Tabulation of Design Standards: P.D 1096: Building Code, P.D. 1185: Fire Code, P.D.

957: Subdivision &


Condominium Law, B.P. 220: Economic & Socialized Housing & B.P. 344: Accessibility Law

P.D 957
Subject P.D 1096 P.D 1185 Subdivision & B.P 220 Economic B.P 220 B.P 344
Building Code Fire Code Condominium Housing Socialized Accessibility
Law Housing Law
Residential
Requirements
Corner Lot Maximum of 90% of N/A N/A N/A N/A N/A
the lot
Inside Lot Maximum of 80% of N/A N/A N/A N/A N/A
the lot
At least 250 mm N/A N/A N/A N/A N/A
Foundation thick, 600 mm below
ground surface
Occupant Load 18.6 sq. m/ person N/A 18.6 sq. m/ person No. of units Multiplied No. of units Multiplied N/A
by 6 by 6
Live Load @ 1 floor At least 200 kg. / sq. N/A N/A N/A N/A N/A
st

.m
Live Load @ 2
nd
At least 150 kg. / sq. N/A N/A N/A N/A N/A
floor m
Stair Width At least 750 mm N/A 1.10 m 600 mm 600 mm
Stair Riser Max. of 200 mm N/A 200 mm 200 mm 200 mm
Stair Tread At least 200 mm N/A 250 mm 250 mm 250 mm
Refer to Fire N/A
Entrance & Exit At least 1 entrance & Code At least 1 entrance & At least 1 entrance & At least 1 entrance &
1 exit Specifications 1 exit 1 exit 1 exit
(Too many to
tabulate)

Light &
Ventilation
Min. dimension of 2.00 m N/A 1.50 m 2.00 m 2.00 m N/A
court
Passageway from At least 1.20 m N/A At least 1.20 m At least 1.20 m At least 1.20 m N/A
Inner Court
Min. Ht. Clearance 1.00 m above the roof N/A 1.00 m above the roof 1.00 m above the roof 1.00 m above the roof N/A
from Firewall
Headroom 2.00 m 2.00 m 2.00 m 2.00 m 2.00 m N/A
Clearance
Min. Ceiling Ht. for 2.40 m – Artificial 2.40 m – Artificial
Habitable Rooms Ventilation 2.30 m Ventilation 2.40 m 2.40 m N/A
2.70 m – Natural 2.70 m – Natural
Ventilation Ventilation

Min. Ceiling Ht. for st


2.70 m – 1 Storey
Buildings nd
2.40 m – 2 Storey 2.30 m N/A
2.10 m – Succeeding
Storeys 2.00 m 2.00 m 2.00 m
1.80 m – Mezzanine 1.80 m - Mezzanine 1.80 m - Mezzanine 1.80 m - Mezzanine
2.13 m

Sum of Areas of Less than 50% of total Less than 50% of Less than 25% of total Less than 25% of
Openings in any area of the wall on that N/A total area of the wall area of the wall on total area of the wall N/A
Storey storey on that storey that storey on that storey

Window Openings At least 10% of the N/A At least 10% of the At least 10% of the At least 10% of the N/A
floor area floor area floor area floor area
Eaves over required At least 750 mm N/A N/A N/A N/A N/A
windows

P.D 957
Size/ Dimension P.D 1096 P.D 1185 Subdivision & B.P 220 Economic B.P 220 B.P 344
of Rooms Building Code Fire Code Condominium Housing Socialized Accessibility
Law Housing Law
Rooms for Human 6.00 sq. m w/ min. N/A 18 sq. m for studio N/A N/A N/A
Habitation dimension of 2.00 m unit
Kitchens 3.00 sq. m w/ min N/A N/A N/A N/A N/A
dimension of 1.50 m
Toilet & Bath 1.20 sq. m w/ min. N/A N/A N/A N/A 2.25 sq. m
dimension of 0.90 m
Exits
Occupant Load of At least 1 exit At least 2 exits At least 1 exit At least 1 exit At least 1 exit N/A
less than 10
Occupant Load of At least 2 exits N/A At least 2 exits N/A N/A N/A
10-499
Occupant load of At least 3 exits N/A At least 3 exits N/A N/A N/A
500-999
Occupant Load of At least 4 exits N/A At least 4 exits N/A N/A N/A
1000-above
Distance to exits
without Sprinkle Max. of 45 m Max. of 46 m Max. of 45 m Max. of 45 m Max. of 45 m N/A
System
Distance to exits
with Sprinkle Max. of 60 m Max. of 61 m Max. of 60 m Max. of 60 m Max. of 60 m N/A
System
Min. exit door width 700 mm 710 mm 700 mm 800 mm 800 mm N/A
Min. exit door 2.00 m 2.00 m 2.00 m 2.00 m 2.00 m N/A
height
Min. corridor width 1.10 m 550 mm 1.10 m 1.20 m 1.20 m 1.20 m
Max. slope of 1:8 N/A 1:8 1:8 1:8
passageway
Dead ends Max. of 6.00 m Max. of 6.00 m Max. of 12.00 m Max. of 12.00 m Max. of 12.00 m N/A

