User Manual

ZQ280(A)
Vector Variable Frequency Drive
Solar Inverter
Safety Information and Precautions
This guide is packaged together with the product for ZQ280(A) Variable Frequency Drive. It
contains basic information for quick start of the drive. For safety and more information, please refer to
the ZQ280(A) VFD User's Manual, which can be downloaded on website: http://www.zest-electric.com
■ Electrical Safety

Extreme care must be taken at all times when working with the VFD or within the area of the VFD. The
voltages used in the VFD can cause severe electrical shock or burns and is potentially lethal. Only
authorized and qualified personnel should be allowed to work on VFD.
■ Machine/System Design and Safety of Personnel

Machine/system design, installation, commissioning startups and maintenance must be carried out by
personnel who have the necessary training and experience. They must read this safety information and
the contents of this manual. If incorrectly installed, the VFD may present a safety hazard.
The VFD uses high voltages and currents (including DC), carries a high level of stored electrical energy in
the DC bus capacitors even after power OFF. These high voltages are potentially lethal.
The VFD is NOT intended to be used for safety related applications/functions. The electronic “STOP
&START” control circuits within the VFD must not be relied upon for the safety of personnel. Such
control circuits do not isolate mains power voltages from the output of the VFD. The mains power
supply must be disconnected by an electrical safety isolation device before accessing the internal parts
of the VFD.
Safety risk assessments of the machine or process system which uses an VFD must be undertaken by the
user and or by their systems integrator/designer. In particular the safety assessment/design must take
into consideration the consequences of the VFD failing or tripping out during normal operation and
whether this leads to a safe stop position without damaging machine, adjacent equipment and machine
operators/users. This responsibility lies with the user or their machine/process system integrator.
The system integrator/designer must ensure the complete system is safe and designed according to
the relevant safety standards. ZEST Technology and Authorized Distributors can provide
recommendations related to the VFD to ensure long term safe operation.
■ Electrical Installation - Safety
Electrical shock risk is always present within an VFD including the output cable leading to the motor
terminals. Where dynamic brake resistors are fitted external to the VFD, care must be taken with regards
to live contact with the brake resistors, terminals which are at high DC voltage and potentially lethal.
Cables from the VFD to the dynamic brake resistors should be double insulated as DC voltages are
typically 300 VDC to 800 VDC.
Mains power supply isolation switch should be fitted to the VFD. The mains power supply must be
disconnected via the isolation switch before any cover of the VFD can be removed or before any
servicing work is undertaken stored charge in the DC bus capacitors of the PWM VFD is potentially lethal
after the AC supply has been disconnected. The AC supply must be isolated at least 10 minutes before any
work can be undertaken as the stored charge will have been discharged through the internal bleed resistor
fitted across the DC bus capacitors.
Whenever possible, it is good practice to check the DC bus voltage with a VDC meter before accessing
the VFD bridge. Where the VFD input is connected to the mains supply with a plug and socket, then
upon disconnecting the plug and socket, be aware that the plug pins may be exposed and internally
connected to the DC bus capacitors (via the internal bridge rectifier in reversed bias). Wait 10 minutes to
allow stored charge in the DC bus capacitors to be dissipated by the bleed resistors before commencing
work on the VFD.
1
Nameplate
ZEST Electric
Product Name Product:Variable Frequency Drive
VFD Model Model:ZQ280(A)T1D5
Application Motor Appli Motor: 1.5KW
Rated Input Rate Input:3PH AC 380-440V 50/60Hz
Rated Output Rate Output:3PH AC 380-440V 0-400Hz 4.1A

Anhui Zest Electric Co.,Ltd


Manufacturer Web: www.zest-electric.com
E-mail: [email protected]

ZQ280(A) - T - 1D5

ZQ280(A) Series Mark Input voltage Application


T Mark
3PH 380V to 440V Motor(KW)
S 1PH 220V to 240V 0D4 0.4
1D5 1.5

......

......
5D5 5.5
7D5 7.5

Type of Variable Frequency Drive


Installation
External
Output dimension L*W-
Type Power Power Supply Dimensions
Current(A) installation screw
L*W*H(mm)
(mm)
ZQ280(A)S0D4 0.4KW 2.1
ZQ280(A)S0D7 0.75KW 3.8
184*86*143.5 173*68-M4
ZQ280(A)S1D5 1.5KW Single phase 7.0
AC
ZQ280(A)S2D2 2.2KW 9.0
200V-240V
ZQ280(A)S3D 3KW 50Hz/60Hz 13.0 216*101*151 204*83.5-M4
ZQ280(A)S4D 4KW 15.0
ZQ280(A)S5D5 5.5KW 20.0
ZQ280(A)T0D4 0.4KW 1.5
ZQ280(A)T0D7 0.75KW 2.1
ZQ280(A)T1D5 1.5KW 3.8 184*86*143.5 173*68-M4
Three phase
ZQ280(A)T2D2 2.2KW AC 5.1
ZQ280(A)T3D 3KW 340V-440V 7.1
50Hz/60Hz
ZQ280(A)T4D 4KW 9.0
216*101*151 204*83.5-M4
ZQ280(A)5D5 5.5KW 12.6
ZQ280(A)T7D5 7.5KW 16.1 237*111*168 216*88-M4

