ZX User Manual
ZX User Manual
User Manual
Index
Disclaimer............................................................................................................................................ 1
Nomenclature...................................................................................................................................... 2
Physical Layout..................................................................................................................................... 3
Product Specification
E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT).................................................. 5
Installation
Electrical Connection................................................................................................................................... 7
Refrigeration Connection............................................................................................................................. 8
Wiring Diagram.................................................................................................................................... 12
Contact Lists......................................................................................................................................... 17
ZX Platform CDU
Disclaimer
Thank you for purchasing the ZX platform condensing unit from Emerson Climate Technologies. ZX platform CDUs are the best
in class within the capacity and operating range available in the market. ZX CDU is designed to operate reliably and to deliver
high operating efficiencies in medium and low temperature refrigeration applications. It also provides constant monitoring
of the compressor operating conditions and displays the running or fault conditions of the CDU. ZX platform CDUs have to
be installed by following the industry trade practices for its safe and reliable operation. It is assumed that the CDU is selected,
installed and serviced only by professionals. The user manual does not cover good industry practices which are essential on a
refrigeration equipment installation. No responsibility can be accepted for damage caused by inexperienced or inadequately
trained site technicians or improper installation design.
If in doubt, please consult your local sales office, quoting unit model and serial number as shown on each unit nameplate. In
case of any ambiguity, the wiring diagram supplied with each unit takes precedence over the diagram in this manual.
Caution! It is very important to check that this holding pressure exists at the time you receive each unit from us or our
authorized representatives. Please inform us or our authorized representative if the holding charge is non-existent. Failure to do
so could void the claim for other related system faults at a later period.
Transit damage is essentially an insurance claim and is not covered under manufacturing defect. It is also advisable to inspect
the rest of the unit for obvious physical damage and inform us or our authorized representative in case any is discovered.
Energy Efficiency - Utilizing Copeland Scroll® compressor technology, variable speed fan motor, large capacity condenser
coil and advanced control algorithms, energy consumption is significantly reduced. End-users can save more than 20% on
annual energy costs rather than using hermetic reciprocating units.
Reliability - Combining the proven reliability of Copeland Scroll® compressors with advanced electronics controller and
diagnostics, equipment reliability is greatly enhanced. Fault code alerts and fault code retrieval capabilities provide information
to help improve speed and accuracy of system diagnostics. Integrated electronics provide protection against over-current,
over-heating, incorrect phase rotation, compressor cycling, high pressure resets, low pressure cut-outs. It can also send out a
warning message to an operator when there is a liquid floodback, which can prevent critical damage on the unit.
Flexibility - The slim shape and light weight make the ZX Condensing Unit aesthetically appealing and eases the installation
process. The ultra quiet variable-speed fan motor significantly reduces exterior sound levels, allowing additional location
flexibility. Combined with wall mounting capability, the ZX Condensing Unit delivers unmatched flexibility.
ZX Condensing Units are greatly suitable for walk-in cooler and freezer applications.
The advance scroll compressor technology, fan speed control and electronic controller are precisely collaborated in all units. It also
introduces variable-speed fan motors that go beyond national standards. Guaranteed dependable performance and operation in
foodservice applications while conveying higher energy efficiency and lower sound levels are the main objectives.
1
ZX Platform Condensing Unit
Nomenclature
Z X L 0 2 0 E - T F D - 4 5 1
TF5 = 200V/230V- 3ph- 60 Hz
PFJ = 220V/240V- 1ph- 50 Hz
TF7=380 - 3ph - 60 Hz
= Medium Temp
O = Mineral Oil
Bill of Material
L = Low Temp
2.0 to 7.6 HP
E = Ester oil
Unit Family
BOM
CDU Family ZX ZXL ZXD
BOM 401 451 451 461 471 450 451 461
Liquid Line Filter Dryer/Sight Glass
Oil Separator
Accumulator
Adjustable LP Switch
Fixed LP Switch
E2 Controller
Diagnostic Module
Buzzer
Digital Scroll Controller
Fan Speed Controller
Circuit Breaker
Sound Jacket
Defrost Module ACC ACC ACC ACC
Filter Drier V
2
Physical Layout
The following figures give an introduction to the physical layout of the ZX Platform CDU.
Figure 02: Identifies the Electronic controller assembly on a ZX platform CDU.