P.D 957
Stairways for P.D 1096 P.D 1185 Subdivision & B.P 220 Economic B.P 220 B.P 344
Buildings Building Code Fire Code Condominium Housing Socialized Accessibility
Law Housing Law
Min. stair width: 750 mm N/A N/A N/A N/A N/A
Occupant load of
10-below
Min. stair width: 900 mm N/A 900 mm 900 mm 900 mm N/A
Occupant load of
10-50
Min. stair width: 1.10 m N/A 1.10 m 1.00 m 1.00 m N/A
Occupant load of 50
- above
Riser 200 mm 190 mm class A 200 mm 200 mm 200 mm N/A
200 mm class B
Tread 250 mm 250 mm class A 250 mm 250 mm 250 mm N/A
230 mm class B
Min. width 1.10 m 1.12 m 1.10 m 600 mm 600 mm N/A
Distance bet. 3.60 m 2.75 m class A 3.60 m 3.60 m 3.60 m N/A
Landings 3.70 m class B
Dimension of Equal to the width of 1.12 m Equal to the width Equal to the width of Equal to the width of N/A
Landings in the the stairway of the stairway the stairway the stairway
direction of travel
Height of handrails 800-900 mm from the 760-895 mm from 800-900 mm from 800-1200 mm from 800-1200 mm from 700-800 mm
nosing the nosing the nosing the nosing the nosing from the floor

Sidewalks & P.D 957


Arcades Subdivision &
P.D 1096 P.D 1185 B.P 220 Economic B.P 220 B.P 344
Building Code Fire Code Condominium Housing Socialized Accessibility
Law Housing Law

Min. of width of 1/6 of R.O.W N/A 1.00 m for major 1.00 m for major road 1.00 m for major
sidewalk road & minor roads & 500 mm minor road road & 500 mm N/A
minor road

Plan Strip 800 mm for sidewalks N/A 1.00 m for major 1.00 m for major road 1.00 m for major N/A
exceeding 2.00 m in road & minor roads & 500 mm minor road road & 500 mm
width minor road

Driveways,
Entrance & Exits
Slope of entryway 1:3 or 1:4 N/A 1:3 or 1:4 N/A N/A N/A

Max. slope of ramps 1:10 10% 1:10 15% 15% 1:12 but length
shall not exceed
6.00 m w/o
landing

Open Space
Requirements
Interior Lots 50% Residential N/A 50% Residential 50% Residential 50% Residential N/A
25% others 25% Others 25% Others 25% Others
Inside Lots 20% Residential N/A 20% Residential 20% Residential 20% Residential N/A
15% others 15% Others 15% Others 15% Others

Corner/Through Lot 10% Residential N/A 10% Residential 10% Residential 10% Residential N/A
5% others 5% Others 5% Others 5% Others
Lot bounded by 5% for all occupancies N/A 5% for all 5% for all Occupancies 5% for all N/A
streets on 3 sides Occupancies Occupancies
P.D 957
Setbacks P.D 1096 P.D 1185 Subdivision & B.P 220 Economic B.P 220 B.P 344
Building Code Fire Code Condominium Housing Socialized Accessibility
Law Housing Law
Low Density 5.00 m Front
Residential (R-1) 2.00 m Side N/A N/A N/A N/A N/A
2.00 m Rear
Medium Density 3.00 m Front
Residential (R-2) 2.00 m Side N/A N/A N/A N/A N/A
2.00 m Rear
High Density 2.00 m Front 3.00 m Front 1.5 m Front 1.5 m Front
Residential (R-3) 2.00 m Side N/A 2.00 m Side 2.00 m Side 2.00 m Side N/A
2.00 m Rear 2.00 m Rear 2.00 m Rear 2.00 m Rear

Parking

Size of Parking Slot 2.40 x 5.00 m 2.40 x 5.00 m 2.40 x 5.00 m 2.40 x 5.00 m
(perpendicular & (perpendicular & (perpendicular & (perpendicular &
diagonal) diagonal) diagonal) diagonal)
2.00 x 6.00 m N/A 2.00 x 6.00 m 2.00 x 6.00 m 2.00 x 6.00 m 3.70 x 5.00 m
(parallel) (parallel) (parallel) (parallel)
Low-income single
detached living Pooled Parking 1 slot/ N/A Pooled Parking 1 Pooled Parking 1 slot/ Pooled Parking 1 slot/ N/A
units w/ individual 10 units slot/ 10 units 10 units 10 units
lot size not more
than 100 sq. m
50 sq. m below 1 slot /8 units 1 slot /8 units
50-100 sq. m 1 slot/ 4 units N/A 1 slot/ 4 units 1 slot / 20 units 1 slot / 20 units N/A
100 sq. m above 1 slot/ 1 unit 1 slot/ 1 unit