Optimized Frequency Scanning
Optimized Frequency Scanning
Abstract—Frequency scanning is a powerful and versatile ap- devices, and shunt active compensation devices have consider-
proach for subsynchronous resonance (SSR) screening in power ably changed the dynamic behavior of power grids [1]–[10]. The
grids. Among different numerical and analytical frequency scan- complex control systems of these types of equipment have intro-
ning techniques, the harmonic injection method is well suited for
the scan of black-box models with active elements, such as in duced new challenges to the power industry [2]–[4]. One of these
wind farms and solar plants. The results can be used for SSR risk challenges is subsynchronous resonance (SSR), also referred to
assessment, in which accuracy performs a decisive role. The ideal as subsynchronous interaction (SSI) by some authors. SSR/SSI
situation for this method, which leads to the most accurate results, is involves the interaction between two or more elements of power
to perform one simulation per single-frequency injection. However, grids within the subsynchronous frequency range (<60 Hz for
for SSR studies with a wide range of frequencies and simulations
with very small time steps (scale of µs), this comes at the expense a 60 Hz system), leading to subsynchronous oscillations (SSO)
of increased simulation time. This article proposes a technique to [10]. Depending on the equipment involved in the interaction,
improve the accuracy of the harmonic injection method through the phenomenon can be categorized in different groups, which
the optimization of the crest factor while injecting all frequencies are as follows [1]–[4].
at one shot, therefore also reducing simulation time. The proposed 1) Torsional Interaction: The oscillation is a result of an inter-
technique was tested on a wind farm connected to a radial test case
and on a portion of a Texas synthetic grid with multiple active ele- action between the mechanical system and the electrical
ments, including two wind farms and a VSC-based STATCOM. The system [1], [4]. This phenomenon is common for conven-
frequency scan results were benchmarked with both time-domain tional generation with long turbine-generator shafts and
transient simulations and the ideal multiple single-frequency in- the oscillation grows relatively slowly [9]. This interaction
jection case and compared with other techniques. The results show might happen between the turbine-generator shaft and a
that the proposed method is superior in accuracy when compared
to the other techniques and is 11.71 times faster when compared to nearby series-compensated line, such as in the Mohave
multiple single-frequency injections. Power Plant incident [15]. It might also be triggered as a
result of interaction between the turbine-generator shaft
Index Terms—Crest factor, frequency scan, harmonic injection,
impedance estimation, multisine signals, nonlinear systems,
and control systems of power-electronic-based devices,
small-signal analysis, subsynchronous control interaction (SSCI), such as between HVDC lines and mass-drive trains of
subsynchronous resonance (SSR), wind farms. generation systems [1]. The second one is mostly known as
subsynchronous torsional interaction and it was observed
for the first time during field tests of a line-commutated-
I. INTRODUCTION
converter HVDC (LCC-HVDC) line that interacted with a
IGH penetration of renewable generation resources and
H other power electronic-based elements such as high-
voltage direct-current (HVDC) lines, series active compensation
turbine-generator of Square-Butte, in the Milton R. Young
power plant [16].
2) Subsynchronous Control Interaction (SSCI): Interaction
between series-compensated lines and control systems
Manuscript received February 19, 2019; revised September 18, 2019 and
November 29, 2019; accepted January 2, 2020. Date of publication February with power electronic-based devices [4], [9].
4, 2020; date of current version April 24, 2020. Paper 2019-PSEC-0221.R2, 3) Induction Generation Effect (IGE): Situation when an
presented at the 2019 IEEE/IAS 55th Industrial and Commercial Power Sys- induction generator shows negative resistance at a sub-
tems Technical Conference, Calgary, AB, Canada, May 5–8, and approved
for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by synchronous resonant frequency and the magnitude of this
the Power Systems Engineering Committee of the IEEE Industry Applications negative resistance exceeds the total resistance of the grid
Society. The work of I. B. M. Matsuo was supported by CNPq, National Council at the same frequency [2], [4].
for Scientific and Technological Development—Brazil. (Corresponding author:
Igor Brandão Machado Matsuo.) SSCI and IGE are purely electrical incidents with the potential
I. B. M. Matsuo, L. Zhao, Y. Zhou, and W.-J. Lee are with the Department to grow very rapidly [9]. Therefore, they can cause serious
of Electrical Engineering, University of Texas at Arlington, Arlington, TX damage to transmission elements and lead to cascading outage.