2
Operating Panel
1. Appearance of Keyboard panel

Item Symbol Function

Digital tube display To display frequency or parameter etc using LED.

Used to read and modify each group of parameters,


Parameter setting
press to enter the parameter group or display the
key
parameter value.
Jog and return keys Used for VFD jog operation or parameter setting return

Increment To increase parameter number or parameter set value

Decrement To reduce parameter number or parameter set value


Start the VFD when using the operating panel control
RUN mode. It is inactive when using the terminal or
communication control mode.
Stop the VFD when the drive is in the RUNNING
STOP status. Perform a reset operation when the drive is in
the FAULT status.

Speed control knob To adjust frequency

After setting the parameters, return to the original interface method:


1. After power off, power on again.
2. Press the ESC button twice or three times.

3
2. Basic operation of panel
Display out frequency
after power on ESC SET SET

50.00 PRG
-d0- d-04 5.3
ESC ESC
Out Current

SET
-F0- F0.00
ESC
Automatic
return after SET
10.0
30 seconds -F6- F0.12
ESC/SET

20.2
ESC
-FB-
Use the RUN button to switch to display the units, tens, hundreds,
and thousands of the digital tube.

3. VFD running command mode setting

The operation command mode of the VFD is set by parameter


F0.02: there are three types of panel control start/stop, terminal control
start/stop and communication control start/stop:
(1) Panel control start and stop: (set to panel start and stop F0.02=0)
To use the panel control to start and stop the VFD, press the green
button on the panel to start, the red button to stop, the VFD starts by
default forward rotation, and the forward and reverse rotation needs to be
Set through input terminals X1-X5, (reverse setting is 2).

4
(2) Terminal start/stop: (set to terminal start/stop F0.02=1)

VFD frequency setting method selection

The VFD frequency setting mode of the VFD is set by parameter


F0.03. When F0.03=4, the running frequency is set by the
potentiometer; when F0.03=2, the running frequency is input by AVI
(0-10V can be connected to a potentiometer); when F0.03=3, the running
frequency is input by ACI (0-20mA); when F0.03=1, it is controlled by
the external terminal (the digital value is set to increase/decrease the
frequency). 5

5
Installment and Wiring
Optional

Breaker Contactor Fuse


P+ PB
R L U

S V M

T N W 220-240V AC
Single phase 220-240V AC (L N/R T) 380-440V AC
PE
Three phase 380-440 AC (R S T)

X1

X2

X3

X4(485+)

X5(485-)

GND
AO
Analog output
GND 0 to 10VDC

0V
+10V
0 to 10 V
1 to 5 kΩ AVI TC
0 to 20 mA Relay output:
ACI TB 250VAC, between 10mA and 3A
TA 24VDC, between 10mA and 2A
GND

Terminal Function Instruction

Terminal Function Setting and Instruction

VFD: Air switch should be used as the


Three phase 220V/380V over-current protection device in front of the
R、S、T Model connect with R、S、T VFD power. If there is LCDI, and it is afraid
terminals of breakdown, please choose the LCDI
Single phase 220V Model whose sensitivity level is above 200mA and
connect with R、T terminals reaction period last more than 100ms.

VFD output, connected In order to reduce the leakage of current, the


U、V、W connection wire should not be over 50
with electrical machine
meters.

P+、PB Connected with braking resistor According to the list of braking resistors,
choose an appropriate one.

PE The VFD should be connected with the


Connected with the ground ground well.

6
Terminal Function Setting and Instruction

X1 Digital input X1 Set according to parameter F5.02,


and factory set defaults to be FWD.

X2 Digital input X2 Set according to parameter F5.03,


and factory set defaults to be REV

Set according to parameter F5.04,


X3 Digital input X3 and factory set defaults to be the
first one of multistage speed.

If it is not the RS485-, it set


X4/485+ Digital input X4 according to parameter F5.05, and
RS485+ factory set defaults to be the
second one of multistage speed

Digital input X5 If it is not the RS485+, it set


X5/485- according to parameter F5.06, and
RS485- factory set defaults to be
external RST.

