Fasteners in Concrete
Fasteners in Concrete
Degree
Bachelor of Civil Engineering
Name, title, and organisation of the client
Ville Laine, chief technology officer, A-Insinöörit Suunnittelu Oy
Abstract
The thesis was written for A-Insinöörit Suunnittelu Oy. The purpose of the work was to
find better and more effective solutions for anchor bolts usage, study phenomena of
the supplementary reinforcement, and study how supplementary reinforcement can
affect headed and post-installed anchor bolts.
The theoretical part describes in general the types of anchor bolts that are applicable
for this work, failure modes of fasteners, phenomena of supplementary reinforcement,
and what conditions must be observed for its usage. This work is based on Eurocode
2. Design of concrete structures. Part 4: Design of fastenings for use in concrete (EN
1992-4).
A big part of this work is analyze of the calculations for supplementary reinforcement
and studies of the impact of each parameter of reinforcement on the design re-
sistance of supplementary reinforcement along with requirements from the standard
EN 1992-4. The design resistance of a fastener and of a supplementary reinforce-
ment was compared.
The supplementary reinforcement can be useful in the combination with anchor bolts
and can improve the strength of anchor bolts in case of concrete cone failure and
concrete edge failure. However, supplementary reinforcement is not always the solu-
tion for increasing the load-carrying capacity of an anchor.
Keywords
Supplementary reinforcement, fastenings, headed anchors, post-installed anchors,
EN 1992-4
Contents
List of symbols
𝑒𝑠 - distance between the line of the shear load and the axis of the supplementary reinforce-
ment for shear
𝑘1 – factor taking into account cracks in the concrete in case of concrete cone failure
𝑘2 - factor taking into account cracks in the concrete in case of pull-out failure
𝑘9 - factor taking into account cracks in the concrete in case of concrete edge failure
𝑙1 - anchorage length of the reinforcing bar in the assumed concrete break-out body
ℎ
𝑁𝐸𝑑 - resultant design tension force of the tensioned fastener in group of fasteners
𝑁𝐸𝑑.𝑠𝑢𝑚 - sum of the design tensile force of the fasteners in tension under the design value
of the actions
𝑁𝑅𝑑,𝑐 - design resistance in case of concrete cone failure under tension load
𝑁𝑅𝑑,𝑐𝑏 - design resistance in case of concrete blow-out failure under tension load
𝑁𝑅𝑑,𝑐𝑝 - design resistance in case of concrete pry-out failure under tension load
𝑁𝑅𝑑,𝑝𝑐 - design resistance in case of combined pull-out and concrete failure of fastener
𝑁𝑅𝑑,𝑠𝑀 - design resistance in case of steel failure with lever arm of fastener
𝑁𝑅𝑑,𝑠𝑝 - design resistance in case of concrete splitting failure under tension load
𝑁𝑅𝑘.𝑐 - characteristic resistance in case of concrete cone failure under tension load
𝑁𝑅𝑘,𝑐𝑏 - characteristic resistance in case of concrete blow-out failure under tension load
𝑁𝑅𝑘,𝑝𝑐 - characteristic resistance in case of pull-out and concrete failure under tension load
𝑁𝑅𝑘,𝑠𝑝 - characteristic resistance in case of concrete splitting failure under tension load
𝑁0.𝑅𝑑.𝑎.𝑖 - design resistance of one rebar associated with anchorage failure in tension
𝑠𝑐𝑟.𝑁 - characteristic spacing of fasteners or anchors of anchor channels to ensure the char-
acteristic resistance of the individual fasteners or anchors of an anchor channel in case of
concrete cone failure under tension load (concrete edge failure under shear load)
𝑉𝑅𝑑,𝑐 - design resistance in case of concrete edge failure under shear load
𝑉𝑅𝑘,𝑐 - characteristic resistance in case of concrete edge failure under shear load
𝑉𝑅𝑘,𝑐𝑝 - characteristic resistance in case of concrete pry-out failure under shear load
𝑉𝑅𝑘,𝑠 - characteristic value of steel resistance of a fastener or a channel bolt under shear
load
𝑉𝑅𝑘,𝑠𝑀 - characteristic resistance in case of steel failure with lever arm under shear load
𝛼𝑐𝑡 - coefficient taking account of long-term effects on the tensile strength and of unfavor-
able effects, resulting from the way the load is applied
𝛼1 - influencing factor
𝛼2 - influencing factor
𝛾𝑀𝑐 - partial factor for concrete cone, concrete edge, concrete blow-out and concrete pry-
out failure modes
𝜂1 - coefficient related to the quality of the bond condition and the position of the bar
4
during concreting
𝑧 - the height of the non-structural element above the level of application of the seismic
action
∅ - diameter
𝜓𝑒𝑐.𝑁 - factor taking into account the group effect when different tension loads are acting on
the individual fasteners of a group in case of concrete cone failure
𝜓𝑒𝑐.𝑉 - factor taking into account the group effect when different shear loads are acting on
the individual fasteners of a group in case of concrete edge failure
𝜓ℎ.𝑉 - actor taking into account the fact that concrete edge resistance does not increase
proportionally to the member thickness
𝜓𝑀.𝑁 - factor taking into account the effect of a compression force between the fixture and
concrete in case of bending moments with or without axial force
𝜓𝑟𝑒.𝑉 - factor taking into account the effect of reinforcement located on the edge in case of
concrete edge failure
𝜓𝑠.𝑁 - factor taking into account the disturbance of the distribution of stresses in the concrete
due to the proximity of an edge in the concrete member in case of concrete cone failure
𝜓𝑠.𝑉 - factor taking into account the disturbance of the distribution of stresses in the concrete
due to the proximity of further edges in the concrete member in case of concrete edge failure
𝜓𝛼.𝑉 - factor taking into account the influence of a shear load inclined to the edge in case of
concrete edge failure
5
1 Introduction
Nowadays anchor bolts are one of the most popular fasteners in the world that are used in
modern buildings. Usually anchor bolts are used to attach steel structural elements to con-
crete structural elements (typically concrete foundation). With modern ways of structural
design, anchor bolts load-bearing capacity can be improved using supplementary reinforce-
ment. Principles and requirements for usage of supplementary reinforcement are repre-
sented in the document “Eurocode 2. Design of concrete structures. Part 4: Design of fas-
tenings for use in concrete” (EN-1992-4). This thesis is focused on how supplementary re-
inforcement can be calculated, what supplementary reinforcement depends on, and how
supplementary reinforcement impacts the anchor bolts. The purpose of the thesis was to
analyze and understand the phenomena, study how supplementary reinforcement can be
used with headed and post-installed anchor bolts according to SFS-EN-1992-4 and to study
how supplementary reinforcement effect load-bearing capacity of anchor bolts, in order to
find better and more effective solutions for usage of anchor bolts. The work was commis-
sioned by A-Insinöörit Suunnittelu Oy.