Scroll Compressor
* ZXD Digital scroll controller not shown in Fig. 02. See Fig. 05 for LED and keypad
Oil Separator
(Optional In MT CDU)
Liquid Receiver
Liquid Sight Glass/
Moisture Indicator
Liquid Filter Drier
Suction And Liquid
Service Valve
Receiver Out Service Valve
Compressor Oil Sight Glass
Figure 04: Shows the layout of the E2 controller, electrical components, dip switches and rotary switch in the E2 control board.
E2 Power Board
Rotary Switch
E2 Control Board
3-Bit Dip Switch
Power Isolation Switch 2-Bit Dip Switch
Defrost Module
(optional)
3
ZX Platform Condensing Unit
Figure 05: Shows LED and keypad of ZXD digital scroll controller.
Suction pressure
ure
Suction temperature
erature display
d
Program Mode: browses parameter codes or
Enter Alarm increase value
Hot Key Insert : Hot key programming
procedure
Manual Restart INFO Menu: Press and release it to access
INFO Menu
Setup Menu Program Mode: below parameter codes or
decrease value
Maintenance /Clock
Condenser
ser pressu
pressure
Condenser temperature display
Product Specification
For application envelope, envelope varies according to applications and refrigerants. Please refer to ZX platform product
catalogue, product manual, or Copeland® Brand Products Selection Software.
REFRIGERANT OIL
Oils are pre-charged in both compressor and oil separator. Total oil volume (liter) for each unit is shown in the table below:
ZX ZXD ZXL
Model BOM Model BOM Model BOM
401 451 ALL ALL
ZX0200/E 1.18 1.68 ZXL0200/E 1.06
ZX0250/E 1.33 1.83 ZXL0250/E 1.06
ZX0300/E 1.33 1.83 ZXL0300/E 1.06
ZXL0350/E 1.74
ZX0400/E 1.83 2.33 ZXD0400/E 1.74 ZXL0400/E 1.74
ZX0500/E 1.83 2.33 ZXD0500/E 2.27 ZXL0500/E 1.74
ZX0600/E 1.66 2.16 ZXD0600/E 2.27 ZXL0600/E 2.27
ZX0750/E 1.66 2.16 ZXD0750/E 2.27 ZXL0750/E 2.27
ZX0760/E 1.66 2.16
4
E2 Control Board - Rotary Switch And Dip Switch Setting (ZX-MT & ZXL-LT)
ON
1 2 3
OFF: Evaporator fan ON/OFF logic is same
as compressor and this is the factory
default setting.
ON: Evaporator fan will be ON for all time
irrespective of whether the compressor is
turned ON or OFF
Not applicable
Notes: The settings given in the table are pre-set at the factory for new units.
5
ZX Platform Condensing Unit
The control target of the fan speed controller is to maintain the average condenser mid-coil temperature and hence the average
discharge pressure at a defined value. This is achieved by varying the fan speed. The set-point can be altered using the SEtF
parameter. Factory setting SEtF is 25oC.Initial setting of set point for saturated suction temperature.Pre-set value is located in the
SEtC position as shown in the diagram below:
SEtC value
Flashing
SEtC value
Flashing
6
Installation
Copeland ZX condensing units are delivered with a holding charge of neutral gas. The condensing unit should be located
in such a place to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins. The unit must be
installed without restricting the airflow. A clogged condenser will increase the condensing temperature, thus reduce the
cooling capacity, and lead to a high-pressure switch tripping. Clean the condenser fins on a regular basis.
Condensing Unit Handling
Transport And Storage
Move ZX/ZXD/ZXL unit only with appropriate mechanical or handling equipment according to weight. Keep in the upright
position. Do not stack single boxes on top of each other without pallet in any case. Keep the packaging dry at all times.
Storage Transport
max max
max
2 2
300 Kg 300
300Kg
Kg
1 1
Net Weight
ZX ZXD ZXL
Notes:
1
100 kg for models under 60 Hz TF5/7 and 50 Hz PFJ
2
109 kg for models under 60 Hz TF7
3
117 kg for models under 60 Hz TF7
4
121 kg for models under 60 Hz TF7
5
127 kg for models under 60 Hz TF7
Electrical Connection
Power supply
The ZX condensing unit electrical connection to the power supply must be made by qualified technicians, who should refer
to the electrical diagrams located inside the electric connection panel. The units are designed for below power supply at ±
10% voltage tolerance. The circuit breaker must be switched off before opening the front panel.
Electrical wiring
Before commissioning, ensure that neutral “N” wire is connected to the terminal block (“N” furthest to the right). After proper
connection of the ZX condensing unit, the control LED on the power board and control board will light. For more details, see wiring
diagram in Appendix.