GND Signal public terminal Zero potential of analog input signal

AVI 0-10V signal input 0-10V, input resistance:>50KΩ

Frequency Setting
10V potentiometer power +10V, the maximum is 10mA
source
ACI 0-20mA analog input 0-20mA, input resistance: 100Ω

AO Analog output Set according to parameter F6.10

Set according to parameter F5.07


Contact rating:
TA、TB、TC Relay output AC 250V/3A
DC 24V/2A

7
Function Parameter Specifications
Function Factory
Name Description Setting range
code default
F0 group-Basic running Parameters
0.00-
F0.00 VF Power The current power of the VFD. Model setting
99.99KW
0:V/F Control
F0.01 Control Mode 0-1 0
1:SVC mode
0:Keyboard command channel
F0.02 Running order channel selection 1:Terminal command channel 0-1/0-2 0
2:Communication command channel(Need RS48)
0:Digita setting (UP/DOWN terminals
requlate,Off electricity does not storage)
1:Digita setting 2(UP/DOWN terminals
requlate,Off electricity storage)
2:AVI analog setting(0~10V)
Frequency given source channel
F0.03 3:ACI analog setting(0~20mA) 0-7/0-8 4
A
4:Keybord potentiometer setting
5:Multi-speed setting
6:Simple PLC
7:PID control
8:Communication(Need RS48)

0:Digita setting (UP/DOWN terminals


requlate,Off electricity does not storage)
1:Digita setting 2(UP/DOWN terminals
requlate,Off electricity storage)
2:AVI analog setting(0~10V)
Frequency given source channel
F0.04 3:ACI analog setting(0~20mA) 0-7/0-8 0
B
4:Keybord potentiometer setting
5:Multi-speed setting
6:Simple PLC
7:PID control
8:Communication(Need RS48)
0:A+B
Channel A and Channel B 1:A-B
F0.05 0-3 0
calculate result selection 2:MAX(A,B)
3:MIN(A,B)
0:Main frequency A
1:Channel A and Channel B calculate result(Refer
to F0.05)
2:Switch Channel A to Channel B
F0.06 Frequency given source selection 0-4 0
3:Switch Channel A to Channel A and Channel B
calculate result
4:Switch Channel B to Channel A and Channel B
calculate result
The set value is the initial value of frequency 0-MAX
F0.07 Digital frequency setting 50.00Hz
digital given Frequency
The maximum output frequency is the highest
Upper limit
frequency that the inverter allows to output, and it
F0.08 Max frequency output frequency - 50.00Hz
is the benchmark for acceleration and
400.00Hz
deceleration settings.
Lower limit
The operating frequency cannot exceed the frequency -
F0.09 Upper limit frequency 50.00Hz
maximum output frequency of this frequency Max
frequency
Function Factory
Name Description Setting range
code default
The operating frequency cannot be lower than 0-Upper limit
F0.10 Lower limit frequency 0.00Hz
this frequency frequency
0:Zero speed running
Lower limit frequency running 1:Run at lower limit frequency
F0.11 0-2 0
mode 2:Stop output, enter into pause running
state

F00.12 Acceleration Time 1 Time for the inverter to accelerate to the 10.0s
maximum output frequency or decelerate to zero 0-999.9S
F00.13 Deceleration Time 1 frequency 10.0s

0:Foward direction
1:Reverse direction
2:Forbidden reverse operation
The forward and reverse selections are valid
F00.14 Running direction selection 0-2 0
when the run command comes from the panel.
No reverse rotation is prohibited No matter what
the source of the running command is, the
inverter will not reverse rotation
When a non-zero number is set, the password
F0.15 User password takes effect; after decryption, if 0000 is set, the 0000-9999 0
password function is canceled.
F0.16 Software version Current software version. 01.00-99.99 Model setting
0: No action
1: Restore factory default (not restoring motor
parameters)
F0.17 Parameter initialization 0-3 0
2: Clear malfunction records
3: Restore factory default (restoring motor
parameters)
F0.18-
Reserved
F0.19
0:Not Storage
F0.20 Digital setting stop hold 0-1 1
1:Storage