To make calculations easier and to trace the causal relationship PTC Mathcad Prime was
used. Mathcad Prime is an engineering mathematic software, that is widely used in A-In-
sinöörit Suunnittelu Oy and other engineering companies. With this program calculations
with formulas can be done more easily, than by hand, and it is possible to trace how a
particular component of the formula affects the result of calculations.
This work covers the usage of supplementary reinforcement only for headed and post-in-
stalled fasteners, but not anchor channels. Supplementary reinforcement can be used to
resist shear forces, tension forces, or both. For shear and tension forces different conditions
should be met in accordance with SFS-EN-1992-4, this should be considered before sup-
plementary reinforcement designing. In this work, anchor bolts can be also named fasten-
ers, anchors, fastenings.
2 General information
For tension load example of the strut and tie model is shown in Figure 1. For the shear load
example of the strut and tie model is shown in Figure 2.
7
Figure 1 Surface reinforcement to take up tension loads with simplified strut and tie model
(SFS-EN-1992-4 2008, 50)
Figure 2 Surface reinforcement to take up shear loads with simplified strut and tie model
(SFS-EN 1992-4 2018, 66)
2.2 Fasteners
Fastener design theory is used to describe the behavior of fasteners. According to this the-
ory, the purpose of all fasteners is to join two or more components. In most cases, the
purpose of anchor bolts is to join steel elements (such as beams and columns) and concrete
elements (foundations, beams).
8
In fastener design theory the concrete tensile capacity is directly used to trans-
fer loads into the concrete component. (SFS-EN 1992-4 2018, 9)
If there is a need to use other fasteners, additional steps in the design provisions are nec-
essary.
In Figure 3 are shown the configurations of anchors without hole clearance for all edge
distances and for all load directions and the configuration of fastenings with hole clearance
situated far from edges for all load directions and the configuration of fastenings with hole
clearance situated near an edge loaded in tension only, that are covered by this work.
9
In Figure 4 are shown the configuration of fastenings with hole clearance situated near an
edge for all load directions, which are covered by this work.
Headed anchors are cast-in fasteners with a head at the embedded end, which are placed
before pouring the concrete. An important fact about headed anchors and cast-in fasten-
ers is that the head is installed inside the concrete. The standard SFS-EN 1992-4
(2018,18) provides that this type of anchor derives its tensile resistance from a mechani-
cal interlock at the head of the fastener.
10
Figure 6 Types of headed fasteners: a) without anchor plate; b) with a large anchor plate at
least in one direction; c) with a small anchor plate in both directions (SFS-EN 1992-4 2018,
16)
Post-installed anchors are fasteners, that are installed in concrete after the concrete hard-
ens. There are several types of post-installed fasteners in the scope of this work and in
accordance with definitions from the standard SFS-EN 1992-4 (2018, 13-20) can be de-
scribed as follows:
• Undercut fastener - post-installed fastener that develops its tensile resistance from
the mechanical interlock provided by undercutting of the concrete at the embedded
end of the fastener (Figure 6 – d, 6 – e);
• Concrete screw - threaded fastener screwed into a predrilled hole where threads
create a mechanical interlock with the concrete (Figure 6 – f);
11
• Bonded fastener - fastener placed into a hole drilled in hardened concrete, which
derives its resistance from a bonding (Figure 6 – g);
• Bonded expansion fastener - bonded fastener designed such that the fastener ele-
ment can move relative to the hardened bonding compound resulting in follow-up
expansion (Figure 6 – h).
On design stage post-installed and headed anchors should be verified for every possible
failure mode. Failure modes are divided into two groups depending on the type of load:
failure modes while the fastener is in tension and failure modes while the fastener is in
shear. Failure modes of fasteners under tension load: steel failure, concrete cone failure,
pull-out failure, combined pull-out failure and concrete failure, concrete splitting failure, and
concrete blow-out failure. Failure modes of fasteners under shear load: steel failure without
lever arm, steel failure with a lever arm, concrete pry-out failure, concrete edge failure.
For all the fasteners the main value to estimate strength capacity in each failure mode is
the corresponding characteristic resistance. Characteristic resistance should be divided by
partial factors to obtain design resistance, which is compared with design force. If the design
force is not bigger than the design resistance, the failure mode is verified, and configuration
can be used.
Detailed information about concrete cone failure and concrete edge failure can be found in
section 3 “Detailing of the supplementary reinforcement” in this work.
12
Steel failure of the fastener is a failure mode that should be verified for anchors in tension.
This failure mode happens when tensile strength is so big, that the fastener strength capac-
ity can’t withstand the load, and the fastener starts to yield at first and then is torn apart.
The SFS-EN-1992-4 (2018, 51) provides that the characteristic resistance of a fastener in
case of steel failure is given in the relevant European Technical Product Specification. For
example, European Technical Product Specification can be Technical Datasheets or spe-
cial magazines for customers, that can be found on websites of companies, that produce
fasteners.
For cast-in place and post-installed fasteners it should be verified that the resultant design
tension force of the tensioned fastener is not bigger, than the design resistance in case of
steel failure under tension load: (SFS-EN 1992-4 2018, 51)
𝑁𝑅𝑘,𝑠 (1)
𝑁𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑠 =
𝛾𝑀𝑠
To ensure that steel failure is prevented designer should choose a fastener from Technical
Product Specification with sufficient characteristic resistance.
According to SFS-EN-1992-4 (2018, 19) pull-out failure is a failure mode in which the fas-
tener pulls out of the concrete without development of the full concrete resistance or in case
of post-installed mechanical fasteners a failure mode in which the fastener body pulls
through the expansion sleeve without development of the full concrete resistance.
