ED-194-08 Elevating & Amusement Devices
ED-194-08 Elevating & Amusement Devices
:
Elevating and Amusement Devices
Safety Division 194 / 08
Date: Date:
Enforcement Procedure
Bulletin October 8, 2008
1. INTRODUCTION
1.1. General
All elevating devices in Ontario are subject to the requirements of Ontario Regulation 209/01 (Elevating
Devices) made under the Technical Standards and Safety Act, 2000, unless the type of elevating device is
specifically excluded from the Regulation.
The elevating devices regulation (209/01) has been recently amended by O.Reg 252/08 (effective January
1, 2009) and now clearly references Parking Garage Lifts (PGL’s) as one of the many forms of regulated
elevating devices.
Elevating devices used to elevate or lower vehicle(s) for the purpose of storing (parking) the vehicle are
included in the Regulation.
A primary reason to reference and not exempt PGL’s is that they are not specifically regulated by any other
Ontario Regulation designed to protect the public. Therefore any persons involved with the ownership,
operation, installation, and maintenance of these types of elevating devices used in publicly accessible
locations are expected to comply with the requirements set forth in the Act and Regulation. The Act and the
Regulation specifies a person’s responsibilities.
The increase in PGL installations has prompted TSSA to work with the PGL industry to ensure the
requirements of the elevating devices regulation are understood and the requirements followed for PGL
installations and maintenance. As the regulatory requirements are new to many in this industry, TSSA is
working to implement a phased approach to regulatory fulfillment. The purpose of this document is to
inform responsible parties on the compliance requirements under the Regulations. Since compliance is
expected to be achieved in stages, this document also specifies the minimum requirements and
implementation timelines.
This bulletin is intended to outline the requirements related to Parking Garage Lifts. The Regulation defines
PGL as:
“Parking Garage Lift” means an elevating device that is used for lifting or lowering a vehicle in or about a
parking facility.
th
3300 Bloor Street West, 14 Floor, Centre Tower, Toronto, Ontario M8X 2X4
Telephone: 416-734-3300 Fax: 416-231-5435 Toll Free: 1-877-682-8772
Putting Public Safety First
ED-194-08.doc 1/7
2. PGL-Transfer Area – An area from which vehicles are transferred to, or returned from, the working
area of the PGL. The transfer area is intended to allow for at least the driver to enter or leave the
vehicle. The transfer area has means to ensure the public does not have access to the working area of
the PGL.
Note: No persons ever ride the transfer device.
3. PGL-Automatic – A parking system which includes a PGL-Transfer Area, and a vehicle storage
area consisting of a PGL-Simple Stacker or PGL-Complex Stacker as defined above.
Note: No persons ever ride in an automatic PGL.
Note 1: At this time, only the requirements of the transfer area of a PGL-Automatic will be addressed.
Note 2: A PGL with two or more loading and unloading landings is considered a PGL elevating device
under section 1.3 below.
In this bulletin, PGL-Simple Stacker, PGL-Complex Stacker, PGL-Transfer Area and PGL-Automatic are
referred to as “Parking Garage Lifts” (PGL’S).
Where elevating devices described in 1, 2, and 3 above are used to carry vehicles, the
requirements of B44 Safety Code for Elevators will form the bases of the design of the elevating
device. These devices will be classified as PGL Elevators.
Ontario Regulation 209/01 as amended by O.Reg. 252/08 specifically recognizes Parking Garage Lifts, and
becomes effective on January 1, 2009.
Prior to January 1, 2009, Parking Garage Lifts were classified as a “special elevating device”, requiring
compliance with prior editions of the Act, regulation and applicable codes.
To facilitate industry compliance, the enforcement process has been divided into two phases.
Phase 1
The first phase will ensure compliance for new and altered installations, which are commissioned on or
after January 1, 2009.
Phase 2
The second phase will address compliance issues for existing installations.
• Identification of existing sites by June 1, 2009
• Periodic inspection activities beginning on or after January 1, 2010.
th
3300 Bloor Street West, 14 Floor, Centre Tower, Toronto, Ontario M8X 2X4
Telephone: 416-734-3300 Fax: 416-231-5435 Toll Free: 1-877-682-8772
Putting Public Safety First
ED-194-08.doc 2/7
The following guidelines will be used to ensure compliance with the O.Reg. 209/01:
2.1.1. This Regulation applies to the design, construction, installation, erection, maintenance, alteration, use and
service of Parking Garage Lifts as defined in this bulletin, except where otherwise indicated.
O.Reg.209/01, s.2
a) For the first phase of the regulation compliance project, contractor registration requirements will be
varied.
b) Only companies authorized and trained by the manufacturers/manufacturer’s representative may be
eligible for registration.
