Nalanda University, at Rajgir, Bihar.: Technical Specifications
Nalanda University, at Rajgir, Bihar.: Technical Specifications
PACKAGE- 5A
TECHNICAL SPECIFICATIONS
(ELV WORKS)
General: All the material shall must confirm the good working condition
as per the local weather/temperature and environmental condition. The
product quality must confirm the seismic zone-IV. Before supply of the
material lost type test certificate issued by the NABL/NABL accredited
laboratory not earlier than 3 years must be submitted for Pre-Despatch
Inspection(s).
-1-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
TECHNICAL SPECIFICATION
SCOPE OF WORK
Devices and services that shall run on the passive network shall include, but not
limited to, the following:
Cabling installation for data and voice communications shall originate at networking
racks and terminate at IOs terminated at wall.
All cables and terminations shall be tested @500 MHz identified, labelled and
documented at all locations.
The system integrator carrying out the SITC shall make the system entirely
operational for its intended use, by addition of components specific to its
make/model even if not specifically mentioned in the BoQ without any additional
cost.
System integrator shall provide Ethernet cabling connectivity for all other services,
utilities and systems (such as, but not limited to – HVAC, Electrical, Plumbing, Lift
Panels and any other such) besides those already forming part of ELV (CCTV, FAS,
ACS, Data and Telecom) upto the device location as indicated by the respective
utility contractor, e.g., DDCs, PLCs, FRTUs and other such. The respective utility
contractor shall indicate the location of their devices and rack where the cabling is
to be terminated.
IEEE 802.3af Data Terminal Equipment (DTE) Power via Media Dependent
Interface (MDI)
-2-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
TIA / EIA
Wherever there is reference to multiple standards and/codes, the ones most recent
and most stringent shall apply.
It shall be the responsibility of the system integrator and OEM manufacturer to ensure that:
All Passive Components in the structured cabling distribution network shall meet or
exceed the relevant component specification of the EIA/TIA 568-B and EIA/TIA
568-C.2 series and ISO/IEC 11801: 2002 standards; or later version as applicable
at the time of installation.
The structured cabling distribution network compliant channels will meet or exceed
the Guaranteed Channel Performance as per relevant standards in the structured
cabling distribution network Performance Specifications in effect at the time of
installation.
The site will be duly certified by OEM for a period of 25 years from the date of
issuance of the registration certificate or installation, whichever is earlier, for which
they shall submit detailed performance test reports for every IO installed.
a.) F/UTP CAT6Acable and associated components such as Patch Panels, IOs/RJ45 Jacks,
Patch Cords
b.) UTP CAT6 cable and associated components such as Patch Panels, IOs/RJ45 Jacks, Patch
Cords
c.) Single-Mode fiber optic cable and associated components such as distribution shelves,
LIUs, pigtails and patch cords
Installation:
The final branch connections with single pair cables in conduits and the maximum
number of cables in each conduit shall be as follows :
-3-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
-4-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
-5-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The containment system for F/UTP CAT6A cabling shall consist of PVC conduits and multi-
compartment raceways. PVC conduits shall be dedicated for all IT/ELV related cabling. Wherever
multi-compartment raceways are to be used, the F/UTP cabling for IT/ELV shall be laid in one of the
dedicated compartments.
F/UTP cables bunched together with electrical distribution cables or other ELV cables such as fire
detection, pubic address and IBMS signal/communication cables are not acceptable.
Sharp bends such as at 90 degrees are to be avoided – the integrator shall follow OEM guidelines for
maintaining bending radii.
-6-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
All fiber cables and components must be from a single OEM (Including
xi Cable / Component
F/UTP CAT6ACabling System)
Must pass the following : -IEC794-1-E1, IEC794-1-E2, IEC794-1-E3,
xii Testing Parameters IEC794-1-E4, EIA-455-104, IEC794-1-E7, IEC794-1-E10, IEC794-1-E11,
IEC794-1-F5 or equivalent tests
The fiber cable must have been designed to provide optimum
xiii Multi-channel capability performance from 1265nm to 1625nm making it suitable for 16 –
channel Course Wavelength Division Multiplexing (CWDM) applications
-7-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
While laying FO cables, excessive sharp bends shall be avoided – as a guideline a bending radius of
not less than 15 x cable diameter shall be maintained, however, integrator shall follow the OEM’s
cable laying guideline for the same wherever they are available.
Spare cable loop having length of 12-15 feet shall be left spare inside the manhole chamber for any
future jointing, maintenance and extension of branches.
-8-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Construction shall be single section welded robust with ventilation holes on the sides
and top & bottom covers with provision to mount 2 fans
Top/ Bottom covers and side panels shall be of sheet steel, powder coated
Vertical 19” metric panel mounts and door trims shall be of sheet steel and powder
coated
The top and bottom covers shall be provided with four cut outs on top and bottom
cover for cable entry and round cuts shall be edge protected with rubber grommets
Two pairs of 19” equipment mounting angles with mounting holes conforming to IEC
297-3
Cooling shall be achieved with the help of two fans, 90 CFM capacity each, mounted
on top
Power shall be provided in form 19” rack mountable power strip which shall consist of
minimum four 5/15A power sockets. Power strip shall be provided with 20A MCB
Cantilever shelf – at least one front mounting 1U cantilever shelf shall be provided
with depth of 250 mm or more
1U vertical cable managers on a/r (as required basis) for dressing of cables for 24
ports patch panel, 24 ports switch
Horizontal managers on A/R basis for ensuring neat and aesthetically clean
installation
Cabinet material – cabinet shall be made of 16 Gauge (1.5mm) thick cold rolled steel
sheets or thicker
EIA standard pattern design with 12-24 tapped holes (EIA-310-E compliant)
-9-
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
perforated door. Top cover with cable entry and Bottom open. 42 U 19" L type angle
Front & Rear on 6 x punched section. Cabinet color should be Black and light grey
The Thickness of the CRCA sheets used for Doors is 1.5mm and for Side Panels is
1.5mm
Top and Bottom Covers and Side panels shall be of sheet steel and Primary Dip Coat
= 20-30 Microns Power Coat = 80-120 Microns
Vertical 19” metric panel mounts and door trims shall be of sheet steel and powder
coated
The Top cover with min. 4 cut out of diameter 100mm or more for cable entry.
Bottom cover with 4 cut out of diameter 100mm or more for cable entry. All cut outs
blanked with plastic caps
Perforation - for full / split perforated doors the style should be” Honeycomb” type of
perforation for maximum air circulation and stiffness. Doors should have min. 75%
perforation for better air circulation
Locks options – options shall be available such as slam lock - common key or unique
key, Swing handle lock, Digital Keypad operated locks, Biometric locks
Side panels – must contain slam latches for locking purpose and option of providing
slam locks, or screw fitted for removal, if required
Two pairs of 19” Equipment mounting angles with mounting holes conforming to IEC
2973
Front glass door made of toughened glass, tinted with easily detachable hinges
Two pairs of slotted vertical cable channel shall be provided at front and back for
managing cables
Rack shall be supplied with equipment mounting hardware in pack of 20s such as
mounting nuts and screws either 12-24 or M6 type as applicable
Minimum 2 nos. of 8 x 5/15 Amps power supply sockets, 2 nos. of vertical cable
managers and 2 no. of 19” 1U size horizontal cable managers
Finish – cabinet shall be black or grey epoxy powder-coated of durable quality. The
Powder coating of the racks is as per Nano coated, electro-dip coat primed to 20
microns, and power coated with texture polyester with 80 to 120 microns for long
lasting paint against corrosion
- 10 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
EIA standard pattern design with 12-24 tapped holes (EIA-310-E compliant) or EIA
standard pattern design with 3/8” (9.5mm) square punches for Cage Nuts for
mounting
Key considerations for network are – gigabit connectivity to each user from the
nearest distribution rack to various users/departments/devices in a topology
consisting of core switches at central server room followed by the distribution and
edge/access switches.
The network shall have a mix of components for supporting PoE+ as well as non-PoE
devices.
A robust fiber optics based backbone is being provided. It shall be based on ring
topology using single mode fiber optics cable. The vendor shall ensure that the
networking switches shall be populated with the necessary transceivers for achieving
this design objective.
The integrators shall propose and supply enterprise class networking switches only.
- 11 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Switch Architecture
The switch should have 8 X 10/100/1000 Base-Tx ports; all ports shall be 802.3at-compliant
PoE+ capable, with the switch capable of providing minimum 120 Watts of PoE power
budget.
The switch should also support PoE as per 802.3af on all ports.
Switch should have 8 Nos. 10 Base-T/100Base-Tx/1000Base-Tx auto-sensing ports complying
to IEEE 802.3, IEEE 802.3at, IEEE 802.3u and 802.3ab standard, supporting half duplex
mode, full duplex mode and auto-negotiation on each port.
Switch should have minimum 2 dedicated SFP ports.
The switching fabric for all the LAN ports shall be non-blocking and each port shall run at
wire-speed / line-rate. Switching fabric capacity of the switch should be capable to run all the
ports at line-rate.
Switch should support both IPv4 and IPv6 – Switch should support features like Neighbour
Discovery, Syslog, Telnet, SSH, Web GUI, SNMP, NTP, DNS, RADIUS over IPv6
Switch should have non-blocking switching bandwidth of minimum 24Gbps.
Switch should have forwarding rate of minimum 14Mpps.
Switch should be IPv6-Ready from Day 1
Layer 2 Features
Security Features
Switch should support MAC Address based Filters / Access Control Lists (ACLs) on all switch
ports.
Switch should support Port based Filters / ACLs.
Switch should support RADIUS and TACACS+ for access restriction and authentication.
Secure Shell (SSH) Protocol, HTTP and DoS protection.
ARP spoofing, DHCP snooping etc.
Switch should support static ARP, Proxy ARP, UDP forwarding and IP source guard.
Management Features
- 12 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Switch should support System & Event logging functions as well as forwarding of these logs
to multiple syslog servers.