13
For cast-in-place headed and post-installed fasteners it should be verified that the resultant
design tension force of the tensioned fastener is not bigger, than the design resistance in
case of pull-out failure of fastener with anchors under tension load: (SFS-EN 1992-4 2018,
51)
𝑁𝑅𝑘,𝑝 (2)
𝑁𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑝 =
𝛾𝑀𝑐
The characteristic resistance for fastenings in case of pull-out failure is given in according
to Technical Product specification, but for headed anchors, it is limited by the pressure of
concrete, that is placed under the head of the fastener. (SFS-EN 1992-4 2018, 56)
To ensure that pull-out failure will not happen designer should choose a fastener from Tech-
nical Product Specification with sufficient characteristic resistance and calculate the limit for
headed anchors.
2.3.3 Combined pull-out and concrete failure in case of post-installed bonded fas-
teners
Сombined pull-out and concrete failure of post-installed bonded fasteners happen when the
connection between the bonding material and concrete base doesn’t have adequate
strength, and failure between them occurs. This can also happen to the anchor bolt and the
bonding material, and in addition concrete cone formed at the end of the fastener breaks
out with the fastener.
14
Figure 10 Combined pull-out and concrete failure of bonded fasteners (SFS-EN 1992-4
2018, 49)
For post-installed bonded anchors, it should be verified that the resultant design tension
force of the tensioned fastener is not bigger, than the design resistance in case of combined
pull-out and concrete failure of fastener with anchors under tension load: (SFS-EN 1992-4
2018, 51)
𝑁𝑅𝑘,𝑝𝑐 (4)
𝑁𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑝𝑐 =
𝛾𝑀𝑝
Provision of strength can be done by choosing enough diameter of the fastener, sufficient
effective embedment depth of a fastener, adequate concrete strength class, and increase
of distance between the fastener and edge of the concrete element.
Concrete splitting failure occurs when tension loads applied to a fastener are so high, that
concrete can’t withstand the load, and splitting cracks start to occur along a plane passing
through the axis of the fastener.
For cast-in-place and post-installed fasteners, it should be verified that the resultant design
tension force of the tensioned fastener is not bigger, than the design resistance in case of
concrete splitting failure with anchors under tension load. (SFS-EN 1992-4 2018, 51)
𝑁𝑅𝑘,𝑠𝑝 (5)
𝑁𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑠𝑝 =
𝛾𝑀𝑠𝑝
Concrete splitting failure during installation (e.g., when applying the installation
torque on a fastener) is avoided by complying with minimum values for edge dis-
tances, spacing, member thickness and requirements for reinforcement as given in
the relevant European Technical Product Specification (SFS-EN 1992-4 2018, 59).
Concrete blow-out failure is usually related to fasteners with a deep embedment and tiny
side covers. Also, it should be mentioned that verification in case of concrete blow-out fail-
ure applies to headed anchors, and if post-installed undercut fasteners are used as headed
anchors with edge distance not bigger than 50% of the effective embedment depth of the
fastener. The SFS-EN-1992-4:2018 (14) provides that concrete blow-out failure can be de-
scribed as spalling of the concrete on the side face of the concrete element at the level of
the embedded head with no major breakout at the top concrete surface.
For headed and post-installed mechanical undercut fasteners designed as headed fasten-
ers, it should be verified that the resultant design tension force of the tensioned fastener is
16
not bigger than design resistance in case of concrete blow-out failure with anchors under
tension load. (SFS-EN 1992-4 2018, 51)
𝑁𝑅𝑘,𝑐𝑏 (6)
𝑁𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑐𝑏 =
𝛾𝑀𝑐
If configuration with several fasteners acting as a group, verification should be done for the
anchor that is closest to the edge.
If at the design stage it is calculated that concrete blow-out failure will occur, it can be pre-
vented by the usage of a higher concrete strength class and with an increase of edge dis-
tances.
According to the SFS-EN 1992-4 (2018, 43) if the fixture is made out of steel and is in
contact with the fastener over a length of at least 50% of thickness of a fixture and the fixture
is fixed directly to the concrete without an intermediate layer or the fixture is fixed using a
levelling mortar with a thickness not larger than 50% of a diameter of a fastener under at
least the full dimensions of the fixture on a rough concrete surface as intermediate layer,
shear loads acting on fastenings may be assumed to act without a lever arm.
Steel failure of fastener without lever arm under shear load can happen because of the low
steel strength capacity of a certain fastener or because the diameter of the anchor is too
small.
The SFS-EN-1992-4 (2018, 66) provides that the characteristic resistance of a fastener in
case of steel failure is given in the relevant European Technical Product Specification.
Figure 13 Steel failure of fastener without lever arm (SFS-EN 1992-4 2018, 64)
For cast-in-place and post-installed fasteners it should be verified that the resultant design
shear force of the most loaded fastener is not bigger, than the design resistance in case of
steel failure without a lever arm with anchors under shear load. (SFS-EN 1992-4 2018, 65)
17
𝑉𝑅𝑘,𝑠 (7)
𝑉𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑠 =
𝛾𝑀𝑠
To prevent steel failure without a lever arm and to increase the resistance, a fastener with
bigger diameter and more resistant steel material should be chosen.
In the case of steel failure of a fastener with a lever arm, a bending effect caused by a shear
load applied with a lever arm in relation to the surface of the concrete element is taken into
account.
Figure 14 Steel failure with lever arm (SFS-EN 1992-4 2018, 64)
For cast-in-place and post-installed fasteners, it should be verified that the resultant design
shear force of the most loaded fastener is not bigger than the design resistance in case of
steel failure with lever arm with anchors under shear load. (SFS-EN 1992-4 2018, 65)
𝑉𝑅𝑘,𝑠𝑀 (8)
𝑉𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑠𝑀 =
𝛾𝑀𝑠
To ensure that the steel failure of the fastener with the lever arm is verified, an anchor with
sufficient characteristic bending resistance should be used. The characteristic bending re-
sistance of the fastener can be found in the relevant Technical Product Specification.
The SFS-EN 1992-4 (2018, 14) provides concrete pry-out failure can be described as failure
that corresponds to the formation of a concrete spall opposite to the loading direction under
shear loading.
