboard, at least five (5) spare
terminals shall be provided for future interfacing works.
4. Wiring and cables for interfacing with the fire alarm system and other fire protection
and life safety systems shall be fire rated to comply with Civil Defence’s
requirements.
5. Unless otherwise specified or shown on the Drawings, interfacing wiring from Fire
Alarm system shall be provided and terminated at the terminals of the interfacing
compartments or panels by the Fire Alarm System and Building Management System
installation respectively. The Contractor shall co-ordinate the current and voltage
requirements for the interfacing works/provisions. The type of provisions for
interfacing signals shall be as follows, unless otherwise specified:
6. All the interface provisions shall be DC operated and rated not more than 50 mA.
7. The Contractor shall provide and make all power cable connections from mechanical
equipment, local control panels, and distribution boards to the electrical isolators or
power points (including cable termination) provided under Division 16 works.
Location of power supply isolators and power points shall be properly coordinated.
8. In addition to the interfacing requirements shown on the Drawings, interfacing
provisions as described below shall also be provided and included in the Contract.
B. Electrical Installation
a. Isolators and power points (fused spur units) for all mechanical equipment and
systems. Where shown on the Drawings, the Electrical installation shall include
direct power cable connections to the mechanical system’s main motor control
centers
b. Electrical bonding of all roof equipment and external metal cladding including
provisions and connection of bonding cables
c. Power supply to ACMV system’s control components/sensors shall however be
provided under the ACMV installation from the corresponding equipment
motor control panel.
a. Water supply connections to water tanks under other mechanical and electrical
installation including isolation valve.
b. Water Reserve tank’s visual level indicator and Ultrasonic Water level
indicator.
c. Drainage with air gap for Backflow Preventer valves and condensate drain from
air handling units and fan coil units including insulation of drain stacks
receiving condensate
3.33 PAINTING
A. All equipment, enclosures, housings, air ducts, Metallic piping, trunking, cable trays,
conduits, etc. which are exposed to view (including those in outdoor plant rooms) shall be
provided with color paint finishes.
B. All metal surfaces requiring painting shall be provided with two (2) coats of asphalt
aluminum paint, primer coated, and two (2) coats of finished paint.
C. No painting shall be done on damp surfaces. Surface should be tidy and clean prior applying
the paint
D. The Contractor shall submit color scheme for the entire Works for co-ordination and
submission for approval by the Engineer.
E. Painting requirements as stated in codes and regulations or required by local authorities shall
also be provided.
A. The Contractor shall supply and install the following safety equipment and notices for each
switchboard/control panel in the respective switch rooms and plant rooms:
1. Solid rubber insulated mats complying with BS 921 in front of and extending the full
length of the control panel/switchboards.
2. Copies of all statutory safety notices, regulations and instructions for resuscitation and
treatment after electrical shock.
3. Danger signs on the switchboards/control panels, the doors of sub-station, switch-
rooms and electrical riser duct rooms and elsewhere to the requirements.
4. A copy of the main single line diagram, varnished and mounted on suitable hard
backing and framed (in glass panel), showing clearly the full details of the electrical
and mechanical systems as supplied and installed.
A. The Contractor shall be responsible for obtaining all necessary licenses as required by all
relevant authorities before operation of any equipment/system.
B. All testing and commissioning to enable proper operation of the Works shall be completed to
the satisfaction of the Engineer in accordance with the construction programme or before the
issuance of Taking Over Certificate, whichever is earlier.
C. All final adjustments and final balancing of the equipment/system operation shall be
completed before the Date of Taking Over Certificate.
D. The complete testing and commissioning are deemed to be concluded successfully only
when the installation operated properly within the specified limits of its rating continuously
without failure of any kind.
E. The Contractor shall establish the dates by which permanent utilities shall be available for
testing and commissioning of equipment and take this into account in his programme, or
make suitable arrangements to test and commission with temporary power based on
programme. All Testing and Commissioning for Non- Fire and Life Safety Systems shall
have the Engineer’s approval prior to inspections / testing.
F. The Contractor shall arrange for all submissions to Authorities and pay the cost of statutory
inspections and certificates.
3.36 HANDOVER TO
A. The Contractor is full responsible to arrange and perform any necessary testing requested
without any additional cost to the Client.
B. Contractor Must arrange the necessary and required testing Devices / instruments / tools with
a valid due calibration during the testing inspection of the system.
C. Contractor shall action all of the comments prior the issuance of take-over certificate by the
Engineer.
D. At the time of handover of the Works after the Taking Over Certificate, the whole
installation shall be in ‘as-new’ conditions. The Contractor shall, during the course of the
Contract, protect all plant and equipment and shall restore/repaint as necessary before
handover of the installation.
A. The Contractor is directed to attend / action for the Engineer snagging prior take over
certificate.
B. Minor snagging may action after the soft opening, but shall be finished prior the official /
grand opening.
A. The Contractor is directed to demolish all of site facilities and their services prior official /
grand opening.
A. The Contractor shall provide all necessary attendance and pertinent documentations to
inspections by the Engineer and authorities for the purpose of Taking Over Certificate
application.
1. The Contractor shall submit the arrangement of the commissioning to the satisfaction
of the Engineer. The Engineer reserves the right to reject any person.
2. The installation shall be ‘practically complete’ following satisfactory commissioning
and the submission of final commissioning data prior to the issuance of Taking Over
Certificate by the Engineer. It is solely the Contractor’s responsibility to ensure that
all plant/equipment shall have their respective warranty by the respective
equipment/plant supplier directly.
3. A joint inspection shall be held among the Employer , the Engineer and Contractor to
establish an outstanding works and defects list. All outstanding works/defects shall be
completed within one month from the date when the Taking Over Certificate was
issued.
4. If, at the end of the one month’s period from the date of issuing the Taking Over
Certificate, any defects/outstanding works mentioned in the list still exist, the
Engineer is empowered to appoint a body to rectify all defects/outstanding works and
deduct the cost involved from the Contract sum.
5. The Contractor shall close / action all of the Non Conformance and Field Observation
Reports that are critical for operation prior issuance of the take-over Certificate by the
Engineer.
6. Room and Field Demonstration Training to the Employer as detailed below in this
Section “Tuition / Training” shall be Conducted prior the issuance of Take-over
Certificate.
7. The Engineer’s instructions (if any) shall be actioned by the Contractor prior the
issuance of takeover Certificate. The Contractor shall submit installation Inspection
against each An Engineer’s Instruction for the Engineer’s approval.
B. The Contractor shall also refer to other requirements in the relevant clauses of the Contract.
1. Before the Taking Over Certificate is issued, the following must be completed:
A. At the time of handover of the Works after the Taking Over Certificate, the whole
installation shall be in ‘as-new’ conditions. The Contractor shall, during the course of the
Contract, protect all plant and equipment and shall restore/repaint as necessary before
handover of the installation.
3.42 TUITION/TRAINING
A. The Tenderer shall submit a schedule in the Tender submission list all works and systems for
which the Contractor has to provide training. The Schedule should have information include
list of recommended training courses within each works/systems, location of the training
courses (local/overseas). Trainers details (from the manufacturers premises where
applicable), courses duration, unit rate of the training in per head basis.
B. The Contractor shall provide sufficient and proper instructions to the trainees nominated by
the Employer in the commissioning, operation, maintenance, servicing and trouble-shooting
of the various plant and systems.
D. The Trainees nominated by the Employer will attend the training courses, and the Contractor
shall allow them reasonable access to technical information and documentation required for
proper operation and maintenance. The Contractor shall also explain this information and
documentation to allow the trainees to become fully conversant with all aspects of the
systems.
E. When training is required to be held in overseas facilities, all necessary costs for airfare,
hotel accommodation, local transportation, food, etc. shall be included.
PART 1 - GENERAL
A Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
B The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
1.3 DEFINITIONS
A Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spac-
es, pipe chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated
spaces, crawlspaces, and tunnels
3. Concealed, Interior Installations: Concealed from view and protected from physical
contact by building occupants. Examples include above ceilings and in chases.
4. Concealed, Exterior Installations: Concealed from view and protected from weather
conditions and physical contact by building occupants but subject to outdoor ambient
temperatures. Examples include installations within unheated shelters.
1. Retain abbreviations that remain after this Section has been edited.
1.4 SUBMITTALS
A Product Data:
a. Transition fittings.
b. Dielectric fittings.
c. Mechanical sleeve seals.
d. Escutcheons.
e. Welding certificates.
1. Qualify processes and operators according to ASME Boiler and Pressure Vessel Code:
Section IX, "Welding and Brazing Qualifications."
a. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
b. Certify that each welder has passed AWS qualification tests for welding pro-
cesses involved and that certification is current.
A Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping,
storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and
moisture.
B Store plastic pipes protected from direct sunlight. Support to prevent sagging and bending.
1.7 COORDINATION
A Arrange for pipe spaces, chases, slots, and openings in building structure during progress of
construction, to allow for plumbing installations.
C Coordinate requirements for access panels and doors for plumbing items requiring access
that are concealed behind finished surfaces. Access panels and doors are specified in Divi-
sion 08, Section 08 31 13 - Access Doors and Frames.
PART 2 - PRODUCTS
A Refer to individual Division 22 piping Sections for pipe, tube, and fitting materials and join-
ing methods.
1. Pipe Threads:
A Refer to individual Division 22 piping Sections for special joining materials not listed below.
1) Full-Face Type: For flat-face, Class 125, cast-iron and cast-bronze flang-
es.
2) Narrow-Face Type: For raised-face, Class 250, cast-iron and steel flang-
es.
b. AWWA C110, rubber, flat face, 3.2 mm thick, unless otherwise indicated; and
full-face or ring type, unless otherwise indicated.
1. Type and material recommended by piping system manufacturer, unless otherwise in-
dicated.
1. ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813.
1. AWS A5.8, BCuP Series, copper-phosphorus alloys for general-duty brazing, unless
otherwise indicated; and AWS A5.8, BAg1, silver alloy for refrigerant piping, unless
otherwise indicated.
1. Same size as, and with pressure rating at least equal to and with ends compatible with,
piping to be joined.
A Description:
1. Combination fitting of copper alloy and ferrous materials with threaded, solder-joint,
plain, or weld-neck end connections that match piping system materials.
B Insulating Material:
C Dielectric Unions:
D Dielectric Flanges:
E Dielectric-Flange Kits:
a. Separate companion flanges and steel bolts and nuts shall have 1035- or 2070-
kPa minimum working pressure where required to suit system pressures.
F Dielectric Couplings:
G Dielectric Nipples:
1. Electroplated steel nipple with inert and noncorrosive, thermoplastic lining; plain,
threaded, or grooved ends; and 2070-kPa minimum working pressure at 107 deg C.
A Description:
1. Modular sealing element unit, designed for field assembly, to fill annular space be-
tween pipe and sleeve.
a. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe. In-
clude type and number required for pipe material and size of pipe.
b. Pressure Plates: Stainless steel. Include two for each sealing element.
c. Connecting Bolts and Nuts: Stainless of length required to secure pressure
plates to sealing elements. Include one for each sealing element.
2.6 SLEEVES
A Galvanized-Steel Sheet:
1. 0.6-mm minimum thickness; round tube closed with welded longitudinal joint.
2.7 ESCUTCHEONS
A Description:
1. Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely fit
around pipe, tube, and insulation of insulated piping and an OD that completely covers
opening.
2. Do not delete or combine types of escutcheons in seven paragraphs below until selec-
tions in Part 3 "Piping Systems - Common Requirements" Article are made.
2.8 GROUT
A Description:
PART 3 - EXECUTION
A Install piping according to the following requirements and Division 22 Sections specifying
piping systems.
B Drawing plans, schematics, and diagrams indicate general location and arrangement of pip-
ing systems. Indicated locations and arrangements were used to size pipe and calculate fric-
tion loss, expansion, pump sizing, and other design considerations. Install piping as indicat-
ed unless deviations to layout are approved on Coordination Drawings.
C Install piping in concealed locations, unless otherwise indicated and except in equipment
rooms and service areas.
D Install piping indicated to be exposed and piping in equipment rooms and service areas at
right angles or parallel to building walls. Diagonal runs are prohibited unless specifically in-
dicated otherwise.
E Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
K Select system components with pressure rating equal to or greater than system operating
pressure.
L Install escutcheons for penetrations of walls, ceilings, and floors according to the following:
1. Piping with Fitting or Sleeve Protruding from Wall: One-piece, deep-pattern type.
2. Chrome-Plated Piping: One-piece, cast-brass type with polished chrome-plated finish.
3. Insulated Piping: One-piece, stamped-steel type with spring clips.
4. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast-brass
type with polished chrome-plated finish.
N Install sleeves for pipes passing through concrete and masonry walls and concrete floor and
roof slabs.
O Install sleeves for pipes passing through concrete and masonry walls, gypsum-board parti-
tions, and concrete floor and roof slabs.
2. Install sleeves in new walls and slabs as new walls and slabs are constructed.
3. Install sleeves that are large enough to provide 6.4-mm annular clear space between
sleeve and pipe or pipe insulation. Use the following sleeve materials:
4. Except for underground wall penetrations, seal annular space between sleeve and pipe
or pipe insulation, using joint sealants appropriate for size, depth, and location of joint.
Refer to Division 07, Section 07 92 00 - Joint Sealants, for materials and installation.
1. Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to al-
low for 25-mm annular clear space between pipe and sleeve for installing mechanical
sleeve seals.
1. Install cast-iron "wall pipes" for sleeves. Seal pipe penetrations using mechanical
sleeve seals. Select sleeve size to allow for 25-mm annular clear space between pipe
and sleeve for installing mechanical sleeve seals.
a. Mechanical Sleeve Seal Installation: Select type and number of sealing elements
required for pipe material and size. Position pipe in center of sleeve. Assemble
mechanical sleeve seals and install in annular space between pipe and sleeve.
Tighten bolts against pressure plates that cause sealing elements to expand and
make watertight seal.
R Fire-Barrier Penetrations:
1. Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetra-
tions. Seal pipe penetrations with firestop materials. Refer to Division 07 Section
"Penetration Firestopping" for materials.
2. Verify final equipment locations for roughing-in.
3. Refer to equipment specifications in other Sections of these Specifications for rough-
ing-in requirements.
A Join pipe and fittings according to the following requirements and Division 22 Sections spec-
ifying piping systems.
B Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
C Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before as-
sembly.
D Threaded Joints:
1. Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full
and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full
ID. Join pipe fittings and valves as follows:
a. Apply appropriate tape or thread compound to external pipe threads unless dry
seal threading is specified.
b. Damaged Threads: Do not use pipe or pipe fittings with threads that are corrod-
ed or damaged. Do not use pipe sections that have cracked or open welds.
E Welded Joints:
1. Construct joints according to AWS D10.12, using qualified processes and welding op-
erators according to Part 1 "Quality Assurance" Article.
F Flanged Joints:
1. Select appropriate gasket material, size, type, and thickness for service application. In-
stall gasket concentrically positioned. Use suitable lubricants on bolt threads.
1. Install unions, in piping DN 50 and smaller, adjacent to each valve and at final con-
nection to each piece of equipment.
2. Install flanges, in piping DN 65 and larger, adjacent to flanged valves and at final con-
nection to each piece of equipment.
3. Edit dielectric connection types in two subparagraphs below for each fluid.
4. Dry Piping Systems: Install dielectric unions and flanges to connect piping materials
of dissimilar metals.
5. Wet Piping Systems: Install dielectric coupling and nipple fittings to connect piping
materials of dissimilar metals.
A Install equipment to allow maximum possible headroom unless specific mounting heights are
not indicated.
B Install equipment level and plumb, parallel and perpendicular to other building systems and
components in exposed interior spaces, unless otherwise indicated.
D Install equipment to allow right of way for piping installed at required slope.
3.6 PAINTING
1. Repair marred and damaged factory-painted finishes with materials and procedures to
match original factory finish.
A Concrete Bases:
a. Construct concrete bases of dimensions indicated, but not less than 100 mm
larger in both directions than supported unit.
b. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 450-mm centers around the full perimeter of the
base.
c. Install epoxy-coated anchor bolts for supported equipment that extend through
concrete base, and anchor into structural concrete floor.
d. Place and secure anchorage devices. Use supported equipment manufacturer's
setting drawings, templates, diagrams, instructions, and directions furnished
with items to be embedded.
e. Install anchor bolts to elevations required for proper attachment to supported
equipment.
f. Install anchor bolts according to anchor-bolt manufacturer's written instructions.
g. Use 20.7-MPa, 28-day compressive-strength concrete and reinforcement as
specified in Division 03 Section "Cast-in-Place Concrete."
h. Install the concrete plinth of pump so the Center Line of the suction pipe Provi-
sion in the tank in higher than or equal to the suction flange of the pump
1. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor plumbing materials and equipment.
2. Field Welding:
A Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and anchor
plumbing materials and equipment.
B Select fastener sizes that will not penetrate members if opposite side will be exposed to view
or will receive finish materials. Tighten connections between members. Install fasteners
without splitting wood members.
3.10 GROUTING
A Mix and install grout for plumbing equipment base bearing surfaces, pump and other equip-
ment base plates, and anchors.
B Clean surfaces that will come into contact with grout.
F Place grout on concrete bases and provide smooth bearing surface for equipment.
PART 1 - GENERAL
A Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
B The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A Section includes general requirements for single-phase and polyphase, general-purpose, hor-
izontal, small and medium, squirrel-cage induction motors for use on ac power systems up to
600 V and installed at equipment manufacturer's factory or shipped separately by equipment
manufacturer for field installation.
1.3 COORDINATION
A Coordinate features of motors, installed units, and accessory devices to be compatible with
the following:
1. Motor controllers.
2. Torque, speed, and horsepower requirements of the load.
3. Ratings and characteristics of supply circuit and required control sequence.
4. Ambient and environmental conditions of installation location.
PART 2 PRODUCTS
A Comply with requirements in this Section except when stricter requirements are specified in
plumbing equipment schedules or Sections.
A Duty:
1. Sufficient to start, accelerate, and operate connected loads at designated speeds, at in-
stalled altitude and environment, with indicated operating sequence, and without ex-
ceeding nameplate ratings or considering service factor.
A Description:
B Efficiency:
C Service Factor:
1. 1.15.
D Multispeed Motors:
1. Variable torque.
a. For motors with 2:1 speed ratio, consequent pole, single winding.
b. For motors with other than 2:1 speed ratio, separate winding for each speed.
E Multispeed Motors:
F Rotor:
G Bearings:
1. Regreasable, shielded, antifriction ball bearings suitable for radial and thrust loading.
H Temperature Rise:
I Insulation:
1. Class F.
K Enclosure Material:
1. Cast iron for motor frame sizes 324T and larger; rolled steel for motor frame sizes
smaller than.
1. Match wiring connection requirements for controller with required motor leads. Pro-
vide terminals in motor terminal box, suited to control method.
C Severe-Duty Motors:
A Motors larger than 1/20 hp shall be one of the following, to suit starting torque and require-
ments of specific motor application:
a. Permanent-split capacitor.
b. Split phase.
c. Capacitor start, inductor run.
d. Capacitor start, capacitor run.
B Multispeed Motors:
C Bearings: -
1. Prelubricated, antifriction ball bearings or sleeve bearings suitable for radial and thrust
loading.
1. Shaded-pole type.
E Thermal Protection:
1. Internal protection to automatically open power supply circuit to motor when winding
temperature exceeds a safe value calibrated to temperature rating of motor insulation.
Thermal-protection device shall automatically reset when motor temperature returns to
normal range.
PART 1 - GENERAL
A Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
B The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A Section Includes:
1.3 DEFINITIONS
A BR:
1. Butyl rubber.
B Buna-N:
1. Nitrile rubber.
C CR:
D CSM:
1. Chlorosulfonyl-polyethylene rubber.
E EPDM:
F NR:
1. Natural rubber.
A Compatibility:
1. Products shall be suitable for piping system fluids, materials, working pressures, and
temperatures.
B Capability:
1. Products shall absorb 200 percent of maximum axial movement between anchors.
1.5 SUBMITTALS
A Product Data:
B Delegated-Design Submittal:
1. For each anchor and alignment guide indicated to comply with performance require-
ments and design criteria, including analysis data signed and sealed by the qualified
professional engineer responsible for their preparation.
C Welding certificates.
1. Product Certificates: For each type of pipe expansion joint, signed by product manu-
facturer.
2. Maintenance Data: For pipe expansion joints to include in maintenance manuals.
A Welding Qualifications:
a. Steel Shapes and Plates: AWS D1.1, "Structural Welding Code - Steel."
b. Welding to Piping: ASME Boiler and Pressure Vessel Code: Section IX.
PART 2- PRODUCTS
2.1 MANUFACTURERS
1. ASTM F 1123, fabric-reinforced rubber with external control rods and complying with
FSA's "Technical Handbook: Non-Metallic Expansion Joints and Flexible Pipe Con-
nectors".
c. Material: EPDM.
d. End Connections: Full-faced, integral, steel flanges with steel retaining rings.
A Description:
1. Steel, factory fabricated, with bolted two-section outer cylinder and base for alignment
of piping and two-section guiding spider for bolting to pipe.
C Washers:
D Mechanical Fasteners:
1. Insert-wedge-type stud with expansion plug anchor for use in hardened portland ce-
ment concrete, and tension and shear capacities appropriate for application.
E Chemical Fasteners:
1. Insert-type-stud bonding system anchor for use with hardened portland cement con-
crete, and tension and shear capacities appropriate for application.
a. Bonding Material: ASTM C 881, Type IV, Grade 3, 2-component epoxy resin
suitable for surface temperature of hardened concrete where fastener is to be in-
stalled.
b. Stud: ASTM A 307, zinc-coated carbon steel with continuous thread on stud,
unless otherwise indicated.
c. Washer and Nut: Zinc-coated steel.
F Concrete:
1. Portland cement mix, 20.7 MPa minimum. Comply with requirements in Division 03
Section "Cast-in-Place Concrete" for formwork, reinforcement, and concrete.
G Grout:
PART 3 - EXECUTION
B Install expansion joints of sizes matching size of piping in which they are installed.
C Install alignment guides to allow expansion and to avoid end-loading and torsional stress.
A Install pipe bends and loops cold-sprung in tension or compression as required to partly ab-
sorb tension or compression produced during anticipated change in temperature.
C Steel Anchors: Attach by welding. Comply with ASME B31.9 and ASME Boiler and Pres-
sure Vessel Code: Section IX, "Welding and Brazing Qualifications."
A Connect risers and branch connections to mains with at least five pipe fittings, including tee
in main.
B Connect risers and branch connections to terminal units with at least pipe fittings, including
tee in riser.
C Connect mains and branch connections to terminal units with at least four pipe fittings, in-
cluding tee in main.
B Fabricate and install steel anchors by welding steel shapes, plates, and bars to piping and to
structure. Comply with ASME B31.9 and AWS D1.1.
E Use grout to form flat bearing surfaces for expansion fittings, guides, and anchors installed
on or in concrete.
PART 1 GENERAL
A Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A Section Includes:
1. Thermometers.
2. Gauges.
3. Test plugs.
B Related Sections:
1. Division 22 Section "Facility Water Distribution Piping" for domestic and fire-
protection water service meters outside the building.
2. Division 22 Section "Domestic Water Piping" for domestic and fire-protection water
service meters inside the building.
1.3 DEFINITIONS
1.4 SUBMITTALS
A Product Data: For each type of product indicated; include performance curves.
B Shop Drawings: Schedule for thermometers and gages indicating manufacturer's number,
scale range, and location for each.
C Product Certificates: For each type of thermometer and gage, signed by product
manufacturer.
PART 2 PRODUCTS
2.1 MANUFACTURERS
B Tube: Red or blue reading, mercury or organic-liquid filled, with magnifying lens.
D Window: Glass.
F Stem: Copper-plated steel, aluminum, or brass for thermowell installation and of length to
suit installation.
G Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
F Window: Glass.
J Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
A Case: Dry type, drawn steel or cast aluminum 152-mm diameter with holes for panel mount-
ing.
F Window: Glass.
J Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
F Window: Glass.
J Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
1. Case: Dry type, drawn steel or cast aluminum 152-mm diameter with holes for panel
mounting.
2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated.
3. Pressure Connection: Brass, DN 8, bottom-outlet type unless back-outlet type is indi-
cated.
4. Movement: Mechanical, with link to pressure element and connection to pointer.
5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings.
6. Pointer: Red or other dark-color metal.
7. Window: Glass.
8. Ring: Stainless steel.
9. Accuracy: Grade A, plus or minus 1 percent of middle half scale.
10. Vacuum-Pressure Range: 100 kPa of vacuum to 103 kPa of pressure.
11. Range for Fluids under Pressure: Two times operating pressure.
C Pressure-Gauge Fittings:
A Description: Corrosion-resistant brass or stainless-steel body with core inserts and gasketed
and threaded cap, with extended stem for units to be installed in insulated piping.
1. Insert material for water service at minus 7 to plus 93 deg C shall be CR.
2. Insert material for water service at minus 35 to plus 136 deg C shall be EPDM.
D Test Kit: Furnish two test kits containing one pressure gage and adaptor, one thermometer,
and carrying case. Pressure gage, adapter probes, and thermometer sensing elements shall be
of diameter to fit test plugs and of length to project into piping.
1. Pressure Gage: Small bourdon-tube insertion type with 51- to 76-mm diameter dial
and probe. Dial range shall be 0 to 1380 kPa.
2. Low-Range Thermometer: Small bimetallic insertion type with 25- to 51-mm-
diameter dial and tapered-end sensing element. Dial ranges shall be minus 4 to plus
52 deg C.
3. High-Range Thermometer: Small bimetallic insertion type with 25- to 51-mm diame-
ter dial and tapered-end sensing element. Dial ranges shall be minus 18 to plus 104
deg C.
4. Carrying case shall have formed instrument padding.
PART 3 EXECUTION
G Install dry-case-type, bimetallic-actuated dial thermometers at inlet and outlet of each Elec-
tric Heater.
1. Domestic Hot Water Secondary Lines: Minus 1 to plus 82 deg C, with 1-degree scale
divisions.
2. Domestic Hot Water Primary Lines: 0 to plus 120 deg C, with 1-degree scale divi-
sions.
3. Domestic Cold Water: Minus 18 to plus 38 deg C, with 1-degree scale divisions.
A Scale range of Pressure gauge shall be suitable for the pressure measured, at any case, the
range shall not exceed Double of the measured value.
B Pressure Rating of Pressure gauges and its syphon shall be rated as pump rated.
C Install dry-case-type pressure gages, 100mm dial diameter with suitable scale range as men-
tioned above for the following:
1. Upstream and downstream of each Pressure Reducing Valve.
2. Primary and secondary piping inlet and outlet of each Domestic water and Swimming
pool Heat Exchangers.
3. Primary and secondary piping inlet and outlet of each Domestic hot water storage
tanks.
4. Suction and Discharge of each pump.
5. Inlet and outlet of each water heater serving swimming pool.
6. Inlet and outlet of each controller of the Automatic Multimedia Filter, Automatic
Activated Carbon Filter and Polishing Softener.
D Install dry-case-type pressure gauges at discharge of Air Blower. Pressure Rating of Pressure
gauge and its syphon shall be rated as Air Blower rated. (0 to Plus 1000) mbar Scale range
with vacuum.
3.3 INSTALLATIONS
B Install remote-mounting dial thermometers on panel, with tubing connecting panel and ther-
mometer bulb supported to prevent kinks. Use minimum tubing length.
C Install direct-mounting pressure gages in piping tees with pressure gage located on pipe at
most readable position.
E Install needle-valve and snubber fitting in piping for each pressure gage.
I Install thermometers and gages adjacent to machines and equipment to allow service and
maintenance for thermometers, gages, machines, and equipment.
J Adjust faces of thermometers and gages to proper angle for best visibility.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
B. The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A. Section Includes:
B. Related Sections:
1.3 DEFINITIONS
A. CWP:
B. EPDM:
C. NRS:
1. Nonrising stem.
D. OS&Y:
E. RS:
1. Rising stem.
F. SWP:
1.4 SUBMITTALS
A. Product Data:
1. Obtain each type of valve from single source from single manufacturer.
B. ASME Compliance:
1. ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design criteria.
2. ASME B31.1 for power piping valves.
3. ASME B31.9 for building services piping valves.
C. NSF Compliance:
C. Use sling to handle large valves; rig sling to avoid damage to exposed parts. Do not use
handwheels or stems as lifting or rigging points.
PART 2 - PRODUCTS
A. Manufacturers:
1. Not less than indicated and as required for system pressures and temperatures.
D. Valve Sizes:
G. Valve-End Connections:
1. MSS SP-45.
1. Description:
a. Standard: MSS SP-80, Type 1.
b. CWP Rating: 1380 kPa.
c. Body Material: ASTM B 62, bronze with integral seat and screw-in bonnet.
d. Ends: Threaded.
e. Stem and Disc: Bronze.
1. Description:
a. Standard: MSS SP-110.
b. SWP Rating: 150 psig (1035 kPa).
c. CWP Rating: 600 psig (4140 kPa).
d. Body Design: Two piece.
e. Body Material: Bronze.
f. Ends: Threaded.
g. Seats: PTFE or TFE.
h. Stem: Bronze.
i. Ball: Chrome-plated brass.
j. Port: Full.
A. 200 CWP, Iron, Single-Flange Butterfly Valves with EPDM Seat and Ductile-Iron Disc:-
1. Description:
1. Description:
A. Class 250, Iron, Globe, Center-Guided Check Valves with Metal Seat:
1. Description:
A. Class 125, Iron, Globe, Center-Guided Check Valves with Resilient Seat:
1. Description:
a. Standard: MSS SP-125.
b. CWP Rating: 1380 kPa.
c. Body Material: ASTM A 126, gray iron.
d. Style: Globe, spring loaded.
e. Ends: Flanged.
f. Seat: EPDM.
1. Description:
a. Standard: MSS SP-80, Type 1.
b. CWP Rating: 1380 kPa.
c. Body Material: ASTM B 62, bronze with integral seat and screw-in bonnet.
d. Ends: Threaded.
e. Stem: Bronze.
f. Disc: Solid wedge; bronze.
g. Packing: Asbestos free.
h. Handwheel: Malleable iron.
1. Description:
a. Standard: MSS SP-80, Type 2.
b. CWP Rating: 1380 kPa.
c. Body Material: ASTM B 62, bronze with integral seat and screw-in bonnet.
d. Ends: Threaded.
e. Stem: Bronze.
f. Disc: Solid wedge; bronze.
g. Packing: Asbestos free.
h. Handwheel: Malleable iron.
1. Description:
1. Description:
1. Description:
1. Description:
1. Description:
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove
special packing materials, such as blocks, used to prevent disc movement during shipping
and handling.
B. Operate valves in positions from fully open to fully closed. Examine guides and seats made
accessible by such operations.
C. Examine threads on valve and mating pipe for form and cleanliness.
D. Examine mating flange faces for conditions that might cause leakage. Check bolting for
proper size, length, and material. Verify that gasket is of proper size, that its material
composition is suitable for service, and that it is free from defects and damage.
A. Install valves with unions or flanges at each piece of equipment arranged to allow service,
maintenance, and equipment removal without system shutdown.
B. Locate valves for easy access and provide separate support where necessary.
3.3 ADJUSTING
A. Adjust or replace valve packing after piping systems have been tested and put into service
but before final adjusting and balancing. Replace valves if persistent leaking occurs.
B. If valves with specified SWP classes or CWP ratings are not available, the same types of
valves with higher SWP classes or CWP ratings may be substituted.
C. Select valves, except wafer types, with the following end connections:
1. For Copper Tubing, DN 50 and Smaller: Threaded ends except where solder-joint
valve-end option is indicated in valve schedules below.