76019 USA (e-mail: [email protected]; [email protected]; yuhao.
[email protected]; [email protected]). The first recorded SSCI event took place in Texas, in 2009, where
F. Salehi is with the Department of Power System Advisory, DNV GL Energy, 20 Hz oscillations damaged the crowbar protection of many
Dallas, TX 75207 USA (e-mail: [email protected]). DFIGs in a wind farm [17]. Many other SSR events happened in
Color versions of one or more of the figures in this article are available online
at https://ieeexplore.ieee.org. China between 2012 and 2013, where the frequencies recorded
Digital Object Identifier 10.1109/TIA.2020.2971434 varied in the range of 6–8 Hz [5]. Other SSR events include
0093-9994 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
2282 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 3, MAY/JUNE 2020
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
MATSUO et al.: OPTIMIZED FREQUENCY SCANNING OF NONLINEAR DEVICES APPLIED TO SSR SCREENING 2283
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
2284 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 3, MAY/JUNE 2020
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
MATSUO et al.: OPTIMIZED FREQUENCY SCANNING OF NONLINEAR DEVICES APPLIED TO SSR SCREENING 2285
TABLE II
METHODS OF DIFFERENT ANGLES AND RESPECTIVE PEAK, RMS,
AND CREST VALUES AFTER NORMALIZATION
TABLE I
RADIAL TEST SYSTEM PARAMETERS
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
2286 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 3, MAY/JUNE 2020
TABLE V
TOTAL REACTANCE ERROR OF METHODS IN RELATION TO THE REFERENCE
TABLE III
FREQUENCY OF OSCILLATION AND RESISTANCE VALUES
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
MATSUO et al.: OPTIMIZED FREQUENCY SCANNING OF NONLINEAR DEVICES APPLIED TO SSR SCREENING 2287
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
2288 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 3, MAY/JUNE 2020
TABLE VI
TOTAL RESISTANCE ERROR OF METHODS IN RELATION TO THE REFERENCE
TABLE VII
TOTAL REACTANCE ERROR OF METHODS IN RELATION TO THE REFERENCE
Fig. 14. Time-domain simulation results at the POI. (a) Active power.
(b) Voltage. (c) Current.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
MATSUO et al.: OPTIMIZED FREQUENCY SCANNING OF NONLINEAR DEVICES APPLIED TO SSR SCREENING 2289
V. CONCLUSION
The harmonic injection method is a strong frequency scanning
technique for black-box models with nonlinear devices, such
as many that are present in active devices. The accuracy of
condition. The system is considered to settle to a steady state if this method is highly dependent on the number of injected
the envelope of the active power reaches and remains within a frequencies in each simulation. Normally, the lesser the number
certain percentage range of its final value (normally 2% or 5%) of multiple frequencies, the higher the accuracy. The ideal case
[33]. This settling time can be utilized to calculate the minimum is performing one simulation per single-frequency injection.
simulation time. However, this accuracy is only achieved at the expense of time.