Switch should support on-line software reconfiguration to implement changes without
rebooting. Any changes in the configuration of switches related to Layer-2 & 3 functions,
VLAN, STP, Security, QoS should not require rebooting of the switch.
Switch should have comprehensive debugging features required for software & hardware
fault diagnosis.
Switch should support multiple privilege levels to provide different levels of access.
Switch should support SNTP (Network Time Protocol).
Switch should support FTP/TFTP for software upgrade.
Switch support multiple configuration file & backup configuration file.
Switch Architecture
The switch should have 24 X 10/100/1000 Base-Tx ports; all ports shall be 802.3at-compliant
PoE+ capable, with the switch capable of providing minimum 350 Watts of PoE power
budget.
The switch should also support PoE as per 802.3af on all ports.
Switch should have 24 Nos. 10 Base-T/100Base-Tx/1000Base-Tx auto-sensing ports
complying to IEEE 802.3, IEEE 802.3at, IEEE 802.3u and 802.3ab standard, supporting half
duplex mode, full duplex mode and auto-negotiation on each port.
Switch should have minimum 4 dedicated or shared SFP ports.
The switching fabric for all the LAN ports shall be non-blocking and each port shall run at
wire-speed / line-rate. Switching fabric capacity of the switch should be capable to run all the
ports at line-rate.
Switch should support auto switch replacement in an existing stack with the new switch
without any configuration for joining the stack
Switch should support link aggregation across multiple switches in a stack.
Switch should support both IPv4 and IPv6 – Switch should support features like Neighbour
Discovery, Syslog, Telnet, SSH, Web GUI, SNMP, NTP, DNS, RADIUS over IPv6
Switch should have non-blocking switching throughput of minimum 52Gbps.
Switch should have forwarding rate of minimum 35Mpps.
Switch should be IPv6-Ready from Day 1
Switch should have the capabilities to stack upto 8 switches with dedicated stacking port/
virtual chassis from day 1 and with minimum stacking bandwidth of 80Gbps
Layer 2 Features
- 13 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Switch should support classification and scheduling as per IEEE 802.1P on all ports.
Switch should support four queues per port.
Switch should support QoS configuration on per switch port basis.
Switch should provide traffic shaping and rate limiting features (for egress as well as ingress
traffic).
Security Features
Switch should support MAC Address based Filters / Access Control Lists (ACLs) on all switch
ports.
Switch should support Port based Filters / ACLs.
Switch should support RADIUS and TACACS+ for access restriction and authentication.
Secure Shell (SSH) Protocol, HTTP and DoS protection.
ARP spoofing, DHCP snooping etc.
Switch should support static ARP, Proxy ARP, UDP forwarding and IP sourceguard.
Management Features
Switch Architecture
- 14 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The Layer 3 switch should support full Layer 3 features like PIM-DM/, PIM-SM, RIPv1/v2,
OSPF, PBR, ECMP, BGP and VRRP; it shall be supplied with all requisite licences for
implementing Layer 3 capabilities
The Layer 3 Switch should support for full IPv6 features like RIPng, MLD v1/v2, OSPFv3,
VRRPv3 and IPv6 management
The Distribution switch should support virtualization routing and forwarding
Inter-VLAN IP routing for full layer 3 routing between two or more VLANs
IP unicast routing protocols (static, RIPv1/v2 & OSPF)
Virtual Router Redundancy Protocol (VRRP) as per RFC 3768 or equivalent
Switch should support IGMP v1/v2/v3 as well as IGMP v1/v2/v3 snooping or Proxy
Switch should support up to 512 multicast groups/entries
Inter-VLAN IP routing for full layer 3 routing between two or more VLANs
Security Features:
Switch should support MAC Address based Filters / Access Control Lists (ACLs) on all switch
ports
Switch should support Port based Filters / ACLs
Switch should support RADIUS and TACACS+ for access restriction and authentication
Secure Shell (SSH) Protocol, HTTP and DoS protection
IP Route Filtering, ARP spoofing, DHCP snooping
Switch should support static ARP, Proxy ARP, UDP forwarding and IP source-guard
Management Features
The switch should support CLI based or Web-based Management, via a console port
Switch should be SNMP manageable with support for SNMP Version 1, 2 and 3
Switch should support all the standard MIBs (MIB-I& II)
Switch should support TELNET and SSH Version-2 for Command Line Management
Switch should support 4 groups of embedded RMON (history, statistics, alarm and events)
Switch should support System & Event logging functions as well as forwarding of these logs
to multiple syslog servers
Switch should support on-line software reconfiguration to implement changes without
rebooting. Any changes in the configuration of switches related to Layer-2 & 3functions,
VLAN, STP, Security, QoS should not require rebooting of the switch
Switch should have comprehensive debugging features required for software &hardware fault
diagnosis
Switch should support multiple privilege levels to provide different levels of access
Switch should support SNTP (Network Time Protocol)
Switch should support FTP/TFTP for software upgrade
Switch support multiple configuration file & backup configuration file
- 15 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Switch Architecture
The switch should have at least 24Nos. 10G Base- SFP+ ports
The switch should have at least 2 Nos. 40G - QSFP+ ports
The switching fabric for all the LAN ports shall be non-blocking and each port shall run at
wire-speed / line-rate. Switching fabric capacity of the switch should be capable to run all the
ports at line-rate
The switch should support both IPv4 and IPv6 – Switch should support features like Neighbor
Discovery, Syslog, Telnet, SSH, Web GUI, SNMP, NTP, DNS, RADIUS overIPv6
The switch should have non-blocking switching bandwidth of minimum 600Gbps
The switch should have forwarding rate of minimum 440Mpps
The switch shall be supplied with at least one redundant power supply
The switch shall be supplied with at least one redundant fan
The switch should be IPv6 Ready from day 1
Switch should have the capabilities to stack upto 8 switches with dedicated stacking port/
virtual chassis from day 1 and with minimum stacking bandwidth of 240Gbps
The Layer 3 switch should support full Layer 3 features like PIM-DM/, PIM-SM, RIPv1/v2,
OSPF, PBR, ECMP, BGP and VRRP; it shall be supplied with all requisite licences for
implementing Layer 3 capabilities
The Layer 3 Switch should support for full IPv6 features like RIPng, MLD v1/v2, OSPFv3,
VRRPv3 and IPv6 management
The Distribution switch should support virtualization routing and forwarding
Inter-VLAN IP routing for full layer 3 routing between two or more VLANs
IP unicast routing protocols (static, RIPv1/v2 & OSPF)
Virtual Router Redundancy Protocol (VRRP) as per RFC 3768 or equivalent
Switch should support IGMP v1/v2/v3 as well as IGMP v1/v2/v3 snooping or Proxy
Switch should support up to 512 multicast groups/entries
Inter-VLAN IP routing for full layer 3 routing between two or more VLANs
Security Features:
Switch should support MAC Address based Filters / Access Control Lists (ACLs) on all switch
ports
Switch should support Port based Filters / ACLs
Switch should support RADIUS and TACACS+ for access restriction and authentication
Secure Shell (SSH) Protocol, HTTP and DoS protection
IP Route Filtering, ARP spoofing, DHCP snooping
Switch should support static ARP, Proxy ARP, UDP forwarding and IP source-guard
- 16 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Management Features
The switch should support CLI based or Web-based Management, via a console port
Switch should be SNMP manageable with support for SNMP Version 1, 2 and 3
Switch should support all the standard MIBs (MIB-I& II)
Switch should support TELNET and SSH Version-2 for Command Line Management
Switch should support 4 groups of embedded RMON (history, statistics, alarm and events)
Switch should support System & Event logging functions as well as forwarding of these logs
to multiple syslog servers
Switch should support on-line software reconfiguration to implement changes without
rebooting. Any changes in the configuration of switches related to Layer-2 & 3functions,
VLAN, STP, Security, QoS should not require rebooting of the switch
Switch should have comprehensive debugging features required for software &hardware fault
diagnosis
Switch should support multiple privilege levels to provide different levels of access
Switch should support SNTP (Network Time Protocol)
Switch should support FTP/TFTP for software upgrade
Switch support multiple configuration file & backup configuration file
- 17 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
2.5.1. ARCHITECTURE
Shall support spectrum analysis from day one - to detect and mitigate non Wi-Fi interference
Shall support band navigation/band select functionality to enables redirection of 5Ghz clients
to 5Ghz radio
Shall support VLAN pooling which ensures assignment of VLANs to SSID
Shall support AP grouping to enables an admin to easily apply AP-based or radio-based
configurations to all the AP that arein the same group
Controller/Solution should have basic profiling capabilities
Controller should support deep packet inspection for all user traffic across Layer 4-7 network
to analyses information about applications usage, peak network usage times for all access
points from day one in a central and local switching mode
- 18 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Shall support integrated system of detection for wireless intrusion from day one
Controller should support Rogue AP detection and classification and should have WIPs
signatures
i. Web-Based Interface
ii. Network Discovery
iii. Detailed AP Status
iv. Station Troubleshooting
v. Policy Configuration
vi. Wireless Heat Maps
vii. Security Monitoring
viii. 802.11 Packet Capture
ix. Device Identification
x. Reporting
WMS dashboard should provide real time summary of status and activity based on
parameters such as:
- 19 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
WMS should have functionality to generate graphical maps showing wireless coverage heat
maps, devices and location
Solution should support troubleshooting tools, packet capture and reports to resolve
connectivity and performance issues
Solution should allow automated deployment of new software image to one or more APs, or
groups of APs for centralized management through controller
Customizable view listing security events by type, detected by APs, with time detected, mac
address of device and SSID
Web access (https) for configuration, SNMP v1, v2c, v3
Syslog support for system monitoring
Dual Radio, with 802.11a/n/ac (5 GHz) and 802.11g/n (2.4 GHz) concurrent operation
4X4:3Multiple Input / Multiple Output (MIMO) Wave 2 access point
Internal/external antennas for 2.4Ghz and 5Ghz operations with one 10/100/1000 Base-Tx
auto-sensing (RJ45) PoE+ port
AP must have two radios (2.4GHz or 5GHz)
Maximum Associated Users: 240 (120 per radio)
AP must have two ethernet ports for link aggregation
Power Supply: via an 802.3at POE+switch port or OEM supplied Power Injector
Access point should be 802.11ac Wave 2 from day 1
IEEE 802.3 10-BASE-T, IEEE 802.3u 100BASE-TX, 1000BASE-T, IEEE 802.3ab 1000BASE-T
AP must include OEM supplied mounting brackets and accessories for various mounting
options such as ceiling, wall or rooftop
Security:
WPA
IEEE 802.11i WPA2
RFC 2246 TLS protocol version 2.0
RFC 3280 Internet X.509 PKI certificate and CRL profile
RFC 4346 TLS protocol version 1.1/1.0
Encryption:
WEP – 64 and 128 bit, TKIP-MIC: RC4 40 bit, 104 bit and 128 bit, SSL & TLS: RC4 128-bit
PHY data rates up to 1.8Gbps per AP
Support for band steering, client load balancing, LLDP
Should support 802.1X authentication
Should support centralized configuration and management and reporting
Solution should have Bonjour Support for supporting Apple devices
Should support Wi-Fi Alliance Protected Access 1.0 (WPA) and 2.0 (WPA2)
Network Discovery
- 20 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
networks, and rich visibility into end-user connectivity and application performance assurance
issues.
