0% found this document useful (0 votes)
22 views11 pages

Report

Uploaded by

abdelrahman emad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views11 pages

Report

Uploaded by

abdelrahman emad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Fire Sprinkler Reports

for

Prepared By:

September 25, 2021


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 2

General Project Data Report

General Data
Project Title: Project File Name: truss 3.fiw
Designed By: Date: September 25, 2021
Code Reference: Approving Agency:
Client Name: Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Ordinary 2 Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 155 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 344.21 gpm Calculated Inflow Residual Pressure: 54.50 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.50 psi Minimum Desired Flow Density: 0.20 gpm/ft²
Maximum Water Velocity: 23.00 ft/s Maximum Frictional Loss / 100 feet: 240.00 psi
Number Of Active Nodes: 18
Number Of Active Pipes: 17 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 12 Number Of Inactive Sprinklers: 0

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Sprinkler ---- 5.65 21.18 0.00 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 23.25 0.00 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 31.08 0.00 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 32.54 0.00 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 21.34 0.00 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 23.44 0.00 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 31.32 0.00 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 32.79 0.00 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 21.95 0.00 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 24.10 0.00 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 32.19 0.00 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 33.70 0.00 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 23.25 0.00 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 25.52 0.00 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 34.05 0.00 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 35.63 0.00 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 48.62 0.00 0.00


17
---- 0.000 0.0 ---- 0.0 0.00

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 54.50 0.00 0.00


18
---- 0.000 0.0 ---- 0.0 0.00

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 5

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

2 3 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

3 4 SCHED 40 WET STEEL 1.250 0 2.95 0.00 2.95 120

5 6 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

6 7 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

7 8 SCHED 40 WET STEEL 1.250 0 2.95 0.00 2.95 120

4 8 SCHED 40 WET STEEL 3.000 0 T 9.84 15.00 24.84 120

9 10 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

10 11 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

11 12 SCHED 40 WET STEEL 1.250 0 2.95 0.00 2.95 120

8 12 SCHED 40 WET STEEL 3.000 0 T 9.84 15.00 24.84 120

13 14 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

14 15 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

15 16 SCHED 40 WET STEEL 1.250 0 2.95 0.00 2.95 120

12 16 SCHED 40 WET STEEL 3.000 0 T 9.84 15.00 24.84 120

16 17 SCHED 40 WET STEEL 3.000 0 T 81.04 15.00 96.04 120

17 18 SCHED 40 WET STEEL 3.000 0 E 36.48 7.00 43.48 120

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 6

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -25.97 26.00 0.00 0.00 21.18

2 1 0 25.97 27.25 0.00 0.00 23.25 0.02763


2 3 0 -53.19

3 2 0 53.19 31.50 0.00 0.00 31.08 0.08243


3 4 0 -84.60

4 3 0 84.60 0.00 0.00 0.00 32.54 -0.00238


4 8 0 -84.61

5 6 0 -26.08 26.10 0.00 0.00 21.34 0.02366

6 5 0 26.08 27.35 0.00 0.00 23.44 0.03799


6 7 0 -53.39

7 6 0 53.39 31.62 0.00 0.00 31.32 0.08384


7 8 0 -84.93

8 4 0 84.61 0.00 0.00 0.00 32.79 0.00112


8 7 0 84.93
8 12 0 -169.54

9 10 0 -26.45 26.47 0.00 0.00 21.95 0.02597

10 9 0 26.45 27.74 0.00 0.00 24.10 0.04099


10 11 0 -54.14

11 10 0 54.14 32.06 0.00 0.00 32.19 0.08922


11 12 0 -86.11

12 8 0 169.54 0.00 0.00 0.00 33.70 0.00221


12 11 0 86.11
12 16 0 -255.64

13 14 0 -27.21 27.25 0.00 0.00 23.25 0.03089

14 13 0 27.21 28.54 0.00 0.00 25.52 0.04740


14 15 0 -55.71

15 14 0 55.71 32.97 0.00 0.00 34.05 0.10066


15 16 0 -88.58

16 12 0 255.64 0.00 0.00 0.00 35.63 0.00919


16 15 0 88.58
16 17 0 -344.21

17 16 0 344.21 0.00 0.00 0.00 48.62 -0.00364


17 18 0 -344.21

18 17 0 344.21 0.00 0.00 -344.21 54.50

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 7

Fire Sprinkler Output Data

Overall Pipe Output Data


Nom. Dia. q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual PF-(psi)
Elevation Inside Dia. Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure PE-(psi)
(feet) C-Value Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) PT-(psi)
(fps) Type-Grp (ft)