Using (15) and (16), we can compare the minimum simulation This article proposes a technique to increase the accuracy of the
times between multiple single-frequency injections and the pro- scan results by optimizing the crest factor of a multifrequency
posed multisine injection. Fig. 16 shows the normalized transient injection signal with a small amplitude and applying differ-
response of the network-side active power after injecting a single ent optimized angles for each frequency. This signal enables
sine wave of 30 Hz. The magnitude is normalized as to set the performing only one simulation per side of the grid, therefore
final value of the upper envelope to 1 (by dividing all values by drastically reducing the total simulation time while maintaining
its final value). A ±5% range from the final value is used as good accuracy. The frequency scan cannot be completely error-
the settling limits. We can see that the settling time for 30 Hz is free, as there is no ideal choice of angles and amplitude that
0.197 s. The settling time results of all frequencies are shown in will nullify the errors in all nonlinear components of the grid
Table IX. at the same time, but this is also the case for any frequency
From the values of Table IX, (15) and (16) give the minimum scanning method, including single-frequency injections. The
simulation time for multiple single-frequency injections and for proposed method was utilized to scan two wind farm black-box
one multisine injection with period T0 = 1 s models and a VSC-based STATCOM to evaluate the risk of SSR.
The frequency scan results were benchmarked against the ideal
35
1 case of multiple single-frequency injections and demonstrated
Tsf = + T stk = 8.010 s high accuracy while being 11.71 times faster. Moreover, when
fk
k=5
compared with other methods, the proposed method led to the
Tms = T0 + max {T stk } = 1 + 0.203 = 1.203 s. smallest errors and closest SSR analysis results to the reference,
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
2290 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 3, MAY/JUNE 2020
thus demonstrating its superiority in terms of accuracy. Finally, [7] K. Narendra et al., “New microprocessor based relay to monitor and protect
time-domain transient simulations were conducted to validate power systems against sub-harmonics,” in Proc. IEEE Elect. Power Energy
Conf., 2011, pp. 438–443.
the results of the frequency scan. [8] L. Zhao, I. B. M. Matsuo, F. Salehi, Y. Zhou, and W. Lee, “Development
of a real-time web-based power monitoring system for the substation of
APPENDIX petrochemical facilities,” IEEE Trans. Ind. Appl., vol. 55, no. 1, pp. 43–50,
Jan./Feb. 2019.
TABLE X [9] F. Salehi, I. Brandao Machado Matsuo, A. Brahman, M. Aghazadeh
PARAMETERS OF THE 161 kV TRANSMISSION LINES ON A 100 MVA BASE Tabrizi, and W. Lee, “Sub-synchronous control interaction detection: A
real-time application,” IEEE Trans. Power Del., vol. 35, no. 1, pp. 106–116,
Feb. 2020.
[10] H. K. Nia, F. Salehi, M. Sahni, N. Karnik, and H. Yin, “A filter-less robust
controller for damping SSCI oscillations in wind power plants,” in Proc.
IEEE Power Energy Soc. General Meeting, 2017, pp. 1–5.
[11] M. A. Chowdhury, M. A. Mahmud, W. Shen, and H. R. Pota, “Nonlinear
controller design for series-compensated DFIG-based wind farms to mit-
igate subsynchronous control interaction,” IEEE Trans. Energy Convers.,
vol. 32, no. 2, pp. 707–719, Jun. 2017.
[12] M. A. Chowdhury and G. M. Shafiullah, “SSR mitigation of series-
compensated DFIG wind farms by a nonlinear damping controller using
partial feedback linearization,” IEEE Trans. Power Syst., vol. 33, no. 3,
pp. 2528–2538, May 2018.
[13] T. Joseph, C. E. Ugalde-Loo, S. Balasubramaniam, and J. Liang, “Real-
time estimation and damping of SSR in a VSC-HVDC connected series-
compensated system,” IEEE Trans. Power Syst., vol. 33, no. 6, pp. 7052–
7063, Nov. 2018.
[14] T. Joseph, C. E. Ugalde Loo, S. Balasubramaniam, J. Liang, and G. Li,
“Experimental validation of an active wideband SSR damping scheme for
series-compensated networks,” IEEE Trans. Power Del., vol. 35, no. 1,
TABLE XI pp. 58–70, Feb. 2020.