System should support Automated configuration deployment and automated staging
capability
Fault Management
System should support comprehensive fault management for all the network devices
Should give event details &and be capable of suppressing fault by launching fault summary
System should be able to monitor & troubleshoot problems at the protocol level
The system shall be capable of pre-provisioning with base lined configuration & image
Performance Management
Security Management
Should support AAA server and user access management for BYOD functionality for minimum
5000 concurrent users with complete Guest life cycle management and should have minimum
3000 devices license from day 1
Should support inventory management on per device basis
Should be able handle Alert/Event management
Should support workflows for improved setup and troubleshooting
System should offer centralized change – audit logging, graphical device management
The Solution should have AAA functionality and Guest Life Cycle Management in redundant
mode (Bidder should propose any additional hardware if required)
Network Management and Monitoring entity should have the capabilities to launch and
integrate AAA functionality
- 21 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
GENERAL
The Surveillance System components must be TCP/IP based components working on the same
backbone network as the Data Network (LAN).
Surveillance system must be scalable in terms of equipment (no. of cameras), storage capacity
and licenses.
True open platform functionality is an essential aspect of this specification; cameras from
different OEMs must be able to integrate seamlessly with the specified 3rd party VMS software
platformswithout any loss of features and functionality. Similarly, supplied VMS software
platforms must also be able to integrate with a variety of cameras from different manufacturers
in future.
For better saving on storage and bandwidth the compression used shall be H.264 high profile for
all types of cameras and devices. H.264 high profile shall be a common requirement for all
cameras and devices irrespective of whether mentioned in individual sub-sections or not or if
mentioned otherwise.
Cameras shall have a wide dynamic range of between 85 to 95dB (for Fixed Box/CS-Mount and
Indoor Dome/Mini-dome models and between 120 to 130dB (for indoor/outdoor PTZ models)for
ensuring good image performance in varying light conditions.
- 22 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
GENERAL REQUIREMENTS:
The camera shall be a Full HD Rapid Dome PTZ camera supporting triple streaming of
codecs;simultaneously generating and transmitting JPEG and two independent H.264High Profile
video streams different in resolutions and frame rates.
The camera shall have a 1/3” type CMOS/CCD/MOS sensor of approx. 2.0 Megapixels and have a
True day/night capability.
The camera shall be capable of 360 degree pan rotation and a minimum tilt range of 0° to 180°,
designed for ceiling mount operation.
The camera shall incorporate a built-in 30X optical, auto-focus zoom lens, and shall have 12X
digital zoom capability with 360X total zoom capability.
The camera shall be able to automatically sequence through the preset positions in
programmable sequence, i.e., preset tours.
The PTZ camera shall be able to send and receive trigger commands from any other camera even
if the VMS is offline.
The camera shall produce a high quality picture with a minimum illumination of 0.4 lux in color
mode or 0.02 lux in B/W mode at F1.6 or better. It shall offer IR cut filter that switches on/off
to enhance low-light sensitivity during B/W mode.
The camera shall be equipped with an intelligent automatic backlight compensation capability,
mask settings and level adjustment capabilities to compensate for backlight by masking out
brighter areas.
The camera shall have feature to transform shadows and dark areas into natural and crisp images
in real time.
The camera shall support automatic tracing white balance adjustment capability.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall support JPEG and H.264 high profile compression. The minimum resolution for
each codec shall be 1920x1080.
The camera shall be capable of generating HTML code for the video image, allowing for easy web
page integration.
The camera shall be capable of supporting up to five (05) users simultaneously over the network.
The camera shall have the capability to stream JPEG and H.264 high profile video in TCP protocol
H.264 in UDP (unicast/multicast) protocol.
- 23 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall incorporate a built-in algorithm for intelligent motion detection capability. The
camera shall offer this feature with minimum four configurable areas per scene and ten sensitivity
levels adjustments.
The camera shall have 2-way audio features, i.e., the camera shall have built-in audio input and
output jacks and be capable of transmitting and receiving full duplex audio stream on the same
Ethernet connection as the video. The audio shall be encoded using the G.726 or equivalent
ADPCM standard.
The camera shall support the following network protocols: TCP/IP, UDP/IP, HTTP, HTTPS, RTSP,
RTP, RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, SNMP, UPnP
The camera shall be compliant with the industry standard ONVIF (Open Network Video Interface
Forum) specification with Profile S compliance.
The camera shall have an email (SMTP) notification capability and shall support scheduled
transfer of image data via FTP to an FTP server.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera software should include IP Setup (including group camera management) program,
Firmware Upgrade Tool, Privacy Masking Tool. The software shall be supplied with the camera as
a standard accessory.
The minimum electronic shutter setting shall be 1 second, and a maximum of 1/20,000 sec.
The camera shall have 4 external I/O Terminals for external alarmsor controls.
The camera shall be capable of limiting bandwidth from 64 kbps to 8 Mbps in H.264 mode while
also being able to operate without bandwidth limitation in JPEG format.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
Terminal inputs, video motion detection alarms, and alarm commands shall be able to trigger
actions such as memory recording, FTP file transfer, e-mail notification, alarm indications on web
browser, alarm terminal output, and alarm command.
The camera shall have a local storage capability via a memory card slot which can support up to
64GB memory card that can cache images in the event of a network failure. The camera shall
also support manual/alarm recording to the optional memory card. The camera shall provide
notification of the remaining capacity of the memory card.
The camera shall have an integrated minimum 30X auto-focus zoom lens.
Focal length shall be 4.3 to 129 mm with field of view coverage of 2.4° to 63.5°.
- 24 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
VIDEO-ELECTRICAL REQUIREMENTS:
The camera input power shall be PoE+ or optionally AC/DC 24V which shall be included in supply,
if necessary.
AUDIO REQUIREMENTS:
The camera shall support bi-directional audio, using G.711 (64kbps) and G.726 (32kbps) codecs.
It shall support audio modes such as - OFF or Mic (Line) input or Audio output or Interactive (Half
duplex) or Interactive (Full duplex)
The camera shall have mini-jack connectors accessible via pigtail to support external microphone
and active speakers.
MECHANICAL REQUIREMENTS:
The camera shall have 360° endless pan rotation and 0° to 180° tilt range. The unit shall be
designed for ceiling mount operation.
The camera shall have pan/tilt speeds of 300° per second in presets
The camera shall be vandal resistant with IK10 rating or IEC 62262 compliance.
GENERAL REQUIREMENTS:
The camera shall be a Full HD Rapid Dome PTZ camera supporting triple streaming code
simultaneously generating and transmitting JPEG and two independent H.264 High Profile video
streams different in resolutions and frame rates.
The camera shall havea 1/3” type CMOS/CCD/MOS sensor of approx. 2.0 Megapixels and have a
True day/night capability.
The camera shall be capable of 360 degree pan rotation and a minimum tilt range of 0° to 180°,
designed for ceiling mount operation.
The camera shall incorporate a built-in 30X optical, auto-focus zoom lens, and shall have 12X
digital zoom capability.
The camera shall be able to automatically sequence through the preset positions in
programmable sequence, i.e., preset tours.
The camera shall produce a high quality picture with a minimum illumination of 0.6 lux in color
mode or 0.07 lux in B/W mode at F1.6 or better. It shall offer IR cut filter that switches on/off to
enhance low-light sensitivity during B/W mode.
The camera shall be equipped with an intelligent auto backlight compensation capability, mask
settings and level adjustment capabilities to compensate for backlight by masking out brighter
areas.
- 25 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall have feature to transform shadows and dark areas into natural and crisp images
in real time.
The camera shall support automatic tracing white balance adjustment capability.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall support JPEG and H.264 high profile compression. The minimum resolution for
each codec shall be 1920x1080.
The camera shall be capable of generating HTML code for the video image, allowing for easy web
page integration.
The camera shall be capable of supporting up to five (05)users simultaneously over the network.
The camera shall have the capability to stream JPEG and H.264 high profile video in TCP protocol
H.264 in UDP (unicast/multicast) protocol.
The camera shall incorporate a built-in algorithm for intelligent motion detection capability. The
camera shall offer this feature with minimum four configurable areas per scene and ten sensitivity
levels adjustment capabilities.
The camera shall have 2-way audio features, i.e., the camera shall have built-in audio input and
output jacks and be capable of transmitting and receiving full duplex audio stream on the same
Ethernet connection as the video. The audio shall be encoded using the G.726 or equivalent
ADPCM standard.
The camera shall support the following network protocols: TCP/IP, UDP/IP, HTTP, HTTPS, RTSP,
RTP, RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, SNMP, UPnP.
The camera shall be compliant with the industry standard ONVIF (Open Network Video Interface
Forum) specification with Profile S compliance.