1 5.65 0.00 26.00 21.18 1.00 26.00 0.21107 9.84 2.078


2 5.65 0.00 27.25 23.25 1.049 25.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 9.64 0 9.84 2.078

2 5.65 0.00 27.25 23.25 1.00 27.25 0.79517 9.84 7.827


3 5.65 0.00 31.50 31.08 1.049 53.19 ----- 0.00 0.000
SCHED 40 WET STEEL 120 19.74 0 9.84 7.827

3 5.65 0.00 31.50 31.08 1.25 31.50 0.49360 2.95 1.458


4 0.00 0.00 0.00 32.54 1.380 84.60 ----- 0.00 0.000
SCHED 40 WET STEEL 120 18.15 0 2.95 1.458

5 5.65 0.00 26.10 21.34 1.00 26.10 0.21272 9.84 2.094


6 5.65 0.00 27.35 23.44 1.049 26.08 ----- 0.00 0.000
SCHED 40 WET STEEL 120 9.68 0 9.84 2.094

6 5.65 0.00 27.35 23.44 1.00 27.35 0.80090 9.84 7.883


7 5.65 0.00 31.62 31.32 1.049 53.39 ----- 0.00 0.000
SCHED 40 WET STEEL 120 19.82 0 9.84 7.883

4 0.00 0.00 0.00 32.54 3.00 0.00 0.01008 9.84 0.251


8 0.00 0.00 0.00 32.79 3.068 84.61 T 15.00 0.000
SCHED 40 WET STEEL 120 3.67 0 24.84 0.251

7 5.65 0.00 31.62 31.32 1.25 31.62 0.49714 2.95 1.468


8 0.00 0.00 0.00 32.79 1.380 84.93 ----- 0.00 0.000
SCHED 40 WET STEEL 120 18.22 0 2.95 1.468

9 5.65 0.00 26.47 21.95 1.00 26.47 0.21829 9.84 2.149


10 5.65 0.00 27.74 24.10 1.049 26.45 ----- 0.00 0.000
SCHED 40 WET STEEL 120 9.82 0 9.84 2.149

10 5.65 0.00 27.74 24.10 1.00 27.74 0.82178 9.84 8.089


11 5.65 0.00 32.06 32.19 1.049 54.14 ----- 0.00 0.000
SCHED 40 WET STEEL 120 20.10 0 9.84 8.089

8 0.00 0.00 0.00 32.79 3.00 0.00 0.03648 9.84 0.906


12 0.00 0.00 0.00 33.70 3.068 169.54 T 15.00 0.000
SCHED 40 WET STEEL 120 7.36 0 24.84 0.906

11 5.65 0.00 32.06 32.19 1.25 32.06 0.50997 2.95 1.506


12 0.00 0.00 0.00 33.70 1.380 86.11 ----- 0.00 0.000
SCHED 40 WET STEEL 120 18.47 0 2.95 1.506

13 5.65 0.00 27.25 23.25 1.00 27.25 0.23017 9.84 2.266


14 5.65 0.00 28.54 25.52 1.049 27.21 ----- 0.00 0.000
SCHED 40 WET STEEL 120 10.10 0 9.84 2.266

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 8

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


Nom. Dia. q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual PF-(psi)
Elevation Inside Dia. Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure PE-(psi)
(feet) C-Value Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) PT-(psi)
(fps) Type-Grp (ft)