2.2.2. All work performed on a PGL after January 1, 2009 must be done by a registered contractor.
O.Reg.209/01, s.21
a) A letter from the equipment manufacturer/manufacturer’s representative stating that the contractor is
authorized to perform work on their equipment.
b) Verifiable proof of experience shall be included with the application.
c) Name of mechanic(s) registered by TSSA (see 2.3)
2.3.1. No work shall be undertaken on a Parking Garage Lift unless by a registered mechanic, or by a mechanic-
in-training under the supervision of a mechanic. O.Reg.209/01, s.24
a) A Parking Garage Lift mechanic must have documented training under the regulation.
b) A certification program for Parking Garage Lift mechanics will not come into effect until a later phase.
c) Until the mechanic certification program is in place, manufacturers and contractors shall provide
information and documentation about their training programs.
d) Until the mechanic certification program is in place, mechanics shall provide information and
documentation about their training history. Ideally this will take the form of a training certificate and
log from their employer.
e) The Elevating Device Regulation 209/01 requires all mechanics to:
1) have full knowledge of the Act, Regulations and any applicable code
2) not undertake work beyond their scope of training
2.4.1. Contractors shall provide a list of all Parking Garage Lifts which they have installed in the province of
Ontario prior to January 1, 2009.
2.4.2. Contractors shall provide a list of all Parking Garage Lifts under their maintenance. O.Reg.209/01, s.23
Note: Condominiums are not included in the private dwelling house exemption as they have components /
areas which are not exclusive to the owners of a single private dwelling, so they need to be included on the
list.
2.5.1. New and/or altered Parking Garage Lifts shall conform to the Technical Standards and Safety Act, 2000,
Ontario Regulation 209/01 and the Elevating Devices Code Adoption Document. Engineering and
inspection related documents (design submission documents) related to the installation shall be provided
with the application for registration of a new installation. The engineering data will identify the applied
codes and provide statements of hazard assessment and mitigation. O.Reg.209/01, s.5 (1), 5(2), 15, 16, 17
a) The first required design submissions will apply to any new or altered installation which will be
commissioned / put into operation after January 1, 2009.
b) The design submission for registration of a new or altered installation shall include those items listed
in O.Reg 209/01, s.15.(4), and shall also include:
1) Proof of electrical equipment certification to CEC C22.1, CSA, cUL, or equivalent.
2) Proof of manufacturer welding certification to CSA W47.1, or equivalent.
3) Number of load carrying units driven by the power unit.
4) Total Capacity of the device and the capacities of the individual carriers.
th
3300 Bloor Street West, 14 Floor, Centre Tower, Toronto, Ontario M8X 2X4
Telephone: 416-734-3300 Fax: 416-231-5435 Toll Free: 1-877-682-8772
Putting Public Safety First
ED-194-08.doc 4/7
5) Operator Training Program
6) Assessment of Hazards and Mitigation - Identify how all minimum safety requirements are to be
addressed (crush, shear, fall, shock hazards)
7) Testing procedures to demonstrate the effectiveness of safety devices and features.
2.5.2. All documents of a design submission shall be under the signature and seal of a professional engineer of
Ontario. O.Reg.209/01, s.15. (6)
a) Submitting engineers will be attesting compliance to any applicable regulations and codes and will
ensure that matters effecting safety are addressed in a manner reflecting good engineering practice.
2.6.1. A contractor who installs or alters a Parking Garage Lift shall arrange for an initial inspection after
ensuring the device complies with the registered design submission and the device is in a safe operating
condition.
2.6.2. The initial inspection fee is the responsibility of the installing contractor. O.Reg.209/01, s.25, s. 44.
2.6.3. Contractors are reminded that new installations are not to be turned over for use until the device has passed
an initial inspection.
2.6.4. Devices undergoing alterations minor in nature and which do not impact safety features can be returned to
service but must be inspected within 60 days O.Reg.209/01, s.19
2.6.5. Full Load tests or loading with vehicles of representative weight will be required on all new devices (and
where applicable on altered devices). Loads and/or other test equipment shall be provided by the contractor.
O.Reg.209/01, s.44
2.6.7. Testing by the contractor will include a demonstration of test procedures included in the design submission.
2.7.1. No code, standard or other technical rule has been authorized under section 36 of the Technical Standards
and Safety Act, 2000 for the Parking Garage Lift. General engineering practice normally applied to
elevating devices shall apply.
a) If the lift was built to the European Standard EN 14010 Equipment for power-driven parking of motor
vehicles, TSSA will deem that it meets an acceptable code except where the EN 14010 is in direct
conflict with another North American standard applicable in Ontario. (example: Canadian Electrical
Code or general requirements of the Code Adoption Document) O.Reg.209/01, s.5 (2)
2.8.1. Existing Parking Garage Lifts shall comply with the Regulation.
a) Periodic inspection of existing Parking Garage Lift installations shall commence after January 1,
2010.
b) Existing Parking Garage Lifts are ones that have been commissioned / put into operation prior to
January 1, 2009.
th
3300 Bloor Street West, 14 Floor, Centre Tower, Toronto, Ontario M8X 2X4
Telephone: 416-734-3300 Fax: 416-231-5435 Toll Free: 1-877-682-8772
Putting Public Safety First
ED-194-08.doc 5/7
c) Owners will be responsible for the inspection fees and future safety inspections, at such intervals as
determined by TSSA. O.Reg.209/01, s.4 (1), s.44.
d) Alterations of Existing Parking Garage Lifts shall conform to the Code Adoption Document.