The camera shall have an email (SMTP) notification capability and shall support scheduled
transfer of image data via FTP to an FTP server.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera software should include IP Setup (including group camera management) program,
Firmware Upgrade Tool, Privacy Masking Tool. The software shall be supplied with the camera as
a standard accessory.
The minimum electronic shutter setting shall be 1 second, and a maximum of 1/20,000 sec.
The camera shall have 4 external I/O Terminals for external alarmsor controls.
- 26 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall be capable of limiting bandwidth from 64 kbps to 8 Mbps in H.264 mode while
also being able to operate without bandwidth limitation in JPEG format.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
Terminal inputs, video motion detection alarms, and alarm commands shall be able to trigger
actions such as memory recording, FTP file transfer, e-mail notification, alarm indications on web
browser, alarm terminal output, and alarm command.
The camera shall have a local storage capability via a memory card slot which can support up to
64GB memory card that can cache images in the event of a network failure. The camera shall
also support manual/alarm recording to the optional memory card. The camera shall provide
notification of the remaining capacity of the memory card.
The camera shall have an integrated minimum 30X auto-focus zoom lens.
Focal length shall be 4.3 to 129 mm with field of view coverage of 2.4° to 63°.
VIDEO-ELECTRICAL REQUIREMENTS:
The camera input power shall be PoE+ or optionally AC/DC 24V which shall be included in supply,
if necessary.
AUDIO REQUIREMENTS:
The camera shall support bi-directional audio, using G.711 (64kbps) and G.726 (32kbps)codecs.
It shall support audio modes such as - OFF or Mic (Line) input or Audio output or Interactive (Half
duplex) or Interactive (Full duplex)
The camera shall have mini-jack connectors accessible via pigtail to support external microphone
and active speakers.
MECHANICAL REQUIREMENTS:
The camera shall have 360° endless pan rotation and 0° to 180° tilt range. The unit shall be
designed for ceiling mount operation.
The camera shall have maximum pan/tilt speeds of 350° per second in presets.
The camera shall be vandal resistant with IK10 rating or IEC 62262 compliance.
The camera shall have inbuilt dehumidification/defog feature to remove moisture from the
camera.
The camera shall be outdoor rated having IP66 rating for ingress protection.
- 27 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
GENERAL REQUIREMENTS:
The camera shall be a Full HD dome network camera supporting three codecs, JPEG and 2 nos.
H.264 high profile, any two of which can be used simultaneously. The camera shall utilize a 1/3”
type CCD/MOS/CMOS sensor of approx. 2.0 Megapixels and have a true day/night capability.
The camera shall have an IK10 rated vandal-proof housing and shall comply with IEC 62262, IEC
60068-2-75 test standard for impact resistance.
The camera shall support JPEGformatand H.264 high profile compression. The camera shall be
able to select the high quality mode in JPEG 1920x 1080 at minimum 25fps. The camera shall
also be able to support full HD mode of 1920 x 1080 in H.264 compression mode with 60fps.
The camera shall incorporate a built-in web server, so that astandard web browser such as
Microsoft Internet Explorer. Mozilla Firefox or Google Chrome can be used to access the camera
without need for special viewer software.
The camera shall have an advanced function which will allow the camera image to be viewed in
JPEG format without using any plug-ins and thus allowing HTML code for the video image to be
generated, allowing for easy web page integration.
The camera shall be capable of supporting up to five (05)users simultaneously over the network.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall support the following Network protocols: TCP/IP, UDP/IP, HTTP, RTSP, RTP,
RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, and SNMP.
The camera shall have an integral 3 to 9 mm p-iris type vari-focal lens with remote zoom and
focus.
The camera shall be Power over Ethernet (PoE) capable, compliant to the IEEE 802.3af standard.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera software should include IP Setup (including group camera management) program,
Firmware Upgrade Tool, Privacy Masking Tool. The software shall be supplied with the camera as
a standard accessory.
- 28 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The minimum electronic shutter setting shall be 1 second, and a maximum of 1/40,000 sec.
The camera shall be capable of limiting the bandwidth from 64 kbps to 8 Mbps in MPEG-4 or
H.264 high profile, and from 0.5 Mbps to an unlimited bandwidth in JPEG.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
The camera shall feature a body-based automatic back focus mechanismfor automatic and
remote back focus adjustment by way of hardware button or software based control.
Focal length shall be 3 to 8 mm with field of view coverage of approximately 90˚ to 34˚
VIDEO-ELECTRICAL REQUIREMENTS:
The camera shall operate at a minimum scene illumination of: 0.3 lux in colour and 0.065 lux in
B/W mode, 0 lux with IR.
The camera shall have multiple ON/OFF/Selectable AGC levels which can be set from the settings
menu.
MECHANICAL REQUIREMENTS:
The camera shall have compliance to IEC 60529 standard. Also, it shall have IK10 rated vandal
resistant body for reliability.
GENERAL REQUIREMENTS:
The camera shall be a Full HD dome network camera supporting three codecs, JPEG and 2 nos.
H.264 high profile, any two of which can be used simultaneously. The camera shall utilize a 1/3”
type CCD/MOS/CMOS sensor of approx. 2.0 Megapixels and have a true day/night capability.
The camera shall have an IK10 rated vandal-proof housing and shall comply with IEC 62262, IEC
60068-2-75 test standard for impact resistance.
The camera shall support JPEGformat and H.264 high profile compression. The camera shall be
able to select the high quality mode in JPEG 1920x 1080 at minimum 25fps. The camera shall
also be able to support full HD mode of 1920 x 1080 in H.264 compression mode with 60fps.
The camera shall incorporate a built-in web server, so that astandard web browser such as
Microsoft Internet Explorer. Mozilla Firefox or Google Chrome can be used to access the camera
without need for special viewer software.
- 29 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall have an advanced function which will allow the camera image to be viewed in
JPEG format without using any plug-ins and thus allowing HTML code for the video image to be
generated, allowing for easy web page integration.
The camera shall be capable of supporting up to five (05)users simultaneously over the network.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall support the following Network protocols: TCP/IP, UDP/IP, HTTP, RTSP, RTP,
RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, and SNMP.
The camera shall have an integral 5 to 50 mm p-iris type vari-focal lens with remote zoom and
focus.
The camera shall be Power over Ethernet (PoE) capable, compliant to the IEEE 802.3af standard.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera software should include IP Setup (including group camera management) program,
Firmware Upgrade Tool, Privacy Masking Tool. The software shall be supplied with the camera as
a standard accessory.
The minimum electronic shutter setting shall be 1 second, and a maximum of 1/40,000 sec.
The camera shall be capable of limiting the bandwidth from 64 kbps to 8 Mbps in MPEG-4 or
H.264 high profile, and from 0.5 Mbps to an unlimited bandwidth in JPEG.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
The camera shall feature a body-based automatic back focus mechanismfor automatic and
remote back focus adjustment by way of hardware button or software based control.
Focal length shall be 5 to 50 mm with field of view coverage of approximately 90˚ to 34˚
VIDEO-ELECTRICAL REQUIREMENTS:
The camera shall operate at a minimum scene illumination of: 0.3 lux in colour and 0.065 lux in
B/W mode, 0 lux with IR.
- 30 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall have multiple ON/OFF/Selectable AGC levels which can be set from the settings
menu.
MECHANICAL REQUIREMENTS:
The camera shall have compliance to IEC 60529 standard. Also, it shall have IK10 rated vandal
resistant body for reliability.
GENERAL REQUIREMENTS:
The camera shall be a Full HD fixed-type CS-mount network camera supporting codecs – JPEG,
MPEG4 and H.264 high profile streams. Camera shall have a 1/3” type CMOS/MOS sensor and
have a resolution of approx. 2.0 MP and have a True day/night capability.
The camera shall support JPEG and H.264 high profile compression. The camera shall be able to
select the high quality mode in JPEG 1920 x 1080 at minimum 25fps. The camera shall also be
able to support full HD mode of 1920X1080 in H.264 compression mode with 30fps.
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall incorporate a built-in web server, so that a standard web browser such as
Microsoft Internet Explorer. Mozilla Firefox or Google Chrome can be used to access the camera
without need for special viewer software.
The camera shall be capable of supporting up to five (05)users simultaneously over the network.
The camera shall incorporate a built-in algorithm for intelligent motion detection capability. The
camera shall offer this feature with minimum four configurable areas per scene and ten sensitivity
levels adjustment capabilities.
The camera shall support the following Network protocols: TCP/IP, UDP/IP, HTTP, HTTPS, RTSP,
RTP, RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, SNMP, UPnP, IGMP, ICMP, ARP
The camera shall have both FTP client and server capabilities.
The camera shall have a CS-mount 2MP IR corrected type 5-50mm vari-focal lens.
The camera shall be Power over Ethernet capable, compliant to the 802.3af standard.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera shall have the capability for Camera ID as well as Date/Time data to be
superimposed on the video image.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
- 31 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
The minimum electronic shutter setting shall be 1second, and a maximum of 1/40,000 sec.
The camera shall be capable limiting the bandwidth from 64 kbps to 8192 kbps in H.264 high
profile and an unlimited bandwidth in JPEG.
The camera shall have a CS-mount DC auto-iris type vari-focal lens - Focal length shall be 5-
50mm.
The camera shall operate at a minimum scene illumination of: 0.3 lux in colour and 0.06 lux in
B/W mode.
The camera shall have multiple ON/OFF/Selectable AGC levels which can be set from the settings
menu.
MECHANICAL REQUIREMENTS
The camera lens supplied with the camera shall be IR corrected lens supplied by the camera OEM
or other reputed makes of lens such as Tamaron or Fujinon or equivalent and having focal length
5-50mm, F1.2 to F1.9, DC auto-iris type vari-focal lens.
The camera shall be outdoor rated and having IP66 rating for ingress protection.
GENERAL REQUIREMENTS:
The camera shall be a Full HD fixed-type CS-mount network camera supporting codecs – JPEG,
MPEG4 and H.264 high profile streams. Camera shall have a 1/3” type CMOS/MOS sensor and
have a resolution of approx. 2.0 MP and have a True day/night capability.