7
ZX Platform Condensing Unit
Refrigeration connections
Usually the suction line is insulated, but the liquid line is not. However the liquid line can pick up additional heat from the
ambient and adversely affect the sub-cooling desirable for the liquid refrigerant before it enters the expansion valve.
The pipe should be sized to ensure optimum performance and good oil return. The sizing must also take into account the full
capacity range through which this particular unit will need to operate.
Pipe runs should be kept as short as possible, using the minimum number of directional changes. Use large radius bends and
avoid trapping of oil and refrigerant. This is particularly important for the suction line. The suction line should ideally slope
gently towards the unit. Recommendation slope is 1/200~1/250. P traps, double risers and reduced pipe diameters may be
required for suction lines where long vertical risers cannot be avoided. All pipes should be adequately supported to prevent
sagging which can create oil traps. The recommended pipe clamp support distance is shown in the table.
Brazing recommendations
Maintain a flow of oxygen-free nitrogen through the system at a very low pressure during brazing. Nitrogen displaces the air
and prevents the formation of copper oxides in the system. If copper oxidization is allowed to form, the copper oxide material
can later be swept through the system and block screens such as those protecting capillary tubes, thermal expansion valves,
and accumulator oil return holes. This minimizes any entry of contaminants and moisture.
8
Location and fixing
The unit should always be installed in a location that ensures clean air flow. It is recommended that a clearance of 300 mm
from the wall (or the next unit) be maintained from the unit’s left and rear panels whereas a clearance of 500 mm must be
maintained from the unit’s right, top and front panels (seen facing the front of the unit). Both service access and airflow
have been considered in making these recommendations. Where multiple units are to be installed in the same location, the
contractor needs to consider each individual case carefully. There can be many variations of unit quantities and available space
and it is not the intention of this manual to go over these. Ideally, the unit should be mounted on a solid concrete slab with
anti-vibration pads between unit feet and concrete. However the ZX condensing unit has also been designed for wall mounting
on suitable brackets. Wall mounting brackets are not included. Another factor to consider in finding a good installation site is
the direction of the prevailing wind. For example if the air leaving the condenser faces the prevailing wind, the air flow through
the condenser can be impeded, causing high condensing temperatures ultimately resulting in reducing unit life. A baffle is a
remedy for this situation.
500
Power
Supply Hole
2 Holes 15mm DIA
Suction
Service Valve
Liquid
840
Service Valve 94
388
110
172
23 2-R7.5MM GROOVE
580
90
424
300 70 70 500 Single Fan Unit
2 to 4 HP
Power
Supply Hole
1242
388
Suction
Service Valve
110
Liquid
94
Service Valve 2-R7.5MM GROOVE 580
172
23
90
9
ZX Platform Condensing Unit
Evacuation
The evacuation procedure is based upon achieving an actual system vacuum standard and is not time dependent. Before the
installation is put into commission, it has to be evacuated with a vacuum pump. Proper evacuation reduces residual moisture
to 50ppm. The installation of adequately sized access valves at the furthest point from the compressor in the suction and liquid
lines is advisable. To achieve undisturbed operation, the compressor valves are closed and the system is evacuated down to
0.3 mbar / 0.225 Torr. Pressure must be measured using a vacuum pressure (Torr) gauge on the access valves and not on the
vacuum pump; this serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to
the pump.
Charging procedure
- Power On
LED 2
LED 1
10
Diagnostic messaging - LED definition (ZX-MT and ZXL-LT)
LED1-Unit Status LED2-Error/Warning Code Controller
Controller
Pause Unit
Dis- Display Warning Signal Lock Unit
Display Status Error/Warning Automatic
play Manual Reset
Reset
PHE Vapor In Temperature Sensor Failure or Over Range 3 Every Protection Action NA NA
PHE Vapor Out Temperature Sensor Failure or Over Range 3 Every Protection Action NA NA
Notes:
1 New start, normal start by program and any start request delay
2 “LP Cutout”signal is not applicable in ZXL condensing unit.
3 PHE Vapor In/Out temperature sensor is not applicable in ZX medium temperature condensing unit.
C-LA LP < LAL - Signaling only Auto reset when LP = LAL + delta (0.3bar) LP
C-HA LP >= HAL - Signaling only Auto reset when LP = HAL -delta (0.3bar) LP
Auto reset when Number of activations
< PEn in PEi time Cond Mid Temp.