PARAMETERS OF THE 500 kV TRANSMISSION LINES ON A 100 MVA BASE [15] D. N. Walker, C. E. J. Bowler, R. L. Jackson, and D. A. Hodges, “Results of
subsynchronous resonance test at Mohave,” IEEE Trans. Power App. Syst.,
vol. PAS-94, no. 5, pp. 1878–1889, Sep. 1975.
[16] M. Bahrman, E. V. Larsen, R. J. Piwko, and H. S. Patel, “Experience with
HVDC - Turbine-generator torsional interaction at square butte,” IEEE
Trans. Power App. Syst., vol. PAS-99, no. 3, pp. 966–975, May 1980.
[17] J. Adams, C. Carter, and S. Huang, “ERCOT experience with sub-
synchronous control interaction and proposed remediation,” in Proc. PES
T&D, 2012, pp. 1–5.
[18] H. Liu et al., “Subsynchronous interaction between direct-drive PMSG
based wind farms and weak AC networks,” IEEE Trans. Power Syst.,
TABLE XII vol. 32, no. 6, pp. 4708–4720, Nov. 2017.
PARAMETERS OF THE TRANSFORMERS [19] I. B. M. Matsuo, F. Salehi, L. Zhao, Y. Zhou, and W. Lee, “An optimized
frequency scanning tool for sub-synchronous interaction analysis of non-
linear devices,” in Proc. IEEE/IAS 55th Ind. Commercial Power Syst. Tech.
Conf., 2019, pp. 1–7.
[20] M. S. Annakkage, C. Karawita, and U. D. Annakkage, “Frequency scan-
based screening method for device dependent sub-synchronous oscilla-
tions,” IEEE Trans. Power Syst., vol. 31, no. 3, pp. 1872–1878, May 2016.
[21] L. Yang, Z. Xu, J. Østergaard, Z. Y. Dong, K. P. Wong, and X. Ma,
“Oscillatory stability and eigenvalue sensitivity analysis of a DFIG wind
turbine system,” IEEE Trans. Energy Convers., vol. 26, no. 1, pp. 328–339,
Mar. 2011.
[22] M. Sahni, D. Muthumuni, B. Badrzadeh, A. Gole, and A. Kulkarni,
REFERENCES “Advanced screening techniques for sub-synchronous interaction in wind
farms,” in Proc. PES T&D, 2012, pp. 1–9.
[1] V. B. Virulkar and G. V. Gotmare, “Sub-synchronous resonance in series- [23] Y. Cheng, S. Huang, J. Rose, V. A. Pappu, and J. Conto, “ERCOT sub-
compensated wind farm: A review,” Renewable Sustain. Energy Rev., synchronous resonance topology and frequency scan tool development,”
vol. 55, pp. 1010–1029, Dec. 2015. in Proc. IEEE Power Energy Soc. General Meeting., 2016, pp. 1–5.
[2] L. Fan, R. Kavasseri, Z. L. Miao, and C. Zhu, “Modeling of DFIG-based [24] A. S. Subburaj et al., “Determination of sub synchronous control interac-
wind farms for SSR analysis,” IEEE Trans. Power Del., vol. 25, no. 4, tion between wind turbines and series compensated transmission lines,”
pp. 2073–2082, Oct. 2010. Int. J. Renewable Energy Res., vol. 6, no. 3, pp. 987–994, 2016.
[3] Y. Song and F. Blaabjerg, “Analysis of middle frequency resonance in [25] A. M. Kulkarni, M. K. Das, and A. M. Gole, “Frequency scanning analysis
DFIG system considering phase-locked loop,” IEEE Trans. Power Elec- of STATCOM - Network interactions,” in Proc. IEEE 6th Int. Conf. Power
tron., vol. 33, no. 1, pp. 343–356, Jan. 2018. Syst., 2016, pp. 1–6.