2. For Copper Tubing, DN 65 to DN 100: Flanged ends except where threaded valve-
end option is indicated in valve schedules below.
1. Bronze Valves: May be provided with solder-joint ends instead of threaded ends.
2. Ball Valves: Two-piece, full port, bronze with bronze trim.
3. Bronze Lift Check Valves: Class 125, bronze disc.
4. Bronze Swing Check Valves: Class 125bronze disc.
5. Bronze Gate Valves: Class 125, NRS.
1. Bronze Valves: May be provided with solder-joint ends instead of threaded ends.
2. Ball Valves: Two pieces, full port, bronze with bronze trim.
3. Bronze Lift Check Valves: Class 125, bronze disc.
4. Bronze Swing Check Valves: Class 125 bronze disc.
5. Bronze Gate Valves: Class 125, NRS.
B. DN 65 and Larger:
1. Bronze Valves: May be provided with solder-joint ends instead of threaded ends.
2. Bronze Angle Valves: Class 125 bronze disc.
3. Ball Valves: Two pieces, full port, or bronze with bronze trim.
4. Bronze Swing Check Valves: Class 125, bronze disc.
5. Bronze Gate Valves: Class 125, NRS.
6. Bronze Globe Valves: Class 125 bronze disc.
1. Bronze Valves: May be provided with solder-joint ends instead of threaded ends.
2. Bronze Angle Valves: Class 125 bronze disc.
3. Bronze Swing Check Valves: Class 125, bronze disc.
4. Bronze Gate Valves: Class 125, NRS.
5. Bronze Globe Valves: Class 125, bronze disc.
A. Refer to the Related Division 22, section 221119 “DOMESTIC WATER PIPING
SPECIALTIES”
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
B. The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A. This Section includes the following hangers and supports for plumbing system piping and
equipment:-
1. Division 22 Section "Expansion Fittings and Loops for Plumbing Piping" for pipe
guides and anchors.
1.3 DEFINITIONS
A. MSS:
1. Manufacturers Standardization Society for The Valve and Fittings Industry Inc.
B. Terminology:
1. As defined in MSS SP-90, "Guidelines on Terminology for Pipe Hangers and Sup-
ports."
A. Design supports for multiple pipes, including pipe stands, capable of supporting combined
weight of supported systems, system contents, and test water.
C. Design seismic-restraint hangers and supports for piping and equipment and obtain approval
from authorities having jurisdiction.
1.5 SUBMITTALS
A. Product Data:
B. Shop Drawings:
1. Signed and sealed by a qualified professional engineer. Show fabrication and installa-
tion details and include calculations for the following:
a. Trapeze pipe hangers. Include Product Data for components.
b. Metal framing systems. Include Product Data for components.
c. Pipe stands. Include Product Data for components.
d. Equipment supports.
e. Welding certificates.
A. Welding:
1. Qualify procedures and personnel according to AWS D1.1, "Structural Welding Code-
-Steel." and ASME Boiler and Pressure Vessel Code: Section IX.
B. Welding:
PART 2 - PRODUCTS
B. Nonmetallic Coatings:
C. Padded Hangers:
1. Hanger with fiberglass or other pipe insulation pad or cushion for support of bearing
surface of piping.
A. Trapeze pipe hangers in this Article require calculation and detail of each unit.
B. Description:
1. MSS SP-69, Type 59, shop- or field-fabricated pipe-support assembly made from
structural-steel shapes with MSS SP-58 hanger rods, nuts, saddles, and U-bolts.
A. Powder-Actuated Fasteners:
1. Threaded-steel stud, for use in hardened portland cement concrete with pull-out, ten-
sion, and shear capacities appropriate for supported loads and building materials
where used.
B. Mechanical-Expansion Anchors:
1. One-piece stainless-steel base unit with plastic roller, for roof installation without
membrane penetration.
1. Assembly of base, vertical and horizontal members, and pipe support, for roof installa-
tion without membrane penetration.
1. Assembly of bases, vertical and horizontal members, and pipe supports, for roof in-
stallation without membrane penetration.
A. Description:
1. IAPMO PS 42, system of metal brackets, clips, and straps for positioning piping in
pipe spaces for plumbing fixtures for commercial applications.
A. Description:
A. Structural Steel:
1. ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.
B. Grout:
PART 3 - EXECUTION
A. Specific hanger and support requirements are specified in Sections specifying piping systems
and equipment.
B. Comply with MSS SP-69 for pipe hanger selections and applications that are not specified in
piping system Sections.
C. Use hangers and supports with galvanized, metallic coatings for piping and equipment that
will not have field-applied finish.
D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in
direct contact with copper tubing.
G. Vertical-Piping Clamps:
2. Unless otherwise indicated and except as specified in piping system Sections, install
the following types:
a. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers,
DN 20 to DN 500.
b. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe ris-
ers, DN 20 to DN 500, if longer ends are required for riser clamps.
H. Building Attachments:
1. Unless otherwise indicated and except as specified in piping system Sections, install
the following types:
a. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to
suspend pipe hangers from concrete ceiling.
b. Top-Beam C-Clamps (MSS Type 19): For use under roof installations with bar-
joist construction to attach to top flange of structural shape.
c. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange
of beams, channels, or angles.
d. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange
of beams.
e. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams
if loads are considerable and rod sizes are large.
l. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
m. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is
required.
n. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to
linear horizontal movement where headroom is limited.
1. Unless otherwise indicated and except as specified in piping system Sections, install
the following types:
a. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids
with insulation that matches adjoining insulation.
b. Protection Shields (MSS Type 40): Of length recommended in writing by man-
ufacturer to prevent crushing insulation.
c. Thermal-Hanger Shield Inserts: For supporting insulated pipe.
1. Unless otherwise indicated and except as specified in piping system Sections, install
the following types:
3) Trapeze (MSS Type 56): Two vertical-type supports and one trapeze
member.
K. Comply with MSS SP-69 for trapeze pipe hanger selections and applications that are not
specified in piping system Sections.
L. Comply with MFMA-102 for metal framing system selections and applications that are not
specified in piping system Sections.
N. Use pipe positioning systems in pipe spaces behind plumbing fixtures to support supply and
waste piping for plumbing fixtures.
A. Comply with the Requirement prescribed on the Division 22, “PLUMBING GENERAL
PROVISIONS – SUPPORTS”.
1. Comply with MSS SP-69 and MSS SP-89. Install hangers, supports, clamps, and at-
tachments as required to properly support piping from building structure.
1. Comply with MSS SP-69 and MSS SP-89. Arrange for grouping of parallel runs of
horizontal piping and support together on field-fabricated trapeze pipe hangers.
a. Pipes of Various Sizes: Support together and space trapezes for smallest pipe
size or install intermediate supports for smaller diameter pipes as specified
above for individual pipe hangers.
b. Field fabricate from ASTM A 36/A 36M, steel shapes selected for loads being
supported. Weld steel according to AWS D1.1.
1. Arrange for grouping of parallel runs of piping and support together on field-
assembled metal framing systems.
1. Install powder-actuated fasteners for use in lightweight concrete or concrete slabs less
than 4 inches (100 mm) thick in concrete after concrete is placed and completely
cured. Use operators that are licensed by powder-actuated tool manufacturer. Install
fasteners according to powder-actuated tool manufacturer's operating manual.
2. Install mechanical-expansion anchors in concrete after concrete is placed and com-
pletely cured. Install fasteners according to manufacturer's written instructions.
1. Pipe Stand Types except Curb-Mounting Type: Assemble components and mount on
smooth roof surface. Do not penetrate roof membrane.
2. Curb-Mounting-Type Pipe Stands: Assemble components or fabricate pipe stand and
mount on permanent, stationary roof curb.
1. Install support devices to make rigid supply and waste piping connections to each
plumbing fixture. Refer to Division 22 Section "Plumbing Fixtures" for plumbing fix-
tures.
2. Install hangers and supports complete with necessary inserts, bolts, rods, nuts, wash-
ers, and other accessories.
J. Load Distribution:
1. Install hangers and supports so piping live and dead loads and stresses from movement
will not be transmitted to connected equipment.
K. Pipe Slopes:
1. Install hangers and supports to provide indicated pipe slopes and so maximum pipe
deflections allowed by ASME B31.9 (for building services piping) are not exceeded.
L. Insulated Piping:
through insulation.
2) Piping Operating below Ambient Air Temperature: Use thermal-hanger
shield insert with clamp sized to match OD of insert.
3) Do not exceed pipe stress limits according to ASME B31.9 for building
services piping.
B. Grouting:
1. Place grout under supports for equipment and make smooth bearing surface.
2. Provide lateral bracing, to prevent swaying, for equipment supports.
A. Comply with the Requirement prescribed on the Division 22, “PLUMBING GENERAL
PROVISIONS – SUPPORTS”.
B. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and equipment
supports.
C. Fit exposed connections together to form hairline joints. Field weld connections that cannot
be shop welded because of shipping size limitations.
D. Field Welding:
1. Comply with AWS D1.1 procedures for shielded metal arc welding, appearance and
quality of welds, and methods used in correcting welding work, and with the follow-
ing:
a. Use materials and methods that minimize distortion and develop strength and
corrosion resistance of base metals.
b. Obtain fusions without undercut or overlap.
c. Remove welding flux immediately.
d. Finish welds at exposed connections so no roughness shows after finishing and
contours of welded surfaces match adjacent contours.
3.5 ADJUSTING
A. Hanger Adjustments:
3.6 PAINTING
A. Touch Up:
1. Clean field welds and abraded areas of shop paint. Paint exposed areas immediately
after erecting hangers and supports. Use same materials as used for shop painting.
Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.
a. Apply paint by brush or spray to provide minimum dry film thickness of 0.05
mm.
B. Touch Up:
1. Cleaning and touchup painting of field welds, bolted connections, and abraded areas
of shop paint on miscellaneous metal are specified in Division 09 painting Sections.
C. Galvanized Surfaces:
1. Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint
to comply with ASTM A 780.
SECTION 220548 - VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND
EQUIPMENT
PART 1 GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. The Qatar construction specification (QCS 2014) shall form the basis of the project
specification. The technical specification is supplemental to QCS (latest revision) and
should be read in conjunction with QCS and all other contract documents. In case of
contradiction or discrepancy between QCS and technical specifications, CONTRACTOR
shall incorporate whichever is more stringent.
A. Inertia bases.
B. Vibration isolation.
1.3 REFERENCES
C. Do not exceed the allowable noise level, 70 dBA measured at a distance of 1200 mm from
source, by proper engineering of equipment assemblies.
A. Fans and other rotating mechanical equipment shall not operate at speeds in excess of
80 % of their true critical speed
B. Vertical vibration of rotating equipment shall not be greater than the levels indicated.
The vibration shall be measured on the equipment or steel frame equipment base when the
equipment is mounted on its vibration isolation mounts. If the equipment has an inertia
base, the allowable vibration level is reduced by the ratio of the equipment weight alone to
the equipment weight plus the inertia base weight.
Vibration Displacement
Equipment Speed
(MILS peak-to-peak)
under 600 rpm 4
600 to 1000 rpm 3
1000 to 2000 rpm 2
over 2000 rpm 1
1.6 SUBMITTALS
B. Include data for each equipment and size of unit showing isolation type, efficiency,
stiffness, natural frequency, and transmissibility at lowest operating speed of equipment,
actual load, static deflection under actual load etc.
D. Indicate vibration isolator locations, on general layout and plant room detail drawings.
E. Flexible pipe connector shop drawings data to include maximum allowable temperature
and pressure rating, overall face to face length, live length, hose wall thickness, and
fundamental frequency of assembly.
F. Submit manufacturer's certificates under provisions of Section 01440 that the vibration
isolators are properly selected and installed in equipment assemblies, to meet with, or to
exceed the Contract requirements.
A. Deliver products to site, store and protect under provisions of Section 01 6000.
PART 2 PRODUCTS
B. TYPE "1" - ISOLATING PADS: This type of vibration isolators shall be generally used
where the vibrating force is transmitted directly to ground or the vibrating force is very small
compared to the absorption capacity of the structural slab at higher levels.
E. TYPE "1C" - CORK PADS: The cork pads shall be constructed from natural cork granules
compressed and steam baked to form slabs and shall have a density of 96 to
106 kg/cu.M . The cork pads shall be treated with hot Bitumen Asphalt coating for
protection of cork.
F. TYPE "2" - MOLDED NEOPRENE RUBBER MOUNTS: These shall be used where a
greater deflection is required than that for pads. The maximum deflection allowable is 12 mm
on these rubber mounts. The normal shape of mount is conical with a captive insert for
attaching to equipment base.
G. TYPE "3" - FREE STANDING SPRING ISOLATORS: These shall be constructed with
open type stable spring and load plates at top and bottom with an adjustable bolt for levelling.
Neoprene rubber acoustical treatment shall be provided to prevent transmission of very high
frequency vibration and noise. The spring shall be so designed that the horizontal stiffness is
more than 75 % of vertical stiffness. The rated loads and deflections for these springs shall
allow additional 50 % travel to that of the rated deflection before the springs are compressed
solid, to accommodate any errors in actual load distribution.
H. TYPE "4" - RESTRAINED SPRING ISOLATORS: These are similar to type "3", but with
additional restraints in the vertical direction. These isolators shall have hold down bolts to
limit vertical movement. The restraints should have adequate clearance so that they are
activated only when a temporary restraint is needed.
I. TYPE "5" - HOUSED SPRING ISOLATORS: These isolators are similar to type "4"
except that they consist of two telescoping houses. The contact surfaces of houses are
separated by resilient inserts such as Neoprene Sponge or equivalent material.
J. TYPE "6" - RUBBER HANGERS: These are similar to type "2" except that the conical
rubber mold is housed in a steel casing and have a through hole for the hanger rod. The
assembly should allow for 20 to 35 degrees angular movement for the hanging rod
without metal to metal contact.
K. TYPE "7" - SPRING HANGERS: These are similar to type "3" except that the spring is
mounted in a steel casing and used for suspension only. The assembly shall allow for
20 to 25 degrees angular movement for the hanging rod without metal to metal contact.
M. TYPE "9" - THRUST RESTRAINTS: These are similar to type "7", but installed in pairs to
counteract the thrust caused by air pressure.
N. TYPE "10" - AIR SPRINGS: These shall consist of constant dry air supplying equipment and
air bellows. These shall be used where 150 mm (6 inch) or greater deflection is required
and natural frequencies do not exceed 80 Hz.
B. Type "A" - INTEGRAL BASES: This type is generally applicable for packaged chillers,
pumps, Air Handling Units, Air conditioning Units etc. which are supplied with factory
fabricated rigid base which can be mounted directly on vibration isolators. Equipment
manufacturer's recommendations should be sought for the number, locations and weight
distribution to select and install vibration isolators.
C. Type "B" - STEEL STRUCTURAL BASES: This type is generally subdivided into closed
frame type (Type B1) and rails type (Type B2). These are steel bases fabricated either as per
the approved shop drawing or as per the equipment manufacturer's recommendation. These
are used for equipment not having a rigid base. The type B1 shall be used where the
vibration isolators are located within the equipment base and type B2 shall be used when the
vibration isolators are outside the equipment and the type B2 base acts as a cradle. The
minimum depth shall be 4 inches.
D. TYPE "C" CONCRETE INTERTIAL BASES: This type generally consists of structural
steel, fabricated pouring form with reinforcing bars. The concrete shall be poured on site.
The minimum depth shall be 6 inches.
E. TYPE "D" - ROOF CURBS: This type is generally used for Roof top Air Handling Units
with direct cutting through roof slab under the units. These roof curbs shall be supplied by
the unit manufacturer. The manufacturer's recommendations should be sought for the
number, locations and weight distribution to select and install vibration isolators.
F. TYPE "E" - HOUSE KEEPING PADS: These are concrete bases used for all equipment
with or without moving parts and shall be suitable for taking up the static and dynamic
loads (if any). Size base to extend 100 mm beyond equipment base in all directions and
minimum 100 mm above finished floor level. Roughen floor slab beneath base for bond
and or provide rebar dowels in floor slab. Locate anchor bolts (welded on to a rebar
framework to maintain spacing) with templates supplied by the equipment manufacturer.
Provide steel angle frame with anchorage lugs at the corners. Also see table 3.03 for
exact heights.
G. TYPE "F" - FLOATING CONCRETE BASE: This is similar to Type "E" (House
keeping pads) but isolated at the bottom and all the side by either pre-compressed glass
fiber pads or Heavy density seasoned cork. The thickness of isolating pads vary from 25
to 100 mm depending on the application.
PART 3 EXECUTION
3.1 APPLICATION
A. General
1. Refer to PART 2 - PRODUCTS of this specification for vibration isolation devices
identified on the schedule or specified herein.
B. Major Equipment
1. Unless otherwise shown or specified, all floor mounted major equipment shall be set
on concrete housekeeping pads as per recommendations of the manufacturer. See
schedule of mounting pads in this section.
2. Types and minimum static deflections of vibration isolation devices for major
equipment items shall be as scheduled on the drawings or specified here under.
D. Piping
1. Provide flexible pipe connections in piping connected to vibration isolated
equipment, as called for and shown on drawings.
2. Anchor piping at the system side of the flexible connector.
A. General
1. Locations of all vibration isolation equipment shall be selected for ease of
inspection and adjustment as well as for proper operation.
2. Installation of vibration isolation equipment shall be in accordance with the
manufacturer's instructions.
B. Isolation Mounts
1. All vibration isolators shall be aligned squarely above or below mounting points of the
supported equipment.
2. Isolators for equipment with bases shall be located on the sides of the bases, which
are parallel to the equipment shaft unless this is not possible because of physical
constraints.
3. If a housekeeping pad is provided, the isolators shall bear on the housekeeping pad
and the isolator base plate shall rest entirely on the pad.
4. Hanger rods for vibration isolated support shall be connected to structural beams or
joists, not from the floor slab between beams and joists. Provide intermediate support
members as necessary.
5. Vibration isolation hanger elements shall be positioned as high as possible in the
hanger rod assembly, but not in contact with the building structure, and so that the
hanger housing may rotate a full 360 degrees about the rod axis without
contacting any object.
6. Parallel running pipes may be hung together on a trapeze, which is isolated from the
building. Isolator deflections must be the largest determined by the provisions for pipe
isolation. Do not mix isolated and non-isolated pipes on the same trapeze.
7. No pipes or equipment shall be supported from other pipes or equipment.
8. Resiliently isolated pipes shall not contact the building construction or other
equipment.
9. The installed and operating heights of vibration isolators supporting any
equipment shall be identical. Limit stops shall be out of contact during normal
operation.
10. Adjust all leveling bolts and hanger rod bolts so that the isolated equipment is
level and in proper alignment with connecting ducts or pipes.
C. Bases
1. No equipment unit shall bear directly on vibration isolators unless its own frame is
suitably rigid to span between isolators and such direct support is approved by the
equipment manufacturer. This provision shall apply whether or not a base frame is
called for on the schedule. In the case that a base frame is required for the unit
because of the equipment manufacturer's requirements and is not specifically called
for on the equipment schedule, a base frame recommended by the equipment
manufacturer shall be provided.
2. Unless otherwise indicated, there is to be a minimum operating clearance of 38- mm
between inertia bases or steel frame bases and the floor beneath the equipment.
Position isolator mounting brackets and adjust isolators so that the required clearance
is maintained. The clearance space shall be checked by the Contractor to ensure that
no construction debris has been left to short circuit or restrict the proper operation of
the vibration isolation system.
E. Thrust Restraints
1. Snubbers shall be adjusted to clear the equipment base and to provide lateral
restraint during on / off cycling, but be out of contact during normal operation of the
equipment.
2. Thrust restraints shall be attached at the center line of thrust and symmetrically
on each of the units. Adjust the restraints to limit equipment movement to the
specified limit.
ISOLATOR DEFLECTION,
NO. EQUIPMENT BASE
TYPE mm
Unitary Pumps (Swim-
1 Type F 1C 6
ming Pools, etc.)
2 Central sand filters Type E None
Packace Pump Sets On
3 Type F 1C 38
elevated slabs
Packaged Pump Set (on
4 Type F 1C 6
raft)
5 Control Panels Type E None
Central Electric Water
6 Type E None
Heater
Hot Water circulating
7 Type F IC 6
Pumps
8 Boilers Type E None
9 Calorifiers Type E None
10 Air Compressor Type E None
3.4 ADJUSTING
B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating
height. After equipment installation is complete, adjust limit stops so they are out of
contact during normal operation.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Pipe labels.
4. Stencils.
5. Valve tags.
6. Warning tags.
1.3 SUBMITTALS
A. Product Data:
B. Samples:
1. For color, letter style, and graphic representation required for each identification mate-
rial and device.
1. Include a listing of all equipment to be labeled with the proposed content for each la-
bel.
2. Valve numbering scheme.
D. Valve Schedules:
1.4 COORDINATION
B. Coordinate installation of identifying devices with locations of access panels and doors.
C. Install identifying devices before installing acoustical ceilings and similar concealment.
PART 2 PRODUCTS
1. Material and Thickness: Anodized aluminum, 0.8-mm minimum thickness, and hav-
ing predrilled or stamped holes for attachment hardware.
2. Minimum Label Size: Length and width vary for required label content, but not less
than 64 by 19 mm.
3. Minimum Letter Size: 6.4 mm for name of units if viewing distance is less than 600
mm, 13 mm for viewing distances up to 1830 mm, and proportionately larger lettering
for greater viewing distances. Include secondary lettering two-thirds to three-fourths
the size of principal lettering.
4. Fasteners: Stainless-steel rivets or self-tapping screws.
5. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
1. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engrav-
ing, 3.2 mm thick, and having predrilled holes for attachment hardware.
2. Letter Color:
3. Background Color:
4. Maximum Temperature: Able to withstand temperatures up to 71 deg C.
5. Minimum Label Size: Length and width vary for required label content, but not less
than 64 by 19 mm.
6. Minimum Letter Size: 6.4 mm for name of units if viewing distance is less than 600
mm, 13 mm for viewing distances up to 1830 mm, and proportionately larger lettering
for greater viewing distances. Include secondary lettering two-thirds to three-fourths
the size of principal lettering.
7. Fasteners: Stainless-steel rivets or self-tapping screws.
8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
C. Label Content:
1. For each item of equipment to be labeled, on 8-1/2-by-11-inch (A4) bond paper. Tab-
ulate equipment identification number and identify Drawing numbers where equip-
ment is indicated (plans, details, and schedules), plus the Specification Section num-
ber and title where equipment is specified. Equipment schedule shall be included in
operation and maintenance data.
1. Multilayer, multicolor, plastic labels for mechanical engraving, 3.2 mm thick, and
having predrilled holes for attachment hardware.
B. Letter Color:
1. Background Color
C. Maximum Temperature:
1. Length and width vary for required label content, but not less than 64 by 19 mm.
1. 6.4 mm for name of units if viewing distance is less than 600 mm, 13 mm for viewing
distances up to 1830 mm, and proportionately larger lettering for greater viewing dis-
tances. Include secondary lettering two-thirds to three-fourths the size of principal let-
tering.
F. Fasteners:
G. Adhesive:
H. Label Content:
1. Preprinted, color-coded, with lettering indicating service, and showing flow direction.
1. Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to
pipe without fasteners or adhesive.
2.4 STENCILS
A. Stencils:
1. Prepared with letter sizes according to ASME A13.1 for piping; and minimum letter
height of 19 mm for access panel and door labels, equipment labels, and similar opera-
tional instructions.
A. Valve Tags:
1. Stamped or engraved with 6.4-mm letters for piping system abbreviation and 13-mm
numbers.
B. Valve Schedules:
1. For each piping system, on 8-1/2-by-11-inch (A4) bond paper. Tabulate valve num-
ber, piping system, system abbreviation (as shown on valve tag), location of valve
(room or space), normal-operating position (open, closed, or modulating), and varia-
tions for identification. Mark valves for emergency shutoff and similar special uses.
2. Valve-tag schedule shall be included in operation and maintenance data.
A. Warning Tags:
PART 3 - EXECUTION
3.1 PREPARATION
A. Clean piping and equipment surfaces of substances that could impair bond of identification
devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and
encapsulants.
A. Piping Color-Coding:
1. Stenciled labels may be provided instead of manufactured pipe labels, at Installer's op-
tion. Install stenciled pipe labels complying with ASME A13.1, on each piping sys-
tem.
2. Locate pipe labels where piping is exposed or above accessible ceilings in finished
spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and
plenums; and exterior exposed locations as follows:
a. Background Color:
b. Letter Color:
a. Background Color:
b. Letter Color:
a. Background Color:
b. Letter Color: Black
A. Install tags on valves and control devices in piping systems, except check valves; valves
within factory-fabricated equipment units; shutoff valves; faucets; convenience and lawn-
watering hose connections; and similar roughing-in connections of end-use fixtures and
units. List tagged valves in a valve schedule.
1. Tag valves according to size, shape, and color scheme and with captions similar to
those indicated in the following subparagraphs:
2. Valve-Tag Size and Shape:
3. Valve-Tag Color:
4. Letter Color:
A. Write required message on, and attach warning tags to, equipment and other items where
required.
PART 1 - GENERAL
1.1 REFERENCES
A. The publications listed below form a part of this specification to the extent referenced. The
publications are referred to within the text by the basic designation only.
B. Adhesives, coatings, and sealants shall have published or certified temperature ratings
suitable for the entire range of working temperatures normal for the surfaces to which they
are to be applied.
1.4 SUBMITTALS
1. Installation Drawings for pipe insulation shall be submitted in accordance with para-
graph entitled, "Installation," of this section.
a. Adhesives
b. Coatings
c. Insulating Cement
d. Insulation Materials
e. Jacketing
f. Tape
PART 2 - PRODUCTS
2.1 Manufacturers:
2.2 MATERIALS
A. Materials shall be compatible and shall not contribute to corrosion, soften, or otherwise
attack surfaces to which applied in either the wet or dry state. Materials to be used on
stainless steel surfaces shall meet ASTM C MÍ95 requirements. Materials shall be asbestos
free and conform to the following.
B. Adhesives:
1. Cloth Adhesives
a. Adhesives for adhering, sizing, and finishing lagging cloth, canvas, and open-
weave glass cloth shall be a pigmented polyvinyl acetate emulsion and shall
conform to the requirements of ATM C 916, Type I.
a. Adhesives for attaching laps of vapor-barrier materials and presized glass cloth
and for attaching insulation to itself, to metal, and to various other substrates,
shall be solvent-base, synthetic-rubber type and shall conform to the require-
ments of ASTM C 916, Type I, for attaching fibrous-glass insulation to metal
surfaces. Solvent shall be nonflammable.
C. Coatings:
3. Coating Color
D. Insulation Materials:
1. Insulation conductances shall be maximum values, as tested at any point, not an aver-
age. Insulation conductance found by test to exceed the specified maximum shall ei-
ther be replaced or augmented by an additional thickness to bring it to the required
maximum conductance and a complete finishing system.
2. Mineral Fiber
a. Mineral fiber shall conform to ASTM C 553 & ASTM C 547 shall be suitable
for surface temperatures up to 188 degrees C 370 degrees F, and shall be of not
less than 64.1 kilograms per cubic meter,4 poundS per cubic foot density.
Thermal conductivity shall be not greater than 0.037 watt per meter per degree
Kelvin 0.26 Btu per hour per Square foot Square per degree F at 66 degrees C
150 degrees F mean.
3. Pipe Barrel
a. Pipe barrel insulation shall be Type II, Molded, Grade A or Type III, Precision
V-Groove, Grade A for use at temperatures up to and including 650 degrees C.
4. Pipe Fittings
a. Pipe fitting insulation shall be molded pipefitting covering for use at Tempera-
tures up to and including 650 degrees C.
5. Cellular Glass
a. Cellular glass shall conform to AS.LM C 552, Type II, Grade 2, pipe covering.
Substitutions for this material shall not be permitted. Minimum thickness shall
be 38 mm.
6. Calcium Silicate.
7.
E. Jacketing:
1. Aluminum Jackets
a. Aluminum sheet shall be in accordance with ASTM B 209M ASTM B 209 and
shall be 0.7 millimeter thick with factory-applied vapor barrier on the insulation
side. Aluminum shall be made from smooth, polished, Temper H16, Alloy
5005. Straps shall be AISZ 300 series corrosion-resistant steel, 0.381 millimeter
15 mils thick, 13 millimeter 1/2 inch wide, for pipe under DN300 12 inch diam-
eter and 20 millimeter wide for pipe over DN300 diameter.
b. Elbow jackets shall be 0.7 millimeter thick, deep-drawn, die-shaped, two-piece
components for long-radius, butt-weld elbows manufactured from the same ma-
terials as specified for jackets, with factory-attached vapor-seals on underside of
the aluminum. Pre-insulated, void-less, jacketed components conforming to
these specifications shall be used. Pre-insulated fittings shall have a 50 millime-
ter overlay beyond route for weld bead.
c. Vapor barrier shall be 3 kilogram per square meter kraft paper.
d. Pipe jackets shall have not less than 50 millimeter longitudinal and circumferen-
tial lap.
e. Sealant for longitudinal and butt joints of aluminum jacketing shall be an alumi-
num-pigmented, butyl, polymer sealant with high-butyl solids.
F. Tape:
1. Glass lagging shall be a knitted elastic cloth specifically suitable for continuous spiral
wrapping of insulated pipe bends and fittings and shall produce a smooth, tight, wrin-
kle-free surface. Tape shall conform to requirements of SAE A4S 3779, SAE AMS
3779, ?'ıSTM D 579, and ASTM C 92., and shall weigh not less than 0.339 kilogram
per square meter.
A. Insulation thickness and pipe sizes are in millimeter inches. Pipe size is inclusive
dimensionally, and includes pipe nominal pipe size (NPS) and tubing outside diameter.
1. Insulation shall be mineral fiber with vapor barrier jacket, Type T-1 cellular class with
vapor barrier jacket, Type T-4. Thickness shall be not less than that given in the fol-
lowing list. Aboveground pipes, valve bodies, fittings, unions, and flanges shall be in-
sulated.
32 38
32 to 80 38
80 and larger 50
1. Insulation shall be mineral fiber with glass cloth jacket, Type T-2. Thickness shall be
not less than that given in the following list. Aboveground pipes, valve bodies, fit-
tings, unions, flanges, and miscellaneous surfaces shall be insulated.
Up to 100 25
100 to 250 38
250 to 300 50
1. Aboveground pipes, valve bodies, fittings, unions, flanges, and miscellaneous surfaces
shall be insulated
2. Insulation shall be 10 millimeter mineral fiber with glass cloth jacket, Type T-2.
+
1. Low Temperature Hot Water and Steam Boilers’ Flue Gas Chimney /Piping, over
draft fan, elbows and miscellaneous surfaces from Boiler’s smoke Box up to atmos-
phere discharge vent cowl including stacks shall be thermally insulated.
1. Diesel Generator’s Flue Gas Chimney /Piping, over draft fan (wherever applicable),
silencer, elbows and miscellaneous surfaces from Flue output flange up to atmosphere
discharge vent cowl including stacks shall be thermally insulated.
2. Insulation shall be 150 mm thick , 100 kg/m3 density, maximum use temperature of
750o Celsius, 0.095 w/m.k at 350o Celsius mean temperature, conform to ASTM C
177 rock wool with galvanized steel wire netting hexagonal netting mish on one side.
3. Aluminum cladding / jacket as specified above with adhesive shall be applied to the
Rockwool thermal insulation where the pipe line running Horizontally as under:
A. For Pipe and pipe fittings: Riveted joints shall be applied.
B. For over deft fan Box Silencer and other miscellaneous surfaces: Clips type shall be
provided.