18
For cast-in-place and post-installed fasteners it should be verified that the resultant design
shear force of the most loaded fastener is not bigger, than the design resistance in case of
concrete pry out failure with anchors under shear load. (SFS-EN 1992-4 2018, 65)
𝑉𝑅𝑘,𝑐𝑝 (9)
𝑉𝐸𝑑 ≤ 𝑁𝑅𝑑,𝑐𝑝 =
𝛾𝑀𝑐
According to SFS-EN 1992-4 the value of the characteristic resistance in case of concrete
pry-out failure is less with supplementary reinforcement, rather than with supplementary
reinforcement. It is better to not use supplementary reinforcement in order to prevent con-
crete pry-out failure.
To increase the resistance in case of pry-out failure, designers can use anchors with bigger
diameters in configurations or increase the volume of engaged concrete
Supplementary reinforcement can take up tension or shear loads and improve the load-
bearing capacity of anchor bolts in cases of concrete cone failure and concrete edge failure.
In accordance with SFS-EN-1992-4 (2018, 47), the supplementary reinforcement shall be
designed for the resultant design tension force of the tensioned anchor (in case of the single
anchor is used) or design value of tensile load acting on the most stressed anchor of a
group (in case of a group of fasteners is used). Properties of suitable reinforcement are then
applied to all reinforcement designed for other anchors. Standardization of reinforcement
makes the process of design faster, makes processes of installation on site easier, and
minimizes the risk of making a mistake in the design stage.
The SFS-EN-1992-4 (2018, 47) provides that in case when supplementary reinforcement
is placed in the direction of the design shear force, the design tension force in the supple-
mentary reinforcement caused by the design shear force acting on a fixture perpendicular
and towards the edge shall be calculated as follows:
19
𝑒𝑠 (10)
𝑁𝐸𝑑,𝑟𝑒 = ( + 1) ∙ 𝑉𝐸𝑑
𝑧
After analyzing Formula (1) it can be concluded, that to minimize design tension force in the
supplementary reinforcement in the design stage, the distance between the axis of rein-
forcement and the line of shear force acting on the fixture should be as small as possible,
and effective depth to supplementary reinforcement should be as big as possible. Forces in
the reinforcement and concomitant distances are shown in Figure 7.
At the design stage, it can be assumed that supplementary reinforcement will take up ten-
sion loads instead of relying this responsibility on concrete cone strength. This can be de-
cided when high tension loads are applied to thin and small anchors or when anchors should
be placed near the corner or the edge of the element. When the design relies on supple-
mentary reinforcement, concrete cone failure does not need to be verified. The values of
the design resistance of supplementary reinforcement will be used instead of design re-
sistance of a fastener in case of concrete cone failure. This means, that supplementary
reinforcement should be assumed effective, if the design resistance of the supplementary
reinforcement will be bigger, than the design resistance of the anchor in case of concrete
cone failure. Sizing and placing of supplementary reinforcement should also be considered
following specific requirements.
Concrete cone failure is one of the failure modes, that can occur when anchor bolts are
used. This failure mode applies both for headed and post-installed fasteners. Most of the
incident’s concrete in case of failure has a cone shape as shown in Figure 8.
For cast-in-place and post-installed fasteners, it should be verified that the resultant design
tension force of the tensioned fastener is not bigger than design resistance in case of con-
crete cone failure under tension load. (SFS-EN 1992-4 2018, 51)
𝑁𝑅𝑘,𝑐 (11)
𝑁𝐸𝑑 < 𝑁𝑅𝑑,𝑐 =
𝛾𝑀𝑐
Partial factor for concrete cone failure mode should be defined before verification of con-
crete cone failure.
Table 1 Partial factors for concrete related failure (SFS-EN 1992-4 2018, 34)
The geometric effect of axial spacing and edge distance on the characteristic resistance is
considered by the division of actual area of the idealized concrete cone of a group of fas-
teners and reference projected area of the concrete cone of an individual fastener: (SFS-
EN-1992-4 2018, 52)
𝐴𝑐,𝑁 (13)
𝐴0𝑐,𝑁
22
Figure 18 Areas of the idealized concrete cone: a) reference projected area of the idealized
concrete cone of an individual fastener; b) actual area of the idealized concrete cone of a
group of four fasteners (SFS-EN-1992-4 2018, 52)
The algorithm for concrete cone failure verification is shown in Figure 19 and an example
of the calculation can be found in Appendix. The resistance can be greatly improved by
using high concrete strength class and by increasing the effective embedment depth of a
fastener. The placing of configuration is also important, it is better to place the configuration
far from edges and make edge distances as much as possible, which can be difficult in real
projects.
23
• The shape of reinforcement shall be ribbed reinforcing bars with characteristic steel
yield strength less than 600 𝑁/𝑚𝑚 2. The diameter of the bars should be no larger
than 16 mm. Reinforcement shall be detailed as stirrups or loops with a mandrel
diameter according to EN-1992-1-1;
• The supplementary reinforcement should be sized for the most loaded fastener in a
group, after that this certain type of reinforcement shall be placed for other fasteners;
• The supplementary reinforcement bars with a distance less than 75 percent of ef-
fective embedment depth from the anchor should be assumed as effective;
• Surface reinforcement should resist the forces arising from the assumed strut and
tie model and the splitting forces. Example of how surface reinforcement should be
provided is shown in Figure 1.
When the design relies on supplementary reinforcement to take up shear loads, concrete
edge failure does not need to be verified. The values of the design resistance of supple-
mentary reinforcement will be used instead of the design resistance of a fastener in case of
concrete edge failure. The supplementary reinforcement can be designed in the form of a
surface reinforcement as shown in Figure 2 or in the shape of stirrups or loops as shown in
Figure 20. Sizing and placing of supplementary reinforcement should also be considered
following specific requirements.
25
Concrete edge failure is one of the failure modes, that can occur when anchor bolts are
used. This failure mode applies both for headed and post-installed fasteners. This failure
mode takes place when the concrete fails towards an edge under shear loading, as shown
in Figure 21.