The camera shall support JPEG and H.264 high profile compression. The camera shall be able to
select the high quality mode in JPEG 1920 x 1080at minimum 25fps. The camera shall also be
able to support full HD mode of 1920X1080 in H.264 compression mode with 30fps.
- 32 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The network interface shall be an 8-pin RJ-45 connector, 10Base-T/100Base-TX Ethernet. Both
IPv6 and IPv4 shall be supported.
The camera shall incorporate a built-in web server, so that astandard web browser such as
Microsoft Internet Explorer. Mozilla Firefox or Google Chrome can be used to access the camera
without need for special viewer software.
The camera shall be capable of supporting up to five (05) users simultaneously over the network.
The camera shall incorporate a built-in algorithm for intelligent motion detection capability. The
camera shall offer this feature with minimum four configurable areas per scene and ten sensitivity
levels adjustment capabilities.
The camera shall support the following Network protocols: TCP/IP, UDP/IP, HTTP, HTTPS, RTSP,
RTP, RTP/RTCP, FTP, SMTP, DHCP, DNS, DDNS, NTP, SNMP, UPnP, IGMP, ICMP, ARP
The camera shall have both FTP client and server capabilities.
The camera shall have a CS-mount 2MP IR corrected type vari-focal lens (3-8 mm/5-50mm) as
standard accessory.
The camera shall be Power over Ethernet capable, compliant to the 802.3af standard.
The camera shall have privacy zone masking for blocking out unwanted or prohibited areas within
the video image to protect privacy.
The camera shall have the capability for Camera ID as well as Date/Time data to be
superimposed on the video image.
The camera shall have light control mode to select the operating environment, i.e., indoor or
outdoor.
The camera shall have a 2D and 3D noise reduction capability for reducing AGC noise to provide
clear images without motion blur.
The camera shall be capable of automatically transmitting alarm images transfer via FTP file
transfer and/or e-mail. In addition the network camera shall support scheduled transfer of image
information via FTP to an FTP server.
The minimum electronic shutter setting shall be 1 second, and a maximum of 1/40,000 sec.
The camera shall be capable limiting the bandwidth from 64 kbps to 8192 kbps in H.264 high
profile and an unlimited bandwidth in JPEG.
The camera shall have a CS-mount DC auto-iris type vari-focal lens - focal length shall be 5-
50mm.
- 33 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The camera shall operate at a minimum scene illumination of: 0.3 lux in colour and 0.06 lux in
B/W mode.
The camera shall have multiple ON/OFF/Selectable AGC levels which can be set from the settings
menu.
MECHANICAL REQUIREMENTS
The camera lens supplied with the camera shall be IR corrected lens supplied by the camera OEM
or other reputed makes of lens such as Tamaron or Fujinon or equivalent and having focal length
5-50mm, F1.2 to F1.9, DC auto-iris type vari-focal lens.
- 34 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
In order to ensure an openness of the system the VMS application provider shall be
different than the camera make.
The VMS shall support SDK (Software Development Kit) integration for integrating
third party systems.
The VMS shall support ONVIF or PSI alliance – industry standards for the interface of
IP-based physical security products.
The VMS shall allow the direct configuration of IP camera device with no requirement
to directly connect via web page of IP camera or encoder to configure parameters
such as Discovery on IP network and set IP Address, Frame Rate, Resolution, Motion
Detection (within camera or server based), Bit Rate, Key frame interval, Digital I/O,
Audio Inputs/Outputs, Ability to update firmware of IP camera or encoder. Any
configuration changes do not require these services to be restarted.
The VMS shall be compatible with both 32-bit and 64-bit operating systems including
clients working on Windows 7 or later and server operating systems version Windows
Server 2003/2008 or later.
The VMS shall be based on a true open architecture that shall allow for use of non-
proprietary workstation and server hardware, non-proprietary network infrastructure
and non-proprietary storage.
The VMS shall offer a complete and scalable video surveillance solution which allows
cameras to be added on a unit-by-unit basis.
All video streams supplied from analog cameras or IP cameras shall be digitally
encoded in H.264 or better compression formats and recorded simultaneously in real
time.
The VMS shall support configuration of individually configurable multiple streams for
Live & Recording. This functionality shall also support configuration of each camera
stream separately. Altering the setting of one camera shall not affect the recording &
display settings of other cameras.
The VMS shall be able to use multiple CCTV keyboards to operate the entire set of
cameras throughout the system, including cameras of various manufacturers’ brands,
including their PTZ functionalities.
The VMS shall be able to retrieve and set the current position of PTZ cameras with
presets.
The VMS shall consist of a role-based architecture, with each server hosting one or
more roles, typical roles or functions such as the following:
The system shall be managed by a Central Database Role that would contain all the
system information and component configuration.
Database Management Role to authenticate users and give access to the system
based on predefined user access rights or privileges, security partition settings,
configuration of camera units, access control units, PTZ functionalities, camera
sequences and recording schedules.
- 35 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Video Recording Role for managing cameras and encoders under its control and
archiving video.
Routing Role for routing video and audio streams across the networks from the
source to destination.
Health Monitoring Role for monitoring and logging health events and warnings from
the various client applications, roles, and services. It shall also log events within the
Windows Event Log, generating reports on health statistics and health history.
Surveillance User Interface shall be provided for monitoring of video from the
cameras, transactions from access control and the events & alarms. The interface
shall also facilitate recording of the video.
A User Interface for controlling of Pan Tilt & Zoom functionality and pre-sets of PTZ
cameras besides other functions such as - control of iris and focus of the camera,
perform digital zooming on the live as well as playback video.
The User Interface shall allow administrators and operators with appropriate
privileges to monitor the VMS system, run reports, and manage alarms.
The User Interface shall support following to enhance usability and operator
efficiency such as:
The User Interface shall have task for investigation of video bookmark, smart motion
search, archive reports, audit trails and activity reporting.
The user shall have full control over the user workspace through a variety of user-
selectable customization options. Administrators shall also be able to limit what users
and operators can modify in their work space through privileges.
The user workspace shall be accessible by a specific user from any client application
on the network.
Facility shall be available for event or alarm lists to be displayed on any part of the
screen, from a portion of the screen up-to the entire screen, and shall be resizable by
the user. The length of event or alarm lists shall be user-defined. Scroll bars shall
enable the user to navigate through lengthy lists of events and alarms.
The User Interface shall support multiple display tile patterns,e.g., 1 display tile(1x1
matrix),16tiles(8x8matrix)and multiple additional variations.
The User Interface shall support as many monitors as the PC video adapters and
Windows Operating System are capable of accepting.
Shall support live video monitoring on each and every display tile within a task in the
user's workspace.
- 36 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The operator shall be able to drag and drop a camera into a display tile for live
viewing.
The operator shall be able to start/stop recording on any camera in the system,
which is configured to allow manual recording, by clicking on a single button.
The operator shall be able to switch one or more video tile to switch for instant
replay. This operation shall not affect live monitoring of other cameras.
Users shall be able to take snapshots of live video and be able to save or print the
snapshots.
The user shall be able to view the same camera multiple times in different tiles.
A Server Monitoring Service shall be installed on all PCs/servers running with VMS
platform. In the event of a malfunction or failure, the Server Monitoring Service shall
restart the failed service. As a last resort, the Server Monitoring Service shall reboot
the server/PC if it is unable to restart the service.
The platform shall support the Alarm Management functionality. The User shall have
the ability to acknowledge alarms, create an incident upon alarm acknowledgement,
and put an alarm to snooze. The user shall able to spontaneously trigger alarms
based on something he or she sees in the system.
- Allowing operators to switch to instant replay of the video for any archiving
camera with the simple click of button.
- Allowing the operator to select between instant synch of all video streams in
play back mode allowing operators to view events from multiple angles or
across several camera fields, or non-synchronous playback.
- Allowing the operator to simultaneously view the same camera in multiple tiles
at different time intervals.
Pause
Lock Speed
Forward and Reverse
Playbackat:1x,2x,4x,6x,8x,10x,20x,40x,100x.
Forward and Reverse Play back frame by frame
Slow Forward and Reverse Playbackat:1x/8x,1/4x,1/3x,1/2x.
Loop play back between two time markers
- Displaying a single timeline, or optionally one timeline for each selected video
stream, with which the operator can navigate through the video sequence by
simply clicking on any point in the timeline.
- Allowing to query archived video using various search criteria, including but not
limited to, time, date, camera, and area, among others.
- 37 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
- Allowing operators to define an area of the video field in which to search for
motion as well as define the amount of motion that shall trigger search results
in order to retrieve all archived video streams which contain motion which
meets the search parameters. There shall be a graphical timeline where the
time of each search hit shall be indicated.
- Providing still image export to PNG, JPEG, GIF, and BMP format with Date and
Time stamp and Camera Name on the image (snapshot).
- Allowing operators to load previously exported video files from their computer
or network.
The VMS shall permit the user to select multiple entities to be monitored from the
Surveillance User Interface.
The User Interface shall support the ability to manually track a moving target with
the single click of a button.
Visual tracking shall be available with both live and recorded video.
The user interface monitoring client shall able to take control of other client station
based on the privilege level and control the tile of the other client like a video wall
application.
The Configuration User Interface shall allow the administrator or users with
appropriate privileges to change video configuration.
It shall provide the ability to change video quality, bandwidth and frame rate
parameters on a per camera (stream)basis for both live and recorded video.
It shall provide the ability to configure brightness, contrast and hue settings for each
camera on the same.
The Configuration user interface shall provide the capability to enable & change audio
parameters, audio recording serial port configuration, I/O configuration on camera
device units.
The Configuration User Interface shall provide the ability to set recording schedules
and modes for each individual camera, e.g.,:
- Continuous
- On motion and Manual
- Manual only
- Disabled
The Configuration User Interface shall support the creation of schedules to which any
of the following functional aspects can be attached:
- 38 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The Configuration User Interface shall provide the capability to set a pan-tilt-zoom
protocol to a specific camera device serial port and allow mixing domes of various
manufacturers within a system.