PART 3 - EXECUTION
A. Contours on exposed work shall be smooth and continuous. Cemented laps, flaps, bands, and
tapes shall be smoothly and securely pasted down. Adhesives shall be applied on a full-
coverage basis.
B. Insulation shall be applied only to system or component surfaces that have been tested and
approved.
C. Joints shall be tight with insulation lengths tightly butted against each other. Where lengths
are cut, cuts shall be smooth and square and without breakage of end surfaces. Where
insulation terminates, ends shall be neatly tapered and effectively sealed, or finished as
specified. Longitudinal seams of exposed insulation shall be directed away from normal
view.
E. Surfaces shall be clean and free of oil and grease before insulation adhesives or mastics are
applied. Solvent cleaning required to bring metal surfaces to such condition shall be
provided.
F. Installation Drawings for pipe insulation shall be in accordance with the adhesive
manufacturer’s written instructions for installation.
1. Piping shall be covered with mineral-fiber pipe insulation with factory-and field-
attached vapor-barrier jacket. Vapor seal shall be maintained. Jackets, jacket laps,
flaps, and bands shall be securely cemented in place with vapor-barrier adhesive.
Jacket overlap shall be not less than 40 millimeter. Jacketing bands for butt joints shall
be 75 millimeter wide.
2. Exposed-to-view fittings and valve bodies shall be covered with preformed mineral-
fiber pipe-fitting insulation of the same thickness as the pipe-barrel insulation. Fitting
insulation shall be temporarily secured in place with light cord ties. A 1.52 millimeter
60-mil coating of white indoor vapor-barrier coating shall be applied and, while still
wet, wrapped with glass lagging tape with 50 percent overlap, and shall be smoothly
blended into the adjacent jacketing. Additional coating shall be applied as needed and
rubber-gloved to smooth fillet or contour coating, then allowed to fully cure before the
finish coating is applied. On-the-job fabricated insulation for concealed fittings and
special configurations shall be built up from mineral fiber and a special mastic consist-
ing of a mixture of insulating cement and lagging adhesive diluted with 3 parts water.
Where standard vapor-barrier jacketing cannot be used, the surfaces shall be made va-
por tight by using coating and glass lagging cloth or tape as previously specified.
3. In lieu of materials and methods previously specified, fittings may be wrapped with a
twine-secured, mineral-wool blanket to the required thickness and covered with
premolded polyvinylchloride jackets. Seams shall be made vapor tight with a double
bead of manufacturer's standard vapor-barrier adhesive applied in accordance with the
manufacturer's instructions. All jacket ends shall be held in place with AISZ 300 se-
ries corrosion-resistant steel straps, 0.381millimeter thick by 15 millimeter inch wide.
4. Pipe insulation shall be set into an outdoor vapor-barrier coating for a minimum of
150 millimeter at maximum 3500 millimeter spacing and the ends of the insulation
sealed to the jacketing with the same material to provide an effective vapor-barrier
stop.
5. Staples shall not be used in applying insulation. Vapor-barrier materials shall be con-
tinuous over all surfaces, including areas inside pipe sleeves, hangers, and other con-
cealments.
6. Piping insulation at hangers shall consist of 208 kilogram per cubic meter 13-pounds
per cubic foot density, fibrous-glass inserts or expanded, rigid, closed-cell, polyvinyl-
chloride. Junctions shall be sealed with vapor-barrier jacket where required, glass-
cloth mesh tape, and vapor-barrier coating.
7. White-bleached kraft paper side of the jacketing shall be on the side exposed to view.
8. Exposed-to-view insulation shall be finished with not less than a 0.152-millimeter 6-
mil dry-film thickness of non-vapor-barrier coating suitable for painting.
1. Piping shall be covered with cellular glass insulation and factory- and field-attached
vapor-barrier jacket. Vapor seal shall be maintained. Jackets, jacket laps, flaps, and
bands shall be securely cemented in place with vapor-barrier adhesive. Jacket overlap
shall be not less than 40 millimeter. Jacket bands for butt joints shall be not less than
75 millimeter wide. Insulation shall be continuous through hangers. Insulation shall be
bedded in an outdoor vapor-barrier coating applied to all piping surfaces.
2. Flanges, unions, valves, anchors, and fittings shall be insulated with factory premold-
ed or prefabricated or field fabricated segments of insulation of the same material and
thickness as the adjoining pipe insulation. When segments of insulation are used, el-
bows shall be provided with not less than three segments. For other fittings and
valves, segments shall be cut to the required curvature or nesting size.
3. Segments of the insulation shall be secured in place with twine or copper wire. After
the insulation segments are firmly in place, a vapor-barrier coating shall be applied
over the insulation in two coats with glass tape imbedded between coats. First coat
shall be tinted, the second shall be white to ensure application two coats. Coating shall
be applied to a total dry-film thickness of 1.6 millimeter minimum. Glass tape seams
shall overlap not less than 25 millimeter and the tape end not less than 100 millimeter.
4. In lieu of materials and methods specified above, fittings may be wrapped with 10
millimeter thick, vapor-barrier, adhesive-coated strips of cellular elastomer insulation.
Insulation shall be under tension, compressed to 25 percent of original thickness, and
wrapped until overall thickness is equal to adjacent insulation. Cellular elastomer shall
be secured in place with twine and sealed with vapor-barrier coating applied to pro-
duce not less than 1.6 millimeter dry-film thickness. Fittings shall then be covered
with premolded polyvinylchloride jackets. Seams shall be made vapor-tight with a
double bead of manufacturer's standard vapor-barrier adhesive applied in accordance
with the manufacturer's instructions. Jacket ends shall be held in place with AISZ 300
series corrosion-resistant steel straps, 0.381 millimeter thick by 15 millimeter wide.
5. BB. Anchors secured directly to piping shall be insulated, to prevent condensation, for
not less than 150 millimeter from the surface of the pipe insulation.
6. White-bleached kraft paper side of jacketing shall be on the side exposed to view. Ex-
posed-to-view insulation shall be finished with not less than a 0.152 millimeter dry-
film thickness of nonvapor-barrier coating suitable for painting.
1. EE. Piping shall be covered with mineral-fiber pipe insulation with factory-attached or
field-applied aluminum jacketing.
2. Fittings and valve bodies shall be covered with preformed mineral-fiber pipe-fitting
insulation of the same thickness as the pipe-barrel insulation. Fitting insulation shall
be secured temporarily in place with light cord ties. A 1.52 millimeter coating of va-
por-barrier mastic shall be applied, and while still tacky, wrapped with glass lagging
tape.
3. Additional mastic shall be applied as needed and rubber-gloved to smooth fillets or
contours. On-the-job fabricated insulation for special configurations shall be built up
from mineral fiber and a mixture of insulating cement and lagging adhesive diluted
with 3 parts water. Only where standard aluminum jacketing cannot be used, the sur-
faces shall be made vapor-tight by using mastic and glass lagging cloth or tape as
specified above with an added finish coat of mastic.
4. Pipe insulation shall be set into outdoor vapor-barrier coating for a minimum of 150
millimeter at maximum 3500 millimeter spacing. Ends of the insulation shall be
sealed to the jacketing with the same material to provide effective vapor barrier stops.
5. Vapor barrier shall be continuous over all surfaces, including areas inside pipe
sleeves, hangers, and other concealment.
6. Piping insulation shall be applied to both sides of pipe hangers. Junctions shall be in-
sulated with a special mastic mixture, glass cloth mesh tape, and mastic as previously
specified.
7. Jacket laps, flaps, and bands shall be securely cemented in place with aluminum jacket
sealant. Jacketing bands for butt joints shall be 150 millimeter 6 inches wide.
8. Joints, wherever possible, shall be lapped against the weather so that the water will
run off the lower edge. Laps shall be in accordance with the pipe drainage pitch. Lon-
gitudinal laps on horizontal lines shall be located 45 degrees below the horizontal cen-
terline and alternately staggered 25 millimeter 1 inch. Jacketing material shall be
lapped a minimum of 50 millimeter, circumferentially sealed with mastic, and
strapped to provide a waterproof covering throughout. Straps shall be located 200 mil-
limeter 8 inches on center and shall be pulled up tight to hold jacketing securely in
place. Screws shall be used in addition to straps when necessary to obtain a waterproof
covering. Extra straps shall be placed on each side of supporting devices and at open-
ings. Where flanging access occurs, a chamfer sheet shall be strapped to the pipe at
jacketing.
9. Exposed longitudinal edges of aluminum jacketing shall be stiffened by bending a 25
millimeter hem on one edge.
10. Expansion joints shall provide for maximum and minimum dimensional fluctuations.
11. To prevent corrosion, the aluminum jacketing shall not come in direct contact with
other types of metal.
12. At openings in jacket, an outdoor vapor-barrier coating shall be applied for 50 milli-
meter in all directions. Jacketing shall be applied while waterproofing is tacky.
13. Screws shall be used at each corner of each sheet, at fitting jackets, and as necessary
for the service. Number 7, 10 millimeter 3/8 inch long, binding-head aluminum sheet
metal screws shall be placed through the mastic seal.
1. Surfaces shall be covered with insulation block bedded in an insulating cement and
3.3 ACCEPTANCE
A. Final acceptance will depend upon providing construction (Record Drawings) details to the
Contracting Officer. Construction details shall include, by building area, the insulation
material type, amount, and installation method. An illustration or map of the duct routing
locations may serve this purpose.
B. This purpose. Data shall have a cover letter/sheet clearly marked with the system name, date,
and the words "Record Drawings insulation/material." Forward to the Systems
Engineer/Condition Monitoring Office/Predictive Testing Group for inclusion in the
Maintenance Database."
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
A. Section Includes:
B. Related Section:
A. Seismic Performance:
1. Domestic water piping and support and installation shall withstand effects of earth-
quake motions determined according to ASCE/SEI 7.
1.4 SUBMITTALS
A. Product Data:
a. Specialty valves.
b. Flexible connectors.
c. Escutcheons.
d. Sleeves and sleeve seals.
e. Water penetration systems.
B. Water Samples:
C. Coordination Drawings:
1. For piping in equipment rooms and other congested areas, drawn to scale, on which
the following items are shown and coordinated with each other, using input from In-
stallers of the items involved:
a. Fire-suppression-water piping.
b. Domestic water piping.
c. HVAC hydronic piping.
d. Field quality-control reports.
A. Piping materials shall bear label, stamp, or other markings of specified testing agency.
B. Comply with NSF 14 for plastic, potable domestic water piping and components. Include
marking "NSF-pw" on piping.
C. Comply with NSF 61 for potable domestic water piping and components.
1. Do not interrupt water service to facilities occupied by Owner or others unless permit-
ted under the following conditions and then only after arranging to provide temporary
water service according to requirements indicated:
1.7 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, fitting
materials, and joining methods for specific services, service locations, and pipe size.
1. ASTM B 88, Type K and ASTM B 88, Type L water tube, annealed temper.
A. General: Pipe, fittings and accessories shall be produced from a material substantially
consisting of polypropylene. Only those additives that are needed may be used for the
manufacture of the polymer and for its conversion into sound, durable extrusions or
mouldings of good surface finish, mechanical strength and opacity.
B. Pipes and fittings shall be of soldered or screwed type joints and flanged with flange
adaptors.
C. Cutting to Length and Chamfering: Pipes shall be of such kind that can be cut to length
using fine tooth wood saw or hacksaw and of an end which can be chamfered with one of the
special hand tools developed for shaping plastics.
E. Dimensions:
F. Quality:
G. Operating Pressure: For cold water at 20°C: up to 20 bar. For hot water at 70°C: up to 10
bar. The regulations and guide-lines-dealing with the different fields of application are to be
observed.
J. Opacity: Pipes shall be fully opaque and when tested the wall of pipe shall not transmit
more than 0.2% of the visible light falling onto it.
A. Ductile-Iron Pipes shall be K9 and fittings shall be K12 or K14 as specified in ISO 2531 or
equivalent.
1. AWWA C110, rubber, flat face, 3.2 mm thick or ASME B16.21, nonmetallic and
asbestos free, unless otherwise indicated; full-face or ring type unless otherwise
indicated.
1. ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813.
A. Standard:
B. Form:
1. Tube.
C. Material:
D. Color:
1. Black.
A. General Requirements:
1. AWWA C219.
2. Plastic-to-Metal Transition Fittings:
A. General Requirements:
1. Assembly of copper alloy and ferrous materials or ferrous material body with
separating nonconductive insulating material suitable for system fluid, pressure, and
temperature.
B. Dielectric Unions:
1. Description:
C. Dielectric Flanges:
1. Description:
D. Dielectric-Flange Kits:
1. Description:
E. Dielectric Couplings:
1. Description:
a. Galvanized-steel coupling.
b. Pressure Rating: 2070 kPa at 107 deg C.
c. End Connections: Female threaded.
F. Dielectric Nipples:
1. Description:
1. Corrugated-bronze tubing with bronze wire-braid covering and ends brazed to inner
tubing.
2.11 ESCUTCHEONS
A. General:
2.12 SLEEVES
1. Fabricated of cast iron, and equivalent to ductile-iron pressure pipe, with plain ends
and integral waterstop unless otherwise indicated.
B. Galvanized-Steel-Sheet Sleeves:
1. 0.6-mm minimum thickness; round tube closed with welded longitudinal joint.
C. Molded-PE Sleeves:
1. Reusable, PE, tapered-cup shaped, and smooth outer surface with nailing flange for
attaching to wooden forms.
D. Molded-PVC Sleeves:
E. PVC-Pipe Sleeves:
F. Galvanized-Steel-Pipe Sleeves:
1. ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc-coated, with plain ends.
1. Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring
and bolts and nuts for membrane flashing.
A. Description:
1. Modular sealing element unit, designed for field assembly, used to fill annular space
between pipe and sleeve.
A. Description:
1. Wall-sleeve assembly, consisting of housing and gland, gaskets, and pipe sleeve.
2.15 GROUT
A. Standard:
B. Characteristics:
C. Design Mix:
D. Packaging:
PART 3 - EXECUTION
3.1 EARTHWORK
A. Comply with requirements in Division 31, Section 31 20 00 - Earth Moving, for excavating,
trenching, and backfilling.
A. Drawing plans, schematics, and diagrams indicate general location and arrangement of
domestic water piping. Indicated locations and arrangements are used to size pipe and
calculate friction loss, expansion, and other design considerations. Install piping as indicated
unless deviations to layout are approved on Coordination Drawings.
1. Install Polypropylene pipes and dimensions and joints and fittings according to DIN
8077 and DIN8078 AND DIN16962.
A. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
B. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings
before assembly.
C. Threaded Joints:
1. Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full
and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full
ID. Join pipe fittings and valves as follows:
1. Push the end of the pipe, without turning, up to the marked welding depth into the
welding tool.
2. At the same time push the fitting, without turning, right down to the welding tool.
3. It is essential to observe the recommended heating times.
4. The heating time starts, when pipe and fitting have been pushed to the correct welding
depth on the welding tool.
5. In order to avoid that the pipe has not been put deep enough into the welding socket, it
is recommended to mark the welding depth.
6. Put both pipe ends completely into the electric welding socket. Ensure that the pipes
are squarly put into the electric welding socket and that the pipe ends cannot slip out.
7. Connect the plugs of the device with the electric welding socket.
A. General-Duty Valves:
1. Comply with requirements in Division 22, Section 220523 - General-Duty Valves for
Plumbing Piping, for valve installations.
2. Install shutoff valve close to water main on each branch and riser serving plumbing
fixtures or equipment, on each water supply to equipment, and on each water supply to
plumbing fixtures that do not have supply stops. Use ball or gate valves for piping
DN 50 and smaller. Use butterfly or gate valves for piping DN 65 and larger.
3. Install drain valves for equipment at base of each water riser, at low points in horizon-
tal piping, and where required to drain water piping. Drain valves are specified in Di-
vision 22, Section 22 11 19 - Domestic Water Piping Specialties.
4. Hose-End Drain Valves: At low points in water mains, risers, and branches.
5. Stop-and-Waste Drain Valves: Instead of hose-end drain valves where indicated.
A. Comply with requirements in Division 22, Section 220529 “Hangers and Supports for
Plumbing Piping and Equipment” and Division 22 “ Plumbing General provision – support”,
for pipe hanger and support products and installation.
3. Multiple, Straight, Horizontal Piping Runs 30 m or Longer: MSS Type 44, pipe rolls.
Support pipe rolls on trapeze.
4. Base of Vertical Piping: MSS Type 52, spring hangers.
C. Rod diameter may be reduced one size for double-rod hangers, to a minimum of 10 mm.
3.6 CONNECTIONS
B. Install piping adjacent to equipment and machines to allow service and maintenance.
C. Connect domestic water piping to exterior water-service piping. Use transition fitting to join
dissimilar piping materials.
D. Connect domestic water piping to water-service piping with shutoff valve; extend and
connect to the following:
1. Water Heaters: Cold-water inlet and hot-water outlet piping in sizes indicated, but not
smaller than sizes of water heater connections.
2. Plumbing Fixtures: Cold- and hot-water supply piping in sizes indicated, but not
smaller than required by plumbing code. Comply with requirements in Division 22,
Sections 224000 - plumbing fixture, for connection sizes.
1. Piping with Fitting or Sleeve Protruding from Wall: One piece, deep pattern.
2. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One-piece, cast brass
with polished chrome-plated finish.
3. Bare Piping at Ceiling Penetrations in Finished Spaces: One piece or split casting,
cast brass with polished chrome-plated finish.
4. Bare Piping in Unfinished Service Spaces: One-piece, cast brass with rough-brass fin-
ish.
5. Bare Piping in Equipment Rooms: One piece, stamped steel with spring clips.
6. Bare Piping at Floor Penetrations in Equipment Rooms: One-piece floor plate.
B. Assemble wall penetration system components with sleeve pipe. Install so that end of sleeve
pipe and face of housing are flush with wall. Adjust locking devices to secure sleeve pipe in
housing.
3.9 IDENTIFICATION
B. Piping Inspections:
1. Do not enclose, cover, or put piping into operation until it has been inspected and ap-
proved by authorities having jurisdiction.
2. During installation, notify authorities having jurisdiction at least one day before in-
spection must be made. Perform tests specified below in presence of authorities having
jurisdiction:
3. Reinspection: If authorities having jurisdiction find that piping will not pass tests or
inspections, make required corrections and arrange for reinspection.
4. Reports: Prepare inspection reports and have them signed by authorities having juris-
diction.
C. Piping Tests:
1. Fill domestic water piping. Check components to determine that they are not air bound
and that piping is full of water.
2. Test for leaks and defects in new piping and parts of existing piping that have been al-
tered, extended, or repaired. If testing is performed in segments, submit a separate re-
port for each test, complete with diagram of portion of piping tested.
3. Leave new, altered, extended, or replaced domestic water piping uncovered and un-
concealed until it has been tested and approved. Expose work that was covered or con-
cealed before it was tested.
4. Cap and subject piping to static water pressure of 345 kPa and / or 1.5 time above the
operating pressure wherever greater, without exceeding pressure rating of piping sys-
tem materials. Isolate test source and allow to stand for 24 hours. Leaks and loss in
test pressure constitute defects that must be repaired.
5. Repair leaks and defects with new materials and retest piping or portion thereof until
satisfactory results are obtained.
6. Prepare reports for tests and for corrective action required.
D. Domestic water piping will be considered defective if it does not pass tests and inspections.
3.11 ADJUSTING
5. Remove plugs used during testing of piping and for temporary sealing of piping during
installation.
6. Remove and clean strainer screens. Close drain valves and replace drain plugs.
7. Check plumbing specialties and verify proper settings, adjustments, and operation.
1. Purge new piping and parts of existing piping that have been altered, extended, or re-
paired before using.
2. Use purging and disinfecting procedures prescribed by authorities having jurisdiction;
if methods are not prescribed, use procedures described in either AWWA C651 or
AWWA C652 or follow procedures described below:
a. Clean the raw and domestic water tanks and offered for the Engineer’s witness-
ing.
b. Mix Calcium Hypochlorite granules or equal approved in the drum.
c. Pour the chemical solution in the raw and domestic water tanks.
d. Allow the chemical to mix properly. Check the concentration of the chlorine on
site it shall be min. of 50 ppm. Value shall be measured via calibrated photome-
ter tester.
e. Start Booster pumps to transfer the chlorinated water from the tanks to the net-
work. The water filtration system shall be isolated during boosting the chemical.
f. Measure the chlorine level on all tanks and network random outlets. Values at
any point shall be not less than 50.0 ppm.
g. Keep the chlorinated water in the tanks and network for 24 hrs.
h. After 24 hrs. mix Sodium Meta-bisulfite (Neutralizer) in drum and pour the
chemical solution into the raw and domestic storage tanks and allow to neutral-
ize the chlorine for 2-3 hrs. Check the concentration of chlorine onsite, it shall
be not more than 3.0 ppm.
i. After 3 hrs., start Booster pumps to transfer the neutralized water from the tanks
to the network and continue replenishing the tanks with fresh water and proceed
the flushing till the water visually clear and having the chlorine less than 1.0
ppm. The water filtration system shall be isolated during boosting the neutral-
izer.
j. Once the chlorine level is achieved (less than 1.00 ppm), Collect the water sam-
ple for chemistry and bacterial analysis against M/s Kahamma drinking water
quality requirement (WHO and EU guidelines) last edition and submit for spe-
cialist contractor / supplier analysis and Third Party Laboratory Analysis.
k. Analysis reports shall be submitted for the Engineer’s approval
B. Clean and disinfect hot water primary circuit ( piping from LTHW Boiler and Water Storage
Tanks) piping as follows:
1. Static and dynamic flushing shall perform to the hot water primary circuit as similar as
perform in the chilled water closed circuit.
2. Upon Completion of static and dynamic flushing and disinfection , water sample shall
be drawn and to send for third party laboratory for analysis. Analysis Reports shall be
submitted for the Engineer’s approval.
A. Transition and special fittings with pressure ratings at least equal to piping rating may be
used in applications below unless otherwise indicated.
B. Flanges and unions may be used for aboveground piping joints unless otherwise indicated.
C. Fitting Option: Extruded-tee connections and brazed joints may be used on aboveground
copper tubing.
D. Under-ground water pipes and main building connection shall be HDPE pipes and fittings.
E. Aboveground water pipes at roof shall be insulated PP-R pipes and fittings (UV resistant).
F. Above ground water pipes from main water tank to elevated water tank (filling line) shall be
PP-R pipes and fittings.
G. Above ground water pipes above ceiling shall be insulated PP-R pipes and fittings.
A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the
following requirements apply:
1. Shutoff Duty: Use ball or gate valves for piping DN 50 and smaller. Use butterfly,
ball, or gate valves with flanged ends for piping DN 65 and larger.
2. Throttling Duty: Use ball or globe valves for piping DN 50 and smaller. Use butterfly
or ball valves with flanged ends for piping DN 65 and larger.
3. Hot-Water Circulation Piping, Balancing Duty: Calibrated balancing valves.
4. Drain Duty: Hose-end drain valves.
B. Use check valves to maintain correct direction of domestic water flow to and from
equipment.
A. Provide expansion joint to prevent pipe movements due to thermal expansion or to relevant
movements at building expansion joints. When underground pipe extended outside the
building structure, provide pipes in shell for inside and outside the building structures.
B. Indicate clearly on shop drawings the locations and details of expansion joints.
1. The maximum distance between entry and the nearest fixed point must be 500 mm.
2. Where pipework penetrates a fire barrier, the pipe must be fire stopped. If this pre-
vents thermal movement expansion joints must be provided.
3. Use suitable pipe clamp taking into consideration the pipe route has to be planned and
installed in a way that the pipe is free-moving within the determined expansion as rec-
ommended by Manufacturer.
4. Maximum vertical support intervals must not exceed 1800 mm for all sizes.
TABLE 1
Maximum Supporting Distances
E. Ensure that the supporting system shall accommodate expansion and contraction. Use only
supports that fit accurately to the pipes and fittings.
F. Testing
1. Apply hydraulic leakage test. Do not apply smoke testing for polypropylene pipe
work unless, after obtaining Engineer’s approval, be certain that the products of com-
bustion of the smoke generating set will have no detrimental effect on polypropylene.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
1. Vacuum breakers.
2. Backflow preventers.
3. Temperature-actuated water mixing valves.
4. Water pressure-reducing valves.
5. Strainers.
6. Hose bibs.
7. Drain valves.
8. Water hammer arresters.
9. Air vents.
10. Trap-seal primer valves.
C. Minimum Working Pressure for Domestic Water Piping Specialties: 860 kPa, unless
otherwise indicated.
1.3 SUBMITTALS
A. Product Data:
B. Shop Drawings:
1. For domestic water piping specialties to include in emergency, operation, and mainte-
nance manuals.
1. Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable
to authorities having jurisdiction, and marked for intended use.
B. NSF Compliance:
1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic
domestic water piping components.
2. Comply with NSF 61, "Drinking Water System Components - Health Effects; Sec-
tions 1 through 9."
PART 2 - PRODUCTS
2.1 MANUFACTURERS
1. Description: Factory calibrated, with gages, fittings, hoses, and carrying case with
test-procedure instructions.
A. Water Regulators:
A. Y-Pattern Strainers:
A. Angle valve shall be Chrome Plated finish with a quick-turn on/off feature.
B. Body shall be made of Quality hot forged brass, with a double “O” ring on the stem and a
Teflon Seat.
D. Hot and Cold index identification (red / blue) shall be provided for hot and cold water
supply.
B. Install the water meter as indicated in the drawings as well as per the Local authorities’ regu-
lations.
B. Install the water meter as indicated in the drawings as well as per the Local authorities’ regu-
lations.
A. These specifications are applicable to all sizes of sluice valves larger than 80 mm diameter.
Sluice valves shall be of the following:
1. Gate Valve shall be fully comply with Kahramaa and / or M/s Marafeq requirements
as well as approved by them
2. Gate Valve shall be constructed in valve chamber ,pit and cover constrution as per
M/s Kahramaa and or M/s Marafeq Regulations.
3. Surface boxes and covers shall be adjustable cast iron of the slip type and fitted to the
sizes and depths of valves as shown on the Drawings and / or as per M/s Marafeq re-
quirements. Covers and frames shall be heavy duty and be suitable for wheel loads
up to 11.43 tonnes.
4. Surface boxes shall be coated by dipping or other equivalent means using a hot ap-
plied coal tar based material complying with BS 4164 or cold applied bitumen materi-
al complying with as 3416 and / or as per M/s Marafeq requirements. No coating shall
be applied to any casting until its surfaces are clean dry' and free from rust oil and del-
eterious materials.
C. Gate Valves shall be of the double flanged ductile / cast iron wedge-gate type unless
otherwise stated.
D. Gate Valves pressure ratings shall equal the class of pipe unless otherwise indicated on the
Drawings.
E. Gate Valve non rising stems shall be of forged aluminium bronze or stainless steel, machined
all over, with a machine cut robust trapezoidal or square form thread, operating gunmetal.
F. Stem seals shall be of stuffing box and gland form arranged for easy replacement of packing.
However, valves may incorporate at least two elastomeric "0" ring stem seals. Both gland
packing and '0' ring seals shall be accessible for maintenance without removal of valve from
service. For each. valve supplied which incorporates '0' rings, two spare '0' rings shall be
supplied, suitably identified and delivered and place into storage at the Employer's
designated stores.
G. Extension spindles shall be of stainless steel and shall be compliant with the requirements for
valve stems. Extension spindle couplings shall be of the muff type and shall be drilled and
provided with a nut and bolt for securing the spindle to the valve stem, which will likewise
be drilled to accept the bolt.
H. Where valves are required to be operated by tee keys, spindle caps shall be fitted. The caps
shall be drilled and each provided with nut and bolt for securing to the spindle which shall
likewise be drilled to accept the bolt. Where caps are fitted they snail be supplied complete
with operating tee key. The extended spindle shall be such that the tee key will be operated
at 0.9 to 1.2 m above floor level.
1. Body: Bronze.
2. Pressure Rating: 860-kPa minimum pressure rating at 60 deg C.
3. Float: Replaceable, corrosion-resistant metal.
4. Mechanism and Seat: Stainless steel.
5. Size: DN 15 minimum inlet.
6. Inlet and Vent Outlet End Connections: Threaded.
1. Standard: ASSE 1044, lavatory P-trap with DN 10 minimum, trap makeup connection.
2. Size: DN 32 minimum.
3. Material: Chrome-plated, cast brass.
A. Cast Bronze body, Globe pattern , stainless steel stem and spring , Body seal non asbestos
gaskets and glass filled Teflon for orifice seal, 304 stainless steel pin , Encapsulated class H ,
Power supply shall be 220 VAC , 50HZ and PN10 operating pressure.
A. Audible and visual indicator/alarm panel including the following features and functions:
1. High water level audible alarm and visual indication - First low level audible alarm
and visual indication - Second low level pump cut-out and indication - Remote
indication contactors.
2.18 Mercury level regulators constructed from polypropylene with enclosed mercury switch ac-
tivated by tilting and electrically connected to the water level indicator
A. Float valve chambers to be provided with central hinged lockable ABS lid, 1.00m x1.00m in
plan, with options of 180mm, 300mm, 500mm depth with provision for type A air gap in
compliance with BS6281 : Part1 : 1992.
B. PART 3- EXECUTION
INSTALLATION
A. Refer to Division 22, Section 22 05 00 - Common Work Results for Plumbing, for piping
joining materials, joint construction, and basic installation requirements.
B. Where the Kitchen Equipment, kitchen sinks and fixture unit having flexible hose connection
, the angle valve shall be provided in piping rough-ins outlet .
C. All base of riser shall be provided with drain cock valve even if not shown on the drawings.
D. Install backflow preventers in each water supply to mechanical equipment and systems and
to other equipment and water systems that may be sources of contamination. Comply with
authorities having jurisdiction.
E. Install water regulators with inlet and outlet shutoff valves. Install pressure gages on inlet
and outlet.
F. Install water control valves with inlet and outlet shutoff valves [and bypass with globe
valve]. Install pressure gages on inlet and outlet.
H. Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets
and with shutoff valve on outlet.
I. Install Y-pattern strainers for water on supply side of each water pressure-reducing valve,
solenoid valve, and pump.
J. Install water hammer arresters in water piping according to PDI-WH 201 as well as the
Manufacturer’s recommendations.
K. Install air vents at high points of water piping. Install drain piping and discharge onto floor
drain.
L. Install supply-type, trap-seal primer valves with outlet piping pitched down toward drain trap
a minimum of 1 percent, and connect to floor-drain body, trap, or inlet fitting. Adjust valve
for proper flow.
M. Install drainage-type, trap-seal primer valves as lavatory trap with outlet piping pitched down
toward drain trap a minimum of 1 percent, and connect to floor-drain body, trap, or inlet
fitting.
2.21 CONNECTIONS
B. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
B. Remove and replace malfunctioning domestic water piping specialties and retest as specified
above.
2.24 ADJUSTING
A. Contractor shall include in the contract to procure and handover under his expenses the
following minimum quantity of the spare parts as per the list and / or that recommended by
the manufacturer. These spare parts shall be brand new and similar to the equipment /
material being installed:
iv- 3 way mixing and diverting valves: 1 No. for each size.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
A. This Section includes variable-speed, multiplex, packaged booster pumps for domestic water
piping systems.
1. Division 22 Section "Domestic Water Pumps" for domestic water circulation pumps.
1.3 SUBMITTALS
A. Product Data:
1. For each packaged booster pump specified. Include certified performance curves with
operating points plotted on curves; and rated capacities of selected models, furnished
specialties, and accessories.
