Test Code

Sheet 4 0 0 1 10
Number

WRAS TEST & ACCEPTANCE CRITERIA Issue No: 1


Date of issue: June 2010

Sheet 1 of 1

TEST CODE SHEET

1. TYPE OF TEST

Leak tightness of waste outlet with push down pop-up waste mechanism (non-adjustable click type)

2. WATER REGULATIONS REQUIREMENTS FOR FITTINGS

Schedule 2.28

(1) Subject to paragraph (2), every bath, wash basin, sink or similar appliance shall be provided with a watertight
and readily accessible plug or other device capable of closing the waste outlet.

3. TEST PROCEDURE

Note Unless otherwise stated the temperature of the test water shall be 20 ± 10°C

3.1 Tests applicable to the following:-

Waste outlet with push down pop-up waste mechanism


NOTE: Not applicable to pop up wastes operated via a linkage mechanism

____________________________________________________________________________________________________

Waste outlets with push down pop up waste


(Derived from BS EN 274-2 2002, Clause 6.1)

TEST METHOD

(i) Fit the waste outlet to the bottom of a test tank with pop-up waste in the closed position (size of test tank base -
400mm x 100 mm minimum)
(ii) Fill the test tank with the water to a height of at least 120mm and collect any water, which flows through the waste
outlet during a period of 1 hour.
(iii) Measure the quantity of water collected
(iv) Place the outlet and pop waste on a rig capable of operating the mechanism, actuate the pop-up waste for 50,000
cycles ensuring the mechanism is kept wet for the duration of the test.
CLOSED-OPEN-CLOSED constitutes 1 cycle
(v) Repeat steps (i) to (iii)

4. ACCEPTANCE CRITERIA

The leakage rate shall be less than 1 litre/hour before and after endurance when tested in accordance with items (i)
to (ii) above.