Condensing Temperature - Compressors are turned off - Fans are Manual reset when Number of activations
E0H High turned on >= PEn in PEi time
Cond Mid
- Press key for 3 sec or - Turn off and on the unit
F-HA HP >= HAF - HFC = yes, compressor are turned off Auto reset when HAF + delta (0.3bar) Cond Mid Temp.
Suction Transducer failure or - Compressors are activated according
P1 Auto reset when probe is normal LP
out of range to SPr or PoPr
Condenser Mid Coil Sensor
P2 - Fans are activated according to FPr Auto reset when probe is normal Cond Mid Temp.
failure or out of range
Discharge Temp Sensor failure -The functions related to No.3 probe
P3 Auto reset when probe is normal DLT
or out of range are disabled
DLT: Discharge line temperature
LP: Low pressure
HP: High pressure
11
ZX Condensing Unit Wiring Diagram
PFJ: 220V-50 Hz -1Ph
ATTENTION: Unit MUST be grounded!
BLUE
ZX Platform Condensing Unit
12
13
ZX/ZXL Condensing Unit Wiring Diagram
TFD: 380V/420V -50 Hz-3Ph
TF7: 380V-60 Hz -3Ph
14
15
ZXD Condensing Unit Wiring Diagram
(With Fan Speed Control Function)
TFD: 380V/420V -50 Hz-3Ph ATTENTION:Unit MUST be grounded!
ZXD Condensing Unit Wiring Diagram (With Fan Speed Control Function)
TF7: 380V-60 Hz-3Ph
TFD - 380/420V, 50Hz, 3Ph Notes:
TF7 - 380V, 60Hz, 3Ph
Dashed line " " is wired by installer.
ATTENTION: Unit MUST be grounded!
052-2662-00
2012-02-15
U V W N COND. Mid
Compressor DLT Coil Temp. Pressure
Sensor LP Switch
Sensor Transducer
1 3 5 Brown White
Circuit
Black Breaker N
M1 "I" 2 4 6
White
Black
Capacitor1 Blue
E
White Fuse
(2A/250V)
Terminal 1 2 3 4 5 6 7 8 9 10 11 12 N N N
Block
Blue L1 T1 Blue
Yellow L2 T2 Yellow
Red L3 T3 Red Blue
Blue Red
Aux 21N/C 22N/C Red
Black PWM Valve
A1 A2 Black
Black
M2
White
Contactor
Capacitor2
E
White Out
0~10V
4~20mA
T1(U)
15 17 19
+ - + -
16 18 20
21 22 23 24
Internal motor Digital Scroll
protector Controller
T2(V) Pb3Pb1Pb2 LP Id3 Id1 HP i2F
Hot KeY / TTL
1 3 5 7 9 11 13 - + - +
T3(W) 2 4 6 8 10 12 14 25 26 27 28
1 3 10 12 COMP'R
E
Fan Speed Controller Crankcase Heater
1 2 HP Switch
15 16 22 23 24
Transformer
Input: Output:
230VAC 12VAC
ZXD Condensing Unit Wiring Diagram
(without Fan Speed Control Function)
TFD: 380V/420V-50 Hz-3Ph
ATTENTION:Unit MUST be grounded!
TF7: 380V- 60 Hz-3Ph
ZXD Condensing Unit Wiring Diagram (Without Fan Speed Control Function)
TFD - 380/420V, 50Hz, 3Ph Notes:
TF7 - 380V, 60Hz, 3Ph
ATTENTION: Unit MUST be grounded! Dashed line " " is wired by installer.
052-2677-00
2012-03-28
U V W N COND. Mid
Compressor DLT Coil Temp. Pressure
Sensor LP Switch
Sensor Transducer
1 3 5 Brown White
Circuit
Breaker N To Fan
Black
M1 To N "I" 2 4 6
White
Capacitor1 Black
Blue
E
White Fuse
(2A/250V)
Red Terminal 1 2 3 4 5 6 7 8 9 10 11 12 N N N
Block
Blue L1 T1 Blue
Yellow L2 T2 Yellow
Red L3 T3 Red Blue
Blue Red
Aux 21N/C 22N/C Red
Black PWM Valve
A1 A2 Black
Black
M2 To N
White
Contactor
Capacitor2
E
White Out
0~10V
Red 4~20mA
T1(U)
15 17 19
+ - + -
16 18 20
21 22 23 24
Internal motor Digital Scroll
protector Controller
T2(V) Pb3Pb1Pb2 LP Id3 Id1 HP i2F
Hot KeY / TTL
1 3 5 7 9 11 13 - + - +
T3(W) 2 4 6 8 10 12 14 25 26 27 28
COMP'R
E
Crankcase Heater
1 2 HP Switch
Transformer
Input: Output:
230VAC 12VAC
ZX Platform Condensing Unit
16
Contact List
Emerson Climate Technologies India - Mumbai Malaysia
Asia Pacific Headquarters Emerson Climate Technologies (India) Ltd Emerson Electric (Malaysia) Sdn. Bhd.
