Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
1.855.206.2490
MENU
+
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 1/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Deluge fire protection systems are a special type of fire sprinkler system, which is connected
directly to the water supply with a deluge valve. In more common types of sprinkler
systems, the sprinkler heads are closed until activated whereas the sprinkler heads or
nozzles in a deluge system remain open at all times. When the deluge valve is activated, it
releases the water into the pipes and through all the sprinkler heads or nozzles all at once,
inundating the protected area.
Foam water deluge systems function in basically the same way but are connected to a
source of concentrated fire suppressant foam in addition to a water supply, which allows
mixing as it is released through the sprinkler heads or nozzles.
A deluge system is an "empty-pipe" system. Unlike a "wet-pipe" system in which the piping
system is filled with water at all times, or a "dry-pipe" system, in which the pipes are filled
with pressurized air or nitrogen, the piping in a deluge system contains only air at the
surrounding atmospheric pressure. The water (and foam, in foam water systems) are held
back by a deluge valve at the water supply connection.
Deluge systems are typically used in high hazard areas such as power plants, chemical
plants, and other industrial or manufacturing facilities where there are large amounts of
combustibles that would allow a fire to become explosive and spread quickly. Because of
their ability to completely flood an area with water within seconds of activation, deluge
systems are very effective in such scenarios.
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 2/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Inspections
Daily Enclosures (during cold weather)
Testing
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 3/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Every ten
Sprinklers tested/replaced
years
While these requirements may seem daunting, they don't have to be. Regardless of the type
of sprinkler system your building has, Koorsen can help you determine what inspections and
tests are required and can help you stay on top of them to keep your system well maintained
and compliant at all times. Contact us today to begin enjoying the peace of mind that if a
fire does break out in your building, your sprinklers will operate as expected to put it out
quickly.
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 4/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
LAST NAME
EMAIL *
PHONE NUMBER
REQUEST TYPE
QUOTE
IMMEDIATE SERVICE
CUSTOMER SERVICE
OTHER
SUBMIT
Disclaimer: The information in this article is for informational purposes only. It is believed to be reliable, but Koorsen Fire & Security
assumes no responsibility or liability for any errors or omissions in the content of this article. It does not constitute professional advice. The
user of this article or the product(s) is responsible for verifying the information's accuracy from all available sources, including the product
manufacturer. The authority having jurisdiction should be contacted for code interpretations.
RELATED POSTS
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 5/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Questions?
Contact Us Now!
NOTIFICATION FREQUENCY *
DAILY
WEEKLY
SUBSCRIBE
RECENT POSTS
The Integration of Access Control Systems with Other Security Systems
Choosing the Right Emergency and Exit Lights for Your Building
The Role of Physical Access Control in Overall Security Strategy
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 6/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
CATEGORIES
Fire Protection (110)
Commercial Security (99)
see all
Julie Mccauley
June 19, 2023
Ron was very professional and was able to help solve our alarm system problems with ease!
Deborah Lloyd
June 19, 2023
Starshine
June 13, 2023
We really appreciate Dave's professionalism and friendliness. He and Jim worked quickly and
efficiently on the camera setup at one of our communities. Also, he explained really well how to use
the monitors and app.
Michael Atwell
June 11, 2023
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 7/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
The fire alarm team from Koorsen, Reid and Nick, show up whenever we have an alarm issue and are
always professional, knowledgeable and prompt. I work in the specialty shop at Ariel Corp in Mt
Vernon and other Koorsen techs have handled our sprinkler system - not sure of their names, but
they also seem to have the same high standards as the alarm guys. Great company to call on for all of
your fire safety needs!
Mark Perri
June 8, 2023
Jason and Noah are doing the annual fire and life safety at my properties and are doing a great job
Patrick Lawler
June 8, 2023
Koorsen has some of the best techs! Jason Blythe took great care of us on the inspections.
Tyler Lawler
June 8, 2023
I had Jason and Noah at all my properties doing inspections! They where great
Omari Hill
June 7, 2023
Dave Green was extremely helpful with setting up the panels and teaching us how to use them! We
highly recommend Koorsen!
Tanya Smith
June 7, 2023
Dave was our technician and he was absolutely wonderful. He was here when he said he was going to
be here. He let me know if there was a day he wouldn't be here and when he would return. He is very
professional and courteous. He reminded me if an Army soldier saying yes ma'am. Dave cleaned up
after himself. I'm so glad the he did our installation.
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 8/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
Truck Driver
June 6, 2023
Thank you so much for helping me out with my fire extinguisher. Really helpful and understandable
people working there. Appreciate your help
FIRE EXTINGUISHERS
EMERGENCY/EXIT LIGHTING
COMMERCIAL SECURITY
EMERGENCY NOTIFICATION
COMMUNICATIONS
HOME SECURITY
OTHER COMPANIES
KOORSEN ENVIRONMENTAL
CONTACT KOORSEN
855-206-2490
FAQS
KOORSEN CAREERS
MEDIA RELATIONS
TRANSPARENCY IN COVERAGE
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 9/10
6/26/23, 9:18 AM Deluge Fire Sprinkler Systems and Their Inspection and Testing Requirements
© 2 0 2 3 K O O R S E N F I R E & S E C U R I T Y | P R I VA C Y P O L I C Y
https://blog.koorsen.com/deluge-fire-sprinkler-systems-and-their-inspection-and-testing-requirements 10/10