Air System Sizing Summary for VRV

Project Name: Batiment de congrès CHU Dakhla 07/16/2024


Prepared by: douaa 04:12

Air System Information


Air System Name:................................................VRV Number of zones:......................................................1
Air System Type:.............................Single Zone CAV Floor Area:............................................................45,0 sqm
Location:..........................................Dakhla, Morocco

Sizing Calculation Information


Calculation Months:...................................Jan to Dec Calculation method:.........Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load:.........................................................4,8 kW Load occurs at:..............................................Jul 1700
Total coil load:.........................................................4,8 kW OA DB / WB:.................................................31,4/19,8
Sensible coil load:...................................................4,3 kW Entering DB / WB:.........................................25,0/18,0
Coil airflow:............................................................335 L/s Leaving DB / WB:.........................................14,4/13,7
Sensible heat ratio:.............................................0,894 Coil ADP:..............................................................13,2 C
Area per unit load:...................................................9,3 sqm/kW Bypass Factor:....................................................0,100
Load per unit area:..............................................107,2 W/sqm Resulting RH:..........................................................57 %
Design supply temp:.............................................14,0 C

Central Heating Coil Sizing Data


Max coil load:..........................................................0,0 kW Load occurs at:...............................................Des Htg
Coil airflow:................................................................0 L/s Ent DB / Lvg DB:........................................-17,8/-17,8
Load per unit area:..................................................0,0 W/sqm
Supply Fan Sizing Data
Actual max airflow:.................................................335 L/s Fan motor BHP:....................................................0,00 BHP
Standard airflow:....................................................334 L/s Fan motor kW:......................................................0,00 kW
Actual max airflow per unit area:...........................7,44 L/(s-sqm) Fan static:.............................................................0,00 Pa

Outdoor Ventilation Air Data


Design airflow:.........................................................77 L/s Airflow per person:................................................7,00 L/s/person
Airflow per unit floor area:.....................................1,71 L/(s-sqm)
Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
RC-01-Détente 3,6 335 Jun 1800 0,0 45,0 7,44

Block Load 4.15 Page 1 of 4


System Design Load Summary for VRV
Project Name: Batiment de congrès CHU Dakhla 07/16/2024
Prepared by: douaa 04:12

DESIGN COOLING DESIGN HEATING


Jul 1700 Design Heating Day
OA DB / WB 31,4 C / 19,8 C OA DB / WB 22,4 C / 7,1 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 4 sqm 281 - 4 sqm - -
Wall Transmission 47 sqm 1006 - 47 sqm 0 -
Roof Transmission 0 sqm 0 - 0 sqm 0 -
Window Transmission 4 sqm 141 - 4 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 45 sqm 0 - 45 sqm 0 -
Partitions/Ceilings 45 sqm 25 - 45 sqm 0 -
Overhead Lighting 360 W 360 - 0W 0 -
Electric Equipment 900 W 900 - 0W 0 -
People 11 825 605 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 3539 605 - 0 0
Thermostat and Pulldown Adjustment - 8 0 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 77 L/s 766 -93 77 L/s -409 0
Supply Fan Load 335 L/s 0 - 335 L/s 0 -
>> Total System Loads - 4312 511 - -409 0
Central Cooling Coil - 4312 512 - -409 0
Central Heating Coil - 0 - - 0 -
>> Total Coil Loads - 4312 512 - -409 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 4


Zone Design Load Summary for VRV
Project Name: Batiment de congrès CHU Dakhla 07/16/2024
Prepared by: douaa 04:12

RC-01-Détente DESIGN COOLING DESIGN HEATING


Jun 1800 Design Heating Day
OA DB / WB 30,2 C / 19,6 C OA DB / WB 22,4 C / 7,1 C
Thermostat Setpoint 23,0 C Thermostat Setpoint 18,0 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 4 sqm 335 - 4 sqm - -
Wall Transmission 47 sqm 1085 - 47 sqm 0 -
Roof Transmission 0 sqm 0 - 0 sqm 0 -
Window Transmission 4 sqm 123 - 4 sqm 0 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 0 sqm 0 - 0 sqm 0 -
Floor Transmission 45 sqm 0 - 45 sqm 0 -
Partitions/Ceilings 45 sqm 5 - 45 sqm 0 -
Overhead Lighting 360 W 360 - 0W 0 -
Electric Equipment 900 W 900 - 0W 0 -
People 11 825 605 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3633 605 - 0 0

Block Load 4.15 Page 3 of 4


System PsychrometricsforVRV
Project Name: Batiment de congrès CHU Dakhla 07/16/2024
Prepared by: douaa 04:12

Location: Dakhla, Morocco


Altitude: 11,0 m
Data for: Jul DESIGN COOLING DAY, 1700
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016

0,014

Specific Humidity ( kg/kg )


0,012

5 2 0,010
4
3 1

0,008

0,006

0,004

0,002

0,000
0 10 20 30
Temperature (C)

Block Load 4.15 Page 4 of 4