For cast-in-place and post-installed fasteners, it should be verified that the design shear
load of the most loaded fastener is not bigger than the design resistance in case of concrete
edge failure under shear load. (SFS-EN 1992-4 2018, 65)
𝑉𝑅𝑘,𝑐 (14)
𝑉𝐸𝑑 ≤ 𝑉𝑅𝑑,𝑐 =
𝛾𝑀𝑐
26
The partial factor for concrete edge failure mode should be defined before verification of
concrete edge failure. This can be done with Formula 3 and Table 1, the same as for con-
crete cone failure.
Only the fasteners located closest to the edge are used for the verification of concrete edge
failure. For fastenings with more than one edge, verification shall be carried out for all edges.
Where design checks are required, this should be for all suitable edges, as shown in Figure
13.
Figure 22 Verification for group of four fasteners at a corner: a) applied action; b) verification
for the left edge; c) verification for the bottom edge (SFS-EN-1992-4 2018, 70)
The geometrical effect of spacing as well as of further edge distances and the effect of
thickness of the concrete member on the characteristic resistance is taken into the account
by the division of actual area of the idealized concrete edge of a group of fasteners and
reference projected area of the concrete edge of an individual fastener: (SFS-EN-1992-4
2018, 71)
𝐴𝑐,𝑉 (15)
𝐴0𝑐,𝑉
27
Figure 23 Areas of the idealized concrete cone under shear loading: a) reference project
area for a single fastener; b) actual projected area for a single fastener at a corner; c) actual
projected area for group of fasteners at an edge in a thin concrete member (SFS-EN-1992-
4 2018, 71)
The algorithm for concrete cone failure verification is shown in Figure 24 and an example
of the calculation can be found in Appendix. The general rule for concrete edge resistance
improvement is using a high concrete class and placing anchors as far as possible from the
edge.
28
According to SFS-EN 1992-4 (2018, 65) , the supplementary reinforcement to take up shear
load shall be designed with following requirements:
• Where supplementary reinforcement has been sized for the most loaded fastener,
the same reinforcement is provided around all fasteners considered effective for
concrete edge failure;
• Bars are within a distance of 75% of edge distance in direction perpendicular to the
edge from the fastener;
• The anchorage length in the concrete breakout body equals at least 10 diameters
for straight bars with or without welded transverse bars and equals at least 4 diam-
eters for bars with a hook, bend or loop;
• The breakout body assumed should be the same as that for calculating the re-
sistance for concrete edge failure;
• Reinforcement along the edge of the member is provided and designed for the
forces according to an appropriate strut and tie model. As a simplification an angle
of the compression struts of 45 degrees may be assumed.
30
In order to increase the resistance of the fasteners against concrete cone failure and con-
crete edge failure, it is possible to use supplementary reinforcement around the fastening.
After the concrete cone crack surface is formed, the reinforcement acts on keeping the
concrete cone and member together. In such conditions not only the resistance of the an-
chorage is increased but also the ductility. So, the supplementary reinforcement delays and
prevents the formation of a concrete cone, and therefore two new failure modes may occur
- steel failure and anchorage failure.
Permanent and
Steel failure in sup- 1,15
transient design
plementary reinforce- 𝛾𝑀𝑠,𝑟𝑒
ment Accidental design
1,0
situation
When steel failure occurs reinforcement rebars are starting to yield at first and are then torn
apart, because of a lack of load-bearing capacity. The main property of reinforcement that
is responsible for load-bearing capacity regarding steel failure is the design resistance of
supplementary reinforcement in case of steel failure.
For steel failure of supplementary reinforcement in tension, it should be verified, that the
design value of tension load acting on the supplementary reinforcement is not bigger than
the design resistance in case of steel failure of supplementary reinforcement: (SFS-EN
1992-4 2018, 51)
31
𝑁𝑅𝑘,𝑟𝑒 (16)
𝑁𝐸𝑑,𝑟𝑒 ≤ 𝑁𝑅𝑑,𝑟𝑒 =
𝛾𝑀𝑠,𝑟𝑒
The characteristic yield resistance of the supplementary reinforcement for one fastener is
calculated with the formula: (SFS-EN 1992-4 2018, 63)
𝑛𝑟𝑒
(17)
𝑁𝑅𝑘,𝑟𝑒 = ∑ 𝐴𝑠,𝑟𝑒,𝑖 ∙ 𝑓𝑦𝑘,𝑟𝑒
𝑖=1
As it can be seen from the formulas, the characteristic yield resistance of the supplementary
reinforcement depends directly proportional on:
The bigger the characteristic yield resistance is, the bigger the design resistance of supple-
mentary reinforcement gets. The bigger the design resistance is, the bigger loads reinforce-
ment can withstand. To increase characteristic yield strength one of the components of the
formula should be increased. Cross section of a reinforcing bar can be increased by using
32
rebars with a bigger diameter, but according to requirements rebars with a diameter no
larger than 16 mm can be used.
One aspect of this work is to analyze how components of formulas can affect the result. In
order to trace the causal relationship between design resistance of supplementary rein-
forcement and changes in numbers of effective rebars, changes in yield strength, and
changes in the diameter of rebars, there should be a reference point. Other results will be
compared to a reference point, and it will be easier to compare other results between them-
selves. The configuration of reinforcement with properties as in Table 3 was used as a
reference point.
It is important to mention that in Finland rebars with a yield strength of 400 N/mm2 or with
a diameter of 14 mm are not used in real projects, but since this thesis work will be published
worldwide, rebars with a yield strength of 400 N/mm2 and a diameter of 14 mm will be used
in calculations.
After reference configuration has been obtained, components of the formula can be
changed one by one. This will show which of the effects of the components result in the
most. In the case of studying steel failure phenomena in this work, the diameter of one
rebar, the number of effective rebars, and yield strength have been increasing. The partial
factor value for all configurations was 1,15.
Figure 26 Design resistance in case of steel failure of the anchor reinforcement depending
on changes in diameter of a rebar
Table 5 Design resistance in case of steel failure depending on changes in number of ef-
fective rebars
34
Figure 27 Design resistance in case of steel failure of the anchor reinforcement depending
on changes in number of effective rebars
Table 6 Design resistance in case of steel failure of the anchor reinforcement depending on
changes in yield strength
Figure 28 Design resistance in case of steel failure of the anchor reinforcement depending
on changes in yield strength
35
To compare the results between themselves the chars were combined in one chart.