B. Shop Drawings:
1. For packaged booster pumps and accessories. Include plans, elevations, sections, de-
tails, and attachments to other work. Shop Drawings shall be signed and sealed by a
qualified professional engineer.
2. For installed products indicated to comply with design loads, include structural analy-
sis data signed and sealed by the qualified professional engineer responsible for their
preparation.
3. Design Calculations: Calculate requirements for selecting vibration isolators and
seismic restraints and for designing vibration isolation bases.
4. Vibration Isolation Base Details: Detail fabrication including anchorages and attach-
ments to structure and to supported equipment. Include auxiliary motor slides and
rails and equipment mounting frames.
5. Wiring Diagrams: Detail power, signal, and control wiring.
1. For each packaged booster pump to include in emergency, operation, and maintenance
manuals.
A. Product Options:
1. Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable
to authorities having jurisdiction, and marked for intended use.
C. ASME Compliance:
A. Retain shipping flange protective covers and protective coatings during storage.
1.6 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Description:
1. Factory-assembled and -tested, packaged booster pump with multiple pumps, piping,
valves, sensors, and controls on skids or base.
C. Pump Arrangement:
1. Triplex, with three equal-size pumps each pump capacity equal 50 % of full load, First
pump lead, second pump lag and third pump stand-by with alternator to Control op-
eration sequence.
D. Pumps:
E. Motors:
1. Variable speed through variable speed drive which shall be integrated with the motor,
with oil-lubricated bearings, unless otherwise indicated. Select motor that will not
overload through full range of pump performance curve. Comply with Division 22
Section "Common Motor Requirements for Plumbing Equipment."
F. Control Valves:
G. Relief Valves:
H. Piping:
a. DN 100 and Smaller: ASTM B 88, Type L, drawn copper water tube; with
copper solder-joint pressure fittings, and brazed joints
b. DN 125 and Larger: ASTM A 53/A 53M, Schedule 40, dip galvanized-steel
pipe with threaded, cast-iron fittings and threaded joints.
c. Header End Connections:
1) DN 50 and Smaller: Threaded.
2) DN 65 and Larger: Flanged.
d. Piping Option: Piping, including valves and other components, may have
grooved ends for grooved joints.
I. Valves:
1. Include shutoff valve at each pump suction, and shutoff valve and check valve at each
pump discharge.
a. Shutoff Valves, DN 50 and Smaller: MSS SP-80, Class 125, bronze rising-stem
gate valve.
b. Shutoff Valves, DN 65 and Larger: MSS SP-70, Class 125, bronze-trim,
OS&Y, cast-iron gate valve with flanged ends.
c. Check Valves, DN 50 and Smaller: Spring, MSS SP-80, Class 125, bronze,
swing check valve.
d. Check Valves, DN 65 and Larger: Spring- or lever-loaded, MSS SP-71,
Class 125, bronze-trim, cast-iron, swing check valve.
J. Sensors:
K. Dielectric Fittings:
1. With insulating material isolating joined dissimilar metals to prevent galvanic action
and to stop corrosion.
L. Controller: The control panel shall be of the programmable logic controller (PLC) type. The
complete control panel assembly and all internal devices shall be CE marked.
M. The panel shall be complete with door interlocked main disconnect, water tight LCD
interface, breaker VFD connections, adjustable time delays and Hand-Off-Auto selector for
each pump. The control circuit shall include fault relay circuit to turn on the next pump
should the lead pump fail. The controller must be capable of controlling up to 5 pumps, using
a 4-20 mA analogue signal using pressure as the control variable.
N. Controller design shall include provisions for system 'soft fill' mode, low flow energy
savings, best-operating-point (BOP) sequencing, automatic alternation of pumps, automatic
omission of failed pumps, built-in pump on-delay timers, pump elapsed run time meters,
smooth pump starting and sequencing. The controller screen shall indicate but not limited to
the following field modifiable control and alarm parameters, high system pressure shutdown
and no-flow shutdown with draw down tank/system optimization.
O. Alarm display with alarm identification shall be incorporated with the following alarms
included: low and high system pressure alarms, low water shutdown, pump failure, drive
fault and discharge pressure transmitter failures. fault descriptions. Non-volatile factory set
parameters must be capable of being restored at any time in the field without requiring any
programming device or connection to an external source.
P. The controller must hold software in FLASH memory storage which prevents accidental loss
of data due to voltage surge or spike.
Q. All controls to be factory pre-wired and tested in accordance with provisions of the national
electrical code. All control wires shall be individually numbered and each component shall
be labeled accordingly.
1. VFD shall be of the VVC-PWM type providing near unity displacement power factor
(cos Ǿ) without the need for external power factor correction capacitors at all loads
and speeds.
1. Pump system shall be supplied with manifold mounted liquid filled pressure gauges
for indicating discharge pressure.
1. Clean flanges and exposed machined metal surfaces and treat with anticorrosion com-
pound after assembling and testing. Protect flanges, pipe openings, and pump nozzles.
2. Pump and Characteristics as indicated in the drawings:
A. Description:
1. Corrugated, bronze inner tubing covered with bronze wire braid. Include copper-tube
ends or bronze flanged ends, braze-welded to tubing. Include 150-psig 1035-kPa min-
imum working-pressure rating and ends according to the following:
a. DN 50 and Smaller: Threaded. Provide flanged ends if pump has flanged con-
nections.
b. DN 65 and Larger: Flanged.
A. Provide auxiliary contacts in pump controllers for interface to building automation system.
Include the following:
B. All activities as per I/O points shall be monitored on Dynamic colour graphics and graphic
control as prescribed in related Division. Submit Graphics for the Engineer’s approval.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for packaged booster pumps to verify actual locations of connections
before booster pump installation.
A. Install concrete bases of dimensions indicated for packaged booster pumps. Refer to
Division 22 Section "Common Work Results for Plumbing."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indi-
cated, install dowel rods on 450-mm centers around full perimeter of base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through con-
crete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, in-
structions, and directions furnished with items to be imbedded.
4. Install anchor bolts to elevation required for proper attachment to supported equip-
ment.
5. Install the concrete plinth of pump so the Center Line of the suction pipe Provision in
the tank in higher than or equal to the suction flange of the Pump.
B. Cast-in-place concrete materials and placement requirements are specified in Division 03.
A. Install packaged booster pumps level on concrete bases with access for periodic maintenance
including removal of pumps, motors, impellers, couplings, and accessories.
B. Vibration Isolation:
3.4 CONNECTIONS
B. Connect domestic water piping to packaged booster pumps. Install suction and discharge
pipe equal to or greater than size of unit suction and discharge piping.
1. Install flexible connectors on piping connections to unit suction and discharge piping.
Install flexible connectors same size as piping.
2. Install shutoff valves on piping connections to each booster pump suction and dis-
charge piping Install gate valves same size as suction and discharge piping. General-
duty valves are specified in Division 22 Section "General-Duty Valves for Plumbing
Piping."
3. Install union or flanged connections on pump suction and discharge piping at connec-
tion to domestic water piping.
4. Install piping adjacent to packaged booster pumps to allow service and maintenance.
C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
A. Install identifying equipment markers and equipment signs on booster pumps. Labeling and
identification materials are specified in Division 22 Section "Identification for Plumbing
Piping and Equipment."
A. Prior startup the pump, Method of statement of testing and commissioning of the pump set
shall be submitted for the Engineer’s approval. All testing records shall be noted on the
Manufacturer’s standard forms.
B. All Testing shall offer for the Engineer’s witnessing and approval.
1. Check the installation of pumps, pipe lines and valves are approved by the Engineer.
2. Check the pipe line are tested and approved by the Engineer.
3. Check the water storage tank and network cleaning and disinfection as prescribed in
division 22, section 221116 “DOMESTIC WATER PIPING - CLEANING,
FLUSHING AND DISINFECTION” are approved by the Engineer.
ommended testing activities for the pump control panel as well as the MCC panel.
5. Set the pressure vessel as per the Manufacture’s recommendations.
6. Perform the activation of Dry run protection float switch, pumps’ cut-in and cut-off.
7. Perform pump performance test for individual pump at the following:
a. Discharge valve fully closed at shut-off head,
b. Adjusted discharge valve at nominated flow;
c. Discharge valve fully opened at minimal head.
8. Perform pump performance test for dual pump in operation at the following:
a. Adjusted discharge valve at nominated flow;
b. Discharge valve fully opened at minimal head.
9. Perform the measurement of pump pressure, Motor speed, current and voltage at each
phase and other related testing parameters recommended by the pump manufacturer
during the individual and dual operation performance testing.
10. Perform the pump trip auto changeover and pump working hrs. Auto changeover.
11. Perform demand based auto change over.
12. For every auto change over, the pump control system shall change the pump sequenc-
ing.
13. Maintain the Minimum and Maximum floor residual pressure as prescribed in Divi-
sion 22 “PLUMBING GENERAL PROVISIONS” and set the pump pressure accord-
ingly.
14. Perform the necessary and required safeties, controls, BMS interfaces and associated
Graphics.
15. Perform the approved system sequence of operation and scheme interlocks.
16. Pump testing will considered as accepted only when the values being tested are equal
to the design parameters and or within the allowable limits / tolerances ±10% .
E. Occupancy Adjustments:
1. When requested within 400 days defect warranty / liability period stated from the
Takeover Certificate of the project, provide on-site assistance in adjusting packaged
booster pumps to suit actual occupied conditions. Provide up to two visits to Project
outside normal occupancy hours for this purpose.
B. The Contractor shall include in the contract to procure and handover the recommended spare
parts by the Equipment Manufacturer under his expenses as detailed in the Division 22
“Plumbing General Provision-Spare Parts and Tools”. These spare parts shall be brand new
and similar to the equipment / material being installed, at any case, Spare parts and tools
shall be not less than the following:
1. Bellows : 1 No. each Size.
2. Mechanical Seal : 1 No. each Size.
3. Pump Bearing : 2 set for each pump.
4. Sensors & Transmitters : 1 No. for each pump unit.
3.9 WARRANTY
A. All Domestic Water Packaged Booster Pumps installed in this project shall have a minimum
warranty of five years of normal performing operation commenced from the takeover
Certificate issued by the Engineer and / or as per the contract as well as per standard
warranty whichever greater.
B. During the warranty period, perform the periodic routine and preventive maintenance as per
the Equipment manufacturer’s requirement to verify its proper operation.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including the General conditions, Conditions of Par-
ticular Applications and Division 1 Specification Sections, apply to this Section.
1. At least equal to system maximum operating pressure at point where installed, but not less than
850 kPa.
1.5 SUBMITTALS
A. Product Data: For each type and size of domestic water pump specified. Include certified perfor-
mance curves with operating points plotted on curves; and rated capacities of selected models, fur-
nished specialties, and accessories.
C. Operation and Maintenance Data: For domestic water pumps to include in emergency, operation, and
maintenance manuals.
A. Product Options: Drawings indicate size, profiles, and dimensional requirements of domestic water
pumps and are based on the specific system indicated. Refer to Division 01 Section "Product Re-
quirements."
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Arti-
cle 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
A. Retain shipping flange protective covers and protective coatings during storage.
1.8 COORDINATION
A. Coordinate size and location of concrete bases. Concrete, reinforcement, and formwork requirements
are specified in Division 03.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. General Description:
1. Centrifugal, close-coupled, end-suction, single-stage, bronze trimmed design, rated for 850 kPa
working pressure.
B. Casings:
1. cast iron with flanged piping connection, and threaded gage tappings at inlet and outlet flange
connections.
C. Impeller:
1. ASTM B 584 cast bronze impeller statically and dynamically balanced, closed, overhung, sin-
gle suction, and keyed to shaft, and secured by a locking cap screw, replaceable bronze casing
wearing ring, stainless steel shaft with bronze sleeve. Include flinger on motor shaft between
motor and seals to prevent liquid that leaks past pump seals from entering the motor bearings.
D. Mechanical Seals:
1. Carbon-steel rotating ring, stainless steel spring, ceramic seat, and flexible bellows and gasket.
E. Motor:
1. Comply with NEMA C Face -TEFC, Class F insulation with temperature rise limited to class
B; the stator winding shall be made of copper and IP55enclosure.
2. Pulse width modulated, integrated motor/variable frequency drive design; the motor and drive
designed and built by a single manufacturer.
3. The variable frequency drive enclosure shall include, dry-contact fault output relay contacts,
analog, and digital inputs.
4. The motor shall detect/protect itself against under voltage, over voltage, excessive temperature,
overload, sensor signal fault, and set-point signal fault.
F. Pump Specialties:
1. Include the pump specialties with end connections matching pump and piping where indicated
and/or required for proper operation. Refer to Division 22 Section "Valves" for general-duty
G. Electronic Controller
1. The controller shall operate the pumps to maintain the design pressure while using minimum
energy and alternating between pumps to maintain relatively equal pump operating hours.
2. All pumps will changeover automatically to maintain the system pressure depending on de-
mand, time, and fault.
3. The controller shall accept a low-suction pressure or other suction fault input to shut down the
system.
4. The controller shall have a keypad and LCD display screen.
H. Programmable Functions
1. System functions will be programmable through the keypad. These programmable functions
and information shall include, but not be limited to:
a. Pump status
b. Elapsed running hours
c. System pressure set-point
d. Actual system pressure
e. Pump speed (percent)
f. Pump min/max speed (percent)
g. System faults
h. Pressure transducer design settings
i. Standby pump designation
j. Current pump rotation order
k. Friction Loss Compensation (set point)
l. High and low discharge pressure shutdown limit
m. Low-suction pressure shut-down limit
n. Analog input for remote set-point control
o. Digital input for remote stop/start
p. Clock Program
I. Control Cabinet
1. The controller shall be mounted in a control cabinet with a NEMA 3R enclosure rating with the
keypad and display screen mounted through the outer door.
2. The control cabinet shall be UL 508 listed as an assembly.
3. The control cabinet shall include circuit breakers for each pump and the control circuit and
control relays for alarm functions.
4. Control cabinet shall include, the followings:
1. VFD shall be of the VVC-PWM type or approved equal , providing near unity displacement
power factor (cos Ǿ) without the need for external power factor correction capacitors at all
loads and speeds.
A. Provide auxiliary contacts in pump controllers for interface to building automation system. Include
the following:
B. All activities as per I/O points shall be monitored on Dynamic colour graphics and graphic control as
prescribed in related Division. Submit Graphics for Engineer’s approval.
PART3 - EXECUTION
3.1 EXAMINATION
A. Examine irrigation -water-piping system to verify actual locations of connections before pump instal-
lation.
A. Install concrete bases of dimensions indicated for pumps and controllers. Refer to Division 22 Section
"Common Work Results for Plumbing."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, in-
stall dowel rods on 450-mm centers around full perimeter of base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base
and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions,
and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported equipment.
5. Install the concrete plinth of pump so the Center Line of the suction pipe Provision in the tank
in higher than or equal to the suction flange of the Pump.
B. Cast-in-place concrete materials and placement requirements are specified in Division 03.
B. Install pumps with access for periodic maintenance including removal of motors, impellers, couplings,
and accessories.
C. Independently support pumps and piping so weight of piping is not supported by pumps and weight of
pumps is not supported by piping.
3.4 CONNECTIONS
A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate gen-
eral arrangement of piping, fittings, and specialties.
C. Connect domestic water piping to pumps. Install suction and discharge piping equal to or greater than
size of pump nozzles. Refer to Division 22 Section "Domestic Water Piping."
1. Install flexible connectors adjacent to pumps in suction and discharge piping of the following
pumps:
a. End-Suction pumps.
2. Install shutoff valve and strainer on suction side of pumps, and check valve and throttling valve
on discharge side of pumps. Install valves same size as connected piping. Refer to Divi-
sion 22 Section "General-Duty Valves for Plumbing Piping" for general-duty valves for do-
mestic water piping and Division 22 Section "Domestic Water Piping Specialties" for strainers.
3. Install pressure gages at suction and discharge of pumps. Install at integral pressure-gage tap-
pings where provided or install pressure-gage connectors in suction and discharge piping
around pumps. Refer to Division 22 .
D. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems."
E. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors and Ca-
bles."
A. Prior startup the pump, Method of statement of testing and commissioning of the pump set shall be
submitted for the Engineer’s approval. All record forms shall be noted on the Manufacturer’s standard
forms.
B. All Testing shall offer for the Engineer’s witnessing and approval.
1. Check the installation of pumps, pipe lines and valves are approved by the Engineer.
2. Check the pipe line are tested and approved by the Engineer.
8. Prime pump by opening suction valves and closing drains, and prepare pump for operation.
9. Start motor.
10. Verify the activation of Dry run protection devices, pumps’ cut-in and cut-off.
11. Verify the system scheme interlocks and safeties.
12. Verify that pump is free to rotate by hand and that pump for handling hot liquid is free to rotate
with pump hot and cold. If pump is bound or drags, do not operate until cause of trouble is de-
termined and corrected.
13. Verify that pump is rotating in the correct direction prior starting.
D. Engage a factory-authorized service representative to perform the following start-up and functionality
testing for each pump:
1. Start the Pump.
2. Open discharge valves slowly and gradually.
3. Adjust all necessary settings as recommended by the Manufacturer.
4. Perform the pre-commissioning, Testing and commissioning approved and / or recommended
testing activities for the pump control panel, irrigation Controller as well as the MCC panel.
5. Perform the activation of Dry run protection float switch, pumps’ cut-in and cut-off.
6. Perform pump performance test for individual pump at the following:
a. Discharge valve fully closed at shut-off head,
b. Adjusted discharge valve at nominated flow;
c. Discharge valve fully opened at minimal head.
7. Perform pump performance test for dual pump in operation at the following:
a. Adjusted discharge valve at nominated flow;
b. Discharge valve fully opened at minimal head.
8. Perform the measurement of pump pressure, Motor speed, current and voltage at each phase
and other related testing parameters recommended by the pump manufacturer during the indi-
vidual and dual operation performance testing.
9. Perform the pump trip auto changeover and pump working hrs. Auto changeover.
10. Perform demand based auto change over (if recommended).
11. For every auto change over, the pump control system shall change the pump sequencing.
12. Maintain the Minimum and Maximum residual pressures as recommended by the irrigation
sprinkler and dripper, and set the pump pressure accordingly.
13. Perform the flow measurement randomly for irrigation sprinkler and drippers.
14. Perform the operation of solenoid valves and gate valves.
15. Perform the necessary and required safeties, BMS interfaces and related Graphics.
16. Perform the approved system sequence of operation and associated scheme interlocks.
17. Pump testing will considered as accepted only when the values being tested are equal to the de-
sign parameters and or within the allowable limits tolerances ±10% .
A. The Contractor is full responsible to arrange and perform any necessary testing requested by the Hotel
Operator without any additional cost to the Client.
B. Contractor Must arrange the necessary and required testing Devices / instruments / tools with a valid
due calibration during the testing inspection of the system with the Operator.
C. Contractor shall action all of the Hotel Operator’s comments that are critical for Hotel Operation prior
the issuance of take-over certificate by the Engineer.
D. At the time of handover to the operator of the Works after the Taking Over Certificate, the whole
installation shall be in ‘as-new’ conditions. The Contractor shall, during the course of the Contract,
protect all plant and equipment and shall restore/repaint as necessary before handover of the
installation.
A. Refer to Division 22, section “PLUMBING GENERAL PROVISIONS – SPARE PAERTS AND
TOOLS”.
B. Contractor shall include in the contract to procure and handover the following minimum quantity of
the spare parts as per the list and / or that recommended by the manufacturer. These spare parts shall
be brand new and similar to the equipment / material being installed:
1. Bellows : 1 No. each size.
2. Mechanical Seal : 1 No. each size.
3. Pump Bearing : 2 set for each pump.
4. Sensors & Transmitters : 1 No. for each pump Unit.
3.3 WARRANTY
A. All Irrigation Water Pumps installed in this project shall have a minimum warranty of five years of
normal performing operation commenced from the takeover Certificate issued by the Engineer and /
or as per the contract as well as per standard warranty whichever greater.
B. During the warranty period, perform the periodic routine and preventive maintenance as per the
Equipment manufacturer’s requirement to verify its proper operation.
PART 1 – GENERAL
1.4 SUBMITTALS
C. Maintenance Data: Submit maintenance data and parts lists for each type of
equipment, control and accessory, including “trouble – shooting” maintenance
guide. Include this data, product data and shop drawings in maintenance manual.
B. Store equipment and components in clean dry place. Protect from weather, dirt,
fumes, water, construction debris, and physical damage.
PART 2 – PRODUCTS
A. The filtered and cooled water storage tanks shall be insulated type and back wash
water holding tank shall be un-insulated type.
B. The manufacture and design of the hot press molded GRP sectional water storage
tanks shall be to the quality standard requirements of BS EN ISO 9001 and shall
comply with BS7491: Part 3: 1994 glassfibre reinforced plastic cisterns for cold
water storage.
C. Cisterns shall be manufactured by the hot press molded method, glass reinforced
plastic, molded at temperatures up to 150 deg.C using isophthalic unsaturated
polyester resins, UV stabilized and ‘E’ glassfibre reinforcement, color mid gray.
D. The cistern design shall incorporate 1.00 x 1.00m pillow panels to walls of non-
insulated cisterns with provision for flat panels for connections and fittings.
Purpose made cover panels 1.00m x 1.00m and 1.00m x 0.50m flat panels
positioned to give free draining channels.
E. Base panels available as internally flanged IFB with 1.00m x 1.00m flat panels,
fasteners internal, or externally flanged EFB with 1.00m x 1.00m flat panels and
one pillow sump panel, fasteners external.
F. All Surfaces of the panels shall be smooth and crevice free to provide hygienic finish
and be dimensionally accurate with sharply defined profiles.
G. Float valve chambers to be provided with central hinged lockable ABS lid, 1.00m
x1.00m in plan, with options of 180mm, 300mm, 500mm depth with provision for
type A air gap in compliance with BS6281 : Part1 : 1992.
I. All tanks deeper than 1.50m shall be fitted with internal SS 316 L ladders, external
standard duty stainless steel access ladders.
J. Where partitions are required, they must be of full height using standard panels. Each
compartment to be capable of supporting water on either side with one side empty.
M. Extruded synthetic rubber sealing strip to be used covering full width of panel flange
providing a watertight seal.
P. Panel strength shall be fully compliant with BS 7491 : Part 3 : 1994 , giving a factor
of safety of tanks in excess of 6 times working pressure against rupture.
Q. The Contractor shall include but not be limited to the following accessories and connections
for each compartment:
ii- Overflow pipe , one higher size than inlet pipe and / or as indicated.
vi- SS-316 / A4 grade Internal and mild steel galvanized to BS729 External Ladders
and ladder’s support
vii- Float switches for pump dry run, pumps’ cut-in and cut-off and overflow.
viii- Ultrasonic level indicator inside the tank connecting to the BMS for the Content of
water volume in the tank.
PART 3 - EXECUTION
B. All cisterns to be installed on either flat continuous foundation or close center beams
conforming to manufacturer’s specification of flatness and deflection.
E. The testing of panels and sealant shall be as listed by Water Research Center, UK
conforming to water fittings Bylaws Scheme.
F. Level indication facility shall be provided for all underground and above ground
water tanks. Monitoring facility from building management system shall be
provided.
G. The tank shall be erected strictly in accordance with the manufacturer’s instructions upon
support structures that are flat and level to within ±3mm with no local protrusions
exceeding 1 m.
H. Each tank shall have a minimum maintenance access way of 600mm and / or as per
Manufacturer’s recommendations at all sides around the tank.
I. All tanks shall have a dedicated Permanent means of access such as steel platform and
catwalk. Not allowed to stand on the tank roof panel/(s) to access the tank for inspection
and further maintenance. Submit for the Engineer approval prior fabrication.
J. Permanent work platform and catwalk shall be designed by the Contractor and provided by
the Contractor for access to the GRP tanks. The catwalk and platform for access shall
allow a minimum width of 750mm.
K. Catwalk to maintenance platform shall be provided with railings and guards designed for
safe movement of personnel in a restricted space including provision for gaining access
and to accommodate maintenance personnel.
L. The design of all permanent work platform, hand rails, etc. shall be submitted to the
Engineer for approval. The loading and fixing method of lifting facilitate shall also be
submitted to the Engineer for approval and checking within 4 weeks on award of Contract
or receipt of letter of intent.
M. Each compartment of each tank shall contain the necessary electrodes or float switches and
controls to accomplish: high water alarm (overflow level), low water alarm (Pump dry run
protection), pump’s cut-in/cut-off, contents gauges and temperature monitoring. Provide a
spare set of DPDT dry contacts for each alarm for remote annunciation by the BMCS Sub-
Contractor.
A. Upon Completion of works, All tanks shall be offered for flood / integrity leak testing, the
water level shall be at the bottom of overflow pipe for 24 hrs. test period.
3.3 WARRANTY
A. Tank shall Grantee for 10 years from the date of takeover certificate issued by the Engineer.
END OF SECTION 22 12 24
PART 1 - - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions.
1.2 SUMMARY
A. This Section includes the following for soil, waste, and vent piping inside the building:
1.3 DEFINITIONS
A. Components and installation shall be capable of withstanding the following minimum working pres-
sure, unless otherwise indicated:
1.5 SUBMITTALS
A. Piping materials shall bear label, stamp, or other markings of specified testing agency.
B. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for plas-
tic piping components. Include marking with "NSF-dwv" for plastic drain, waste, and vent
piping; "NSF-drain" for plastic drain piping; "NSF-tubular" for plastic continuous waste pip-
ing; and "NSF-sewer" for plastic sewer piping.
PART 2 - - PRODUCTS
A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and joining materi-
als.
A. Pipe, fittings and accessories shall be conform to ASTM D2997 & ASTM D 3517-01 QCS last
edition requirements.
C. GRP pipes and fittings shall be manufactured by an approved process utilising a mandrel or rotating
mould incorporating equipment to accurately control the quantities and placement of all resins, glass
and aggregates.
A. Pipe, fittings and accessories shall be produced from a material substantially consisting of unplas-
ticiezed polyvinyl chloride. Only those additives that are needed may be used for the manufacture of
the polymer and for its conversion into sound, durable extrusions or mouldings of good surface finish,
mechanical strength and opacity.
1. Dimensions: Pipes 80 mm and larger shall conform to the outside diameters and wall thickness
as described in BS 3505.
2. Pipe 50 mm and smaller shall conform to the requirements of ASTM 2665.
3. Lengths: Pipes shall be supplied in straight lengths, normally of 1.8 m, 2.4 m and 3 m or other
lengths as may be agreed upon between the Contractor and manufacturer and approved by the
Engineer.
4. Cutting to Length and Chamfering: Pipes shall be of such kind that can be cut to length using
fine tooth wood saw or hacksaw and of an end which can be chamfered with one of the special
hand tools developed for shaping plastics.
D. Physical Characteristics:
E. Chemical Characteristics: UPVC pipes and fittings shall be tested for water absorption, resistance to
acetone and resistance to sulpheric acid and shall comply with requirements of MUPVC pipes, fittings
shall comply to the requirements of ASTM 2665.
F. Mechanical Characteristics: uPVC pipes and fittings shall comply with requirements of MUPVC
pipes, fittings shall comply with the requirements of ASTM 2665.
G. Marking: Pipes shall be indelibly marked. In no case shall mark intervals exceed 3 m. Pipe markings
a. Manufacturer’s name
b. Nominal size
c. Identification code
H. All fittings shall be marked on the body on hub on both sides. The marking shall, at least consist of
the manufacturer’s name or trace mark or both.
A. PE, Pipe and fitting shall be according to DIN 19535-10: High – density polyethelene (PE-HD) Pipes
and fittings for Hot Water Resistant waste and sewerage discharge system outside Buildings.
B. Insert Fittings for PE Pipe: ASTM D 2609, made of PA, PP, or PVC with serrated male insert ends
matching inside of pipe. Include bands or crimp rings.
A. Flexible, Nonpressure Pipe Couplings: Comply with ASTM C 1173, elastomeric, sleeve-type, reduc-
ing or transition pattern. Include shear ring, ends of same sizes as piping to be joined, and corrosion-
resistant-metal tension band and tightening mechanism on each end.
1. Sleeve Materials:
a. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC.
b. For Dissimilar Pipes: ASTM D 5926, PVC or other material compatible with pipe mate-
rials being joined.
B. Shielded Non pressure Pipe Couplings: ASTM C 1460, elastomeric or rubber sleeve with full-length,
corrosion-resistant outer shield and corrosion-resistant-metal tension band and tightening mechanism
on each end.
C. Rigid, Unshielded, Non-pressure Pipe Couplings: ASTM C 1461, sleeve-type reducing- or transition-
type mechanical coupling molded from ASTM C 1440, TPE material with corrosion-resistant-metal
tension band and tightening mechanism on each end.
D. Pressure Pipe Couplings: AWWA C219 metal, sleeve-type same size as, with pressure rating at least
equal to, and ends compatible with, pipes to be joined.
E. Flexible Ball Joints: Ductile-iron fitting with combination of flanged and mechanical-joint ends com-
plying with AWWA C110 or AWWA C153. Include gasketed ball-joint section and ductile-iron
gland, rubber gasket, and steel bolts.
F. Expansion Joints: Two or three-piece, ductile-iron assembly consisting of telescoping sleeve(s) with
gaskets and restrained-type, ductile-iron, bell-and-spigot end sections complying with AWWA C110
or AWWA C153. Select and assemble components for expansion indicated. Include AWWA C111,
ductile-iron glands, rubber gaskets, and steel bolts.
G. Wall-Penetration Fittings: Compound, ductile-iron coupling fitting with sleeve and flexing sections
for up to 20-degree deflection, gaskets, and restrained-joint ends complying with AWWA C110 or
AWWA C153. Include AWWA C111, ductile-iron glands, rubber gaskets, and steel bolts.
A. Description: ASTM A 674 or AWWA C105, high-density, crosslaminated PE film of 0.10-mm min-
imum thickness.
B. Form: tube.
C. Color: Black.
PART 3 - EXECUTION
3.1 EXCAVATION
A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling.
A. Flanges and unions may be used on aboveground pressure piping, unless otherwise indicated.
A. Sanitary sewer piping outside the building is specified in Division 22 Section "Facility Sanitary Sew-
ers."
B. Basic piping installation requirements are specified in Division 22 Section "Common Work Results
for Plumbing."
C. Install seismic restraints on piping. Seismic-restraint devices are specified in Division 22 Section "Vi-
bration and Seismic Controls for Plumbing Piping and Equipment."
D. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary
sewers.
E. Install cleanout fitting with closure plug inside the building in sanitary force-main piping.
F. Make changes in direction for soil and waste drainage and vent piping using appropriate branches,
bends, and long-sweep bends. Sanitary tees and short-sweep 1/4 bends may be used on vertical stacks
if change in direction of flow is from horizontal to vertical. Use long-turn, double Y-branch and 1/8-
bend fittings if 2 fixtures are installed back to back or side by side with common drain pipe. Straight
tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90
degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected.
Reducing size of drainage piping in direction of flow is prohibited.
G. Lay buried building drainage piping beginning at low point of each system. Install true to grades and
alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install
required gaskets according to manufacturer's written instructions for use of lubricants, cements, and
other installation requirements. Maintain swab in piping and pull past each joint as completed.
H. Install soil and waste drainage and vent piping at the following minimum slopes, unless otherwise in-
dicated:
1. Building Sanitary Drain: 2 percent downward in direction of flow for piping DN 65 and
smaller; 1 percent downward in direction of flow for piping DN 80 and larger.
2. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack.
