Daily Quality Observation Report-M/s.

Crescon Electrical

Project Name: MRF-TBR-PCR Expansion Project-Trichy


Date
Report No. JLL/CRESC/ Electrical /005/2023
S no Concern Area Snaps Observation Location Suggested Mitigation Compliance photographs STATUS

DS-1 Near pipe properly cable dressing


1 HT Cable dressing pending Closed - waiting for inspection
rack to be done

Earth Flat welding not done DS-2 Near pipe proper Welding and
2 Closed - waiting for inspection
rack connectivity to be done

proper Welding and


Support Welding and
3 CT-5 Vertical drop Painting to be done Closed - waiting for inspection
painting not done properly.
properly.

cable tray laying to be


cable tray and cable
4 Quituplex TBR done properly and cable Closed - waiting for inspection
dressing not completed.
dressing to be done.

Earth flat overlooping


Earth flat welding and earth
Fisher cutter body mini 50mm and welding
5 flat connectivity not Closed - waiting for inspection
ply PCR and painting to be done
proper.
properly.

Support welding and


Support welding and
support erection and Closed
6 support erection not DS-1 GF
leveling to be done 19-06-2024
properly.
properly.

Earth flat overlooping


Earth flat welding and earth
Fisher cutter body mini 50mm and welding
7 flat connectivity not Closed - waiting for inspection
ply PCR and painting to be done
proper.
properly.

Lighting cable laying and


lighting cable dressing not
8 Zone-1 dressing to be done Closed - waiting for inspection
done.
properly.

Busduct support welding


Busduct support welding Closed
9 DS-1 and painting to be done
not completed. 19-06-2024
properly.

Cable laid and dressing not cable dressing to be


10 Zone-2 Closed - waiting for inspection
properly. done properly.

Trench-2 outgoing press


tray support and leveling
11 cable tray support not done Zone-3 Closed - 25.10.2023
to be done properly.
and leveling not done.
cable tray and cable
oper tray and cable
12 Zone-4 dressing to be done Closed - waiting for inspection
dressing not done properly.
properly.

Support welding and


Support welding not
13 Curing PDB Room painting to be done Closed - waiting for inspection
properly.
properly.

Cable tray laying and


without cable tray and
14 Zone-4 dressing to be done Closed - waiting for inspection
cable dressing not done.
properly.

Earth flat laying and


Panel charged eathing not
15 Zone-3 connection to be done Closed - waiting for inspection
done.
properly.

Earth flat welding and


Earth flat welding not done
16 Compressor room. Connection to be done Closed - waiting for inspection
properly.
properly.

Properly cable uncoile


Closed - waiting for inspection MENTIONE
17 Cable twised Zone-01 and laying to be done CABLE REMOVED FROM ZONE-1
proper methods .

cable tray support


tray laid without supporting painting not done and
18 Compressor room. Closed - waiting for inspection
leve not proper primary painting to be
done properly.

Support need to change


tray laid without supporting
19 Compressor room. and providing the level of Closed - 25.10.2023
leve not proper
the tray.

cable tray need to rectify


Cable tray not proper and
20 Compressor room. and proper bend Closed - 25.10.2023
support to provide
,support to providing.

Ones work completion


Material is damaged not
balance material to be
21 proper stocking ,material Zone-3 Closed - waiting for inspection
stock properly and
scraped
proper location.