Figure 29 Chart for the relationship between design resistance of supplementary reinforce-
ment in case of steel failure and changes in numbers of rebars, yield strength, the diameter
of rebars
As it can be seen from the chart, an increase in yield strength affects design resistance
least out of all components, so in the design stage changes in yield strength can be done
last. At a short distance increase in effective rebars increase design resistance more, than
the increase in diameter of rebars. But on long-distance changes in the diameter of rebars
increase design resistance more, than changes in the amount of rebars. In a conclusion, it
can be said, that if a small increase in design resistance is needed, the number of rebars
can be increased in the first order, but if there is a need for a great improvement of design
resistance, changes in diameter can be done first.
Due to lack of space, it is sometimes impossible to increase the number of effective re-bars.
It is important to understand how design resistance is increasing without changing the num-
ber of effective rebars. In that case, only the yield strength and diameter of rebars can be
changed. To track how to design resistance is changing according to the increase of those
two parameters calculations were made.
Results showed that the peak value for design resistance that can be obtained with two
effective rebars is 210 kN. This peak value is achieved in configuration with a possibly
36
highest diameter of the rebar 16 mm and possibly highest yield strength of 600 N/mm2
according to requirements for supplementary reinforcement design.
After comparison of results for configurations with yield strengths of 400 N/mm2 and 500
N/mm2 as a conclusion, it can be said that design resistance growth is 25% for each pos-
sible diameter of the rebar. If the same comparison would be applied to configurations with
yield strengths of 500 N/mm2 and 600 N/mm2 , design resistance growth is 20%. In com-
parison for configurations with yield strengths of 400 N/mm2 and 600 N/mm2 design re-
sistance growth is 50%.
400 19
1,15 2 6 500 24
600 29
400 35
1,15 2 8 500 43
600 52
400 55
1,15 2 10 500 69
600 82
400 79
1,15 2 12
500 98
37
600 118
400 107
600 161
400 140
600 210
Table 6 Design resistance depending on the different yield strengths and changes in diam-
eter of a rebar
Figure 31 Chart for the relationship between design resistance of supplementary reinforce-
ment in case of steel failure and supplementary reinforcement with different yield strength
and changes in the diameter of rebars
The design resistance growth is almost the same for configurations with different yield
strengths. This can be explained by Figure 17 and among all the parameters yield strength
affects design resistance the least.
It can be seen that the bigger diameter gets, the lower the design resistance growth be-
comes. If the diameter of supplementary reinforcement will be changed from 6 mm to 8 mm,
design resistance will become almost two times bigger. But if in the same conditions diam-
eter would be changed from 14 mm to 16 mm, design resistance growth will be 30%.
Figure 32 Growth of the design resistance depending on the diameter of the rebar
39
2 24
1,15 500 6 3 37
4 49
2 43
1,15 500 8 3 65
4 87
2 69
4 137
2 98
4 197
2 134
4 268
2 175
4 350
Table 7 Design resistance depending on the number of the rebars and changes in diame-
ter of a rebar
40
Figure 33 Chart for the relationship between design resistance of supplementary reinforce-
ment in case of steel failure and supplementary reinforcement with different number of ef-
fective rebars and changes in the diameter of rebars
For steel failure of supplementary reinforcement in shear it should be verified, that the de-
sign value of tension load acting on the supplementary reinforcement is not bigger than the
design resistance in case of steel failure of supplementary reinforcement. The design value
of the tension load should be calculated according to Formula 10. (SFS-EN 1992-4 2018,
65)
𝑁𝑅𝑘,𝑟𝑒 (18)
𝑁𝐸𝑑,𝑟𝑒 ≤ 𝑁𝑅𝑑,𝑟𝑒 =
𝛾𝑀𝑠,𝑟𝑒
𝑛𝑟𝑒
(19)
𝑁𝑅𝑘,𝑟𝑒 = 𝑘10 ∙ ∑ 𝐴𝑠,𝑟𝑒,𝑖 ∙ 𝑓𝑦𝑘,𝑟𝑒
𝑖=1
As it can be seen from the formulas, all calculations and conclusions in the case of tension
load can be applicable in the case of shear load, but the efficiency factor should be consid-
ered.
The efficiency factor takes into account the shape of the supplementary reinforcement: sur-
face reinforcement as in Figure 2 or the shape of stirrups or loops enclosing the fastener as
in Figure 11 (SFS-EN-1992-4 2018, 75). Values for the efficiency factor are shown in Table
8.
Surface reinforcement 1
Efficiency
𝑘10 Shape of stirrups or loops enclosing the
factor 0,5
fastener
supplementary reinforcement in the shape of surface reinforcement under shear load the
design resistance values are the same as under tension load.
Supplementary reinforcement used to resist either tensile or shear forces must be properly
anchored into the assumed concrete cone failure zone. The main property of reinforcement
that is responsible for load-bearing capacity regarding anchorage failure is the design re-
sistance of supplementary reinforcement in case of anchorage failure.
The design resistance of the supplementary reinforcement provided for one fastener asso-
ciated with anchorage failure in the concrete cone is: (SFS-EN 1992-4 2018, 63)
𝑛𝑟𝑒
0
𝑁𝑅𝑑,𝑎 = ∑ 𝑁𝑅𝑑,𝑎,𝑖 (21)
𝑖=1
In order to calculate the design resistance of the supplementary reinforcement, design re-
sistance of one rebar should be calculated first: (SFS-EN 1992-4 2018, 64)
0
𝑙1 ∙ 𝜋 ∙ ∅ ∙ 𝑓𝑏𝑑 (22)
𝑁𝑅𝑑,𝑎 =
𝛼1 ∙ 𝛼2
To calculate the design resistance of one rebar, design bond strength should be calculated.