14 5.65 0.00 28.54 25.52 1.00 28.54 0.86632 9.84 8.527


15 5.65 0.00 32.97 34.05 1.049 55.71 ----- 0.00 0.000
SCHED 40 WET STEEL 120 20.68 0 9.84 8.527

12 0.00 0.00 0.00 33.70 3.00 0.00 0.07800 9.84 1.938


16 0.00 0.00 0.00 35.63 3.068 255.64 T 15.00 0.000
SCHED 40 WET STEEL 120 11.09 0 24.84 1.938

15 5.65 0.00 32.97 34.05 1.25 32.97 0.53733 2.95 1.587


16 0.00 0.00 0.00 35.63 1.380 88.58 ----- 0.00 0.000
SCHED 40 WET STEEL 120 19.00 0 2.95 1.587

16 0.00 0.00 0.00 35.63 3.00 0.00 0.13525 81.04 12.989


17 0.00 0.00 0.00 48.62 3.068 344.21 T 15.00 0.000
SCHED 40 WET STEEL 120 14.94 0 96.04 12.989

17 0.00 0.00 0.00 48.62 3.00 0.00 0.13525 36.48 5.881


18 0.00 0.00 0.00 54.50 3.068 344.21 E 7.00 0.000
SCHED 40 WET STEEL 120 14.94 0 43.48 5.881

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 9

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

1 5.65 0.00 21.18 130.00 0.200 26.00


Sub Totals For Non-Group 130.00 0.200 26.00

2 5.65 0.00 23.25 130.00 0.210 27.25


Sub Totals For Non-Group 130.00 0.210 27.25

3 5.65 0.00 31.08 130.00 0.242 31.50


Sub Totals For Non-Group 130.00 0.242 31.50

5 5.65 0.00 21.34 130.00 0.201 26.10


Sub Totals For Non-Group 130.00 0.201 26.10

6 5.65 0.00 23.44 130.00 0.210 27.35


Sub Totals For Non-Group 130.00 0.210 27.35

7 5.65 0.00 31.32 130.00 0.243 31.62


Sub Totals For Non-Group 130.00 0.243 31.62

9 5.65 0.00 21.95 130.00 0.204 26.47


Sub Totals For Non-Group 130.00 0.204 26.47

10 5.65 0.00 24.10 130.00 0.213 27.74


Sub Totals For Non-Group 130.00 0.213 27.74

11 5.65 0.00 32.19 130.00 0.247 32.06


Sub Totals For Non-Group 130.00 0.247 32.06

13 5.65 0.00 23.25 130.00 0.210 27.25


Sub Totals For Non-Group 130.00 0.210 27.25

14 5.65 0.00 25.52 130.00 0.220 28.54


Sub Totals For Non-Group 130.00 0.220 28.54

15 5.65 0.00 34.05 130.00 0.254 32.97


Sub Totals For Non-Group 130.00 0.254 32.97

Totals For All Groups 1560.00 0.221 344.84

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 10

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 1
HMD Actual Residual Pressure: 21.18 psi
HMD Actual GPM: 26.00 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.200 gpm/ft²
Application Average Density: 0.230 gpm/ft²
Application Average Area Per Sprinkler: 125.00 ft²
Sprinkler Flow: 344.84 gpm
Average Sprinkler Flow: 28.74 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 14 - 15 ) 20.68 ft/sec
Maximum Velocity Pressure ( In Pipe 14 - 15 ) 2.88 psi

Allowable Maximum Nodal Pressure Imbalance: 0.1000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0986 psi
Actual Average Nodal Pressure Imbalance: 0.0227 psi
Actual Maximum Nodal Flow Imbalance: 0.1007 gpm
Actual Average Nodal Flow Imbalance: 0.0338 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 17
Number Of Flowing Sprinklers: 12

Pipe System Water Volume: 60.92 gal

Sprinkler Flow: 344.84 gpm


Non-Sprinkler Flow: 0.00 gpm

Minimum Required Residual Pressure At System Inflow


54.50 psi
Node:
Demand Flow At System Inflow Node: 344.21 gpm

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem
heaven Page 11

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100

90

80

70
Pressure psi

60
55

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 54.50 psi
Calculated Flow Rate: 344.21 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

C:\Program Files (x86)\Elite\Firew\PROJECTS\truss 3.fiw Saturday, September 25, 2021, 3:12 PM

You might also like