I. Install engineered soil and waste drainage and vent piping systems as follows:
1. Combination Waste and Vent: Comply with standards of authorities having jurisdiction.
2. Sovent Drainage System: Comply with ASSE 1043 and sovent fitting manufacturer's written
installation instructions.
3. Reduced-Size Venting: Comply with standards of authorities having jurisdiction.
J. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is
without membrane waterproofing.
K. Install uPVC soil and waste drainage and vent piping according to ASTM D 2665.
L. Install underground uPVC soil and waste drainage piping according to ASTM D 2321.
M. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities
having jurisdiction.
A. Basic piping joint construction requirements are specified in Division 22 Section "Common Work Re-
sults for Plumbing."
A. General valve installation requirements are specified in Division 22 Section "General-Duty Valves for
Plumbing Piping."
C. Check Valves: Install swing check valve, between pump and shutoff valve, on each sewage pump
discharge.
1. Horizontal Piping: Horizontal backwater valves. Use normally closed type, unless otherwise
indicated.
2. Floor Drains: Drain outlet backwater valves, unless drain has integral backwater valve.
3. Install backwater valves in accessible locations.
4. Backwater valve are specified in Division 22 Section "Sanitary Waste Piping Specialties."
A. Seismic-restraint devices are specified in Division 22 Section "Vibration and Seismic Controls for
Plumbing Piping and Equipment."
B. Pipe hangers and supports are specified in Division 22 Section "Hangers and Supports for Plumbing
Piping and Equipment." Install the following:
3. Multiple, Straight, Horizontal Piping Runs 30 m or Longer: MSS Type 44, pipe rolls. Support
pipe rolls on trapeze.
4. Base of Vertical Piping: MSS Type 52, spring hangers.
C. Install supports according to Division 22 Section "Hangers and Supports for Plumbing Piping and
Equipment."
E. Rod diameter may be reduced 1 size for double-rod hangers, with 10-mm minimum rods.
F. Install hangers for steel piping with the following maximum horizontal spacing and minimum rod di-
ameters:
H. Install hangers for uPVC piping with the following maximum horizontal spacing and minimum rod
diameters:
J. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written in-
structions.
3.7 CONNECTIONS
B. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting to join dis-
similar piping materials.
1. Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required
by plumbing code.
2. Plumbing Fixtures and Equipment: Connect atmospheric vent piping in sizes indicated, but not
smaller than required by authorities having jurisdiction.
3. Plumbing Specialties: Connect drainage and vent piping in sizes indicated, but not smaller than
required by plumbing code.
4. Equipment: Connect drainage piping as indicated. Provide shutoff valve, if indicated, and un-
ion for each connection. Use flanges instead of unions for connections DN 65 and larger.
A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be
made. Perform tests specified below in presence of authorities having jurisdiction.
1. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after
roughing-in and before setting fixtures.
2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe
tests specified below and to ensure compliance with requirements.
B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make
required corrections and arrange for reinspection.
C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.
D. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction or, in
absence of published procedures, as follows:
1. Test for leaks and defects in new piping and parts of existing piping that have been altered, ex-
tended, or repaired. If testing is performed in segments, submit separate report for each test,
complete with diagram of portion of piping tested.
2. Leave uncovered and unconcealed new, altered, extended, or replaced drainage and vent piping
until it has been tested and approved. Expose work that was covered or concealed before it
was tested.
3. Roughing-in Plumbing Test Procedure: Test drainage and vent piping, except outside leaders,
on completion of roughing-in. Close openings in piping system and fill with water to point of
overflow, but not less than 30 kPa. From 15 minutes before inspection starts to completion of
inspection, water level must not drop. Inspect joints for leaks.
4. Finished Plumbing Test Procedure: After plumbing fixtures have been set and traps filled with
water, test connections and prove they are gastight and watertight. Plug vent-stack openings
on roof and building drains where they leave building. Introduce air into piping system equal
to pressure of 250 Pa. Use U-tube or manometer inserted in trap of water closet to measure
this pressure. Air pressure must remain constant without introducing additional air throughout
period of inspection. Inspect plumbing fixture connections for gas and water leaks.
5. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfac-
tory results are obtained.
6. Prepare reports for tests and required corrective action.
E. Test force-main piping according to procedures of authorities having jurisdiction or, in absence of
published procedures, as follows:
1. Leave uncovered and unconcealed new, altered, extended, or replaced force-main piping until
it has been tested and approved. Expose work that was covered or concealed before it was
tested.
2. Cap and subject piping to static-water pressure of 345 kPa above operating pressure, without
exceeding pressure rating of piping system materials. Isolate test source and allow to stand for
four hours. Leaks and loss in test pressure constitute defects that must be repaired.
3. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfac-
tory results are obtained.
4. Prepare reports for tests and required corrective action.
3.9 CLEANING
B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to
prevent damage from traffic and construction work.
C. Place plugs in ends of uncompleted piping at end of day and when work stops.
3.10 PROTECTION
A. Exposed PVC Piping: Protect plumbing vents exposed to sunlight with two coats of water-based latex
paint.
PART 1 GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
B. The Qatar construction specification (QCS 2014) shall form the basis of the project specifi-
cation. The technical specification is supplemental to QCS (latest revision) and should be
read in conjunction with QCS and all other contract documents. In case of contradiction or
discrepancy between QCS and technical specifications, CONTRACTOR shall incorporate
whichever is more stringent.
1.2 SUMMARY
1. Cleanouts.
2. Garage drains.
3. Floor drains.
4. Shower drains.
5. Planter drain.
6. Trench drains.
7. Grease interceptors
8. Sand traps
9. Grease interceptors
10. Sand traps
11. Inspection chambers
12. Gully trap
13. Retarding chambers
14. Air-admittance valves.
15. Through-penetration fire-stop assemblies.
16. Miscellaneous sanitary drainage piping specialties.
17. Flashing materials.
1. Division 22 Section "Storm Drainage Piping Specialties" for trench drains for storm
water, channel drainage systems for storm water, roof drains, and catch basins.
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Shop Drawings: Show fabrication and installation details for frost-resistant vent terminals.
C. Operation and Maintenance Data: For drainage piping specialties to include in emergency,
operation, and maintenance manuals.
A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing
agency.
C. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic
sanitary piping specialty components.
1.6 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
PART 2 PRODUCTS
2.1 CLEANOUTS
1. Floor Cleanout
2. Standard: ASME A112.36.2M for threaded, for heavy duty adjustable housing
cleanout.
3. Size: Same as connected branch.
4. Type: Threaded, adjustable housing.
5. Body or Ferrule: Cast iron.
6. Clamping Device: Required.
7. Outlet Connection: Spigot.
8. Closure: Brass plug with straight threads and gasket.
9. Adjustable Housing Material: Cast iron with threads.
10. Frame and Cover Material and Finish: Nickel-bronze, copper alloy.
11. Frame and Cover Shape: Square.
12. Top Loading Classification: Heavy duty.
1. Material: ABS.
2. Water proofing layer: Required.
3. Number of outlet: One
4. Type of cover: Stainless steel.
5. Outlet diameter: 50mm
6. Outlet: Bottom or side as applicable.
7. Top Shape: Square.
8. Odor trap: Required.
9. Hair filter: Required.
1. Grates: heavy duty," with slots and of width 300mm and thickness that fit recesses in
frames sections.
2. Show locations and lengths of covers on Drawings. Supports, Anchors, and Setting
Devices: Manufacturer's standard, unless otherwise indicated.
1. Standard: EN 1825-1.
2. Operation: Automatic disposal and cleaning system.
3. Body Material: Corrosion free polyethylene
4. Sludge trap: Required.
5. Flow Rate: As indicated in drawing and BOQ.
6. Cleanout: Integral.
7. Mounting: Above floor, flush with floor.
8. Flow-Control Fitting: Required.
1. Type: Factory-fabricated interceptor for separating and removing light oil from
wastewater.
2. Body Material: Cast iron or steel.
3. Interior Lining: Corrosion-resistant enamel.
4. Exterior Coating: Corrosion-resistant enamel.
5. Body Dimensions: As per drawings.
6. Inlet and Outlet Size: 75mm.
7. Cleanout: Integral.
8. Location: Under-ground, flush with floor.
9. Flow-Control Fitting: Required.
10. Oil Storage Tank: Fabricated steel tank according to UL 142, single wall, horizontal.
A. Reinforced concrete sand trap, heavy duty cast iron covers and frames, cast iron steps,
inlet and outlet wall pipe, interior and exterior water proofing.
A. Shall be cast-in-situ concrete with dimensions as indicated in the drawings and depth as
required.
A. Shall be plastic type inside concrete chamber (where required) with dimensions as
indicated in the drawings and depth as required.
E. Steps shall be painted with three approved coats of coal tar epoxy coating.
1. Standard: UL 1479 assembly of sleeve and stack fitting with firestopping plug.
2. Size: Same as connected soil, waste, or vent stack.
3. Sleeve: Molded PVC plastic, of length to match slab thickness and with integral nail-
ing flange on one end for installation in cast-in-place concrete slabs.
4. Stack Fitting: ASTM A 48/A 48M, gray-iron, hubless-pattern, wye branch with neo-
prene O-ring at base and gray-iron plug in thermal-release harness. Include PVC pro-
tective cap for plug.
5. Special Coating: Corrosion resistant on interior of fittings.
A. Air-Gap Fittings:
1. Standard: ASME A112.1.2, for fitting designed to ensure fixed, positive air gap be-
tween installed inlet and outlet piping.
2. Body: Bronze or cast iron.
3. Inlet: Opening in top of body.
4. Outlet: Larger than inlet.
5. Size: Same as connected waste piping and with inlet large enough for associated indi-
rect waste piping.
1. Description: Manufactured, cast-iron fitting, with clamping device, that forms sleeve
for pipe floor penetrations of floor membrane. Include galvanized-steel pipe exten-
sion in top of fitting that will extend 51 mm above finished floor and galvanized-steel
pipe extension in bottom of fitting that will extend through floor slab.
2. Size: As required for close fit to riser or stacks piping.
1. Description: Counter flashing-type, cast-iron fitting, with bottom recess for terminat-
ing roof membrane, and with threaded or hub top for extending vent pipe.
2. Size: Same as connected stack vent or vent stack.
D. Vent Caps:
1. Description: Cast-iron body with threaded or hub inlet and vandal-proof design. In-
clude vented hood and setscrews to secure to vent pipe.
2. Size: Same as connected stack vent or vent stack.
E. Expansion Joints:
A. Lead Sheet: ASTM B 749, Type L51121, copper bearing, with the following minimum
weights and thicknesses, unless otherwise indicated:
B. Copper Sheet: ASTM B 152/B 152M, of the following minimum weights and thicknesses,
unless otherwise indicated:
C. Zinc-Coated Steel Sheet: ASTM A 653/A 653M, with 0.20 percent copper content and 1.01-
mm minimum thickness, unless otherwise indicated. Include Z275 hot-dip galvanized, mill-
phosphatized finish for painting if indicated.
F. Metal Accessories: Sheet metal strips, clamps, anchoring devices, and similar accessory units
required for installation; matching or compatible with material being installed.
2.17 MOTORS
A. General requirements for motors are specified in Division 22 Section "Common Motor
Requirements for Plumbing Equipment."
1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load
will not require motor to operate in service factor range above 1.0.
2. Controllers, Electrical Devices, and Wiring: Electrical devices and connections are
specified in Division 26 Sections.
PART 3 EXECUTION
3.1 INSTALLATION
A. Refer to Division 22 Section "Common Work Results for Plumbing" for piping joining
materials, joint construction, and basic installation requirements.
B. Install backwater valves in building drain piping. For interior installation, provide cleanout
deck plate flush with floor and centered over backwater valve cover, and of adequate size to
remove valve cover for servicing.
C. Install cleanouts in aboveground piping and building drain piping according to the following,
unless otherwise indicated:
1. Size same as drainage piping up to DN 100. Use DN 100 for larger drainage piping
unless larger cleanout is indicated.
2. Locate at each change in direction of piping greater than 45 degrees.
3. Locate at minimum intervals of 15 m for piping DN 100 and smaller and 30 m for
larger piping.
4. Locate at base of each vertical soil and waste stack.
D. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with
finished floor.
E. For cleanouts located in concealed piping, install cleanout wall access covers, of types
indicated, with frame and cover flush with finished wall.
F. Install floor drains at low points of surface areas to be drained. Set grates of drains flush
with finished floor, unless otherwise indicated.
3. Install floor-drain flashing collar or flange so no leakage occurs between drain and ad-
joining flooring. Maintain integrity of waterproof membranes where penetrated.
4. Install individual traps for floor drains connected to sanitary building drain, unless
otherwise indicated.
G. Install trench drains at low points of surface areas to be drained. Set grates of drains flush
with finished surface, unless otherwise indicated.
H. Assemble and install ASME A112.3.1, stainless-steel channel drainage systems according to
ASME A112.3.1. Install on support devices so that top will be flush with surface.
K. Install stack air-admittance valves at top of stack vent and vent stack piping.
M. Install roof flashing assemblies on sanitary stack vents and vent stacks that extend through
roof.
N. Install flashing fittings on sanitary stack vents and vent stacks that extend through roof.
P. Assemble open drain fittings and install with top of hub 51 mm above floor.
Q. Install deep-seal traps on floor drains and other waste outlets, if indicated.
R. Install floor-drain, trap-seal primer fittings on inlet to floor drains that require trap-seal
primer connection.
T. Install sleeve flashing device with each riser and stack passing through floors with
waterproof membrane.
V. Install expansion joints on vertical stacks and conductors. Position expansion joints for easy
access and maintenance.
X. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is
indicated.
Y. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and
within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding pipe fittings.
3.2 CONNECTIONS
C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes are
required. Join flashing according to the following if required:
1. Lead Sheets: Burn joints of lead sheets 30-kg/sq. m, 2.4-mm thickness or thicker.
Solder joints of lead sheets 20-kg/sq. m, 1.6-mm thickness or thinner.
2. Copper Sheets: Solder joints of copper sheets.
B. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in floors
and roofs with waterproof membrane.
1. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 250 mm, and
skirt or flange extending at least 200 mm around pipe.
2. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 200 mm around
sleeve.
3. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least 200
mm around specialty.
E. Install flashing for piping passing through roofs with counterflashing or commercially made
flashing fittings, according to Division 07 Section "Sheet Metal Flashing and Trim."
F. Extend flashing up vent pipe passing through roofs and turn down into pipe, or secure
flashing into cast-iron sleeve having calking recess.
G. Fabricate and install flashing and pans, sumps, and other drainage shapes.
1. Grease interceptors.
Leak Test: After installation, charge system and test for leaks. Repair leaks and retest
until no leaks exist.
Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
3.6 PROTECTION
A. Protect drains during remainder of construction period to avoid clogging with dirt or debris
and to prevent damage from traffic or construction work.
B. Place plugs in ends of uncompleted piping at end of each day or when work stops.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
A. This Section includes the following sewage pumps and accessories for sanitary drainage
piping systems in buildings:
1.3 SUBMITTALS
A. Product Data:
1. For each type and size of sewage pump specified. Include certified performance
curves with operating points plotted on curves; and rated capacities of selected mod-
els, furnished specialties, and accessories.
B. Shop Drawings:
1. For each sewage pump to include in emergency, operation, and maintenance manuals.
2. As built drawings.
A. Product Options:
1. Drawings indicate size, profiles, and dimensional requirements of sewage pumps and
are based on the specific system indicated. Refer to Division 01 Section "Product Re-
quirements."
1. Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable
to authorities having jurisdiction, and marked for intended use.
A. Retain shipping flange protective covers and protective coatings during storage.
1.6 COORDINATION
A. Coordinate size and location of concrete pits. Concrete, reinforcement, and formwork
requirements are specified in Division 03.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
a. Casing: Cast iron, with open inlet, legs (or guide-rail supports) that elevate
pump to permit flow into impeller, and vertical discharge with companion
flange for piping connection.
b. Impeller: ASTM A 532/A 532M, abrasion-resistant cast iron; statically and dy-
namically balanced, closed or semiopen design for clear wastewater; overhung,
single suction, and keyed and secured to shaft.
c. Pump and Motor Shaft: Stainless steel with factory-sealed, grease-lubricated
ball bearings and double mechanical seals.
d. Motor: Hermetically sealed, capacitor-start type; with built-in overload protec-
tion; lifting eye or lug; and three-conductor, waterproof, power cable of length
required and with grounding plug and cable-sealing assembly for connection at
pump. Comply with Division 22 Section "Common Motor Requirements for
Plumbing Equipment."
C. Pit Cover:
1. Cast iron or coated steel and suitable to support controls. See Part 2 "Sewage Pump
Pits" Article for other requirements.
D. Controls:
1. NEMA 250, Type 1, enclosures, pedestal mounted unless wall mounting is indicated;
with mercury-float switches in NEMA 250, Type 6 enclosures; mounting rod; and
electric cables. Include automatic alternator to alternate operation of pump units on
successive cycles and to operate multiple units if one pump cannot handle load.
a. Float Guide: Pipe or other restraint for floats and rods in basins of depth greater
than 60 inches (1500 mm).
b. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 enclosure with mercu-
ry-float -switch alarm matching control and electric bell; 120-V ac, with trans-
former and contacts for remote alarm bell.
a. Casing: Cast iron, with open inlet, legs (or guide-rail supports) that elevate
pump to permit flow into impeller, and vertical discharge with companion
flange for piping connection.
b. Impeller: ASTM A 532/A 532M, abrasion-resistant cast iron; statically and dy-
namically balanced, closed or semi open design for solids handling; overhung,
single suction, and keyed and secured to shaft.
c. Pump and Motor Shaft: Stainless steel with factory-sealed, grease-lubricated
ball bearings and double mechanical seals.
d. Motor: Hermetically sealed capacitor-start type; with built-in overload protec-
tion; lifting eye or lug; and three-conductor, waterproof, power cable of length
required and with grounding plug and cable-sealing assembly for connection at
pump. Comply with Division 22 Section "Common Motor Requirements for
Plumbing Equipment."
C. Pit Cover:
1. Cast iron or coated steel and suitable to support controls. See Part 2 "Sewage Pump
Pits" Article for other requirements.
D. Controls:
1. NEMA 250, Type 1, enclosures, pedestal mounted unless wall mounting is indicated;
with mercury-float switches in NEMA 250, Type 6 enclosures; mounting rod; and
electric cables. Include automatic alternator to alternate operation of pump units on
successive cycles and to operate multiple units if one pump cannot handle load.
a. Float Guide: Pipe or other restraint for floats and rods in basins of depth greater
than 60 inches (1500 mm).
b. High-Water Alarm: Rod-mounted, NEMA 250, Type 6 enclosure with mercu-
ry-float -switch alarm matching control and electric bell; 120-V ac, with trans-
former and contacts for remote alarm bell.
A. Description:
1. Concrete pit with sump, pipe connections, curb frame, and separate cover.
B. Sump:
a. Pipe Connections: Sleeved openings large enough for mechanical sleeve seals
for drainage piping. Sleeves and mechanical sleeve seals are specified in Divi-
sion 22 Section "Common Work Results for Plumbing" and drainage piping is
2. Cover: Fabricate with openings having gaskets, seals, and bushings; for access to
pumps, pump shafts, control rods, discharge piping, vent connections, and power ca-
bles.
A. Provide auxiliary contacts in pump controllers for interface to building automation system.
Include the following:
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for plumbing piping to verify actual locations of sanitary drainage and
vent piping connections before sewage pump installation.
3.2 CONCRETE
A. Install concrete bases of dimensions indicated for pumps and controllers. Refer to
Division 22 Section "Common Work Results for Plumbing."
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indi-
cated, install dowel rods on 450-mm centers around full perimeter of base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through con-
crete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, in-
structions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported equip-
ment.
B. Cast-in-place concrete materials and placement requirements are specified in Division 03.
3.3 INSTALLATION
A. Excavating, trenching, and backfilling are specified in Division 31 Section "Earth Moving."
C. Install pumps and arrange to provide access for maintenance including removal of motors,
impellers, couplings, and accessories.
D. Suspend wet-pit-mounted, vertical sewage pumps from pit covers. Make direct connections
to sanitary drainage piping.
E. Set submersible sewage pumps on pit floors. Make direct connections to sanitary drainage
piping.
1. Anchor guide-rail supports to pit bottoms and sidewalls or covers. Install pumps so
pump and discharge pipe disconnecting flanges make positive seals when pumps are
lowered into place.
F. Install sewage pump basins and connect to drainage and vent piping. Brace interior of basins
according to manufacturer's written instructions to prevent distortion or collapse during
concrete placement. Set basin cover and fasten to basin top flange. Install cover so top
surface is flush with finished floor.
G. Construct sewage pump pits and connect to drainage and vent piping. Set pit curb frame
recessed in and anchored to concrete. Fasten pit cover to pit curb flange. Install cover so top
surface is flush with finished floor.
H. Install packaged, submersible sewage pump units and make direct connections to drainage
and vent piping.
I. Install packaged, wastewater pump unit basins on floor or concrete base unless recessed
installation is indicated. Make direct connections to drainage and vent piping.
3.4 CONNECTIONS
A. Piping installation requirements are specified in Division 22 Section "Sanitary Waste and
Vent Piping." Drawings indicate general arrangement of piping, fittings, and specialties.
C. Connect sanitary drainage and vent piping to pumps. Install discharge piping equal to or
greater than size of pump discharge piping. Install vent piping equal to or greater than size
of pump basin vent connection. Refer to Division 22 Section "Sanitary Drainage and Vent
Piping."
D. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
1. Start motors.
2. Open discharge valves slowly.
3. Check general mechanical operation of pumps and motors.
1. Pump Controls: Set pump controls for automatic start, stop, and alarm operation as
required for system application.
2. Set field-adjustable switches and circuit-breaker trip ranges as indicated, or if not indi-
cated, for normal operation.
E. Occupancy Adjustments:
3.6 DEMONSTRATION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
A. This Section includes the following storm drainage piping inside the building:
1.3 DEFINITIONS
1.5 SUBMITTALS
B. Shop Drawings:
A. Piping materials shall bear label, stamp, or other markings of specified testing agency.
B. Comply with NSF 14, "Plastics Piping Systems Components and Related Materials," for
plastic piping components. Include marking with "NSF-drain" for plastic drain piping and
"NSF-sewer" for plastic sewer piping.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting, and
joining materials.
1. PVC Socket Fittings: ASTM D 2665, socket type, made to ASTM D 3311, Storm pat-
terns.
D. PVC Socket Fittings: ASTM D 2466, for Schedule 40Solvent Cement and Adhesive Primer:
1. Use PVC solvent cement that has a VOC content of 510 g/L or less when calculated
according to 40 CFR 59, Subpart D (EPA Method 24).
2. Use adhesive primer that has a VOC content of 550 g/L or less when calculated ac-
cording to 40 CFR 59, Subpart D (EPA Method 24).
A. Pipe, fittings and accessories shall be conform to ASTM D2997 & ASTM D 3517-01 QCS
last edition requirements.
C. GRP pipes and fittings shall be manufactured by an approved process utilising a mandrel or
rotating mould incorporating equipment to accurately control the quantities and placement of
all resins, glass and aggregates.
A. Flexible, Nonpressure Pipe Couplings: Comply with ASTM C 1173, elastomeric, sleeve-
type, reducing or transition pattern. Include shear ring, ends of same sizes as piping to be
joined, and corrosion-resistant-metal tension band and tightening mechanism on each end.
1. Sleeve Materials:
a. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC.
B. Shielded Nonpressure Pipe Couplings: ASTM C 1460, elastomeric or rubber sleeve with
full-length, corrosion-resistant outer shield and corrosion-resistant-metal tension band and
tightening mechanism on each end.
C. Pressure Pipe Couplings: AWWA C219 metal, sleeve-type same size as, with pressure
rating at least equal to, and ends compatible with, pipes to be joined.
E. Wall-Penetration Fittings: Compound, ductile-iron coupling fitting with sleeve and flexing
sections for up to 20-degree deflection, gaskets, and restrained-joint ends complying with
AWWA C110 or AWWA C153. Include AWWA C111, ductile-iron glands, rubber gaskets,
and steel bolts.
B. Form: tube.
C. Color: Black.
PART 3 - EXECUTION
3.1 EXCAVATION
A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling.
A. Flanges and unions may be used on aboveground pressure piping, unless otherwise indicated.
C. Underground storm drainage piping DN 160 and smaller shall be any of the following:
1. Solid-wall Cellular-core PVC pipe, PVC socket fittings, and solvent-cemented joints.
2. Glass reinforced plastic (GRP) pipes and fittings.
D. Underground, storm drainage piping DN 200 and larger shall be any of the following:
A. Storm sewer and drainage piping outside the building are specified in Division 33 Section
"Storm Utility Drainage Piping."
B. Basic piping installation requirements are specified in Division 22 Section "Common Work
Results for Plumbing."
C. Install cleanouts at grade and extend to where building storm drains connect to building
storm sewers. Cleanouts are specified in Division 22 Section "Storm Drainage Piping
Specialties."
E. Install wall-penetration fitting system at each service pipe penetration through foundation
wall. Make installation watertight.
G. Make changes in direction for storm drainage piping using appropriate branches, bends, and
long-sweep bends. Do not change direction of flow more than 90 degrees. Use proper size
of standard increasers and reducers if pipes of different sizes are connected. Reducing size
of drainage piping in direction of flow is prohibited.
H. Lay buried building storm drainage piping beginning at low point of each system. Install
true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends
of piping upstream. Install required gaskets according to manufacturer's written instructions
for use of lubricants, cements, and other installation requirements. Maintain swab in piping
and pull past each joint as completed.
I. Install storm drainage piping at the following minimum slopes, unless otherwise indicated:
1. Building Storm Drain: 1 percent downward in direction of flow for piping DN 80 and
smaller; 1 percent downward in direction of flow for piping DN 100 and larger.
K. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if
N. Do not enclose, cover, or put piping into operation until it is inspected and approved by
authorities having jurisdiction.
A. Basic piping joint construction requirements are specified in Division 22 Section "Common
Work Results for Plumbing."
B. Grooved Joints: Cut groove ends of pipe and assemble grooved ends of pipes, grooved-end
fittings, and grooved-end-piping couplings according to AWWA C606.
C. Check Valves: Install swing check valve, between pump and shutoff valve, on each sump
pump discharge.
1. Horizontal Piping: Horizontal backwater valves. Use normally closed type, unless
otherwise indicated.
2. Install backwater valves in accessible locations.
3. Backwater valve are specified in Division 22 Section "Storm Drainage Piping Special-
ties."
B. Pipe hangers and supports are specified in Division 22 Section "Hangers and Supports for
Plumbing Piping and Equipment." Install the following:
3. Multiple, Straight, Horizontal Piping Runs 30 m or Longer: MSS Type 44, pipe rolls.
Support pipe rolls on trapeze.
4. Base of Vertical Piping: MSS Type 52, spring hangers.
C. Install supports according to Division 22 Section "Hangers and Supports for Plumbing
Piping and Equipment."
E. Rod diameter may be reduced 1 size for double-rod hangers, with 10-mm minimum rods.
F. Install hangers for PVC piping with the following maximum horizontal spacing and
minimum rod diameters:
H. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's
written instructions.
3.7 CONNECTIONS
B. Connect interior storm drainage piping to exterior storm drainage piping. Use transition
fitting to join dissimilar piping materials.
C. Connect storm drainage piping to roof drains and storm drainage specialties.
A. During installation, notify authorities having jurisdiction at least 24 hours before inspection
must be made. Perform tests specified below in presence of authorities having jurisdiction.
B. Reinspection: If authorities having jurisdiction find that piping will not pass test or
inspection, make required corrections and arrange for reinspection.
C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.
D. Test storm drainage piping according to procedures of authorities having jurisdiction or, in
absence of published procedures, as follows:
1. Test for leaks and defects in new piping and parts of existing piping that have been al-
tered, extended, or repaired. If testing is performed in segments, submit separate re-
port for each test, complete with diagram of portion of piping tested.
2. Leave uncovered and unconcealed new, altered, extended, or replaced storm drainage
piping until it has been tested and approved. Expose work that was covered or con-
cealed before it was tested.
3. Test Procedure: Test storm drainage piping, except outside leaders, on completion of
roughing-in. Close openings in piping system and fill with water to point of overflow,
but not less than 30 kPa. From 15 minutes before inspection starts to completion of
inspection, water level must not drop. Inspect joints for leaks.
4. Repair leaks and defects with new materials and retest piping, or portion thereof, until
satisfactory results are obtained.
5. Prepare reports for tests and required corrective action.
3.9 CLEANING
B. Protect drains during remainder of construction period to avoid clogging with dirt and debris
and to prevent damage from traffic and construction work.
C. Place plugs in ends of uncompleted piping at end of day and when work stops..
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
1. Cleanouts.
2. Trench drains.
3. Through-penetration fire stop assemblies.
4. Roof drains.
5. Miscellaneous storm drainage piping specialties.
6. Flashing materials.
1. Division 22 Section "Sanitary Waste Piping Specialties" for backwater valves, floor
drains, trench drains and channel drainage systems connected to sanitary sewer, air
admittance valves, FOG disposal systems, grease interceptors and removal devices, oil
interceptors, and solid interceptors.
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Product Data:
A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing
agency.
1.6 COORDINATION
PART 2 - PRODUCTS
2.1 MANUFACTURERS
E. Steps shall be painted with three approved coats of coal tar epoxy coating.
A. Downspout Boots:
1. Description: Manufactured, ASTM A 48/A 48M, gray-iron casting, with strap or ears
for attaching to building; outlet; and shop-applied bituminous coating.
2. Size: Inlet size to match downspout.
3. Description: ASTM A 74, Service class, hub-and-spigot, cast-iron soil pipe.
4. Size: Same as or larger than connected downspout.
B. Conductor Nozzles:
1. Description: Bronze body with threaded inlet and bronze wall flange with mounting
holes.
2. Size: Same as connected conductor.
A. Copper Sheet:
1. ASTM A 653/A 653M, with 0.20 percent copper content and 1.01-mmminimum
thickness, unless otherwise indicated. Include G90 (Z275) hot-dip galvanized, mill-
phosphatized finish for painting if indicated.
D. Fasteners:
E. Metal Accessories:
1. Sheet metal strips, clamps, anchoring devices, and similar accessory units required for
installation; matching or compatible with material being installed.
F. Bituminous Coating:
PART 3 - EXECUTION
3.1 INSTALLATION
A. Refer to Division 22 Section "Common Work Results for Plumbing" for piping joining
materials, joint construction, and basic installation requirements.
B. Install cleanouts in aboveground piping and building drain piping according to the following,
unless otherwise indicated:
1. Size same as drainage piping up to DN 100. Use DN 100 for larger drainage piping
unless larger cleanout is indicated.
2. Locate at each change in direction of piping greater than 45 degrees.
3. Locate at minimum intervals of 15 m for piping DN 100 and smaller and 30 m for
larger piping.
4. Locate at base of each vertical soil and waste stack.
C. For cleanouts located in concealed piping, install cleanout wall access covers, of types
indicated, with frame and cover flush with finished wall.
D. Install trench drains at low points of surface areas to be drained. Set grates of drains flush
with finished surface, unless otherwise indicated.
E. Install through-penetration fire stop assemblies in plastic conductors and stacks at floor
penetrations.
F. Install roof drains at low points of roof areas according to roof membrane manufacturer's
written installation instructions.
1. Install roof-drain flashing collar or flange so that there will be no leakage between
drain and adjoining roofing. Maintain integrity of waterproof membranes where pene-
trated.
2. Position roof drains for easy access and maintenance.
G. Install sleeve-flashing device with each riser and stack passing through floors with
waterproof membrane.
