Column Design With Excel
Column Design With Excel
Calculations
Factored Load: P
Calculation for Square Tied Column: (WSD) Calculation for Square Tied Column: (USD)
Dim. of Column: 18 X 18
Rectangular Tied Column (USD)
Area of Column: 324 in 2
Breath: 15.6 in
So, Area of Steel: -1.486474 in 2
So Dim. Of Column: 10
So, ρg -1.487 in 2
We know,
For Spiral Column,
Rectangular Tied Column ( WSD)
Pu= Ø0.85Ag[.85f'c(1-ρg)+fyρg]
Breath: 31.4 in 32 in
Ag 115.45411 in2
Area of the Column: 310 in2
Area of Column = πr2
So, The dimension of the column is:
Radius : r 6.0765007 in
10 X 32 320 in 2
Ag 116.89894 in2
So, ρg -0.919118 0.01
Area of Steel Ast: -23.42345
So, Ast : 3.2 in 2
P= Ag [0.25f'c + fsρg
so, r is 9.218923 in 10 in
ρg -7.19246 0.01
0.01
national University of Business Agriculture and Technology E-mail: [email protected]
Result Last update: 27-08-2013
18 in WSD
10 in WSD 13 in USD
10 in USD
18 in WSD
13 in USD
32 in WSD
16 in USD
2.5 in
Square Column
0.31 2.48 in 2
8 No. of # 5 bar 0.31 2.48
0.11 0 in2 0 No. of # 3 bar 0.11 0
Total Area of Steel : 2.48 in2 Total Area of Steel : 2.48
in2 Required Amount of St. in WSD Method: -481.79 in2 Required
in2 Required USD Method: 18.47 in2 Required
Circular Column
Tie Design
200 Kip
Tied Column: (USD)
Capacity Finder:
Area of Steel: 7.2 in2
Area of the Column: 300 in2 (Rect.)
Load Capacity of the Column is: 388.40256
108.07364
101.25
9.17 circu rat 191347.92
156 in 2
191.34792 kip
13 in 300
7.2
169 in2
0.024 3
18.47 in 2
10 in
18 in 10
10 in
ar Tied Column (USD)
10
16 in 18 10
10
X 16
in2
USD ρg 0.03
160 in 2
9.32 in2
d Column ( USD )
116 in2
6.1 in
117 in2
in2
78.54
-7.19246
58934.76 lb
58.93476 Kip
0.0236822
in2
in2
in2
in2
in2
in2
10 in C/C
10 in C/C
19.635
78.54 in2(Cir.)
Kip (Rec.)
Kip ( Cir.)
10125
Tie Design
3
10 in
18 in 10 in
18 in
10 in
18 in 10 in
13 in
If you put values in the main sheet of "Column Design" same as the given values of the p
Ultimately if it becomes Main sheet, that means " Column Design" = Check (1, 2) Then t
Check
ame as the given values of the pictures bellow then you will find all other content and values same as the main sheet.
mn Design" = Check (1, 2) Then this sheet should work properly.
Check 01
Check 02
Column Design by USD Method
Column: Columns are defined as members that carry loads chiefly in compression. Columns are generally referred
member because compression force or stress dominates their behavior. Compression member includes
· Arch ribs
· Rigid frame member
· Compression member in trusses
· Shells
· Portion that carry axial compression
Fig: Arch
Types of column according to reinforcement used
1. Member reinforced with longitudinal bars and lateral ties.
2. Member reinforced with longitudinal bars and continuous spirals.
3. Composite compression member reinforced with structural steel.
Type-3
· Short column – fail by crushing of concrete, lateral bucking need not to be considered.
· Long / Slender column – fail by lateral bucking
Concrete contribution
Reinforcement ratio is defined by, ρ = As/Ag and the its range is 0.01≤ρ≤0.08
According to this minimum steel ration in column is 1% of gross concrete area of column
To avoid congestion most column are designed with a ratio below 0.04.
· A minimum four longitudinal bar is required when the bar s are enclosed by spaced re
· A minimum six longitudinal bar is required when the bar s are enclosed by a continuou
Clear distance between longitudinal bars shall not be less than 1.5db nor less than 1.5”.
ACI 7.10.4: Spacing may not be less than 1” and may not be larger than 3”
Example 1
Design a square tied column to support an axial dead load of 400 K and a live lode of 210 K using f’c =
Solution:
1.
Column side =
2. Because larger section is adopted, the steel percentage may be reduced by using
11
(2)
(3)
Assignment:
Design a circular spiral column to support an axial dead load of 400 K and a live load of 250 K using f’c =
and a steel ratio of about 2.0%. Also, design the necessary spirals.
