Motor Energy Efficiency Self-Assessment Tool

Introduction:
The Punjab Energy Efficiency and Conservation Authority (PEECA) of the Governnment of Punjab, Pakistan is working rigurously to improve energy
efficiency and promote a culture of Energy Conservation in the province. To aide the efforts, PEECA has developed excel based self-assessment
tools to calculate energy efficiency and enerrgy saving potentials in different industrial and commercial utilities.

About this tool:


This tool calculates investigates motor performance and gives recommendations for Motor Control, Phase Balance and Motor Temperature.

Version Information:
Version No. V01_170301
Previous Version: N/A

How to Use?
- Enter data in the "Data Input" sheet. Please refer to "Example Data Input" sheet for guidance to fill.
- Please add rows in "Data Input" sheet if required. To do so, please right click inside the table and click "Add Rows Above" or "Add Rows Below"
whichever is applicable.
- Blue tab sheets show results of calculations.
- All Red labelled fields with white colored cells are data entry fields
- All blue labelled fields with Grey colored cells are Calculation and Output Fields.
- Please do not try to temper with any calculation cells as this will alter the results. Please contact PEECA or the developers for any alteration or
change requests.

References:
- Compressed Air Best Practice Tool; Sustainable Energy Authority of Ireland (seai)
- Recuperable heat from compressors, Energy Agency NRW
- Compressed Air Systems in the European Union, EU 2001
- International Energy Agency (IEA)
- Energy Markets International Limited
- ISO 11011 Compressed air – Energy Efficiency – Assessment
- Energy Efficiency Guide for Industry in Asia – www.energyefficiencyasia.org
- US Department of Energy – www.eere.energy.gov/industry
- www.motorsmatters.org
- www.rapidtables.com
- www.easa.com
- www.electromotores.com
- Bureau of Energy Efficiency India

Disclaimer:
The information, calculations and conclusions in this tool are based on the sources as mentioned above. The tool has been field tested, however,
qualified engineers must be consulted before makinng any decision based on these calculations. PEECA, Government of Punjab or the Developers
accept no liability whatsoever to any person, company or entity for any injury, loss or damage that may arise in connection with any misuse or
reliance on the information.

The tool is provided as a freeware. Users may make copies and distribute the tool without making any changes.

Contact:
Users may contact following for any clarification, suggestion and/or improvement in this tool;

Managing Director Developer


Punjab Energy Efficiency and Conservation Agency (PEECA) M. Salman Butt
Energy Department, Government of the Punjab ESPIRE Consult
[email protected] +92 305 555 2343
48-A, Block C-II, Ghalib Road, Gulberg-III, Lahore [email protected]
Pakistan 198 A-1, M. A. Jauhar Town, Lahore, Pakistan
Motor Data Sheet

ELECTRICITY Price PKR/kWh


Motor Parameters Motor Controller Phase Balance Motor Temperature Recommendations
C C C
o o o
l l l
Measured u Motor Load Average Energy Saving Energy Saving u u Recommend
Rated Motor Design Motor Power Annual mVFD Type Load on for Installing for Installing Investment for Payback m Voltage mMotor Motor ed Motor
Motor Code Power Efficiency at Full Load Operation nInstalled or [Variable or motor VFD VFD VFD Period n Imbalance nTemperature Insulation Temperature
# [Identity] [kW] [%] [kW] [hrs/y] 8Not! Constant] [%] [kWh/y] [MPKR/y] [MPKR] [months] 5R Y B [%] 9[⁰C] Class [⁰C] Column6 1 2 3
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
N/A 0.00 N/A 0.0% 0
0 0 0.00 #DIV/0! #DIV/0! 0.00 0.00 0.00 N/A
Motor Efficiency Dashboard

Motor Data Summary VFD Installation


Total No. of Motors 0 Motors Without VFD 0
Total Installed Motor Capacity 0 kW No. of VFDs Recommended 0
Average Running Hours #DIV/0! hrs/y Energy Saving Potential 0 kWh/y
Total Energy Consumption #DIV/0! kWh/y Energy Saving Potential 0.00 MPKR/y
Total Energy Consumption #DIV/0! MPKR/y Total Investment for VFD 0 MPKR
Payback Period #DIV/0! Months

Phase Voltage Balance Motor Temperature

Max. allowable phase imbalance 5.0% No. of Motors with high temperature 0
No. of Motors with high imbalance 0 Max. measured motor temperature 0.00 ⁰C
Max. calculated phase imbalance 0.0%
Example Motor Data Sheet

ELECTRICITY Price 18.00 PKR/kWh


Motor Parameters Motor Controller Phase Balance Motor Temperature Recommendations
C C C
o o o
l l l
Measured u Motor Load Average Energy Saving Energy Saving u u Recommend
Rated Motor Design Motor Power Annual mVFD Type Load on for Installing for Installing Investment for Payback m Voltage mMotor Motor ed Motor
Motor Code Power Efficiency at Full Load Operation nInstalled or [Variable or motor VFD VFD VFD Period n Imbalance nTemperature Insulation Temperature
# [Identity] [kW] [%] [kW] [hrs/y] 8Not! Constant] [%] [kWh/y] [MPKR/y] [MPKR] [months] 5R Y B [%] 9[⁰C] Class [⁰C] Column6 1 2 3
1 M-Knit-0001 15 90.00% 12.5 1728 No Variable 27% 14,128 0.25 0.12 5.66 220 218 201 5.6% 70 A 60 Install VFD Check cable sizes, loose connections or load balance Check Cooling, Monitor Load and Temperature Regularly
1 15 12.50 1728 27% 14128.13 0.25 0.12 5.66