Power Calculation

MX960

25 June 2024

Copyright © 2024 , Juniper Networks, Inc.


Power Calculation - MX960

MX960

Power Zone 1

Line Cards

Slot SKU/Value Power Consumed

MPC 0 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 1 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 2 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 3 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 4 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 5 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

Base Chassis

Slot SKU/Value Power Consumed

SCB 0 RE-X6 + SCBE3 495

Copyright © 2024 , Juniper Networks, Inc. 2


Power Calculation - MX960

Slot SKU/Value Power Consumed

MX960 Base System MX960 Base System 25

Power Zone 0 & 1

Base Chassis

Slot SKU/Value Power Consumed

Fan Tray (Upper) High Capacity Fan 320

Fan Tray (Lower) High Capacity Fan 320

Power Zone 0

Line Cards

Slot SKU/Value Power Consumed

SCB 2/MPC 6 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 7 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 8 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 9 MPC10E-15C 720

MIC 0 none selected 0

Copyright © 2024 , Juniper Networks, Inc. 3


Power Calculation - MX960

Slot SKU/Value Power Consumed

MIC 1 none selected 0

MPC 10 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

MPC 11 MPC10E-15C 720

MIC 0 none selected 0

MIC 1 none selected 0

Base Chassis

Slot SKU/Value Power Consumed

SCB 1 RE-X6 + SCBE3 495

MX960 Base System MX960 Base System 25

Power Units

Slot SKU

PEM Type* High Capacity DC

Redundant Yes

Feed Size* Dual-Feed

Copyright © 2024 , Juniper Networks, Inc. 4


Power Calculation - MX960

Results

Name Value

Max Ambient Temperature (° C) 25

MIC Aware Power Management True

Number of PEMs 2

Number of PEMs for Zone 0 2

Number of PEMs for Zone 1 2

Zone 0 FRU Power Required 5160

Zone 1 FRU Power Required 5160

Total FRU Power Required 10320

Thermal Output (BTU/hr) 40946

Maximum Total Power Drawn (Watts) : 12000

CO2 Emissions

Name Value

CO2e/Unit/Hour (kg) 5.724

CO2e/Unit/Hour (Metric Ton) 0.005724

1-year CO2e/Unit (Metric Ton) 50.176584

5-year CO2e/Unit (Metric Ton) 250.88292

Copyright © 2024 , Juniper Networks, Inc. 5


Power Calculation - MX960

Legend

Name Description

Number of PEMs Number of PEMs required to operate the chassis based on your configuration.

Number of PEMs for Zone Number of PEMs required to operate the chassis based on your Zone 0 configuration.
0

Number of PEMs for Zone Number of PEMs required to operate the chassis based on your Zone 1 configuration.
1

Zone 0 FRU Power Sum of output power of all field replaceable units configured in Zone 0.
Required

Zone 1 FRU Power Sum of output power of all field replaceable units configured in Zone 1.
Required

Total FRU Power Required Total FRU power is the sum of output power of all the field replaceable units.

Thermal Output (BTU/hr) After you have calculated the power consumption for your configuration, you can
use that information to determine the system thermal output (BTUs per hour). To
do so, multiply the maximum power consumption in watts by 3.412142.

Maximum Total Power Maximum power consumed or input power required is calculated by dividing the
Drawn (Watts) total output power by the efficiency of the power supply.

CO2e/Unit/Hour (kg) CO2 emissions per unit per hour (kg). Calculated by multiplying Maximum Total
Power Drawn (Watts) with a fixed factor 0.000477

CO2e/Unit/Hour (Metric CO2 emissions per unit per hour (Metric Ton). Calculated by dividing
Ton) CO2e/Unit/Hour (kg) by 1000

1-year CO2e/Unit (Metric 1-year CO2 emissions per unit (Metric Ton). Calculated by multiplying
Ton) CO2e/Unit/Hour (Metric Ton) with (24 * 365.25)

5-year CO2e/Unit (Metric 5-year CO2 emissions per unit (Metric Ton)
Ton)

Copyright © 2024 , Juniper Networks, Inc. All rights reserved.

By accessing information contained in this document, you agree that:


- the information you are accessing is confidential to Juniper Networks
- you will not disclose this information to any party outside Juniper Networks
- you are authorized by Juniper Networks to access the information

The information in this document is provided "AS IS", with no warranties of any kind attached to the information.
Any reliance upon the information shall be at the user's own risk. Juniper assumes no liability for the information
contained in this document.

Copyright © 2024 , Juniper Networks, Inc. 6

You might also like