(SFS-EN 1992-1-1 2004, 133)
In order to calculate design bond strength, the design tensile concrete strength should be
calculated. (SFS-EN 1992-1-1 2004, 34)
43
According to the SFS-EN-1992-4, design resistance of one rebar should be no larger than
followed product of the parameters: (SFS-EN-1992-4 2018, 64)
0
1 (25)
𝑁𝑅𝑑,𝑎,𝑖 ≤ 𝐴𝑠,𝑟𝑒 ∙ 𝑓𝑦𝑘,𝑟𝑒 ∙
𝛾𝑀𝑠,𝑟𝑒
According to standard SFS-EN 1992-1-1 (2004, 133) due to the increasing brittleness of
higher strength concrete, the characteristic axial tensile strength of concrete should be lim-
ited to the value for C60/75, unless it can be verified that the average bond strength in-
creases above this limit. Values for the characteristic axial tensile strength of concrete are
given in Appendix 1.
Long term coefficient is a coefficient taking account of long-term effects on the tensile
strength and unfavorable effects, resulting from the way the load is applied. (SFS-EN 1992-
1-1 2004, 34)
A partial safety factor for concrete is used to negotiate the fact, that calculations are based
on a simplified model and the possible heterogeneity of the material. Value for partial fac-
tor for concrete depends on the design situation: accidental or persistent and transient.
Values for partial factors for concrete are given in Table 10. (SFS-EN 1992-1-1 2004, 24)
The bond condition coefficient relates to the quality of the bond condition and the position
of the rebar during concreting. There can be good bond conditions and all other cases, or
situations when bars in structural elements build with slip-forms unless it can be shown that
good bond conditions exist. (SFS-EN 1992-1-1 2004, 133)
Sym-
Coefficient Situation Value
bol
The bar diameter coefficient is related to the bar diameter. Due to supplementary reinforce-
ment design requirements, the rebar diameter cannot be bigger than 16 mm. If the rebar
diameter is no larger than 32 mm, the bar diameter coefficient value is 1,0. (SFS-EN 1992-
1-1 2004, 134)
Influence factors are considering the effect of the form of the bars assuming adequate
cover (See Figure 21) and the effect of concrete minimum cover (See Figure 22).
Figure 37 Methods of anchorage other than by a straight bar (SFS-EN 1992-1-1 2004, 133)
As it can be seen from the formulas, the design resistance of the supplementary reinforce-
ment depends on:
• diameter of a rebar
• anchorage length
• shape of reinforcement
• bond conditions
By increasing the strength class for concrete, the design tensile concrete strength will grow
in its turn. When design tensile concrete strength increases, design bond strength grows
too, which directly affects the design resistance of the supplementary reinforcement. If the
diameter of the rebar is changed with a bigger diameter, the anchorage length minimum
value will get bigger due to Table 14, which is also increasing the design resistance of the
supplementary reinforcement. Even so, in real projects, the values of minimum anchorage
length are not used, and the actual anchorage leg length is larger than the minimum. The
actual anchorage length is limited by the embedment length of the fastener, thus in the
actual case, it might be impossible to use bigger diameter rebars because bigger anchorage
lengths will be above the limit set by embedment length. However, in general, bond re-
sistance is better with smaller diameter rebars.
In most cases, the anchorage length of the reinforcement is a crucial parameter out of all,
since it can be assumed as effective only if placed in a possible concrete cone break-out
body and have relatively small values. The anchorage length also is reducing because of
the concrete cover and because it cannot be placed right next to the anchor bolts. According
to the requirements for supplementary reinforcement placing, reinforcement should be
placed at a distance within 75% of the effective embedment depth of the anchor.
48
To estimate the maximum length of anchorage reinforcement, anchor bolt HILTI HAS-U
M12 has been used in calculations. In a possible concrete cone to get the biggest values
for anchorage length, the reinforcement should be placed as close to the anchor as possi-
ble. The most important properties of the configuration for anchorage length estimation are
shown in Table 15.
Diameter of reinforcement ∅ 12 mm
Concrete cover - 20 mm
Figure 40 Supplementary reinforcement with diameter 12 mm with anchor bolt HILTI HAS-
U M12 effective embedment depth 110 mm
As it can be seen from the calculations the anchorage length is 72 mm, which is low for
proper anchorage in general, but according to the SFS-EN 1992-4 requirements, this an-
chorage length is bigger than four diameters of reinforcement and is applicable for use.
If in the same configuration reinforcement with a lower diameter were used, the anchorage
length would get bigger. The use of reinforcement with a bigger diameter can be more com-
plicated because rebars have minimum bending radius characteristics, which is depending
on the diameter of the rebar. In the case of applying a rebar with a bigger diameter, it might
need a bigger distance between the fastener and the rebar in order to make a curve for a
loop. A bigger distance between the fastener and rebar brings the reinforcement closer to
the surface of the concrete cone and at the same time makes the anchorage length value
lower.
50
Figure 40 Supplementary reinforcement with diameter 6 mm with anchor bolt HILTI HAUS-
U M12 effective embedment depth 110 mm
Another aspect is a consideration of how large rebar diameter can be used in order to fulfill
anchorage requirements with the use of fasteners with small effective embedment lengths.
With the assumption that the anchorage length value is about 70% of the embedment length
in Table 15, this relation is shown.
Table 15 Relation between diameter of a rebar and short effective embedment depths
After analyzing the relation between the diameter of rebar and effective embedment depths
as conclusion it can be said that it is almost impossible to use straight reinforcement with
short anchorages, which according to Formula 19 and Table 8 will lead to two times less
resistant reinforcement in the case of steel failure under shear.
51
The parameter that influences the anchorage length the most is effective embedment depth.
An increase of effective embedment depth will lead to the great improvement of anchor-age
length, but at the same time will lead to significant improvement of concrete cone failure,
which will cause doubts about the effectiveness of supplementary reinforcement in the cur-
rent design situation.
Figure 41 Supplementary reinforcement with diameter 6 mm with anchor bolt HILTI HAUS-
U M12 effective embedment depth 220 mm
There are also other factors besides anchorage length that can help to increase the re-
sistance of supplementary reinforcement. Also, due to element size restrictions, it is some-
times impossible to increase the number of effective rebars. The supplementary reinforce-
ment design resistance can be improved by increasing concrete strength class and bigger
diameter instead. To track how design resistance is changing without changing the number
of rebars and anchorage length, the calculations were made using the reference configura-
tion, with two effective rebars and using different concrete strength classes and with diam-
eter changes. Results can be seen in Figure 42. However, it is important to understand that
there can be other ways of improving the design resistance of supplementary reinforcement,
for example in order to increase the resistance one rebar with a big diameter due to element
size restrictions can be changed to two rebars with less diameter, which will also lead to
increase of design resistance. There are no good and bad ways of design, they are depend-
ent on the situation and all of them can lead to a positive result.