1) Alterations shall be performed by registered contractors.
e) Identification of general safety and regulatory violations during the first periodic inspection of existing
Garage Parking Lifts may require modifications to bring the devices into compliance.
f) Safety requirements for existing lifts will be determined and refined over time by TSSA in conjunction
with an Industry Working Group made up of manufacturer, contractor, and owner representatives.
g) Data-capture for existing devices will be conducted by TSSA field staff during the first periodic
inspection.
h) After the first Periodic inspection is complete, TSSA will determine the frequency for the next Periodic
inspection. (Frequency will be determined using a risk based model,)
2.9.1. Every Parking Garage Lift requires a license that must be posted at the device and is to be renewed on an
annual basis by the owner. O.Reg.209/01, s.12, s.28, s.30.
a) During the Initial inspection, an application for the device license will be supplied to the owner to fill
in and return to the inspector along with payment based on the current license fee schedule.
b) Owners of existing devices shall apply for a license prior to January 1, 2010.
c) The initial application for the licensing of an existing device shall include:
1) Owner name and address
2) Device address
3) Number of load carriers (per power unit)
4) Total load and load carrier capacity ratings
5) Description of controls used to prevent access to the device by the general public
d) Each power unit will constitute an installation and will require a separate license.
2.10.1. The owner shall ensure the device is maintained by a registered contractor. Maintenance and maintenance
frequency shall be in accordance with the manufacturer’s recommendations, but in no case shall the time
between maintenance visits be longer than one year. O.Reg.209/01, s.32
a) For new or altered installations, maintenance requirements are effective January 1, 2009.
b) Maintenance requirements of existing installations are effective June 1, 2009.
c) Maintenance shall include inspection and testing of the safety device. O.Reg.209/01, s.33.
2.10.2. Every owner of a Parking Garage Lift and every contractor shall maintain a log book, in accordance with
the manufacturer’s recommendations, for the device that they own or maintain. The log book shall be
readily available at the location of the device. O.Reg.209/01, s.34
a) A manufacturer supplied list of items requiring regular maintenance and the recommended
maintenance frequency for each item shall be provided by the supplier of the equipment and should be
included as part of the maintenance log book.
b) Log books shall remain on site for 5 years as per O.Reg.209/01, s.34.(2)
c) Maintenance requirements for PGL’s will be determined and refined over time by TSSA in conjunction
with an Industry Working Group made up of manufacturer, contractor, and owner representatives.
th
3300 Bloor Street West, 14 Floor, Centre Tower, Toronto, Ontario M8X 2X4
Telephone: 416-734-3300 Fax: 416-231-5435 Toll Free: 1-877-682-8772
Putting Public Safety First
ED-194-08.doc 6/7
2.11. Operating Requirements (for Owners)
2.11.1. Every owner of an elevating device shall ensure that the attendants and operators have knowledge of the
device and complies with the Technical Standards and Safety Act, 2000 and O.Reg.209/01. O.Reg.209/01,
s.40, s. 13.
2.11.2. Owners shall have an operator training program and a log of trained persons.
2.11.3. Operation shall be restricted to only trained operators through the use of keys or equivalent systems.
2.11.4. Owners shall annually renew and post the device license at the power unit, controller or operating station.
2.11.5. Owners shall post:
a) The installation number tag at the power unit and identify each load carrier unit.
b) Shall post a capacity sign (in kilograms) at the operating station and each load carrier.
c) Shall post safe operating procedure signage at each operating station.
1) Signs may be shared between operating stations.
2) The sign must be legible from the operating station otherwise individual signs shall be required.
2.11.6. Where an accident or incident occurs, the owner and/or contractor shall notify TSSA as per requirements of
O.Reg.209/01, s.36.
2.11.7. Every owner of a Parking Garage Lift shall ensure safe and unobstructed access to all serviceable parts of
the device for maintenance and service.
2.11.8. Keys for access to all locked parts of the device shall be readily available. O.Reg.209/01, s.37.
Electronic copies of these documents can be found on the Government of Ontario web site at:
http://www.e-laws.gov.on.ca or
http://www.tssa.org/regulated/elevating/elevatingSafety.asp?loc3=act
Electronic copies of these documents can be found on the TSSA web site at:
http://www.tssa.org/regulated/elevating/elevatingSafety.asp?loc3=act
4. Effective Date
________________________ ________________________
Rob Kremer, P. Eng., Roger Neate
Engineering Manager, EDAD Program Operations Manager, EDAD Program