ARCHIVING
The Archiver (Recording role) shall use an event and time stamp database for
advanced search of audio/video archives. This database shall be Microsoft SQL 2008
or SQL 2012 or later
The Archiver shall offer a plug and play type hardware discovery service with the
following functionalities:
The Archiver shall have the capacity to configure the key frame intervalin seconds or
number of frames.
The Archiver shall support configuration of pre-alarm and post-alarm recording option
that can be set between one second and 5 minutes on a per camera basis.
The Archiver shall support minimum 300 cameras or 300 Mbps of recording
throughput whichever comes first in case the network is end to end multicast.
Software level motion detection shall able to divide camera field of view in 5
detection zone for setting up individual motion setting in each zone and trigger an
event for each zone separately.
The Archiver shall be able to communicate with camera using 128bits SSL encryption
and HTTPS secure protocol.
The Archiver shall be able to receive multicast UDP streams directly from the camera.
For network topologies that restrict the camera from sending multicast UDP streams,
the Archiver shall redirect audio/video streams to active viewing clients on the
network using multicast UDP.
The Archiver shall be able to redirect audio/video stream to active viewing clients on
the network using unicast UDP or TCP.
The user interface of the monitoring station shall support dynamically switching the
live stream from – High Resolution, Low Resolution & Live (normal).
The Archiver shall allow configuration of retention period for archiving video for pre-
set number of days. It shall also delete oldest video data if the disk is full before the
retention time occurs.
The Archiver shall allow important video sequences to be protected against normal
disk clean-up routines.
- 39 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The Archiver shall keep a log and compile statistics on disk space usage.
The Archiver shall have the capacity to down-sample video streams for storage
saving purposes.
The Standby Directory Role shall take over the responsibility of system management in
case the primary directory fails. The fail over shall occur in less than 1 minute. No action
from the user shall be required.
The Standby Archiver shall act as replacement of Archiver role on hot standby in case
the primary Archiver role is unavailable. Failover shall occur in less than 1 minute. No
action from the user shall be required.
Failover Archiver shall take over for – server failure, storage failure, manually shift the
Archiver Role to standby Archiver to perform maintenance activity on primary server.
It shall be possible for a single Standby Archiver Server to act as the Standby for one or
multiple Archiver roles.
It shall be possible for any Archiver role in the system to be designated as another's
stand by and vice-versa.
The Standby Archiver shall have the ability to act as a Redundant Archiver and maintain
an exact copy of everything recorded by the default Archiver, i.e., audio/video archives,
events and bookmarks.
The Redundant Archiver shall use a multicast video stream from the camera and shall
not require an additional connection to any camera.
UNIFIED WEBCLIENT
The Web client shall be a thin client with no download required other than an internet
web browser or standard web browser plug-ins.
The Web client shall be platform independent and run within Microsoft Internet Explorer,
Firefox, Safari, and Google Chrome.
The VMS shall support mobile apps for various popular smart phones and tablets,
including e.g., Apple iPod Touch, iPhone, and iPad., RIM BlackBerry smart-phones,
Android-compatible smart-phones and tablets.
It shall support monitoring of live camera, receive alarm push notifications, save
snapshots locally on device or control PTZ.
- 40 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Configuration & Specification for Storage System for Video Surveillance &
Recordings on a 24 Hrs x 30Days Basis
1. High Availability
The proposed solution should be a storage system configured with dual, redundant
controllers.
Each controller must have Intel Sandy Bridge Quad core CPU per controller or
equivalent.
The proposed solution should be based on real time optimized operating system and
should not be a general purpose OS.
The proposed solution should support online Microcode / OS upgrades.
Must provide five 9’s availability (99.999%)
2. Investment Protection
Storage system quoted by the OEM should be in the Leaders Quadrant in the latest
Gartner Magic Quadrant for Midrange and High End Modular Storage Arrays Report.
The controllers should have a minimum 30GB cache spread across dual controllers.
The proposed solution should be scalable to more than 110 drives in the same
storage array without the need for upgrading the controllers.
The offered storage shall be supplied with at least 8nos x 1G iSCSI Ports across dual
controllers for host connectivity.
The array proposed should have a minimum of 4nos x 6Gbps 2.0 SAS backend
architecture.
The Proposed storage disk should ensure a minimum total aggregate bandwidth of
2500Mbps on a 90% write &10% read application environment.
6. RAID Support
All RAID types should be industry standard RAID and solution to be configured with
RAID5 protection.
For every 30 disks, 1 no disk should be configured as Global hot spare.
7. Management
The proposed solution must support and be configured for FC &iSCSI protocols.
- 41 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The proposed storage array should be configured with Minimum 150TB usable
capacity using SATA/NL-SAS Drives. The usable capacity is defined as the net storage
capacity available for the application stack, after deducting the penalties imposed by
storage infrastructure requirements, disk and array formatting, RAID penalties, host
OS and file system formatting including overheads or any other penalties which eat
away usable disk space. Drives offered for the above capacity shall be of the highest
capacity offered by the vendor.
The same storage system should support 50% extra growth in terms of performance
and capacity for future expansion without any controller upgrade.
The device should have the following certifications - FCC Class A or CE Mark for
immunity against electromagnetic emissions.
The device should have the following quality and safety standard certifications - CAN/
CSAC22.2-60950/UL60950.
- 42 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Server Hardware - Industry standard Intel based platform, rack mountable, redundancy
architecture for critical hardware components, licensed Microsoft Server Operating
system as per VMS OEM and requisite user licenses, licensed application suites,
Processor: 2 x Quad Core Intel® Xeon® 5150, 2.66 GHz, 4 MB Cache, 1333 MHz FSB or
better or as per CCTV/VMS OEM, min. 8 GB of RAM, 500 GB storage or more, additional
hard drive(s) for video storage, 1360 x 768 or higher screen resolution, 10/100/1000
Ethernet Network Interface Card, DVD ROM Drive.
Client Hardware - Industry standard Intel based platform, rack mountable, licensed
Microsoft Operating system and requisite user licenses, licensed application suites. Intel
Core i7 2600 @ 3.4 GHz or higher, min. 8 GB RAM DDR3, 500 GB SATA II hard drive for
OS and VMS applications, NVidia GTX 570 or DirectX VA 2.0 compatible card with 1 GB
of RAM, 1600 x 1200 or higher screen resolution , 10/100/1000 Mbps Ethernet Network
Interface Card, min. 16x DVD+/- RW Drive.
3.10. 5-PORT INDUSTRIAL PoE+ SWITCH WITH 2-PORT POPULATED MINI GBIC
SFP PORTS:
Switch Properties:
Interface:
- 43 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Physical Characteristics
Standards
1. UL 508
2. UL 60950-1
3. CSA C22.2 No. 60950-1
4. EN 60950-1
Environmental Limits
- 44 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
This section of the specification includes the furnishing, installation, connection and testing of the
microprocessor controlled, intelligent reporting fire alarm equipment required to form a complete,
operative, coordinated system. It shall include, but not be limited to, alarm initiating devices,
alarm notification appliances, Fire Alarm Control Panel (FACP), auxiliary control devices,
annunciators, and wiring as shown on the drawings and specified herein.
The fire alarm system shall comply with requirements of NFPA Standard 72(2013), IS 2189(2008)
and NBC 2016 for Protected Premises Signalling Systems. The system shall be electrically
supervised and monitor the integrity of all conductors.
The fire alarm system shall be manufactured by an ISO 9001 certified company and meet the
requirements of BS EN9001: ANSI/ASQC Q9001-1994
The system and its components shall be Underwriters Laboratories, Inc. listed under the
appropriate UL testing standard for fire alarm applications. Itshould be FM (Factory Manual)
approvedand the installation shall be in compliance with the UL listing.
The panel shall be supplied with all accessories, control modules and power supplies in the
required quantities as per site requirements for all types of field devices to make the system fully
operational.
The FAS shall be supplied with necessary hardware and software so as to ensure networking of
all panels. This shall include all devices such as modules and interfaces for providingfiber-optics
based connectivity between panels and any licences, as applicable.
The detectors and devices connected to the fire alarm panel’s loop(s) shall be auto-addressable
via panel or software or manually addressable via a rotary switch or DIP switch.
The FAS system shall be supplied with all functionality including hardware, software and licences
for integration with a third party IBMS system for real-time monitoring, supervision and control.
The necessary interfaces and functionality for such networking protocols as BaCNet/IP shall be
provided.
FAS panels shall have facility for at least two levels of password based access – typically such as
complete admin rights providing access to all functions (primary or admin or master) and a
secondary level access for reading only and accessing logs and reports etc.
SCOPE
Basic Performance:
- Alarm, trouble and supervisory signals from all intelligent reporting devices shall be encoded
on Class A Signalling Line Circuits (SLC).
- Initiation Device Circuits (IDC) shall be wired Class A as part of an addressable device
connected by the SLC Circuit.
- Notification Appliance Circuits (NAC) shall be wired Class A as part of an addressable device
connected by the SLC Circuit.
- 45 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
- On Class A configurations a single ground fault or open circuit on the system Signalling Line
Circuit shall not cause system malfunction, loss of operating power or the ability to report an
alarm.
- Alarm signals arriving at the FACP shall not be lost following a primary power failure (or
outage) until the alarm signal is processed and recorded.
All equipment and components shall be new, and the manufacturer's current model. The
materials, appliances, equipment and devices shall be tested and listed by a nationally recognized
approvals agency for use as part of a protective signalling system, meeting the National Fire
Alarm Code.
All equipment and components shall be installed in strict compliance with manufacturers'
recommendations. Consult the manufacturer's installation manuals for all wiring diagrams,
schematics, physical equipment sizes, etc., before beginning system installation.
All equipment shall be attached to walls and ceiling/floor assemblies and shall be held firmly in
place (e.g., detectors shall not be supported solely by suspended ceilings). Fasteners and
supports shall be adequate to support the required load.