Columns loaded with axial load and uniaxial moment is designed based on factored load, which must no
øMn ≥ Mu
øPn ≥ Pu
A column can be designed by solving the above two equations for a specific column section.
A better approach, providing the basis for practical design, is to construct a strength interaction diagram
failure moment for a given column for the full range of eccentricities from zero to infinity.
Pn
Figure:
Interaction
diagram for Compression failure range
nominal column
strength in
combined axial
and bending load. e small
Load path
e=0
for given e
eb
Tension failure range
e large
e=
Design Aid: With a representative column design chart column can be designed easily. And this can de d
1.
a) Select trial cross section dimensions b and h
b) Calculate the ratio γ based on required cover distances to the bar centroid, and select the corresp
d) From the graph, for the values found in (c), read the required reinforcement ratio
2.
a. Select the reinforcement ratio
d. Calculate
Selection of reinforcement for column of given size : In a three-story structure, an exterior column is to
load of 222 kips, maximum live load of 297 kips, dead load moment of 136 ft-kips, and live load momen
load compatible with the full live load moment is 166 kips, obtained when no live load is placed on the
the second floor. Architectural considerations require that a rectangular column be used, with dimensi
(a) Find the required column reinforcement for the condition that full live load acts.
(b) Check to ensure that the column is adequate for the condition of no live load on the roof.
(a) The column will be designed initially for full load, then checked for adequacy when live load is parti
According to the ACI safety provisions, the column must be designed for a factored load
a factored moment A column
the column perimeter will be used. Bar cover is estimated to be 2.5 in. from the column face to the stee
(assuming bending about the strong axis) are
Selecting No. 3 (No. 10) ties for trial, the maximum tie spacing must not exceed,
20 in. Spacing is controlled by the diameter of the ties, and No. 3 (No. 10) ties will be used at 18 in. spac
20”
22.5”
12 no # 9
Selection of column size for a given reinforcement ratio: A column is to be designed to carry a factored
and factored moment ft-kips. Material strengths
Cost studies for the particular location indicate that a reinforcement ratio
required dimensions b and h of the column. Bending will be about the strong axis, and an arrangement
concentrated in two layers, adjacent to the outer faces of the column and parallel to the axis of bendin
Solution:
It is convenient to select a trial column dimension h, perpendicular to the axis of bending; a value of h =
and assuming a concrete cover of 2.5 in. to the bar centers, the parameter
the stated loads the eccentricity is and
and from the trial dimension
15”
22.5”
8 no # 11
Fig: Design Column Section 2.5”
Approximate method:
Design of column for biaxial bending: The column shown below is reinforced
with eight No. 9 (No. 29) bars arranged around the column perimeter, providing an area
A factored load of 255 kips is to be applied with eccentricities in. and ,
as shown. Material strengths are and . Check Ihe adequa
the trial design using the reciprocal load method.
Solution:
By the reciprocal load method, first considering bending about the Y axis,
With the reinforcement ratio , using the average of Graphs A.
Then the bending about the X axis, , and
From which Thus, according to the Bresler method, the design load of
can be applied safely.
[In general biaxial bending should be taken into account when the estimated eccentricity ratio
y USD Method
Fig: Column
e considered.
crete area of column
and at least #4 (12 mm) tie for #11,14, and 18(36,43,57 mm) and bundled longitudinal bars must be used.
48 diameters of tie bars, nor the least dimension of column.
support by ties having a included angle not more than 135⁰.
e from laterally supported bar.
# 3 Tie @ 15 in c/c
12.5”
14 no # 8
ored load, which must not exceed the design strength, i.e.
umn section.
ngth interaction diagram defining failure load and
Mn
easily. And this can de done by two methods
ortioned section
d on the roof.
cy when live load is partially removed.
kips and
A column is specified, and reinforcement distributed around
e column face to the steel centerline for each bar. The column parameters
exceed, or
will be used at 18 in. spacing.
# 3 Tie @ 18 in c/c
22.5”
2.5”
igned to carry a factored load
and are specified.
of about 0.03 is optimum. Find the
xis, and an arrangement of steel with bars
llel to the axis of bending, will be used.
ranged in two layers of four bars each, similar to the sketch shown in Graph A.11
# 4 Tie @ 15 in c/c
22.5”
2.5”
and
ow is reinforced
g an area .
, and
average of Graphs A.6 ( ) and A.7 ( ),
Graph A.5 of the Appendix A gives
he design load of
E-mail: [email protected]
Cell: +88 01771123050
Watch the Tutorial of "Column Design with Excel" at: http://youtu.be/Jh9uz1F-u3Q
e/Jh9uz1F-u3Q
nd Technology.
he author.