[4] A. E. Leon and J. A. Solsona, “Sub-synchronous interaction damping [26] X. Jiang and A. M. Gole, “A frequency scanning method for the identi-
control for DFIG wind turbines,” IEEE Trans. Power Syst., vol. 30, no. 1, fication of harmonic instabilities in HVDC systems,” IEEE Trans. Power
pp. 419–428, Jan. 2015. Del., vol. 10, no. 4, pp. 1875–1881, Oct. 1995.
[5] L. Wang, X. Xie, Q. Jiang, H. Liu, Y. Li, and H. Liu, “Investigation of SSR [27] R. Pintelon and J. Schoukens, System Identification: A Frequency Domain
in practical DFIG-based wind farms connected to a series-compensated Approach. New York, NY, USA: IEEE, 2001.
power system,” IEEE Trans. Power Syst., vol. 30, no. 5, pp. 2772–2779, [28] IXYS, IXSH 35N120A High Voltage, High Speed IGBT. [Online]. Avail-
Sep. 2015. able: http://ixapps.ixys.com/datasheet/92774.pdf
[6] L. Vanfretti, M. Baudette, J. L. Domínguez-Garcíaz, A. White, M. S. [29] J. M. Guerrero, M. Leetmaa, F. Briz, A. Zamarron, and R. D. Lorenz,
Almas, and J. O. Gjerdeóy, “A PMU-based fast real-time sub-synchronous “Inverter nonlinearity effects in high-frequency signal-injection-based
oscillation detection application,” in Proc. IEEE 15th Int. Conf. Environ. sensorless control methods,” IEEE Trans. Ind. Appl., vol. 41, no. 2,
Elect. Eng., 2015, pp. 1892–1897. pp. 618–626, Mar./Apr. 2005.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.
MATSUO et al.: OPTIMIZED FREQUENCY SCANNING OF NONLINEAR DEVICES APPLIED TO SSR SCREENING 2291
[30] C. Basso, “Small-signal modeling and analytical analysis of power con- Long Zhao (Student Member, IEEE) received the
verters,” in Proc. Appl. Power Electron. Conf. Expo, 2013, pp. 14–18. B.S. degree from Eastern Washington University, Ch-
[31] S. Boyd and L. Vandenberghe, Convex Optimization. New York, NY, USA: eney, WA, USA, in 2012, and the M.S. degree from
Cambridge Univ. Press, 2004, pp. 215–223. Wichita State University, Wichita, KS, USA, in 2014,
[32] J. Schoukens, R. M. Pintelon, and Y. J. Rolain, “Broadband versus stepped both in electrical engineering. He is currently working
sine FRF measurements,” IEEE Trans. Instrum. Meas., vol. 49, no. 2, toward the Ph.D. degree in power and energy systems
pp. 275–278, Apr. 2000. in the University of Texas at Arlington (UTA), Arling-
[33] K. Ogata, Modern Control Engineering, 5th ed. Englewood Cliffs, NJ, ton, TX, USA.
USA: Prentice-Hall, 2010. He is a member of the Energy Systems Research
[34] N. W. Miller, J. J. Sanchez-Gasca, W. W. Price, and R. W. Delmerico, Center (ESRC), UTA. His research interests include
“Dynamic modeling of GE 1.5 and 3.6 MW wind turbine-generators for power system analysis, demand response, renewable
stability simulations,” in Proc. IEEE Power Eng. Soc. General Meeting, energy, energy storage, power system markets, and arc flash protection.
2003, vol. 3, pp. 1977–1983. Mr. Zhao is currently the IEEE Industry Applications Society Student Chapter
[35] A. B. Birchfield, T. Xu, K. M. Gegner, K. S. Shetye, and T. J. Overbye, Chair at UT Arlington.
“Grid structural characteristics as validation criteria for synthetic net-
works,” IEEE Trans. Power Syst., vol. 32, no. 4, pp. 3258–3265, Jul. 2017.
[36] ERCOT Nodal Protocols: Sub-Synchronous Resonance, ERCOT NPRR
562, 2018.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on May 25,2020 at 04:46:37 UTC from IEEE Xplore. Restrictions apply.