H. Install expansion joints on vertical stacks and conductors. Position expansion joints for easy
access and maintenance.
I. Install manufactured, gray-iron downspout boots at grade with top 250 mm above grade.
Secure to building wall.
J. Install conductor nozzles at exposed bottom of conductors where they spill onto grade.
K. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and
within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding pipe fittings.
3.2 CONNECTIONS
A. Fabricate flashing from single piece unless large pans, sumps, or other drainage shapes are
required. Join flashing according to the following if required:
1. Lead Sheets: Burn joints of lead sheets 30-kg/sq. m, 2.4-mm thickness or thicker.
Solder joints of lead sheets 20-kg/sq. m, 1.6-mm thickness or thinner.
2. Copper Sheets: Solder joints of copper sheets.
B. Install sheet flashing on pipes, sleeves, and specialties passing through or embedded in floors
and roofs with waterproof membrane.
1. Pipe Flashing: Sleeve type, matching pipe size, with minimum length of 250 mm, and
skirt or flange extending at least 200 mm around pipe.
2. Sleeve Flashing: Flat sheet, with skirt or flange extending at least 200 mm around
sleeve.
3. Embedded Specialty Flashing: Flat sheet, with skirt or flange extending at least 200
mm around specialty.
E. Fabricate and install flashing and pans, sumps, and other drainage shapes.
3.4 PROTECTION
A. Protect drains during remainder of construction period to avoid clogging with dirt or debris
and to prevent damage from traffic or construction work.
B. Place plugs in ends of uncompleted piping at end of each day or when work stops..
PART 1- GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions.
B. Section 221119 "Domestic Water Piping Specialties" for plumbing piping strainers
1.2 SUMMARY
A. Section Includes:
1. Multimedia sand filters.
2. Water softener
A. Seismic Performance: multimedia sand filters shall withstand the effects of earthquake
motions determined according to ASCE/SEI 7.
1. The term "withstand" means that "the unit will remain in place without separation of
any parts from the device when subjected to the seismic forces specified and the unit
will be fully operational after the seismic event.
B. Shop Drawings: For water filtration equipment. Include plans, elevations, sections, details,
and attachments to other work.
A. Seismic Qualification Certificates: For multimedia sand filters and/or any other used filters /
separators, accessories, and components, from manufacturer.
1. Basis for Certification: Indicate whether withstand certification is based on actual test
of assembled components or on calculation.
B. Certificates of Shop Inspections and Data Reports: For products required to have ASME
label, signed by product manufacturer.
C. Welding certificates.
A. Operation and Maintenance Data: For water filtration equipment to include in emergency,
operation, and maintenance manuals.
A. Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
A. Equipment supplied shall have local agents certified by the manufacturer to check, test,
adjust and commission the equipment.
B. Product data, certified pump performance characteristics with selection plotted, data on
equipment dimensions, service connections, operating weight and installation drawings and
instructions shall be submitted under provisions of the general conditions of Contract.
D. Packaged pump sets shall be assembled and tested at the manufacturers or licensee's own
premises. Furnish copy of manufacturing license along with material submittal, where
appropriate.
E. Source Limitations: Obtain each type of water filtration equipment through one source from
a single manufacturer.
F. Welding Qualifications: Qualify processes and operators according to ASME Boiler and
Pressure Vessel Code.
G. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
by a qualified testing agency, and marked for intended location and application.
H. Comply with NSF 61 Annex, "Drinking Water System Components - Health Effects," for all
components that will be in contact with potable water.
J. Equipment shall have labels indicating the following, attached permanently to them:
1. Name of Manufacturer.
2. Model no. and Serial no.
3. Certified Ratings.
4. Maximum Operating Parameters.
1.9 HANDLING
A. Products shall be delivered to site, stored and protected under provisions of the general
conditions of Contract.
A. The contractor shall be responsible for the performance of the plumbing equipment to
achieve the design requirements and the Hotel operator special requirements indicated in the
Operator’s DCD Document as well as M/s Kahramaa requirements for drinking water
quality.
A. Feedwater Analysis:
B. Feedwater Properties:
A. Domestic water quality for treated raw water (domestic water) shall comply with the local
authorities requirements M/s Kahramaa.
B. All the quality of drinking water and / or water utilized for cooking purpose shall be comply
with M/s Kahramaa as well as WHO standard and EU guidelines. Refer to Kahramaa
Drinking Water Quality Requirement 2014 edition.
C. The water supply as distributed within the hotel to have the following characteristics:
A. Provide complete spare parts and maintenance equipment for two (2) years maintenance of
all the plumbing equipment. Spare parts in a location designated by the Engineer or the
Employer.
B. All spare parts and maintenance equipment shall be brand new, same as being installed,
provided in original packing, clearly identified and labeled. Provide complete schedules of
spare parts and maintenance equipment clearly cross-referenced with the “Record Drawings”
and maintenance instructions and manuals.
C. All spare parts and maintenance equipment shall be as recommended by the equipment
manufacturer and shall be subject to the final approval of the Engineer.
D. Spare parts and maintenance equipment provided shall, as a minimum, equal the items used
during the two (2) years maintenance period. The Contractor shall carefully log all spare
parts utilized during maintenance period.
E. Provide spare parts and maintenance equipment for all pumps, control panel etc. requiring
maintenance and replacement.
F. Provide two new complete sets of tools for the proper operation, routine maintenance and
adjustment of all components and equipment.
1.14 WARRANTY
A. Manufacturers shall provide their standard warranty for products furnished under this
Section.
1.15 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.Concrete,
reinforcement, and formwork requirements are specified in Division 03.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
C. Construction: ASME rated glass reinforced plastic shell with dished end, welded inlet and
outlet pipes with flanged ends, steel / ABS distribution and collection pipes and laterals,
access manhole with synthetic gasket and external locking bar, integral jack supports and
lifting lugs.
D. Protective coatings: Food grade epoxy internally and rust inhibiting primer and one coat of
enamel externally.
F. Valves: Hydraulically operated diaphragm type, steel body with flanged ends.
A. Provide auxiliary contacts in system control panel for the required and necessary interfaces
to building automation system as per the approved I/O points and / or related BMS drawings.
B. All activities as per I/O points shall be monitored on Dynamic colour graphics and graphic
control as prescribed in related Division. Submit Graphics for the Engineer’s approval.
B. Standard: Comply with NSF 61 Annex, "Drinking Water System Components - Health
Effects
D. Media : Zeolite
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and conditions, with Installer present, for compliance with requirements for
installation tolerances and other conditions affecting performance of filters.
3.2 SELECTION
A. Pump motors shall be selected for the maximum loading of the selected impeller.
B. Pumps shall be selected with the operating points within 20 % on either side of the
maximum efficiency point.
C. The maximum and minimum impeller sizes shall not be selected for unit pumps, as far as
possible.
3.3 COORDINATION
A. The size of doorways and other accesses to technical areas shall be coordinated to ensure that
these are amply sized to allow for the movement of equipment.
B. Hooks, rails or other provisions shall be provided to allow for hoisting or movement of
equipment in technical areas.
C. Data on heat loss to surroundings from equipments located in air conditioned areas shall be
furnished to the HVAC trade.
D. Data on the required power supplies shall be furnished to the Electrical trade.
3.4 INSTALLATION
A. Standard clearances shall be provided around equipment for operation, maintenance and
ventilation.
C. Lifting devices shall be attached to equipment only at designated points. The equipment shall
not be dropped or subjected to any kind of shock.
a. Softening tank(s)
b. Brine tank, saturation type, complete with measuring indica1or, overflow,
strainer, brine drain-off and supporting gravel.
c. Hard water by-pass proportional controller, flow controls for backwash and
reuse, and an au1omatic reset water meter for controlling the regeneration
cycle.
d. Water testing kit.
e. Total by-pass line for maintenance and servicing.
A. Equipment Mounting: Install filters and softener on concrete bases. Comply with
requirements for concrete bases specification.
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 450-mm centers around full perimeter of concrete
base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through
concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams,
instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported
equipment.
3.6 CONNECTIONS
A. Comply with requirements for piping specified in Section 221116 "Domestic Water Piping."
Drawings indicate general arrangement of piping, fittings, and specialties.
C. Make piping connections between water filtration equipment and dissimilar-metal water
piping with dielectric fittings. Comply with requirements for dielectric fittings specified in
Section 221116 "Domestic Water Piping."
1. Install shutoff valves on feed water-inlet and outlet piping of any water filtration
equipment and on inlet and outlet headers Comply with requirements specified in
Section 221119 – "DOMESTIC WATER PIPING SPECIALTIES".
D. Install pressure gages on feed water-inlet and filtrate-outlet piping of each water filtration
equipment. Comply with requirements for pressure gages specified in Section 220519
"Meters and Gages for Plumbing Piping."
E. Install valved bypass water piping around any water filtration equipment. Comply with
requirements specified in Section 221119 – "DOMESTIC WATER PIPING
SPECIALTIES".
F. Install drains as indirect wastes to spill into open drains or over floor drains.
A. Install identifying equipment makers and equipment signs on booster pumps. Labeling and
identification materials are specified in Division 22 Section "Identification for Plumbing
Piping and Equipment."
1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest
until no leaks exist.
2. Operational Test: After electrical circuitry has been energized, start units to confirm
proper unit operation.
3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
D. Domestic water filtration equipment will be considered defective if it does not pass tests and
inspections.
B. Sample filter filtrate after startup and at three consecutive seven-day intervals (total of four
samples), and prepare certified test reports for required water performance characteristics.
A. Prior startup the system, Method of statement of testing and commissioning of the system
shall be submitted for the Engineer’s approval. All testing records shall be noted on the
Manufacturer’s standard forms
B. Check the installation of Equipment, pipe lines and valves are approved by the Engineer
prior start-up.
C. Check the pipe lines are tested and approved by the Engineer prior start-up.
E. The domestic water filtration system shall be subject to testing and commissioning as per
manufacturer recommendations, local Authorities regulations and consultant / Hotel
Operator requirements
A. Water samples shall draw on site prior and post filtration system and sent for third party
laboratory for analysis in order to verify the proper performance of the filtration system.
B. Third party Laboratory chemical analysis and bacterial reports shall be analyzed based on
M/s Kahramaa drinking water quality requirement 2014 edition as well as WHO standard
and EU guidelines.
C. After satisfaction of the performance testing for the filtration system, Water sample shall be
drawn on site by the specialist contractor / supplier and witnessed by the Engineer. Analysis
reports shall submitted for the Engineer’s perusal and approval.
A. The Contractor and / or the specialist contractor shall keep the system in operation after the
system approved from the Engineer in order to avoid water contamination and algae growth.
Chemical to be injected continuously and the filtration system shall run regularly to
maintaining the water quality as per above said parameters.
B. After testing approval from the Engineer, the whole system shall run as a normal till the
takeover certificate issued by the Engineer. For this period, Chemicals to be provided under
the contractor expenses without additional cost to the client.
3.15 WARRANTIES
A. The Employer shall be furnished with guarantee and warranty certificates, duly registered
with the manufacturer.
B. All Filtration overall system of domestic water installed in this project shall have a minimum
warranty of five years of normal performing operation commenced from the takeover
Certificate issued by the Engineer and / or as per the contract as well as per standard
warranty whichever greater
C. During the warranty period, perform the periodic routine and preventive maintenance as per
the Equipment manufacturer’s requirement to verify its proper operation.
PART 1 GENERAL
1.2 SUMMARY
A. Work includes providing all materials, equipment accessories, services and tests necessary to
complete and make read of operation by owner.
B. All piping and equipment for recalculating, filtering, disinfecting and heating water in the
swimming pool.
1.3 SUBMITTALS
A. Detailed shop drawings indicating piping valves, pumps, gauges, flow meters, controls, etc.
Shop drawings shall show at least the following general categories of information:
1. Penetrations through floors, walls, and other structural members;
2. Plinth details.
3. Equipment positions and operating weights;
4. Entry positions, access routes, Maintenance allocated space ,weight of
equipment or components during delivery to site;
5. Services access openings;
6. Location, details of concealed/buried conduits, inserts, and pipes;
7. Temporary openings in floors/walls;
8. Detailed workshop and manufacturing drawings;
9. Equipment schedules;
10. Electrical wiring and control diagram;
11. General layout plans and sections (1:50 scale for plans and 1:20 scale for
sections);
12. Schematic / P&I (Piping and Instrumentations) diagram;
13. Support and mounting details and schedule;
14. Material/Component specifications;
15. Setting out dimensions and level; and
16. Interfacing BMS & FA (wherever applicable) details and co-ordination with
Engineering, structural and all installation Works.
17. Plant Configuration and Sequence of operation.
18. Bund wall for backwash line discharge.
D. When written instruction on items requiring maintenance and recommended spare parts list.
A. Manufacturer: Firms regularly engaged in the manufacture of equipment of the types and
capacities required, whose product have been in satisfactory use in similar service for not
less than five years. Provide products produced by a manufacturer listed as an accepted
manufacturer in this section.
B. Standard: Compliance with requirements is applicable, local codes, NEC, UL, NEMA,
IBEEE and ANSI standards pertaining to products. Provide products and components which
have been listed and labeled.
A. During the course of the Contract, the Contractor shall keep progressive record
drawings of all installation works.
E. The As-Built drawings must be checked and verified by the Contractor prior
submission to the Engineer for final Confirmation and Approval.
F. Prior to close any of false ceilings, the Partial As-built drawing for the
Particular area should be arranged by the Contractor and accepted by the
Engineer.
G. The Contractor shall submit three /3 set of Hard copies (prints) and One/1
AutoCad copy on CD for each As-Built drawings submitted for the Engineer’s
review and approval.
H. No final payment shall be made until the As-built drawings are completed in all
respects and approved by the Engineer.
I. Indicate the following on the lower right hand corner of each As-Built
drawings:
vii- Number all pages and drawings in product data Brochures consecutively
from beginning to end.
2. Within one month after notice to proceed by the Project Manager, submit a
complete typed list of all equipment manufacturers and material suppliers for
the equipment proposed for this project, as well as names of all subcontractors.
3. Within one month after notice to proceed by the Project Manager, prepare an
index of all submittals for the project. Include a submittal identification number,
a cross-reference to the Specification sections or Drawing number, and an item
description. Prefix the submittal identification number by the Specification
sections to which they apply. Indicate on each submittal, the submittal
identification number in addition to the other data specified.
4. After the Contract is awarded, obtain complete shop drawings, product data
and samples from the manufacturers, supplier’s vendors, and all subcontractors,
for all materials and equipment as specified. Submit data and details of such
materials and equipment for review. Prior to submission, certify that the shop
drawings, product data and samples are in compliance with the Contract
Documents. Check all materials and equipment upon their arrival on the job site
and verify their compliance with the Contract Documents. Modify any work,
which proceeds prior to receiving accepted shop drawings as required to
comply with the Contract Documents and the shop drawings.
5. A minimum period of Fifteen /15 days from the date of receiving the
submittal and / or as per the Contract documents, exclusive of transmittal time,
will be required in the Consultant’s office each time a shop drawing, product
data and/or samples are submitted for review. A minimum of Twenty one /21
days from the date of receiving the submittal and / or as per the contract
documents required for review the Operation and Maintenance Manuals.
6. Submit three prints / hard copies (prints) and one AutoCad on CD of all
drawings. Submit three copies of manufacturer’s product submittals.
B. Review of submittals is for general compliance with the design concept and
Contract Documents. Comments or absence of comments shall not relieve the
Contractor from compliance with the Contract Documentations. The Contractor
remains solely responsible for details and accuracy, for confirming and for co-
ordinating the work with that of other trades. The Contractor is not relieved of
the responsibility for dimensions or errors that may be contained on
submissions, or for deviations from the requirements of the Contract
Documentations.
3. Include dimensional data for roughing in and installation and technical data
sufficient to verify that equipment meets the requirements of the Contract
Documents. Include wiring, piping and service connection data.
5. Unless the above information is included, the submittal will be returned for
re-submission. Re-submittals of product data or brochures shall include a cover
letter summarizing the corrections made in response to the review comments.
E. Maintain a complete set of reviewed and stamped shop drawings and product
data on site.
F. For Material and Equipment submittals, the Contractor shall provide full
compliance statement to the Specifications. Full Comparison between the
proposed and specified itemes in case of the material deviates from the
specified. At any Case, the propsed item/(s) shall be higher quality and / or
equal to the specified item/(s).
H. Indicate the following on the lower right hand corner of each shop drawing and
on the front cover of each product data brochure cover:
vii- Number all pages and drawings in product data Brochures consecutively
from beginning to end.
PART 2 PRODUCTS
2.1 MANUFACTURERS
2.2 FILTERS
A. Type
1. High flow rate, sand filter, pressure type, designed for specified filtration
rate and operating pressure and hydrostatically tested at factory to specified
test pressure. Quality of filtrate to be guaranteed to be in the 2 micron range.
B. Operation
1. High grade tank steel welded internally and externally and of adequate
thickness for specified operating and test pressure.
E. Aaccessories
a. Standard size manhole on top dished head with boiler type cover.
b. Four jack type supports individually adjustable for filter level adjustment and of
adequate strength to carry filter and contents.
c. Automatic air release valve on top dished head.
d. Gauge panel of cast bronze with two 100 mm minimum diameter dial pressure
gauges connected with copper tubes to filter inlet and outlet connections.
e. Filter drain valve.
f. Substantial lifting lugs.
F. Paint
1. Supply filters painted inside and outside with two coats of chemical resistant
epoxy paint.
G. Filter media
H. Filter media
I. Filter media
1. To be graded rock and gravel to fine sand from bottom up, in layers of
thickness to manufacturer's recommendations.
1. Clean, hard, round stones with average specific gravity of not less than 2.5,
free from shale, mica, clay, sandstone, sand, loam or other impurities.
Gravel is not to have more than 2% by weight of thin, flat or elongated
pieces.
K. Sand
1. Hard, durable grains of round or sub angular silica sand, free from clay, loam,
dirt and organic matter. Not more than 1% to be flat particles. Sand is to
meet screen requirements given in the following table and have effective size
of 0.35 to 0.45 mm and uniformity coefficient of 1.45 to 1.69.
A. Generally
B. Inlet fittings
1. Underground type with outer face fixable in any position for regulating flow
of water into pool, with 50 mm IPS female threaded connection.
C. No-leak flanges
1. Pipe spool with center flange and gussets, with 50 mm IPS female threaded
pipe connections at both ends and fitted to inlet fittings within concrete wall
of pool.
D. Gutter drains
E. Main drains
1. Square grate and frame anti vortex type to cover sumps. Grate is to fit frame
closely and be flush at surface.
F. Wanchors
1. For securing ladders and are to be embedded, flush type, with integral
anchor flange and webs, cast bronze inwardly tapering body with removable
bronze locking wedge and stainless steel draw bolt and washer and suitable
for use with 48 mm OD tube or 40 mm IPS pipe.
G. Escutcheons
1. Used with each wedge anchor are to be specifically designed for use with
wedge anchor. They are to be cast bronze with polished chrome finish and
fitted with locking screws.
H. Underwater lights
1. Cooper and brass appear shall be the selected material for light body and
niche, and silicon bronze for the light rings.
A. Ladders
C. Vacuum cleaner
1. Hard ware plastic cleaning bush 50 m working width, curved head and
adjustable wheels, suitable for use with 50 mm vacuum hose and with 15 m
of 50 mm white, corrugated, floating, flexible plastic hose with formed
polyethylene ends and 4.8 m long x 32 mm diameter anodized aluminum
telescopic handle complete with bolts and wing nuts.
2. Hose to wall fitting to connect vacuum hose to vacuum fitting is to be solid
aluminum with 25 mm IPS male thread one end and 25 mm hose sleeve
other end.
3. Telescopic handles to be anodized aluminum consisting of two concentric
tube sections that can telescope from 2.4 m to 4.8 m, with positive locking
device. They are to be 32 mm diameter and fluted for added strength. Inner
tube to be 29 mm diameter drilled for two 6 mm mounting bolts at 76 mm
centers and with bolts and wing nuts.
D. Algae brushes
E. Wall brushes
1. 450 mm long with curved ends, consisting of four dense rows of 29 mm long
nylon bristles permanently set in strong molded synthetic back reinforced
with extruded aluminum section. Die-cast aluminum handle holder with two
punched holes is to be securely attached to back.
F. Leafe rake
1. Synthetic fiber mesh screen set in plastic covered aluminum frame with
aluminum tube handle attachment and 25 mm OD anodized aluminum fluted
handle.
2.6 SUNDRIES
A. Strainers
1. Heavy cast bronze with clear plastic or Pyrex cylinder with bottom 50 mm
male threaded connections for easy removal.
C. Venturi tube
1. Heavy duty, close grain cast iron, with flanged ends, with two 20 mm IPS
tapped holes in side of body for pressure differential connections.
1. For checking pH, free residual chlorine, Alkalinity and Calcium Hardness of
pool water to be complete with Electronic Pool Tester (Photometer 6 in 1
kit), test tablets, operating instructions and carrying case. At any case time,
the amount shall be within the recommended allowable limits were
mentioned below.
2. The free residual chlorine shall be tested at shallow and deep end at least two
times a day (directly after shock dosing and 3.30PM) till the free residual
chlorine in the pool during shock dosing drops to 1.5 ppm.
3. The pH and free residual chlorine shall be tested at shallow and deep end at
least three times a day (8.30 AM, 12.30PM and 3.30PM) for three days
period normal operation test.
4. Total Alkalinity, cyanuric Acid and Calcium Hardness are to be tested at
shallow and deep end in conjunction with PH and Free residual chlorine at
least Two times for three days period normal operation test.
5. Add the chemical and set the Controller in order to achieve the mentioned
below allowable and recommended limits.
2.7 PUMPS
A. Motors: Supply pumps complete with electric motors. Horizontal base mounted pumps to
have motor mounted on common cast iron or steel base properly aligned at factory.
B. Shaft packing or mechanical seal: to be compatible with pump design and nature of liquid
pumped, in accordance with manufacturer's recommendations.
D. Plugged connections:to be provided for casing vent, drain and suction and discharge pressure
gauges.
E. Operating point of flow and head: is to fall near point of maximum efficiency obtained from
manufacturer's published data. Do not select pumps to operate near the end of their curve.
F. Horsepower rating of electric motor: is to ensure non- overloading throughout capacity range
of pump.
G. Electric motors: to be supplied for available current. Speed is not to exceed 1450 rpm unless
otherwise specified.
H. SUBMISSIONS
1. submit the following for approval for each pump prior to shipment:
a. certified performance curves showing job number, customer, customer order
number, pump designation number shown on the Drawings, date of manufac-
ture, model number, pump size, impeller diameter, impeller type, maximum im-
peller diameter pump can accommodate, rpm, flow- head characteristic curve,
consumed horsepower curve, pump efficiency curve parts numbers and parts
lists.
2. Outline dimensional drawing showing overall dimensions, location of
foundation bolt holes and size, location and rating of suction and discharge
nozzels.
3. Recommended list of spare parts.
4. Installation, operation and maintenance instruction manual.
5. Details and wiring diagrams of pump controllers, starters, controls or other
electrical device or accessories.
6. Special instructions for installation and connection of each electrical device,
control or accessories.
7. Motor data such as make, model number, serial number, horsepower rating,
rpm, voltage, phase, frequency, class of insulation, allowable temperature
rise, full load amperes and locked rotor amperes.
8. Starter data such as make, model number, size, heater sizes, ampere rating,
line voltage, control voltage and frequency.
A. Type: Horizontal, base mounted, end suction, single stage, centrifugal type, directly
connected to motor through heavy duty flexible coupling, with heavy gauge coupling guard.
B. Base: Pump and motor to be mounted on common cast iron base reinforced against
deflection, with drip rim, drain tapping, bolt holes and grouting hole.
C. Pump casing: high tensile strength close grain cast iron with smooth waterways, register
fitted and bolted to bearing frame for permanent alignment, with bronze wear rings and
tapped and plugged bottom drain and top vent connections.
D. Impeller: bronze, enclosed type, fitted to shaft with key and locked in place.
E. Shaft: one piece stainless steel, sized to carry axial and radial thrust with minimum
deflection.
F. Mechanical seal: Ni-resist face, carbon washer and stainless steel metal parts.
G. Bearings: Pump rotating element to be supported by two heavy duty grease lubricated ball
bearings mounted in heavy iron frame with supports to base for maximum rigidity.
H. Electric motor: totally enclosed, squirrel cage, induction type with permanently lubricated
and sealed ball bearings.
2.9 UV DISINFECTION
B. The UV treatment unit shall have the bypass line to enable isolation for the recirculation line
and permit essential maintenance without shutting down the system.
A. Flanges: to be of same pressure rating, facing, drilling and thickness as mating flanges on
valves, accessories and equipment.
B. Gaskets: for flat face flanges to be full face ring type with punched holes.
C. Pressures PVC pipe: to be sch 40 and comply with ASTM D1785, and shall withstand a
minimum continuous 30º c water flow rate.
D. Pressure PVC fittings: integral parallel sockets with solvent welded joints for pipes up to 65
mm, and couplers with rubber sealing rings for pipes 82 mm and larger.
E. Sealing rings on PVC pipes to provide for expansion and contraction to be rubber to BS 2494
Part 2.
F. Storage: handle pipes with care. Store in the shade. Support along entire length on level
ground free from loose stones. Do not stack more than three layers high. Place sockets at
alternate ends of stack and protruding beyond pipes. Stake stacks to prevent movement. For
long term storage provide pipe racks with continuous supports. Comply with manufacturer's
recommendations for storage.
G. Pipes and fittings: to have cleanly cut square ends. Pipes to be reasonably straight.
H. Joints: make rubber ring joints or welded solvent joints in accordance with manufacturer's
instructions. Use solvent made and supplied by manufacturer.
I. Underground pipes: anchor at changes in direction and at valves and stop ends.
J. Underground pipes excavation: trench is not to be open too far in advance of pipe laying and
then backfilled as soon as possible.
K. Underground pipe bedding: use free draining sand, gravel, loam or soil. Compact fill firmly
between side of pipe and trench. Bedding to be thoroughly compacted in layers not
exceeding 150 mm to give uniform bed. Lay pipes directly on bedding. Do not use brick or
hard material under pipe. Further bedding material to be placed around pipe and thoroughly
compacted in 75 mm layers by careful tamping.
L. Underground pipes: backfill trench above pipe in layers 300mm thick each layer well
rammed.
A. Wall and / or floor mounted manufactured system control panel, RAL 7032 powder coated,
IP 55 ingress protection, incorporating the required and necessary switches, transformer
contactors, indication lamps, adjustable thermal overloads, circuit breakers, controllers, etc .
4. Channel Plates:
A. Dosing Pump:
1. Calcium Hypochlorite (disinfectant), Sodium Bisulphate (PH Regulator):
Diaphragm type, continues interlocks with filtration pump /(s), synchronous
motor driven, 12 LPH, power 20 watt max, 100:1 turndown, completed with
foot valve, multifunction valve, 6/9mm dosing tubing with suction filter,
control cable, and wall bracket
2. PAC / Aluminum Bisulphate Coagulant / Flocculent: 28mm Diaphragm
type, stepper motor driven, side fitted control panel with function valve and
wall bracket, 1.8 LPH, 1000:1 turndown, manual control , continues
interlocks with filtration pump /(s), PE 4/6mm suction discharge and venting
dosing tubing with suction filter , power 20 watt max., control cable, and
wall bracket
B. Injector:
1. Calcium Hypochlorite (disinfectant) and Sodium Bisulphate (PH Regulator):
Withdrwal solution lance with isolating ball valve, Lacing ending flapper
valve, pipe mounting R ¾” (BSPT male), NRV ½” BSP m inj / NRV, feed
connection 6/9 mm od tubing, injector saddle DN 150 bronze pipe saddle
tapped Rc ½”.
2. PAC / Aluminum Bisulphate Coagulant / Flocculent: R ½” injection pipe
with spring loaded NRV for 4/6 mm tubing, injector saddle DN 150 bronze
pipe saddle tapped Rc ½”
A. Provide auxiliary contacts in swimming pool water system control panel for interface to
building automation system. Include the necessary and required interfacing recommended
by the manufacture’s supplier, the Engineer and / or the Hotel Operator :
B. All activities as per I/O points shall be monitored on Dynamic colour graphics and graphic
control as prescribed in related Division. Submit Graphics for Engineer’s approval.
PART 4 EXECUTION
4.1 INSTALLATION
A. Install piping, fittings and jointing as indicated in accordance with manufacturer’s written
instructions, applicable codes and regulations and in accordance with recognized industry
particles to ensure that installation complies with the requirements and serves intended
function.
B. Coordinate as necessary to interface installation of piping, fittings and jointing with other
work.
C. Do not run piping through electric rooms, electric spaces, electric closets and other electrical
or electronic equipment spaces.
D. Clean exterior surfaces of installed piping system of super flow materials and prepare for
application of specified coatings (if any). Flush out piping system with clean water before
proceeding with required tests. Inspect each run of each system for completion of joints,
supports and accessory items.
E. Install equipment so that sufficient clearance is provided to permit adequate serving of the
component.
H. Provide three complete sets of printed instructions for the proper care and operation of the
swimming pool.
A. Prior startup the piping leak test, Method of statement for piping leak testing shall be
submitted for the Engineer’s approval. All testing records shall be noted on the
Manufacturer’s standard forms.
B. All Testing shall offer for the Engineer’s witnessing and approval
C. Check the installation of the valves, piping are approved by the Engineer prior conducted the
test.
E. Test piping system before insulation is installed wherever feasible and removes control
devices before testing.
F. Test each natural section of each piping system independently but do not use piping system
valves to isolate sections where test pressure exceeds valves pressure rating. Fill each section
with water and pressurize for indicated pressure and time as follows:
1. Test period: 2 hours
2. Pressure: For long run of schedule 40 pipe, 150 psi, except where fittings are
lower class or pressure rating; for each piping system, 150% of operating
pressure indicated but not less than 25 psi test pressure.
G. Observe each test section for leakage at end of test period. Test fails if leakage is observed or
if pressure drop exceed 5% of test pressure.
H. Repair or replace piping system section which fail required piping test. Do not use chemical,
stop-length compounds, mastics or other temporary repair methods.
I. All pool re-circulating, return and supply piping shall be tested at a hydrostatic pressure of
100 psi, vacuum piping tested at 50 psi which pressure shall be maintained without pumping
for a period of four (4) hours.
J. All gravity drainage piping, shall be tested under hydrostatic pressure corresponding to a
head of at least ten (10) feet of water above the highest point of the piping tested. Test
pressure shall be maintained without loss for a period of (4) hours.
A. Chlorine Controller:
1. Prior to utilize the dosing system, The Controller shall be calibrated as per
Manufacturer’s recommendations. Chlorine level amount being shown on
the controller display shall be verified with the same pool water by
photometer test kit. Adjust the value shown on the controller display based
from the reading being shown on the Photometer display accordingly
B. PH Controller:
1. Prior to utilize the dosing system, The Controller shall be calibrated as per
Manufacturer’s recommendations. Probe to be immersed with PH -7 and
PH-9 standard buffer solution to compare with the value being displayed on
the controller. Adjust the value shown on the controller display base on the
buffer solution concentration accordingly.
A. Contractor Must arrange the necessary and required testing Devices / instruments / tools with
a valid due calibration along with its Calibration Certificate and all of necessary pertinent
documentations during the testing inspection of the system with the Engineer and the
Operator as well.
A. The water sample station (water sample collecting discharge, water filter, Union, Isolating
Valves and by pass line) shall be provided in the network inside the plantroom at location as
recommended by the system manufacture for further sample collection purpose.