Main FACP or network node shall contain a microprocessor based Central Processing Unit (CPU)
and power supply. The CPU shall communicate with and control the following types of equipment
used to make up the system: intelligent addressable detectors of various types, addressable
modules, printer, annunciators, and other system controlled devices.
CENTRAL MICROPROCESSOR
The microprocessor shall be a state-of-the-art, high speed, 16-bit RISC device and it shall
communicate with, monitor and control all external interfaces. It shall include an EPROM for
system program storage, Flash memory for building-specific program storage, and a "watch dog"
timer circuit to detect and report microprocessor failure.
The microprocessor shall contain and execute all control-by-event programs for specific action to
be taken if an alarm condition is detected by the system. Control-by-event equations shall be held
in non-volatile programmable memory, and shall not be lost even if system primary and
secondary power failure occurs.
The microprocessor shall also provide a real-time clock for time annotation of system displays,
printer, and history file. The time-of-day and date shall not be lost if system primary and
secondary power supplies fail. The real time clock may also be used to control non-fire functions
at programmed time-of-day, day-of-week, and day-of-year.
A special program check function shall be provided to detect common operator errors.
For flexibility and to ensure program validity, an optional Windows(TM) based program utility
shall be available. This program shall be used to off-line program the system with batch
upload/download, and have the ability to upgrade the manufacturers (FLASH) system code
changes. This program shall also have a verification utility, which scans the program files,
identifying possible errors. It shall also have the ability to compare old program files to new ones,
identifying differences in the two files to allow complete testing of any system operating changes.
This shall be in incompliance with the NFPA 72 requirements for testing after system modification.
- 46 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
OPERATOR CONTROL
1. Acknowledge Switch:
Activation of the control panel acknowledge switch in response to new alarms and/or troubles
shall silence the local panel piezo electric signal and change the alarm and trouble LEDs from
flashing mode to steady-ON mode. If multiple alarm or trouble conditions exist, depression of this
switch shall advance the LCD display to the next alarm or trouble condition.
Depression of the Acknowledge switch shall also silence all remote annunciator piezo sounders.
Activation of the alarm silence switch shall cause all programmed alarm notification appliances
and relays to return to the normal condition after an alarm condition. The selection of notification
circuits and relays that are silence-able by this switch shall be fully field programmable within the
confines of all applicable standards. The FACP software shall include silence inhibit and auto-
silence timers.
The Alarm Activate switch shall activate all notification appliance circuits. The drill function shall
latch until the panel is silenced or reset.
Activation of the System Reset switch shall cause all electronically-latched initiating devices,
appliances or software zones, as well as all associated output devices and circuits, to return to
their normal condition.
5. Lamp Test:
The Lamp Test switch shall activate all local system LEDs, light each segment of the liquid crystal
display and display the panel software revision for service personal.
Each loop of the fire alarm panel shall provide power to and communicate with up to a minimum
of 127 intelligent addressable detectors and 127 intelligent addressable modules (monitor or
control) or a mix of up to 250 detectors and devices in any combination.
Type 1: The control panel or each network node shall be equipped with 1 installed loop with each
loop having a capacity of a minimum 127 addressable detectors and 127 addressable modules or
a mix of up to 250 detectors and devices in any combination with max. 80% of loop loading in a
single loop. It shall be modularly expandable up to minimum 10 loop capacity with each loop
having a capacity of minimum 127 addressable detectors and 127 addressable modules or a mix
of up to 250 detectors and devices in any combination with max. 80% of loop loading in a single
loop. However, the number of loop cards can be done as per the OEM configuration.
Type 2: The control panel or each network node shall be equipped with 2 installed loops with
each loop having a capacity of a minimum 127 addressable detectors and 127 addressable
modules or a mix of up to 250 detectors and devices in any combination with max. 80% of loop
loading in a single loop. It shall be modularly expandable up to minimum 10 loop capacity with
each loop having a capacity of minimum 127 addressable detectors and 127 addressable modules
or a mix of up to 250 detectors and devices in any combination with max. 80% of loop loading in
a single loop. However, the number of loop cards can be done as per the OEM configuration.
- 47 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Type 3: The control panel or each network node shall be equipped with 3 installed loops with
each loop having a capacity of a minimum 127 addressable detectors and 127 addressable
modules or a mix of up to 250 detectors and devices in any combination with max. 80% of loop
loading in a single loop. It shall be modularly expandable up to minimum 10 loop capacity with
each loop having a capacity of minimum 127 addressable detectors and 127 addressable modules
or a mix of up to 250 detectors and devices in any combination with max. 80% of loop loading in
a single loop. However, the number of loop cards can be done as per the OEM configuration.
The FACP or each network node shall provide the following features:
- Drift compensation to extend detector accuracy over life. Drift compensation shall
also include a smoothing feature, allowing transient noise signals to be filtered out.
- Positive Alarm Sequence - PAS pre signal, meeting NFPA 72 3-8.3 requirements.
- Rapid manual station reporting (less than 3 seconds) and shall meet NFPA 72
requirements for activation of notification circuits within 10 seconds of initiating
device activation.
- Self optimizing pre-alarm for advanced fire warning, which allows each detector
to learn its particular environment and set its prealarm level to just above normal
peaks.
- Cross zoning with the capability of counting: two detectors in alarm, two
software zones in alarm, or one smoke detector and one thermal detector.
- Walk test, with a check for two detectors set to same address.
- 48 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The system shall be supplied with a LCD display or a VGA colour LCD display with touch screen.
The system shall include a full featured operator interface control and annunciation panel that
shall include a backlit Liquid Crystal Display (LCD) or a VGA colour LCD display with touch screen,
individual colour coded system status LEDs, and an alphanumeric keypad for the field
programming and control of the fire alarm system.
The display shall provide all the controls and indicators used by the system operator such as
ACKNOWLEDGE, ALARM SILENCE, ALARM ACTIVATE (drill), SYSTEM RESET, and LAMP TEST.
The display shall annunciate status information and custom alphanumeric labels for all intelligent
detectors, addressable modules, internal panel circuits, and software zones.
The LCD display or VGA colour LCD display with touch screen shall provide Light-Emitting-Diodes
(LEDs) that indicate the status of the following system parameters: AC POWER, FIRE ALARM,
PREALARM WARNING, SECURITY ALARM, SUPERVISORY EVENT, SYSTEM TROUBLE, ALARM
SILENCED, DISABLED POINTS, OTHER EVENTS, CPU FAILURE and Controls Active.
The LCD display or VGA colour LCD display with touch screen shall provide a set of "soft" keys for
screen navigation or to accomplish dedicated programming functions. Full programming access
shall require use of a laptop and the proper programming utility.
The FACP shall be capable of communicating with each other on a Local Area Network (LAN) over
dedicated 12 core single mode fiber optic cable connectivity, utilizing a peer-to-peer protocol.
The system shall include min. two serial EIA-232 interfaces. Each interface shall be a means of
connecting respected certifications or standards (UL/FM).
Besides, the system shall include interfaces for connecting devices such as printers, LAN
interface, RS485, Fiber Optics based connectivity interface, BacNet/IP and Modbus/IP for 3rd party
communication.
The system shall be capable to integrate with ELV and other 3rd party services like Public Address
system, Lifts, HVAC, Electric panel etc.
4.5. ENCLOSURES:
The control panel shall be housed in a standardized cabinet suitable for surface or semi-flush
mounting. The cabinet and front shall be corrosion protected, given a rust-resistant prime coat,
and manufacturer's standard finish.
The door shall provide a key lock and shall include a glass or other transparent opening for
viewing of all indicators. For convenience, the door may be site configured for either right or left
hand hinging.
An off-line switching power supply shall be available for the fire alarm control panel or network
node and provide 6.0 amps of available power for the control panel and peripheral devices.
Provisions will be made to allow the audio-visual power to be increased as required by adding
modular expansion audio-visual power supplies.
- 49 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
The main power supply shall operate on 230 VAC, 50Hz and shall provide all necessary power for
the FACP.
The main power supply shall provide a battery charger using dual-rate charging techniques for
fast battery recharge and be capable of charging batteries up to 100 AH.
System shall be proposed with backup power from UPS and also independent power backup
through Sealed Maintenance Free (SMF) Lead acid Batteries with backup of 24 hours under
Normal working condition & 30 minutes under emergency condition of operation under alarm
condition with adequate spare capacity overhead.
The system shall be provided with requisite power supplies, including additional power supplies
for the operation of devices such as sounders.
Addressable devices shall use simple to install and maintain decade, decimal address switches.
Detectors shall connect with two wires to the fire alarm control panel signalling Line Circuits.
The fire alarm control panel shall permit detector sensitivity adjustment through field
programming of the system. The panel on a time-of-day basis shall automatically adjust
sensitivity.
Detectors shall automatically compensate for dust accumulation and other slow environmental
changes that may affect their performance.
The detectors shall be ceiling-mount and shall include a separate twist-lock base with tamper
proof feature. Bases shall include a sounder base with a built-in (local) sounder rated at 85 DBA
minimum, a relay base and an isolator base designed for Style 6/7 applications.
Addressable devices shall store an internal identifying code that the control panel shall use to
identify the type of device.
Addressable modules shall mount in a 4-inch square (101.6 mm square), 2-1/8 inch (54 mm)
deep electrical box.
The intelligent multi-sensing detector shall be an addressable device that is designed to monitor a
minimum of photoelectric and thermal technologies in a single sensing device. The design shall
include the ability to adapt to its environment by utilizing a built-in microprocessor to determine
its environment and choose the appropriate sensing settings. The detector design shall allow a
wide sensitivity window, no less than 1 to 4% per foot obscuration. This detector shall utilize
advanced electronics that react to slow smouldering fires and thermal properties all within a
single sensing device.
The microprocessor design shall be capable of selecting the appropriate sensitivity levels based
on the environment type it is in (office, manufacturing, kitchen etc.) and then have the ability to
automatically change the setting as the environment changes (as walls are moved or as the
occupancy changes).