10/F, Pioneer Building, Unit No. 4,5,6 & 7, Bhaveshwar Arcade Level M2, Blk A, Menara PKNS-PJ
213 Wai Yip Street, Jalan Yong Shook Lin
LBS Marg, Opp. Shreyas Cinema
Kwun Tong, Kowloon, Hong Kong 46050 Petaling Jaya, Selangor, Malaysia
Ghatkopar (West)
Tel: (852) 2866 3108 Tel: (60-3) 7949 9222
Fax: (852) 2520 6227 Mumbai 400 086, Maharashtra, India Fax: (60-3) 7949 9333
Tel: (91-22) 2500 6630/ 2500 6632
Australia Fax: (91-22) 2500 6570 Middle East & Africa
Emerson Climate Technologies Australia Emerson Climate Technologies
Pty Ltd India - PUNE PO Box 26382
Unit R7, 391 Park Road Emerson Climate Technologies (India) Ltd Jebel Ali Free Zone – South
Regents Park, NSW 2143, Australia Dubai, UAE
Plot No. 23, Rajiv Gandhi Infotech Park,
Tel: (61-2) 9795 2800 Tel: (971- 4) 811 8100
Phase - II, Hinjewadi,
Fax: (61-2) 9738 1699 Fax: (971- 4) 886 5465
Pune 411 057, Maharashtra, India
China - Beijing Tel: (91-20) 2553 4988 Philippines
Emerson Climate Technologies (Suzhou) Fax: (91-20) 2553 6350 Emerson Climate Technologies
Co. Ltd 23rd Floor San Miguel Properties Centre
Beijing Sales Office Indonesia #7 St. Francis Street, Ortigas Center,
Room 1017 JianWei Building, PT Emerson Indonesia Mandaluyong City, Philippines
66 Nan Lishi Road, XiCheng District, Tel: (632) 689 7288 / (632) 479 5200
Wisma 46 - Kota BNI, 16th Floor, Suite 16.01,
Beijing, PRC
Tel: (86-10) 5763 0488 Jl. Jend.Sudirman Kav.1. Taiwan
Fax: (86-10) 5763 0499 Jakarta 10220, Indonesia Emerson Electric (Taiwan) Co. Ltd
Tel: (62)21-2513003 3F No. 2 DunHua South Road Sec.1,
China - Guangzhou Fax: (62)21-2510622 Taipei (105), Taiwan
Emerson Climate Technologies (Suzhou) Tel: (+886-2) 8161 7688
Co. Ltd Japan Fax: (+886-2) 81617614
Guangzhou Sales Office
Emerson Japan Ltd
508-509 R&F Yinglong Plaza, Thailand - Bangkok
Shin-yokohama Tosho Building
No. 76 Huangpu Road West, Emerson Electric (Thailand) Ltd
Guangzhou, PRC No. 33-9-5 Shin-Yokohama, Kohoku-ku 34th Floor Nation Tower
Tel: (86-20) 2886 7668 Yokohama 222-0033 Japan 1858/133 Bangna Trad
Fax: (86-20) 2886 7622 Tel: (81-45)475 6371 Bangkok 10260 , Thailand
Fax: (81-45)475 3565 Tel: (66-2) 716 4700
China - Shanghai Fax: (66-2) 751 4240
Emerson Climate Technologies South Korea
(Suzhou) Co. Ltd Vietnam
Emerson Electric (South Korea) Ltd.
Shanghai Sales Office Emerson Climate Technologies - Vietnam
3F Pharos Tower, 119 Nonhyeon-dong
1801 Building B, New CaoHeJing Suite 307-308,
International Business Center, Gangnam-gu, Seoul, South Korea 135-010 123 Truong Dinh St., Dist.3
391Guiping Rd, Shanghai, PRC Tel: (82-2) 3483-1500 Ho Chi Minh, Vietnam
Tel: (86-21) 3418 3968 Fax: (82-2) 592-7883 / 592-7886 Tel: 84 908 009 189
EmersonClimate.com/Asia
Asia 02 A01 10 – R00 Issued 4/2012