A. The system shall have flocculation / coagulant feeding facility in order to solve any further
water clarity problems and / or to avoid draining the entire swimming pool water in case of
sandstorm climate.
A. Install pool fittings and piping embedded under pool and in concrete walls of pool and plant
room during concreting.
4.10 CONCERNING
A. member of the setting crew is to be present during concreting to check grade and alignment
of embedded fittings and pipe work and to correct any displacement before concrete has
hardened.
4.11 LAY
A. Embedded fittings and piping to proper elevation, line and grade and support and anchor
during concreting.
A. Provide on pipe connections to inlet and drain fittings within concrete pool wall.
A. Through plant room walls to have no-leak flanges fitted centrally in wall.
4.15 EQUIPMENT
4.16 STRAINERS
a. Suction pressure gauge: 100 mm dial gauge diameter, (- 0.10 to 1.0 bar) range,
stainless steel, Bourdon type, glycerin filled.
b. Discharge pressure gauge: 100 mm dial gauge diameter, (0 to 4.0 bars) range,
stainless steel, Bourdon type, glycerin filled.
ii- Primary and secondary inlet and outlet of each heat exchanger.
a. Primary inlet pressure gauge: 100 mm dial gauge diameter, (0.10 to 4.0 bar) range,
stainless steel, Bourdon type, glycerin.
b. Primary outlet pressure gauge: 100 mm dial gauge diameter, (0 to 7.0 bar) range,
stainless steel, Bourdon type, glycerin.
c. Secondary inlet pressure gauge: 100 mm dial gauge diameter, (0 to 4.0 bar) range,
stainless steel, Bourdon type, glycerin.
d. Secondary outlet pressure gauge: 100 mm dial gauge diameter, (0 to 4.0 bar)
range, stainless steel, Bourdon type, glycerin.
4.18 THERMOMETER
A. The Area floor drain for filter backwash line discharge shall have a concrete up-stand / bund
wall to avoid the water floor flood during the backwash. Bund wall size and height shall be
constructed to accommodate the water volume and water velocity during backwash without
floor flooding and / or water splashing on the floor.
B. Water proof recommended type shall be applied to the Bund wall wet surfaces.
A. The chemical drums shall have its own bund wall as prescribed above in “DOSING
CONTROL AND ANALYZING”.
B. Water proof recommended type shall be applied to the Bund wall inner surfaces.
A. Install on backwash pipe from each filter to provide visual check of backwash flow.
A. Upon the completion of waterproofing of the pool, the pool shall be offered for flood test.
4.24 SHOCK DOSING / SUPER CHLORINATION AND POOL TILES ACID WASHING:
A. Prior to fill the pool with fresh water, the pool shall be clean properly with acid. After
satisfaction of tile cleaning and acceptance by the Engineer, the contractor shall drain and all
of residual waste acid and ensure all tile grouting in a good condition.
B. Upon Completion of filling the pool by fresh water, the shock dosage with minimum
chlorine initial concentration of 9.0 ppm shall be demonstrated and witness by the Engineer.
C. During the shock dosage, the filter multi-port manual valve shall be on recirculation position
and dosing pumps and controller are in off mode.
A. Make chemical and bacterial analysis in accordance with procedures recommended in the
Standard Methods of the Examination of Water, Sewage and Industrial Wastes of the
American Public Health Association and / or SPATA standards in so far as these methods are
applicable to swimming pool water.
i- After satisfaction of the performance and functionality of pool Equipment and approved
by the Engineer, the water sample shall be drawn on site from the pool water and to
send to third part Laboratory for chemistry and bacteriological / bacterial analysis.
The allowable / permitted limits as follow:
PH 7.4 – 7.6
ii- Water sample analysis reports comparing against the above said water chemistry and
biological allowable limits shall send to the Engineer for review and approval.
B. Water to be clear: When pool is in use, water is to be sufficiently clear to permit a 150 mm
diameter black disc on a white background placed on bottom of pool to be clearly visible
from side walls of pool at all distances up to 10 m measured from a line drawn across the
disc.
Water to be sterile: When pool is in use not more than 15% of samples of water taken
covering any considerable period are to contain more than 200 bacteria per milliliter or are to
show positive test in any of five 10 ml samples of water. Primary fermentation tubes
showing gas should be confirmed.
A. Carry out tests as necessary and as directed to demonstrate that equipment meets design
requirements as noted on the Drawings , in the Specification and in accordance with the
approved Method of Statements.
B. Prior startup the system, Method of statement of testing and commissioning of the system
shall be submitted for the Engineer’s approval. All testing records shall be noted on the
Manufacturer’s standard forms.
C. Manufacturer’s and / or equipment supplies authorized representative shall spend not less
than 5 consecutive days on job site during and after installation to check equipment, plant it
in operation, balance and adjust all equipment, and inform the Engineer and the owner’s
representative in its operation, in addition, the service of the manufacturer’s and/or
equipment suppliers authorized representative shall be provided for two days during the first
year of operation.
D. All Testing shall offer for the Engineer’s witnessing and approval
E. Check the installation of the Equipment, valves, piping and instruments are approved by the
Engineer prior carry-out the start-up.
F. All instrument / tools will utilize for testing shall have a valid due calibration and calibration
certificate.
A. The Contractor and / or the specialist contractor shall keep the system in operation after the
system approved from the Engineer in order to avoid water contamination and algae growth.
Chemical to be injected continuously and the filtration system shall run regularly to
maintaining the water quality as per above said parameters.
B. After testing approval from the Engineer, the whole system shall run as a normal till the
takeover certificate issued by the Engineer. For this period, Chemicals to be provided under
the contractor expenses without additional cost to the client.
A. The Contractor is full responsible to arrange and perform any necessary testing
requested by the Hotel Operator without any additional cost to the Client.
C. Contractor shall action all of the Hotel Operator’s comments that are critical for
Hotel Operation prior the issuance of take-over certificate by the Engineer.
D. At the time of handover to the operator of the Works after the Taking Over
Certificate, the whole installation shall be in ‘as-new’ conditions. The
Contractor shall, during the course of the Contract, protect all plant and
equipment and shall restore/repaint as necessary before handover of the installa-
tion.
4.29 WARRANTIES
A. The Contractor shall warrant that the capacity, rating or duty of all equipment
used in the installation shall not be less than the performance specified on the
Drawing or in the Specification when operating under the specified conditions
and in accordance with the equipment manufacturer’s instructions. Any
equipment/system not meeting this requirement shall be rejected.
B. Both main and Specialist Contractors / supplier shall provide written guarantee
that when pool equipment is operated in accordance with manufacturer's
instructions, pool water will be crystal clear, sparkling bright, free from
suspended matter and completely sterilized at all times.
E. All Swimming Pool overall system installed in this project shall have a
minimum warranty of five years of normal performing operation commenced
from the takeover Certificate issued by the Engineer and / or as per the contract
as well as per the standard warranty whichever is greater.
F. During the warranty period, perform the periodic routine and preventive
maintenance as per the Equipment manufacturer’s requirement to verify its
proper operation.
A. The Contractor is obliged to provide a written guarantee that the spare parts for
the Works or other equal and approved spare parts will be available for a period
of fifteen (15) years beyond the issue date of Taking over Certificate for the
Works. Failure to provide the guarantee may, at the sole discretion of the
Employer, result in the Tender being rejected.
B. The Contractor to liaise with the Engineer to determine the recommended lists
of spare parts for three years operation and maintenance covering all systems
and sub-systems of the specification. This list will be subject to the Engineer’s
discretion; by which the Contractor is committed to order these spare parts in
part or in whole at any time up to the issue of the Performance Certificate
without any cost escalation.
F. Spare Parts as mentioned in “E” above shall be supplied and handed-over by the
Contractor under his expenses without additional cost to the Employer prior
Take over Certificate.
G. Provide spare parts and maintenance equipment for all pumps, control panel etc.
requiring maintenance and replacement.
H. Provide two new complete sets of tools and repairing kits for the proper
operation, routine maintenance and adjustment of all components and
equipment.
4.31 TRAINING
A. The Tenderer shall submit a schedule in the Tender submission list all works
and systems for which the Contractor has to provide training. The Schedule
should have information include list of recommended training courses within
each works/systems, location of the training courses (local/overseas). Trainers
details (from the manufacturers premises where applicable), courses duration,
unit rate of the training in per head basis.
B. The Contractor shall provide sufficient and proper instructions to the trainees
nominated by the Employer in the commissioning, operation, maintenance,
servicing and trouble-shooting of the various plant and systems.
C. The Contractor shall provide training facilities and training courses and ensure
that the trainees nominated by the Employer / Hotel Operator will acquire full
knowledge and appreciation of all aspects of the day to day operation,
breakdown and routine maintenance, and fault diagnosis of all plant, equipment
and system installed under this Contract. Detailed syllabus and the timing of the
training courses shall be submitted.
D. The Trainees nominated by the Employer will attend the training courses, and
the Contractor shall allow them reasonable access to technical information and
documentation required for proper operation and maintenance. The Contractor
shall also explain this information and documentation to allow the trainees to
become fully conversant with all aspects of the systems.
B. The Contractor shall also refer to other requirements in the relevant clauses of
the Contract.
1. Before the Taking Over Certificate is issued, the following must be complet-
ed:
a. Operation and Maintenance Instructions Manual, test data and “as-built” draw-
ings must be submitted and approved by the Engineer. Computer “soft” copies
of these manuals and drawings shall also be submitted.
b. The Employer or his representative /Hotel Operator must be fully instructed in
the operation of the system. A written acknowledgment from the Employer
shall be required.
c. All tools, Repairing kits and spares shall be handed over. A written acknowl-
edgment from the Employer shall be required.
d. Written confirmation from the Contractor to indicate the installation is complet-
ed according to Performance Requirement.
e. Submit and obtain the approval by the Engineer. Maintenance schedule for the
installation during the Maintenance and Defect Notification Period.
A. Immediately answering the breakdown calls, the Contractor shall attend to such
calls within a maximum time limit of three hours during Night and Two hours
during Daytime of receiving such Calls.
B. During the defects warranty period, the Contractor shall at his own cost repair
all faults or defects in the works which in the opinion of the Engineer are due to
faulty materials and workmanship.
C. If the Contractor fails to remedy such faults and or defects within a reasonable
time, the Employer may deploy other Contractor to do such work under the
expenses of the contractor and without prejudice to such other rights as the
Employer may have under the contract.
PART 1 - GENERAL
A Drawings and general provisions of the Contract, including General and Supplementary
Conditions, apply to this Section.
1.2 SUMMARY
A This Section includes the following conventional plumbing fixtures and related components:
1.3 DEFINITIONS
B Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people
with disabilities.
E Fitting: Device that controls the flow of water into or out of the plumbing fixture. Fittings
specified in this Section include supplies and stops, faucets and spouts, shower heads and tub
spouts, drains and tailpieces, and traps and waste pipes. Piping and general-duty valves are
included where indicated.
1.4 SUBMITTALS
A Product Data: For each type of plumbing fixture indicated. Include selected fixture and
trim, fittings, accessories, appliances, appurtenances, equipment, and supports. Indicate
materials and finishes, dimensions, construction details, and flow-control rates.
C Operation and Maintenance Data: For plumbing fixtures to include in emergency, operation,
and maintenance manuals.
A Source Limitations: Obtain plumbing fixtures, faucets, and other components of each
category through one source from a single manufacturer.
1. Exception: If fixtures, faucets, or other components are not available from a single
manufacturer, obtain similar products from other manufacturers specified for that
category.
E NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health
Effects," for fixture materials that will be in contact with potable water.
F Select combinations of fixtures and trim, faucets, fittings, and other components that are
compatible.
G Comply with the following applicable standards and other requirements specified for
plumbing fixtures:
H Comply with the following applicable standards and other requirements specified for
lavatory and sink faucets:
1. Backflow Protection Devices for Faucets with Side Spray: ASME A112.18.3M.
2. Backflow Protection Devices for Faucets with Hose-Thread Outlet:
ASME A112.18.3M.
3. Faucets: ASME A112.18.1.
4. Hose-Connection Vacuum Breakers: ASSE 1011.
5. Hose-Coupling Threads: ASME B1.20.7.
6. Integral, Atmospheric Vacuum Breakers: ASSE 1001.
7. Pipe Threads: ASME B1.20.1.
8. Supply Fittings: ASME A112.18.1.
9. Brass Waste Fittings: ASME A112.18.2.
I Comply with the following applicable standards and other requirements specified for bathtub
and shower faucets:
J Comply with the following applicable standards and other requirements specified for
miscellaneous fittings:
K Comply with the following applicable standards and other requirements specified for
miscellaneous components:
1.6 WARRANTY
2. Warranty Period for Commercial Applications: One & Three year(s) from date of
Substantial Completion.
A Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
1. Faucet Washers and O-Rings: Equal to 10 percent of amount of each type and size
installed.
2. Faucet Cartridges and O-Rings: Equal to 5 percent of amount of each type and size
installed.
3. Flushometer Valve, Repair Kits: Equal to 10 percent of amount of each type installed,
but no fewer than 12 of each type.
4. Provide hinged-top wood or metal box, or individual metal boxes, with separate
compartments for each type and size of extra materials listed above.
5. Flushometer Tank, Repair Kits: Equal to 5 percent of amount of each type installed,
but no fewer than 2 of each type.
6. Water-Closet Tank, Repair Kits: Equal to 5 percent of amount of each type installed.
7. Toilet Seats: Equal to 5 percent of amount of each type installed.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
a. Bowl Type: Elongated with siphon-jet design. Include bolt caps matching fix-
ture.
b. Height: Standard Accessible.
c. Flush range: Low flush as per GSAS (3.75 LPF).
d. Color: As per architectural package.
1. Identical as type (WC1) and provided with heavy duty chrome plated brass back
and side grab bars for physical challenged individuals.
2. Style: Flush meter valve.
2.3 LAVATORIES
A Lavatories, (LAV1):
a. Type: Self-rimming.
b. Lavatory Size: as indicate in architectural drawings.
c. Faucet flow rate for public Lavatories: as per GSAS (1.5 LPM)
d. Faucet (tap) aerators 1.5 LPM outlet accepted by the Architect shall be fitted to
the tap.
e. Faucet Hole Punching: One hole.
f. Faucet Hole Location: Top.
g. Color: As per architectural package.
h. Faucet: Lavatory with pop-up waste.
i. Supplies: DN 10 chrome-plated copper with stops.
j. Drain Piping: DN 32 chrome-plated, cast-brass P-trap; (DN 32), 1.1-mm thick
tubular brass waste to wall; and wall escutcheon.
k. Drain Piping: Schedule 40 ABS or PVC, (DN 32) P-trap; (DN 32), tubular
waste to wall; and wall escutcheon.
B Lavatories, (LAV2):
2.4 SHOWERS
B. Shower (Two Valve Mixer with Thermostatic Mixing Valves): As indicated below.
1. Thermostatic mixing valve with lever handle, individual angle check stops, GPM
shower head with adjustable spray, arm and flange.
2. Flow rate for private shower : as per GSAS (5.7 LPM).
3. Shower head equipped with vacuum flow valve / flow control.
2.5 SINKS
1. Description: White color enameled fire clay sink with stainless steel bucket grating
and hard wood rim as model selected by interior designer, or approved equal.
a. Chrome plated, 40 mm waste fitting with chain stay, chain and plug screw pipe
connection with chrome plated anti-syphon tubular trap.
PART 3 - EXECUTION
3.1 EXAMINATION
A Examine roughing-in of water supply and sanitary drainage and vent piping systems to verify
actual locations of piping connections before plumbing fixture installation.
B Examine cabinets, counters, floors, and walls for suitable conditions where fixtures will be
installed.
C Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
1. Use carrier supports with waste fitting and seal for back-outlet fixtures.
2. Use carrier supports without waste fitting for fixtures with tubular waste piping.
3. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.
C Install back-outlet, wall-mounting fixtures onto waste fitting seals and attach to supports.
F Install floor-mounting, back-outlet water closets attached to building floor substrate and wall
bracket and onto waste fitting seals.
I Install water-supply piping with stop on each supply to each fixture to be connected to water
distribution piping. Attach supplies to supports or substrate within pipe spaces behind
fixtures. Install stops in locations where they can be easily reached for operation.
1. Exception: Use ball, gate, or globe valves if supply stops are not specified with
fixture. Valves are specified in Division 22 Section "General-Duty Valves for
Plumbing Piping."
J Install trap and tubular waste piping on drain outlet of each fixture to be directly connected
to sanitary drainage system.
K Install tubular waste piping on drain outlet of each fixture to be indirectly connected to
drainage system.
L Install tanks for accessible, tank-type water closets with lever handle mounted on wide side
of compartment.
O Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets
are not available with required rates and patterns. Include adapters if required.
P Install water-supply flow-control fittings with specified flow rates in fixture supplies at stop
valves.
Q Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if
faucets are not available with required rates and patterns. Include adapters if required.
R Install shower flow-control fittings with specified maximum flow rates in shower arms.
T Install escutcheons at piping wall ceiling penetrations in exposed, finished locations and
within cabinets and millwork. Use deep-pattern escutcheons if required to conceal
protruding fittings. Escutcheons are specified in Division 22 Section "Common Work
Results for Plumbing."
U Set bathtubs & shower receptors in leveling bed of cement grout. Grout is specified in
Division 22 Section "Common Work Results for Plumbing."
V Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-part,
mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants are specified
in Division 07 Section "Joint Sealants."
3.3 CONNECTIONS
B Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent
piping. Use size fittings required to match fixtures.
C Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
A Verify that installed plumbing fixtures are categories and types specified for locations where
installed.
B Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified
components.
C Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components.
D Test installed fixtures after water systems are pressurized for proper operation. Replace
malfunctioning fixtures and components, then retest. Repeat procedure until units operate
properly.
3.5 ADJUSTING
A Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures,
fittings, and controls.
B Adjust water pressure at faucets and flushometer valves to produce proper flow and stream.
C Replace washers and seals of leaking and dripping faucets and stops.
3.6 CLEANING
A Clean fixtures, faucets, and other fittings with manufacturers' recommended cleaning
methods and materials. Do the following:
1. Remove faucet spouts and strainers, remove sediment and debris, and reinstall
strainers and spouts.
2. Remove sediment and debris from drains.
3.7 PROTECTION
B Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by
Ministry.
PART 1- GENERAL
3. Application Devices
8. Bubblers
15. Filters
16. Controllers
22. Miscellaneous
F. The contractor shall prepare the shop drawings showing but not limited to The Main
line, Laterals, solenoid valves, control wires route and numbers, Irrigation
Controllers, integrated dripper lines, on line drippers, Bubblers and flush valves.
2. The contractor shall submit for Engineer’s approval the technical information
and samples of the material he intends to use which should be in accordance
with the material specifications of this project.
3. It shall be the responsibility of the contractor specialist to ensure that the plant
and equipment supplied by them produces the desired results. The Specialist
shall include all equipment, materials, accessories, finishing materials etc.,
required so as to have a complete functional system. This shall include all
items of a minor nature necessary to complete the installation and usually
included in similar work whether or not specifically mentioned in the contract
documents.
5. The complete irrigation system for each site shall be fine-tuned to efficiently
and evenly irrigate all areas in accordance with the engineered design and shall
be complete in every respect. The system shall be set in operation and adjusted
to the satisfaction of the Engineer’s.
7. The contractor shall commission the irrigation system upon completing the
work and then shall be handed over.
8. The contractor and upon completing the work shall provide the Engineer with
four original sets of As-Built drawings accurately reflecting the executed works
and installation details.
9. The contractor shall upon completing the works provide the Engineer with
detailed Operation and Maintenance Manuals (With applicable Arabic
translations) in four originals. The manuals shall include but not limited to;
complete and marked literature of all products used on the project and its
reordering part numbers. It shall also include a list of the recommended spare
parts for a period of 5 years. It shall include original color print and softcopy of
the As Built drawings.
10.
11. The Engineer prior to issuing the Project Handing Over Certificate shall
approve the As-Built Drawings and the Operation & maintenance Manual.
1.3 REFERENCES
1. QCS 2010 - Section 28 specifications are applied unless conflicted with this
project specification. In case of a contradiction this project specification should
prevail.
4. ASTM D1785 - American standard for testing of material for PVC pipes.
5. ASTM D2219-02 - Specification for PVC insulation for wire and cable
6. ASTM B-3 - Bare soft and annealed copper un-insulated uncoated 14-4 AWG
solid wire.
9. BS: 1780 - Specification for bourdon tube pressure and vacuum gauges.
10. BS: 3505 - Specification for UPVC pressure pipes for cold potable water.
11. BS: 4346 - Joints and fittings for use with UPVC pressure pipes.
12. BS: 5150 - Specification for cast iron wedge and double disk gate valves for
general purposes.
13. BS: 5154 - Specification for copper alloy globe, globe stop and check, check
and gate valves for general purposes.
B. Where more than one applicable standards are specified or in case of differences
with this specification, use the most restrictive provisions and recommendation or as
directed by the engineer.
1.5 SUBMITTALS
A. Prior to start of any work at site the contractor has to approach all Service Authori-
ties in Qatar to get their no objection for the work included in this contract and rec-
ord drawings for their existing services. Copy of these drawings and no objection
certificate should be submitted to the Engineer before starting the actual work at
site.
Shop Drawings - The contractor to prepare the project shop drawings in 3 sets of
black hardcopies, one set colored hardcopy and a soft copy, which to be approved
by the Engineer representative prior to commencing installation work. The shop
drawings shall show but not limited to valves, control wires route and numbers, con-
trollers’ location and flow balancing.
Please note that the contractor to make detail survey of existing levels in the contract
area.
Trial pits should be taken at every 50 meter interval, mark all the existing services in
reference to the road edge & building line along with its depth from existing the
ground level & the proposed Landscape finish level. Contractor to check availability
of all the existing ducts that are marked on the tender drawings. Contractor to pro-
pose the route of Irrigation piping based this information. All this information re-
garding trial pits, existing and proposed levels, availability of existing ducts shall be
made available to the Engineer within mobilization period of the contract. All this
information shall be made available on hardcopy & in Digital format to the Engineer
as it is required for adjusting landscape and pipes/services alignment.
Any delay to provide the above-mentioned information regarding trial trenches, ex-
isting services & levels which affects the progress of works shall be the responsibil-
ity of the Contractor
The successful contractor shall submit shop drawings, for approval by the Engineer,
for the following:
1. In case of any conflict between contract drawings and any existing or future
services which may necessitate re-routing proposed irrigation Main or laterals,
the contractor has to prepare the shop drawings accordingly and submit it to the
Engineer for approval. This should be considered as integral part of the con-
tract.
2. The Pump /Filtration Chamber mechanical, electrical and civil works shop
drawings. Necessary modifications to the existing feeding chambers ( civil and
mechanical). Valve chambers including valves, pipe works and civil works.
Electrical control equipment with circuit diagrams.
3. Details of mainline, Profile drawings for Mainline, lateral pipes and other typi-
cal connections.
4. Wiring diagrams including conduits, pull boxes, sizing and calculations to veri-
fy that cable sizing is in accordance with Kahramaa regulations and equipment
manufacturer’s recommendations.
5. Electrical power and control wiring diagrams for irrigation controllers, field
wiring and grounding.
8. Detail of valve chambers and any modification to the existing feeding cham-
bers.
9. The approval shall not relieve the Contractor of any of his responsibility under
the contract for successful completion of the work
B. Products – The contractor shall submit for Engineer’s approval prior to commencing
installation works; the products he intends to use with all technical details and litera-
ture in accordance with the specifications below. Material submittal should includ-
ing all irrigation system component, fitting and accessories including but not limited
to warning tape, PVC cement and cleaner, wires, Teflon tape. A sample board
should be submitted for approval. A material submittal list and form is as per Table
#1 below.
Maintenance Manual and one softcopy with equipment reordering codes and litera-
ture.
D. As-Built Drawings- The contractor shall submit 3 sets of black hardcopies, one set
colored hardcopy and a soft copy of the complete project as-built drawings reflect-
ing the actual site installation.
E. Calculation: The contractor shall submit a friction loss calculation for the irrigation
system installed including a full system flow balance calculation.
F. Guarantees: The contractor should submit manufacturer and supplier material guar-
antees for materials submittal as specified in the material specification below.
G. All catalogue cuts, diagrams, samples, drawings and such other data may be re-
quired to demonstrate compliance with the specification.
TABLE #1: MATERIAL SUBMITAL LIST AND FORM
SUBMITTAL
DATES
ITE ABBREVIATIONS
DESCRIPTION
M#
SUBMITTAL
DATES
SOLENOID VALVES
QUICK COUPLING VALVE
100 MM GATE VALVE
GATE VALVE
CHECK VALVE
VALVE BOXES
PVC PIPES
PVC FITTINGS
PVC CEMENT
PVC CLEANER
DC ALUMINUM COVER
SHOP DRAWING SUBMITTAL
FLOW BALANCE SUBMITTAL
IRRIGATION PUMPS & Panels
SUBMERSIBLE PUMP
WATER TANKS
WATER COOLER
PART 2 – PRODUCTS
C. All primary distribution pipe fittings shall be solvent welded UPVC 16 bars.
F. Flexible Pipes for irrigation on line drippers shall be in the required sizes as shown
on the drawings and extruded from linear low density polyethylene version raw ma-
Newton Lusail School
Mechanical Specification - Rev. 00 328400 - 8
328400 – PLANTING IRRIGATION
terial. Pipes shall be resistant to algae and ultraviolet deterioration with Carbon
Black content not less than 2.25%.
G. Pipes and fittings manufacturer should be ISO certified with 5 years manufacturing
experience, test certificate from reputable labs should be available prior to material
ordering.
1. The spray pop-up sprinkler shall be equipped with an adjustable arc (25-360)
nozzle discharging at half circle as shown in design drawings.
2. The spray pop-up sprinkler nozzle shall automatically adjust the flow depend-
ing on the arc setting in order to have a matched precipitation rate.
3. The sprinkler shall have arc and radius reduction capability. It shall also be
possible to adjust arc and radius from the top of the riser assembly, using an
adjustment key.
4. The sprinkler shall have an inlet screen. The body and riser of the sprinkler
shall be constructed of non-corrodible, heavy duty A.B.S
6. Refer to design drawing for exact radius of coverage and flow needed for each
sprayer.
8. The sprinkler shall carry a one-year manufacturer and supplier exchange war-
ranty (not prorated).
1. The rotor pop-up sprinkler shall be of the gear-driven, closed case rotary type
or as specified in the design drawings.
2. The rotor pop-up sprinkler shall have a gear drive reversing or non-reversing
mechanism.
3. The rotor pop-up sprinkler shall be available with standard nozzles discharging
from .9 to 8.2 GPM.
6. The adjustable part circle unit shall be minutely adjustable from 40° to 360°.
The adjustable unit shall be adjustable in all phases of installation (i.e., before
installation, after installation while static and after installation while in opera-
tion).
7. The sprinkler shall have a constant rotation speed irrespective of the nozzle in-
stalled.
8. The sprinkler shall have a minimum of 4-inch (10 cm) pop-up stroke to bring
the rotating nozzle turret into a clean environment.
9. The sprinkler shall have a thick rubber cover firmly attached to the top of the
sprinkler riser.
10. The sprinkler shall be equipped with a drain check valve to prevent low head
drainage, and be capable of checking up to 10 feet (3, 0 m) in elevation change.
11. The sprinkler shall be serviceable after installation in the field by unscrewing
the body cap, removing the riser assembly, and extracting the inlet filter screen.
12. The body and riser of the sprinkler shall be constructed of non-corrodible,
heavy-duty A.B.S.
13. It shall have a stainless steel spring for positive retraction of the riser when ir-
rigation is complete.
14. Sprinkler flow, radius coverage, and operating pressure should be as per design
drawings.
15. The sprinkler shall carry a one-year manufacturer and supplier exchange war-
ranty (not prorated).
1. The dripper line shall consist of a ultra violet resistant low density Linear poly-
ethylene tube with internal pressure compensating continuously self-cleaning
integral flat drippers welded to the inside of wall of the tube at the specified
spacing as an integral part of the tubing assembly.
3. The dripper shall be constructed of plastic with a hard plastic diaphragm re-
tainer and a self-cleaning diaphragm extending the full length of the dripper. It
shall have an inlet filter raised from the wall of the tubing. It shall have the
ability to independently regulate discharge rates with a constant flow at an inlet
pressure of 7-70 psi.
8. The dripper line shall have a 5 years guarantee against solar radiation and 5
years manufacturer and supplier warranty against manufacturing defects.
10. The dripper line shall have a 5 years guarantee against solar radiation and 5
years manufacturer and supplier warranty against manufacturing defects.
E. Bubblers
1. The bubbler shall be of the pressure compensating type having a fixed flow un-
der a pressure range of 20 to 90 PSI. It shall be constructed of corrosion and
UV resistant plastic material.
2. The bubbler shall have an integral flow bushing to maintain a constant flow at
different pressure range.
3. The bubbler shall have a plastic screen filter to protect it from debris that could
be available in the water.
5. Bubblers flow and numbers are as per design drawing details and two bubblers
are needed for each tree or palm, one bubbler at opposite corner of the tree.
6. The bubbler shall carry a two years manufacturer and supplier replacement
warranty.
1. The electrical control solenoid valves shall be of the electronically actuated, di-
aphragm operated.
4. The valve shall be equipped with a flow control mechanism with handle, which
regulates the flow from full on to completely off. It shall have an accurate set
pressure regulator, to keep the downstream pressure constant after setting it.
The regulator shall be of the top dial model with clearly shown pressure values
in bars and PSI. It shall regulate the flow at a pressure range of 20 to 100 PSI.
5. The valve shall be available in 1, 1.5, 2 and 3” inch sizes and it shall have a
BSP female thread inlet and outlet. It shall accommodate a flow rate from 0.1
gpm (1”size) to 100 gpm (3”size)
6. The valve shall be equipped with automatic self-cleaning system for filter.
7. The valve sizes, number and flow rate are shown on the design drawings.
8. The valve shall carry a five years manufacturer and supplier exchange warran-
ty.
3. The valve shall be operated by a 90º turn in clockwise direction with reverse
turn for closure and be capable of 360-swivel action.
5. The Valve Body shall be made from brass material and have the two-section
type with removable upper body. It shall be supplied with spring loaded lock-
ing cover made from thermoplastic rubber. The cover spring shall be of stain-
less steel material.
7. The valve shall carry a five years manufacturer and supplier exchange warran-
ty.
H. Gate Valves
1. Gate valves shall be designed for a working pressure of not less than 10 bars
and water operating temperature of 45° C.
2. Valves shall be the same size as the incoming line size with a clear waterway
equal to the full nominal diameter of the valves and shall be opened by turning
counterclockwise.
3. The operating nut or wheel shall have an arrow cast in valve indicating the di-
rection of opening.
Newton Lusail School
Mechanical Specification - Rev. 00 328400 - 13
328400 – PLANTING IRRIGATION
4. Valves smaller than 4” shall be all bronze or brass conforming to BS 5154 with
screwed end connections. Valves 4” and larger shall be cast iron body, and
shall conform to BS 5150 with flange end connections.
5. The valve shall carry a five years manufacturer and supplier exchange warran-
ty.
6. PVC valves up to 4" diameter, with working pressure of not less than 10 bars
and watering temperature of 50° C are acceptable with 10 years manufacturer
and supplier exchange warranty.
1. Air relief valves shall be 2” size as shown on the Drawings and shall be of the
kinetic/automatic type that will automatically release air when the lines are be-
ing filled with water and when air entrapment occurs while the system is work-
ing.
3. The body of the valve shall be constructed of heavy duty plastic or 100% cor-
rosion resistant materials.