- 50 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Thermal detectors shall be intelligent addressable devices rated at 135 degrees Fahrenheit (58
degrees Celsius) and have a rate-of-rise element rated at 15 degrees F (9.4 degrees C) per
minute. It shall connect via two wires to the fire alarm control panel signalling line circuit.
The detector shall be capable to configure and to be addressed manually as well as from software
or remote locations also.
Level 1 — 25%.
Level 2 — 30%.
Level 3 — 40%.
Level 4 — 50%.
Alignment Aid using optical gun sight or integral signal strength indication or Two-digit display.
Addressable manual fire alarm boxes shall on command from the control panel, send data to the
panel representing the state of the manual switch and the addressable communication module
status. They shall use a key operated test-reset lock, and shall be designed so that after actual
emergency operation, they cannot be restored to normal use except by the use of a key.
All operated stations shall have a positive, visual indication of operation and utilize a key type
reset.
All entrances and stair levels shall be equipped with a pull type manual call point toactivate an
alarm. Manual call points shall be located in a manner so as to give aneasy access to occupants in
emergency; these shall be at entry/exits and within 30meters distance.
Electronic sounders shall be field programmable without the use of special tools, at a sound level
of at least 90 dBA measured at 3 meters from the device.
- 51 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Shall produce broad band directional sound with 20 Hz to 20 Khz frequency band to guide
occupants to safe exists even in complete darkness.
Strobe lights shall meet the requirements of the ADA, be fully synchronized, and shall meet the
following criteria:
For ease of service all panel I/O wiring terminal blocks shall be removable, plug-in types and have
sufficient capacity for #18 to #12 AWG wire. Terminal blocks that are permanently fixed are not
acceptable.
Addressable Relay Module shall provide a dry potential contact o/p for activating a variety of
auxiliary devices and other services equipment (i.e. Smoke Exhaust Fans, Fire Dampers, Access
control doors, elevators, PA equipment and HVAC electrical panel such as for AHUs).
It shall have a various current handling capability of 1A/2A/3A (as required) @ 30 VDC to
integrate with third party system.
Addressable control modules shall be provided to supervise and control the operation of one
conventional NACs of compatible, 24 VDC powered polarized audio/visual notification appliances.
Audio/visual power shall be provided by a separate supervised power circuit from the main fire
alarm control panel or from a supervised remote power supply from the same OEM.
The control module shall be suitable for pilot duty applications and rated for a minimum of 2.0
amps at 24 VDC.
Isolator modules shall be provided to automatically isolate wire-to-wire short circuits on an SLC
Class A or branch. The isolator module shall limit the number of modules or detectors that may
be rendered inoperative by a short circuit fault on the SLC loop segment or branch. Each loop
shall have isolator module after every 20 detectors to protected zone of the building.
If a wire-to-wire short occurs, the isolator module shall automatically open-circuit (disconnect)
the SLC. When the short circuit condition is corrected, the isolator module shall automatically
reconnect the isolated section.
The isolator module shall not require address-setting, and its operations shall be totally
automatic. It shall not be necessary to replace or reset an isolator module after its normal
operation.
The isolator module shall provide a single LED that shall flash to indicate that the isolator is
operational and shall illuminate steadily to indicate that a short circuit condition has been
detected and isolated.
MONITOR MODULE
- 52 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
RESPONSE INDICATOR
Remote Response Indicator shall be installed outside the areas normally kept closed to identify
the detectors response even if the room is locked. These indicators shall be able to indicate the
status of the corresponding detectors in these areas.
Fire-fighter telephone jack is semi-flush mounted receiving plate with a single-gang box. The
plate has a single phone jack mounted on an attractive, single-gang, stainless steel plate. Color
coded wires, approx. 6 inches long, are prewired to the jack to enable fast and accurate wiring to
the system
Fire-fighter telephone handset comes with a coiled cord. The attached plug fits Fireman’s Phone
Jack and it is allowing fire-fighters to make direct communication with a central control area
When a fire alarm condition is detected and reported by one of the system initiating devices, the
following functions shall immediately occur:
- A backlit LCD display shall indicate all information associated with the fire alarm condition,
including the type of alarm point and its location within the protected premises.
- Printing and history storage equipment shall log the information associated each new fire
alarm control panel condition, along with time and date of occurrence.
Smoke Detector Sensitivity Adjust: A means shall be provided for adjusting the sensitivity of any
or all addressable intelligent detectors in the system from the system keypad. Sensitivity range
shall be within the allowed standard window and have a minimum of 11 application specific
sensitivity levels.
Alarm Verification: Each of the intelligent addressable smoke detectors in the system may be
independently selected and enabled to be an alarm verified detector. The alarm verification delay
shall be programmable from 5 to 30 seconds and each detector shall be able to be selected for
verification. The FACP shall keep a count of the number of times that each detector has entered
the verification cycle. These counters may be displayed and reset by the proper operator
commands.
Point Disable: Any addressable device or conventional circuit in the system may be enabled or
disabled through the system keypad.
- 53 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Point Read: The system shall be able to display or print the following point status diagnostic
functions:
a. Device status
b. Device type
c. Custom device label
d. View analog detector values
e. Device zone assignments
f. All program parameters
System Status Reports: Upon command from an operator of the system, a status report will be
generated and printed, listing all system status.
System History Recording and Reporting: The fire alarm control panel shall contain an events
buffer that will be capable of storing a minimum of 5000 events. Up-to 1000 events shall be
dedicated to alarm and the remaining events are general purpose. Each of these activations will
be stored and time and date stamped with the actual time of the activation. The contents of the
history buffer may be manually reviewed, one event at a time, or printed in its entirety. The
history buffer shall use non-volatile memory. Systems that use volatile memory for history
storage are not acceptable substitutes.
Automatic Detector Maintenance Alert: The fire alarm control panel shall automatically interrogate
each intelligent detector and shall analyze the detector responses over a period of time. If any
intelligent detector in the system responds with a reading that is above or below normal limits,
then the system will enter the trouble mode, and the particular detector will be annunciated on
the system display, and printed on the optional printer. This feature shall in no way inhibit the
receipt of alarm conditions in the system, nor shall it require any special hardware, special tools
or computer expertise to perform.
Pre-Alarm Function: The system shall provide pre-alarm levels of warning to give advance notice
of a possible fire situation. Both pre-alarm levels shall be fully fielded adjustable. The first level
shall give an audible indication at the panel. The second level shall give an audible indication and
may also activate control relays. The system shall also have the ability to activate local detector
sounder bases at the pre-alarm level, to assist in avoiding nuisance alarms.
Software Zones: The FACP shall provide minimum 70 software zones, minimum 5 additional
special function zones, minimum 5 releasing zones, and minimum 10 logic zones.
The fire alarm control panel shall include a walk test feature. It shall include the ability to test
initiating device circuits and notification appliance circuits from the field without returning to the
panel to reset the system. Operation shall be as follows:
SUPERVISORY OPERATION
An alarm from a supervisory device shall cause the appropriate indication on the system display,
light a common supervisory LED, but will not cause the system to enter the trouble mode.
The FACP shall have the ability to program each output circuit (notification, relay, speaker etc) to
deactivate upon depression of the signal silence switch.
- 54 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Any addressable initiating device in the system may be used as a non-alarm input to monitor
normally open contact type devices. Non-alarm functions are a lower priority than fire alarm
initiating devices.
4.10. INSTALLATION
All fire detection and alarm system devices, control panels and remote annunciators shall be flush
mounted when located in finished areas and may be surface mounted when located in unfinished
areas.
4.11. TEST
- Before energizing the cables and wires, check for correct connections and test
for short circuits, ground faults, continuity, and insulation.
- Open initiating device circuits and verify that the trouble signal actuates.
- Open and short signalling line circuits and verify that the trouble signal
actuates.
- Open and short notification appliance circuits and verify that trouble signal
actuates.
- Each of the alarm conditions that the system is required to detect should be
introduced on the system. Verify the proper receipt and the proper processing
of the signal at the FACP and the correct activation of the control points.
- 55 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Conductor:
Nos. of cores x size in sq. mm: 3 X 1.5
Material: Plain annealed copper(Cu)
Type of pair: Shielded twisted pair
Copper as per Class 1 of IS: 8130/84
Max. d.c. resistance of conductor at 20° C: 12.10 (ohm/km)
Shape of the conductor: Solid Circular
Outer Sheath color: RED
Insulation:
Material: XLPE as per IS 7098(Pt-1)/88, Latest
Nominal thickness (mm): 0.7
Minimum thickness (mm): 0.53
Core Identification: Red, Black
Armouring:
Material: Galvanised Steel
Type of armouring: Round Wire
Nominal size of armour (mm): 1.40
Electrical Parameters:
Approx. overall diameter of the cable (mm): 10
Minimum bending radius: 12 times Overall diameter
- 56 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Date: ________________
To,
____<<< NAME OF CLIENT/ORGANIZATION>>______________
___________________________________________________
___________________________________________________
Dear Sirs,
We hereby authorize <<NAME AND ADDRESS OF INTEGRATOR>> to offer our range of product in
their tender bids. Being authorized <<NAME AND ADDRESS OF INTEGRATOR>> may make techno-
commercial and commercial proposal for this tender.
Upon being awarded the work <<NAME AND ADDRESS OF INTEGRATOR>> are authorized to install
and commission our range of products falling under <<SECTION/PRODUCT CATEGORY>> of this
tender.
We as Original Electronic Manufacturers will provide all the techno-commercial and service support
necessary to <<NAME AND ADDRESS OF INTEGRATOR>>for this project during the commissioning
phase of the equipments and until hand-over.
We also confirm that the items would be serviceable during the warranty period of 12 months and for
at least five years thereafter.
Yours faithfully
- 57 -
ELV SYSTEMS WORKS MATERIAL SPECIFICATIONS FOR NALANDA UNIVERSITY, RAJGIR
Note: Before approval of the make for supplying the material technical particulars
confirming to the TS must be submitted by the contractor.
- 58 -