52
Figure 42 Chart for the relationship between design resistance of supplementary reinforce-
ment in case of anchorage failure and supplementary reinforcement with same anchorage
length and different concrete strength classes and changes in the diameter of rebars
Track of design resistance growth depending on the concrete strength class is shown in
Figure 25. The bigger the concrete strength class gets the less is design resistance growth.
on changes in the diameter is shown in Figure 26. The bigger diameter gets, the lower the
design resistance growth becomes. If the diameter of supplementary reinforcement will be
changed from 6 mm to 8 mm, the design resistance will become 80% bigger. But if in the
same conditions the diameter would be changed from 14 mm to 16 mm, design resistance
growth will be 30%.
Figure 44 Growth of the design resistance depending on the diameter of the rebar
For supplementary reinforcement in shear in case of anchorage failure all the verifications
are the same as for tension load. For applications with supplementary reinforcement in the
shape of stirrups or loops in contact with the fastener (see Figure 20) no proof of the an-
chorage capacity of the supplementary reinforcement in the assumed concrete break-out
body is necessary. For applications in shear with supplementary reinforcement as a surface
reinforcement (See Figure 2) the design resistance is calculated as if the application would
have been in tension. (SFS-EN 1992-4 2018, 75)
55
For fastenings with supplementary reinforcement design resistances for concrete cone fail-
ure and for a concrete edge failure are replaced with corresponding values for the failure of
supplementary reinforcement. (SFS-EN 1992-2-4 2018, 76)
Edge distance 𝑐1 65 mm
Spacing distance 𝑠1 65 mm
Eccentricity 𝑒𝑛 0
Embedment length 𝑙𝑓 = ℎ𝑓 70 mm
57
Inclination angle 𝛼𝑣 0
Table 17 Configuration with anchor bolt HILTI HAUS-U M12 without supplementary rein-
forcement
Design tension force and design shear forces are bigger than the design resistances of a
fastener, and this means that supplementary reinforcement is needed in both situations, for
tension load and for shear load too (or changes in configuration). After the design resistance
for the anchor bolt has been calculated, the supplementary reinforcement properties should
be selected. In given example supplementary reinforcement is designed taking up tension
loads only and taking up shear loads only, but have same properties for both situations. In
Figure 47 are shown drawings for supplementary reinforcement for tension load only and
for shear load only.
Diameter of reinforcement ∅ 12 mm
Anchorage length 𝑙1 49 mm
Figure 47 Supplementary reinforcement with anchor bolt HILTI HAS-U M12: a) to take up
tension loads only; b) to take up shear loads only
The supplementary reinforcement has bigger design resistances than the design re-
sistances of a fastener, which means that selected reinforcement can improve the strength
of an anchor bolt HILTI HAS-U M12 with given design forces. However, because of low
embedment depth and strict limits for anchorage length it was difficult to choose appropriate
reinforcement.
The design resistance of supplementary reinforcement in case of steel failure under tension
is many times higher than other design resistances, which means that in most cases steel
failure is not a problem with supplementary reinforcement usage. With such high steel fail-
ure design resistance, the anchorage failure design resistance barely withstands the load.
It is important to understand, that if the design shear load was bigger, the anchor failure
would not be verified, and it would be impossible to somehow improve the anchor design
resistance due to the impracticability of anchoring the reinforcement with requirements
given in standard SFS-EN 1992-4. In that case, in order to improve the anchorage length
of the reinforcement, an increase in effective embedment depth and edge distances would
be needed. The effective embedment depth and edge distances are affecting concrete cone
design resistance and concrete edge resistance nearly the most out of all possible factors,
so the increase of those factors will greatly increase the design resistances of a fastener.
After the design resistances of an anchor bolt would be increased, the use of supplementary
reinforcement can be arguable. This means that supplementary reinforcement cannot be
used as a good solution in every design situation, the main principle of the anchor reinforce-
ment usage is to apply it only when it is needed and design it according to the standard
restrictions.
60
6 Summary
The thesis demonstrates the full process of the supplementary reinforcement design for the
cast-in-place headed and post-installed anchor bolts. This work can be useful to familiarize
with supplementary reinforcement phenomena, and with failure modes for a fastener. All
the requirements and coefficients related to supplementary reinforcement design according
to standard EN 1992-4 have been collected in this work with examples for failure modes
verification.
An example of properly chosen reinforcement, which can increase the load-carrying capac-
ity of anchor bolts is shown in this work. The supplementary reinforcement can improve
fastener resistance to concrete cone failure and concrete edge failure. However, this thesis
it is explained why the use of supplementary reinforcement in some cases can be arguable.
Due to strict limits of anchorage length of supplementary reinforcement, it sometimes can
be difficult to choose reinforcement with sufficient diameter, which leads to low strength
abilities. In order to increase the leg of anchorage, changes in the configuration of a fas-
tening are needed, which in its turn increases the design resistance of a fastener and makes
applying supplementary reinforcement questionable.
61
References
SFS-EN 1992-4 (2018): Eurocode 2. Design of concrete structures. Part 4: Design of fas-
tenings for use in concrete
SFS-EN 1992-1-1 (2004): Eurocode 2: Design of concrete structures. Part 1-1: General
rules and rules for buildings
Sharma, A.; Eligehausen, R.; Asmus, J. & Bujnak, J. 2018. Behavior of Anchorages with
Supplementary Reinforcement Tension or Shear Forces. Stuttgart: Springer International
Publishing AG 2018. Retrieved on 12 August 2022. Available at: https://www.re-
searchgate.net/publication/322168220_Behavior_of_Anchorages_with_Supplemen-
tary_Reinforcement_Under_Tension_or_Shear_Forces
Appendix 1. Strength and deformation characteristics for concrete (SFS-EN 1992-1-1 2004,
29)
Appendix 2. Settling details for HILTI HAS-U anchor bolts
Appendix 3. Concrete cone failure verification example
Appendix 4. Concrete edge failure verification example