5. The Valve shall remain open even when pipeline air pressure reaches 10 psi.
6. The air release valve shall employ rolling seal mechanism made of EPDM.
J. Check Valves
2. The valve shall allow flow in one direction by the action of a spring loaded flap
which closes against a rubber seal.
3. The spring and the flap shall be connected via a moment arm in order to ensure
that the spring pressure is maximum when the valve is closed.
5. The valve shall have an external position indicator that may be made electric
for signaling a control system.
K. Valve Boxes
1. The valve boxes shall have enclosures, which are injected molded polyofin
plastic with ultra violet additives, according to ASTM-D-V1248. It shall be
light in weight with reduced side angles and increased break resistance.
3. The valve boxes shall be available in sizes to fit the solenoid valve assembly
including the union fittings and allow for easy removal of valves for mainte-
nance.
4. The valve box should have a two years replacement warranty against buckling
and five years against cracking. All valve boxes should be name tagged with
aluminum or brass name tags, placed inside the valve box and riveted to the
outside box cover. The name tag size should be 2" by 3" and 2mm thick.
L. Filters
1. Use a 3” disc filter on all distribution chambers with a disc filters of 120 mesh
size of 0.10 mm.
2. Disc filters should be corrosion resistant, with minimum pressure and high par-
ticle retention filter area.
4. The filter shall carry a five years manufacturer and supplier exchange warranty.
M. Controllers
3. The number of stations for each controller should be equal to the total of exist-
ing stations for all used solenoid valves, the extra spare wires for future use and
wires for future flow meter and master gate valves at each chamber.
N. Power Source
1. The contractor shall be responsible for providing the electrical power source to
the controller from any nearby distribution panel board.
2. The location of the controllers should not be changed and the power sourcing
should be done to suit that condition. All coordination and permits should be
arranged by the contract and at his own expense.
1. The irrigation control cables shall be used between the solenoid valves and the
irrigation controllers. The cables shall be of the single conductor type UF and
they shall be engineered for direct burial use. The common wire should be
gauge 14 and the control wire should be gauge 12.
2. For master control valves and flow meter wires use 10 gauge wires.
3. The wires shall be of the solid or stranded construction with soft bare copper
conductor. They shall have extra heavy thickness of special polyvinyl chloride
insulation highly resistant to the saline, acid or alkaline contaminants.
4. The copper conductors of the wires shall meet the requirements of ASTM B-3,
B-8.
5. The thermoplastic insulation shall meet ASTM D-2219. All irrigation wires
shall have surface printing on insulation.
P. Irrigation Pump
2. The irrigation pump should have a variable frequency drive that controls and
keep pressure constant with a variable drive system.
3. The pump should be made of the best materials and made by a reputable manu-
facturer.
5. The minimum replacement warranty for the pump should be 2 years if defect
occurs more than twice per year.
6. The supplier should submit a guarantee of 2 days maximum repair time for the
pump including availability of spare parts.
7. The pump warranty should cover all parts of the pumping system including the
control board piping and check valve to a minimum of five years against manu-
facturer defects.
Q. Flow Meter
3. Capable of reading flow from 0 to 25% higher than the maximum flow in the
largest mainline pipe.
5. The warranty should include the flow meter and the signal converter and
should be for 5 years suppliers’ warranty.
1. The master control valve should be cast iron compatible with the existing con-
troller and operated with 24 V direct Electrical current.
2. The warranty should be for 5 years suppliers warranty and 2 years minimum
manufacturer warranty.
3. The local supplier should be an existing Qatari firm with minimum 5 years of
operational history.
S. Miscellaneous
1. Irrigation Drip Line Stakes: Stakes for securing flexible pipes shall be heat
resistant plastic.
2. Keys: the Contractor shall provide Keys for all valves, controller cabinets,
boxes, quick couplers, etc. The number of keys to be provided to the Engineer
for each type of fitting shall be six (6).
4. Quick couplers Swivel end unit: One (1) quick coupler with swivel end unit
should be provided for each installed eight (8) quick coupling valves.
The aluminum cover should be made to fit the new chambers shown on the
project details drawing and it should have the following:
e) The faces of the frame which will come into contact with the cement mor-
tar or concrete shall be painted with two coats of bituminous paint before
installation of the frame.
PART 3 - EXECUTIONS
3.1 PROTECTION
B. Work and materials shall be protected from damage during storage, handling and
construction. Particularly, non-metallic pipes and fittings shall be protected from di-
rect sunlight during storage. Facilities of the necessary dimensions shall be provided
and maintained for storage of all non-metallic irrigation materials in their entirety.
All non-metallic materials shall be handled carefully and stored under cover to avoid
damage. Pipes that have been damaged or dented will not be used in this work.
D. Openings into the system, apparatus and equipment shall be securely covered, both
before and after being set in place, to prevent obstruction in the pipes and the break-
age, misuse or disfigurement of the apparatus or equipment.
E. Barricades, guards, warning signs and lights as necessary or required, for the protec-
tion of the public and the work force shall be provided.
F. Utilities: The location of existing underground utilities shall be determined and the
works performed in a manner which will avoid possible damage. Hand excavation,
as required shall be carried out to minimize the possibility of damage to existing un-
derground utilities.
3.2 PERFORMANCE
A. The Contractor shall stake-out the locations of all pipe and valves and the layout of
work as accurately as possible.
B. The Contractor shall verify all horizontal and vertical site dimensions prior to stak-
ing.
C. The Contractor will be responsible for relocating any existing services after first ob-
taining the Engineer's approval. The Contractor shall remove and relocate such ser-
vices, at his own expense, if so directed by the Engineer.
D. Before starting work on irrigation systems, the Contractor shall carefully check all
grades to determine that work may safely proceed, keeping within the specified ma-
terial depths.
3.3 INSPECTION
A. The Contractor shall inspect all products for damage immediately before installa-
tion. Any products that are found to be damaged or not in accordance with the speci-
fications shall immediately be repaired or removed from the site and replaced. Re-
pairs shall not be undertaken without the Engineer's approval of Contractor's pro-
posed action.
3.4 INSTALLATION
D. In bedding and backfilling granular material shall be used below and above the
pipes. The backfill material shall be free of stones bigger than
F. All products shall be installed in accordance with the manufacturer's instruction and
the Drawings.
1. Where the location of an irrigation line is not clearly dimensioned on the Draw-
ings, the irrigation line shall not be laid horizontally closer than 3.0 meters
from a sewer.
2. However, where the bottom of the irrigation line will be at least 0.3 meters
above the top of the sewer pipe, the irrigation line shall not be laid closer hori-
zontally than 1.5 meters from the sewer.
3. Where irrigation lines cross under gravity-flow sewer lines, the sewer pipe
shall be fully encased in concrete, for a distance of at least 3.0 meters each side
of the crossing or shall be made of pressure pipe with no joint located within
1.0 meters horizontally of the crossing.
4. Irrigation lines shall, in all cases, cross 0.6 meter above sewage pressure mains.
5. Lateral lines should be 2 meters away from center of trees, palms and large
shrubs.
1. Pipes shall not be laid in water or when trench conditions are otherwise unsuit-
able for the work. Water shall be kept out of the trench until the material in the
joints has hardened or until caulking or jointing is completed. When work is
not in progress, open ends of the pipe, fittings, and valves shall be securely
closed so that no substance will enter the pipes or fittings.
2. Pipe ends left for future connections shall be valved, plugged or capped, and
anchored, as shown or as directed. Pipes that have the grade or joint disturbed
after laying shall be taken up and re-laid.
3. All piping with the exception of the flexible irrigation drip line shall be sur-
rounded by a sand bed to the dimensions as shown on the Drawings.
I. Plastic pipes
1. Pipes with threaded joints shall be snaked from side to side of the trench to al-
low for expansion and contraction.
J. Jointing:
2. UPVC male adaptors with specified threaded joint compounds to make connec-
tions between plastic pipe and valves shall be used as detailed, and tightened
with light wrench pressure.
K. Concrete thrust blocks shall be constructed on main pipelines at all changes in direc-
tion or size. The thrust blocks shall be non-reinforced concrete and shall have a
minimum dimension of 300 mm. The pipelines shall be located centrally in the
thrust blocks.
L. Irrigation piping from the remote control valve boxes to the end of the irrigation drip
lines shall be buried to the depths as shown on the Drawings.
2. Flushing: All pipes and tubing shall be thoroughly flushed out before installa-
tion of the emitter control valves. Butt joints, fittings and connections shall re-
main visible.
N. Tagging and Identification: All remote control valves, motor-operated valves, pres-
sure reducing valves, manually-operated gate valves and controllers shall be tagged
and identified. All identifying numbers shall be consistent with like designations in-
dicated on the irrigation controller schedule.
a) The top of all boxes shall be set parallel with the grade and as detailed in a
neat and orderly fashion.
c) All box locations shall be reviewed with the Engineer prior to installation
of valves.
d) Valve boxes shall not rest on or come in contact with the valve, piping,
hose or conduit.
e) Solenoid valve boxes should have a weather proof tag attached on the in-
side showing the valve number, controller number and station number.
f) A filter fabric should cover the valve box and the soak away and taped to
the valve box side just 10 cm below cover.
P. Control System:
1. Irrigation Controller:
a) An irrigation controller shall be installed in locations approved by the En-
gineer, with the control cables, clearly marked with identification mark-
ers, attached to the appropriate terminals in the approved manner.
Q. Irrigation – Electrical
1. The contractor shall provide, install, test and commission all items of electrical
equipment associated with the irrigation systems.
3. The irrigation system shall commence at the controllers, which shall be fitted
into a dwarf type distribution cabinet with solar shade and shall have a bolting
down foot for mounting on a pre-formed concrete base. All incoming and out-
going cables shall be from below ground level. The cabinet shall have a hinged
lockable opening door to provide full front access to the controller and equip-
ment and shall be sized according to the equipment being installed.
4. All equipment, conductors, termination, etc., within the pillar and throughout
the irrigation system generally shall be fully insulated such that there are no
live parts or connections exposed and shall be to the complete satisfaction of
the Engineer.
5. The irrigation pillar shall have sufficient free space for fitting a kWh meter to-
gether with any additional equipment or accessories required to complete the
equipment.
6. Each irrigation pillar shall have permanently fixed on the inside of the door, a
distribution diagram showing all circuits connections, ratings, cable sizes, etc.,
together with a current controller schedule.
7. All terminals shall be of the crimped spade type with insulated grip. At all con-
nection locations 150 mm of "slack" shall be provided.
8. Conductor markers shall be used throughout which shall clearly indicate the
circuit reference or number. These shall be white plastic with black letters or
numbers and of the type which acts as a sleeve over the conductor insulation.
9. Connections onto valves shall be made in a below ground PVC resin filled
molded waterproof connector with integral wire clamp.
10. Solenoid valve cables should be laid along the mainline 20 cm horizontal dis-
tance from the irrigation pipe.
R. Drip Line / Soft Line Testing
1. Drip lines shall be carefully uncoiled and laid in position without kinking. Any
kinked section shall be cut from the line and subsequently rejoined with a line
joiner section.
2. Drip lines shall be snaked as required for maximum coverage without the use
of compression fittings. Sharp bends shall be avoided where there is a likeli-
hood of causing kinks in the line.
3. Drip lines shall be laid on the ground surface for a minimum of 48 hours prior
to the installation of irrigation emitters or stakes.
S. Concrete Pads:
4. The anchor bolts shall be set in coordination with enclosure hole locations.
A. Purging:
2. Mainline piping system may be tested in sections. Lateral Systems shall be test-
ed valve by valve.
4. Water shall be introduced into lines to be tested at full operating head and the
water flow at end discharge point, and observed until all air and residual debris
has been expelled from the line.
1. Individual parts of the main network between isolation valve points having a
length not greater than 500 meters shall be tested together with dead legs before
backfilling operation.
2. Test shall be made only after completion of the above operations and not until at
least seven days after the last concrete thrust anchor block has been cast.
3. Contractor shall supply all testing material and equipment, including all caps,
valves, pumps, tanks, water and gauges as required.
4. Pressure gauges shall be dual reading in bar and psi units. Calibration shall be
such that accurate determination of potential pressure loss can be ascertained.
5. The section of the main pipeline to be tested shall be filled with potable water
and all air expelled. After the main pipeline has been completely filled, the pres-
sure shall be steadily and gradually increased until the specified test pressure
has been reached. Simultaneous pressure and leakage tests and separate pressure
test shall be made at 150 % of working pressure at the point of test, but not less
than 125% of normal working pressure at highest elevation. Separate elevation
test shall be made at 150 % of normal working pressure of the segment tested.
The minimum pressure test for mainlines is 9 bars and leakage test for lateral
lines. Duration of pressure and leakage tests shall be 4 hours. All testing shall
comply with AWWA M23-80, Polyvinyl Chloride Pipe Design and Installation.
Testing shall comply with AWWA specifications and requirements.
6. Separate tests shall be applied to the lateral distribution pipe work and the irriga-
tion pipe work from the remote control valves outwards. Test pressures for these
shall be as described above.
7. When testing the irrigation lines from the valves, discharge devices shall be re-
placed with temporary plugs or caps.
8. All trenches with pipe installed shall be immediately backfilled with preliminary
sand backfill sufficient to prevent arching or slipping under pressure. All joints,
fittings and connections are to remain exposed until successful completion of
hydrostatic testing.
9. Other than for preliminary sand backfill over pipes, no work shall be covered
before it has been inspected, tested and approved by the Engineer.
10. During the tests, all exposed couplings, fittings and valves shall be carefully ex-
amined for defects and leakage. Leaking pipes, couplings, joints, fittings and
equipment shall be repaired or replaced and the section retested as previously
specified.
11. Upon receipt of approval of the Engineer to proceed, the remaining backfill
shall be placed and compacted to ninety percent (90%) of maximum dry density.
C. Final System Test: The tests as specified above shall be repeated for the entire net-
work after pipelines have been backfilled, cleaned and inspected. Each test shall be re-
stricted to pipes of one class and particular care shall be taken to isolate air valves, etc.
and not to apply higher pressures than specified at any point on the pipeline and to en-
sure that the pipelines are adequately anchored before any test is carried out.
D. Test Results: Written records of every test clearly identifying the tested section of the
pipe together with time of test and name of testing engineer in tabulated format shall
be submitted for review and approval by the Engineer upon completion of the tests.
3.6 FLUSHING
A. General: On completion of the system test, the system is to be thoroughly flushed, the
velocity of water being at least 1 m/s. Should the main water supply be unavailable or
inadequate for this purpose at the time of flushing, then a swab of adequate size shall
be used to remove all foreign matter from the pipeline. This process shall continue un-
til the pipeline is completely clean. Each control valve shall be opened separately and
the terminal systems also thoroughly flushed. After completion of flushing, the emit-
ters and other discharge devices shall be fitted.
B. Operation Test: After the hydrostatic test, emitters shall be installed and the system
completed and tested to demonstrate functional efficiency. This shall be prior to cov-
ering the laterals with mulch if used.
C. The lines shall be operated for a period of 24 hours, not necessarily in one continuous
period, and all emitters checked for satisfactory operation. Any faulty/blocked emit-
ters shall be replaced.
2. Adjustment and re-testing of emitters, control valves etc., shall be carried out
until satisfactory result is obtained and the whole system is functioning to the
design requirement.
B. Maintenance Manual: Upon completion of work and prior to initial acceptance, pro-
vide the Engineer with Four (4) copies of a bound maintenance manual and one (1)
softcopy.
The manual shall contain a list of all irrigation system components including:
Component description.
Maintenance program by date for each component and the description of the
maintenance procedure, cleaning, flushing, lubricating, changing parts, updating
etc.
C. The general manual headings and descriptions should be both Arabic and English.
The manual should contain a list of all irrigation system components including:
Operational schedules.
The general manual headings and descriptions should be both in Arabic and Eng-
lish.
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
PLUMBING
Lawton UK
Crane USA
Yorkshire UK
1 Copper Pipes & Fittings
Wednesburry UK
Victaulic USA/Europe
Mueller UK
Franklin Hodge UK
2 Steel Tank SUNNIK MALYSIA
BRAITHWAITE UK
Japan
bridgeston
Balmoral UK
Sekisui Japan
AC plastic UK
3 Water Tank (Sectional GRP)
SAMSUNG Malasia
POTAGLASS Malaysia
DAEJOO SOUTH KOREA
SUNNIK Malaysia
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Durapipe UK
Redi italy
Nicoll France
5 UPVC Pipe & Fittings
FIP Italy
Pestan Serbia
Hepworth UK
THEMOCELL USA
ZOTEFOAM UK
6 Thermal Insulation (Fiber Izocam Turkey
Glass Insulation) Australia
Thermobreak
Kimmco Kuwait
ODE Turkey
Grundfos Denmark
KSB Germany
DP Netherland
7 Water pump Set
Xylam- Lowara Italy
Wilo EU
Pentair EU
ITALIAN CORRUGATI ITALY
Victolic USA/EUROPE
HDPE PIPES, FITTINGS and coestilen
8 italy
VALVES
Hepworth UK
akatherm Netherland
ABO EU
hattersley UK
9 Valves FLOWCON ITALY
WATTS USA
FRESE Demark
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Wefatherm Germany
Hakan Turkey
PPR, PEX and Silent PIPES, Banninger Germany
10
FITTINGS and VALVES Interplast UK
Onur Turkey
Coes Italy
Crane UK
Zurn USA
FLOWCON ITALY
WATTS USA
WILKINS USA
11 Pressure reducing valve CLAVAL Swiss
Victaulic/Bermad USA
Viking USA
NIBBCO USA
Mason Industries, Inc.; Mercer Rubb USA
Manikin UK
VIMCO USA
FLOWCON ITALY
AYVAZ Turkey
TOZEN JAPAN
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
FLOWCON ITALY
WATTS USA/CHINA
EXPANSION JOINT
13 TOZEN JAPAN
WEICCO INDIA
VICTAULIC USA
AYVAZ Turkey
Minikin UK
PUROFLUX USA/EUROPE
Filtrine USA
Culligan UK
CARESS USA
Water Filter and Terminal
14 Culligan ITALY
Filters
Pentair UK
METITO USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Amberbooth USA
Kinetics USA
Vimco USA
MASON USA
Vibration Isolators WEICCO INDIA
17
DIAMOND INDIA
PACKLESS USA
INDUSTRIAL ACOUSTICS UK
TOZEN JAPAN
GETZNER AUSTRIA
Georg Fischer Germany
Sika Swirzerland
Tolico USA
Hilti USA
Fischer Germany
MUPRO GERMANY
18 Pipe Supports
MUNGO SWITZERLAND
FLAMCO UK
TEMPO INDIA
WEICCO INDIA
MASON USA
Tyco USA
PENTAIR USA
Fountains and swimming HYWARD
19 USA
pools specialist
ASTRAL SPAIN
Interfit France
20 Pipe Fitting Anvil USA
Victaulic USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
FOSTER USA
SANDFIRE UK
21 Fire stop material
Hilti Germany
MORGAN USA / INDIA
WATTS USA
ZURN USA
22 Water hammer arrestor Wilkins Canada
ALBION USA
FLOWCON ITALY
Hydrus-Hydrometer EUROPE
Itron-Echodis Compact PLUS USA
23 Water meter domestic SIEMENS EUROPE
SMART ENERG PLUS EU
Badger USA
ABB USA
24 Water meter bulk SMART ENERG PLUS EU
Siemens EUROPE
WATTS USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
MASON USA
WEICCO INDIA
28 Anti- vibration mountin&pads KINETICS USA
TOZEN JAPAN
GETZNER AUSTRIA
CONEX USA
PERGLER UK
29 Ball Float Valve
NEWMAN HATTERSELY UK
WATTS USA
HOUSEMAN UK
METITO USA
30 Water Treament CULLIGAN UK
DEARBORN USA
DREW CHEMICALS USA
GASCO QATAR
31 LPG/SNG Qatar Gas QATAR
Uni Gas QATAR
Econosto Europe
32 Fuel oil system Pipes BIS Japan
Interpipe Ukraine
Any other product not listed in vendor list or have different origin subject to ENGINEER and DESIGNER
approval
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
DRAINAGE
MARLEY UK
Durapipe UK
1 uPVC pipes/Fittings Hepworth UK
HUNTER UK
REDI ITALY
ISCO UK
HEPORTH UK
Victaulic USA/Europe
ADS USA
cose ITALY
wavin Germany
ZURN USA
J R Smith USA
Thermax UK
Drainage Specialties, Manhole Saint Gobain PAM France
4
Covers & Frames WATTS USA/CHINA
KESSEL ITALY
FERPLAST ITALY
ACO UK
Wade UK
Frost UK
Hepworth UK
5 Floor Gulley JOSAM USA
ZURN USA
WATTS USA
J R Smith USA
ZURN USA
Floor drain, channel JOSSAM USA
6 SMITH USA
grating&cover
KESSEL GERMANY
WATTS USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
ZURN USA
OIL/SAND/LINT/ GREASE JOSSAM USA
7 SMITH USA
Interceptor
Thermax UK
WATTS USA
GBH Clay Pipes Malaysia
8 ESVC Pipe Naylor UK
Hepworth Qatar
Frost UK / USA
Wade USA
Oatey USA
9 Rain Water Drain Outlet SAB Italy
R Smith USA
Josem USA
Enpoco Canada
Lowera Italy
GrundFoss Denmark
Pentair Italy
10 Sump Pump KSB Germany
DP Netherland
HOMA Germany
XYLEM STEADY SWEDEN
SILIKA GERMANY
Caddy USA/ Europe
TYCO USA
Fischer Germany
MUPRO GERMANY
INKA TURKEY
11 Pipe support
MUNGO SWITZERLAND
FLAMCO UK
TEMPO INDIA
WEICCO INDIA
MASON USA
HILTI USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Any other product not listed in vendor list or have different origin subject to ENGINEER and DESIGNER approval
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
IRRIGATION SYSTEM
Pestan Serbia
Victaulic USA/Europe
1 HDPE Pipe
Gibrit Germany
Hepworth Qatar
Durapipe UK
Pestan Serbia
2 Pressure UPVC Pipe & Fittings
Sappco Aplaco (KSA) KSA
Hepworth UK
Gibrit Germany
MEAC KSA
3 Driper Pestan Serbia
Toro Italy
Rain Bird USA
Hunter USA
4 Solenoid Valve Rain Bird USA
WINGFIELD Australia
Hunter USA
5 Quick Coupler Valve Rain Bird USA
WINGFIELD Australia
Pegler UK
Hettersley UK
WATTS USA/CHINA
6 Gate Valve FLOWCON ITALY
ALBION USA
IMI (TA) EU/CHINA
Giacomany Italy
Hunter USA
7 Sprinkler / Bubler / Emitter Rain Bird USA
Wing field USA
Hunter USA
8 Irrigation Controller Rain Bird USA
Mottrolla USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Ebara Germany
Grundfos Denmark
Willo Germany
KSB Germany
9 Irrigation Pump
DP Netherland
HYDRO SPAIN
PENTAIR EU
BIRAL SWITZERLAND
Hunter USA
10 Sprinkler / Bubler / Emitter Rain Bird USA
Wing field USA
PUROFLUX USA/EUROPE
Filtrine USA
Water Filter and Terminal Culligan UK
11
Filters CARESS USA
METITO USA
STF FILTERS SPAIN
WATTS USA
Georg Fischer Germany
Caddy Denmark / USA
12 Sika Swirzerland
Pipe Supports
Tolico USA
Hilti USA
Tyco USA
Any other product not listed in vendor list or have different origin subject to ENGINEER and DESIGNER
approval
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
FIRE PROTECTION
Victaulic USA/Europe
Globe USA
Viking USA
Grinnel USA
Shield UK
Globe USA
Grinnel USA
Valves (OS&Y, Butterfly & Shield UK
2
Check Valves) Victaulic USA/Europe
CRANE UK
System Sensor USA
Moyne Roberts Ireland
Thorn Norsen UK
Shield UK
NAFFCO QATAR
Kiddie UK
FIKE USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
UK
Galvanized threaded fittings Shield
6 and Grooved Fittings (UL Victaulic USA
listed and or FM Approved). Tyco
USA
Siam Japan
Viking USA
Reliable USA
Alarm Check Valves ,
7 Deluge Valves & Peracion Shield UK
Valves Victaulic USA/Europe
Tyco USA
System Sensor USA
Supervisory Switches , Flow
Potter Electric USA
8 Switches , Pressure
Automatic Sprinkler USA
Switches
Central / Tyco USA
Cla-val USA
Watts USA
9 Pressure Reducing Valves Wilkins USA
Singer Valve Canada
Shield UK
AGF USA
Winters USA
10 Pressure Gauges BRANNAN UK
Watts USA
Potter USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Bell Flow UK
Global Vision USA
Potter Roemer USA
11 Water Flow Meter Gerand USA
SMART ENERG PLUS Europe
Flomag EUROPE
Potter USA
Patterson USA
Grundfos USA
Arrora USA
12 Fire Pump Set Peerless USA
Armstrong USA
XYLEM AC FIRE USA
R-B Pumps USA
Caterpillar USA
13 Diesel Engine Clarks USA
Cummins USA
Chub UK
Shield UK
ElKhart USA
14 Landing Valve Giacomini Europe
NAFFCO QATAR
Angus UK
Moyne Robert Ireland
Chub UK
Shield UK
Angus UK
15 Fire Extinguishers
Viking USA
NAFFCO QATAR
Amerex USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Chub UK
Shield UK
17 Fire Department Connection
Potter USA
NAFFCO QATAR
Magnum USA
Chemtron USA
Item COUNTRY OF
PRODUCT DESCRIPTION BRAND / MANUFACTURER
No. ORIGIN
Taco USA
21 Automatic Air Vents Cla-val USA
National USA
Foster USA
Sander Fire UK
22 Fire Stopping Materials
Idenden UK
SVT GERMANY
Any other product not listed in vendor list or have different origin subject to ENGINEER and DESIGNER
approval
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
HVAC WORKS
DAIKIN Malaysia
York Malaysia
1 PACU /SPLIT (ECO-FRIENDLY) LG Korea
Petra Jordan
General Thailand
DAIKIN Malaysia
2 AIR HANDLING UNIT carrier Turkey
Trane Malysya
EUROCLIMA ITALY
DAIKIN Malaysia
STULZ GERMANY
CLIMAVENETA ITALY
EDPAC IRELAND
Sondex Denmark
Taco USA
6 HEAT EXCHANGER
Alfa Laval Sweden
Danfoss France
ELTA UK
SYSTEM AIR GERMANY
7 VENTILATION FANS
Flakt woods UK
S&P SPAIN
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
British steel UK
INTERPIPE ukraine
shield UK
CHILLED WATER SEAMLESS
8 surya india
PIPES
DALMINE ITALY
NIPPON JAPAN
Sumitomo JAPAN
SPPI KSA
EPPI UAE
PRE INSULATED CHILLED
9 INSAFOAM UAE
WATER PIPES
PERMAP PIPE UAE
BCCI UAE
SCHULTZ Germany
Delcorte France
CHILLED WATER PIPE National USA
10
FITTINGS BIS Japan
GRINNELL USA
Central USA
YOUN WOO Korea
CHILLED WATER GROOVED Central USA
11
PIPE FITTINGS GRINNELL USA
Victaulic USA
CRANE UK
OVENTROP GERMANY
KITZ JAPAN
CHILLED WATER VALVES AND
12 Frese Denmark
PICV VALVES
Danfose Denmark
IMI POLAND
Nibco USA
Hattersely UK
KITZ JAPAN
PEGLER UK
13 STRAINERS
CRANE USA
IMI (TA) EU/China
Frese Denmark
Taco USA
CRANE UK
ITT USA
14 PRESSURIZATION PACKAGE PATTERSON USA
Wilo GERMANY
Flamco Netherlands
GRUNDFOS DENMARK
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
ARMSTORNG UK
WEICCO India
FLAMCO ITALY
SPIRAX SARCO USA
15 AUTOMATIC AIR VENT
XYLEM B&G China
IMI (TA) Eu
Procedyne India
OVENTROP GERMANY
MASON USA
Hattersely UK
KINETICS USA
16 FLEXIBLE CONNECTIONS MINIKIN UK
KINFLEX USA
Ayvaz TURKEY
SHOURJOINTS USA
HOUSEMAN UK
METITO USA
CHEMICAL DOSAGE POT & CULLIGAN UK
17
CHEMICALS DEARBORN USA
Prominent Germany
DREW CHEMICALS USA
KIEBACK&PETER Germany
Honeywell HBS USA
BUILDING MANAGEMENT Siemens Building Technology Germany
18
SYSTEM Johnsons Control USA
SAUTER Switzerland
SCHNEIDER EUROPE
Yorkshire UK
Wednesburry UK
19 COPPER PIPES & FITTING Crane UK
Mueller UK
Lawton UK
Kimmco KUWAIT
Kflex UAE
THERMOBREAK Australia
ARMACELL INDIA
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
Nippon Japan
Kobe Japan
JEF Japan
Sumitomo Japan
Ciaco KUWAIT
22 AIR TERMINAL
KBE Lebanon
Flowtech Qatar
DEVAC Qatar
Danfose Denmark
Emerson USA
MASON USA
Hattersely UK
KINETICS USA
MINIKIN UK
KINFLEX USA
24 FLEXIBLE CONNECTIONS
SHOURJOINTS USA
FLOWCON ITALY
TOZEN JAPAN
Ayvaz TURKEY
WATTS USA
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
SHIELD UK
Flowtech UAE
DEVAC Qatar
BLE UK
SHIELD UK
26 SMOKE AND FIRE CURTAINS Colt Germany
Flowtech UAE
EPS UK
LEBANON
KBE
QATAR
KMC
27 VOLUME CONTROL DAMPERS
Qatar
Flowtech
TURKEY
KES KLIMA
USA
KBE
SWEDEN
KMC
28 SILENCERS Singapore
SAFID
Qatar
Flowtech
QATAR
AIR MASTER
KBE USA
KMC SWEDEN
29 FLEXI DUCT
SAFID Singapore
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
AAF U.S.A/Europe
31 AIR FILTRATION SYSTEM METITO USA
THERMAX UK
Rubatex USA
32 RUBBER FOAM INSULATION ARMAFLEX INDIA
SUPERLON MALYSIA
Kamstrup EUROPE
Lanpis Denmark
Danfoss Denmark
Landis-Gyr EUROPE
DURODYNE USA
DUCT FLEXIBLE UK
34 CONTRACT COMPONENTS LTD.
CONNECTIONS
DYNAIR ITALY
FOSTER USA
ADHESIVE, COATING,
35 Childers USA
SEALANTS
Pidlilite-FEVICOL INDIA
EVOTEK QATAR
S1KLA GERMANY
36 DUCT & PIPE SUPPORTS
Weicco Qatar
TYCO USA
MASON USA
AMBERBOOTH USA
KINETICS USA
37 VIBRATION ISOLATORS
Weicco India
TOZEN JAPAN
GETZNER Austria
Item
PRODUCT DESCRIPTION BRAND / MANUFACTURER COUNTRY OF ORIGIN
No.
Winters Canada
TAYLOR USA
38 INSTRUMENTS & GAUGES JOHNSON USA
Brannan UK
HUNTER USA
SPC UK
Thermax GERMANY
HEAT RECOVERY,AIR Denmark
Dantherm
39 PURIFICATION
&DEHUMIDIFIERS CALOREX UK
PoolPak USA
MUNTERS EUROPE
Promat UK/Belgium
Intumex Austria
FIRE STOP MATERIAL AND
40
FIRE RATED DUCT
Hilti Germany
MORGAN USA
Any other product not listed in vendor list or have different origin subject to ENGINEER and DESIGNER
approval