F1 group:V/F Control Parameters


0:Beeline
1:VF square curve
F1.00 V/F curve set 2:1.5 respectively VF power curve 0-4 0
3:1.2 respectively VF power curve
4:Custom VF curve; see [F1.04.01-F1.09];
Fixed torque boost while it is set other values.
Improve low frequency torque trait by voltage
F1.01 Torque boost 0.0-30.0% 3.0%
compensation.
Automatically torque boost while it is set 0.
Set torque improves valid range. While output
F1.02 Torque boost cut-off frequency frequency is over this value, torque improving 0.0-50.00Hz 15.00Hz
function stops.
This feature is mainly used to improve noise and
vibration during operation of the inverter, but at
F1.03 PWM Carrier frequency the same time the main parts switch loss and the 2.0-16.0KHz Model setting
heat are heavy while the efficiency would be
reduced.
Function Factory
Name Description Setting range
code default
0.01-
F1.04 Self-setting frequency F1 12.50Hz
frequency F2

0.0-
F1.05 Self-setting voltage V1 25.0%
voltage V2

F1.06 Self-setting frequency F2 F1-F3 25.00Hz

F1.07 Self-setting voltage V2 V1-V3 50.0%

F2-Motor
F1.08 Self-setting frequency F3 rated 37.50Hz
frequency

F1.09 Self-setting voltage V3 Voltage is a percentage of the rated voltage of the V2-100% 75.0%
motor
0:Forbid
F1.10 AVR function 1:All Effective 0-2 0
2:Forbid only deceleration
F1.11 Brake ratio Braking resistor braking ratio 0-100% 90%
F1.12 Torque compensation gain · 0-150% 0%
F1.13 VF overexcitation gain 0-200% 84%
F1.14 Oscillation suppression ffunction 0-6 5
F2 group:Vector Control Parameters
F2.00 ASR Low speed Kp 1-100 20
F2.01 ASR Low speed Ki 1-10.00 0.50
F2.02 ASR High speed Kp 1-100 10
F2.03 ASR High speed Ki 1-10.00 1.0
Lower limit
ASR Low speed switch frequency -
F2.04 10.00Hz
frequency Max
frequency
Lower limit
ASR High speed switch frequency -
F2.05 30.00Hz
frequency Max
frequency
F2.06 Electric slip compensation gain 0.0-100.0% 0
F2.07 Reserved
F2.08 Reserved
F2.09 Reserved
F2.10 Current loop Kp 0-60000 2000
F2.11 Current loop Ki 0-60000 1300
F2.12 Reserved
F2.13 Reserved
F2.14 SVC motor slip compensation 0-200% 100%
F2.15 Reserved
F2.16 Reserved
F2.17 Reserved
F2.18 Reserved
Speed control (drive) torque
F2.19 0.0-200.0% 150.0%
upper limit digital setting
Function Factory
Name Description Setting range
code default
Maximum torque coefficient in
F2.20 50-200% 100%
field weakening region
Current loop M-axis proportional
F2.21 5-300 5
coefficient
Current loop M-axis integral
F2.22 0-65535 0
coefficient
Open loop vector velocity loop
F2.23 0-100 25
filter time constant
F2.24 Open loop vector torque boost 0-500 100
Lower limit
Open loop vector torque boost frequency -
F2.25 20.00Hz
cut-off frequency Max
frequency
F2.26 Torque given filter 0-31 28
Maximum field weakening
F2.27 0-110% 105%
voltage overmodulation factor
Magnetic flux observation
F2.28 0-100% 100%
compensation factor
F2.29 Flux observation filter coefficient 0-2000 300
T-axis current closed-loop
F2.30 0-500 0
coefficient
F2.31 Torque limit method 0-1 0
F2.32 Reserved
F2.33 Reserved
F3 group: Auxiliary Operation Parameters
0:Start frequency
F3.00 Start-up mode 0-1 0
1:DC breake+start frequency
F3.01 Start frequency Initial frequency of inverter start 0.50-20.00Hz 0.50hz
F3.02 Holding time of start frequency Start frequency run time 0.0-60.0s 0
Current value for applying DC braking:
When the rated current of the motor is less than
or equal to 80% of the rated current of the
inverter, it is a percentage base value relative to
F3.03 Start DC brking current the rated current of the motor: 0.0-100% 0.00%
When the rated current of the motor is greater
than 80% of the rated current of the inverter, it is
relative to 80% of the rated current of the inverter
as the percentage base value.
F3.04 Start DC brking time Duration of applying DC braking 0.0~100.0s 0.1s
0:Decelerate stop
F3.05 Stop mode 1:Decelerate stop + DC brking 0-2 0
2:Free stop
0.0-upper
Initial frequency for Stop DC When the frequency reaches the preset
F3.06 limited 0.00Hz
braking frequency, DC braking starts
frequency
Applying the same braking current value as DC
F3.07 Stop DC brking current 0.0-100% 0.00%
braking current
F3.08 Stop DC braking time Duration of applying DC braking 0.0-30.0% 0.0s
F3.09-
Reserved
F3.15
0:No status
F3.16 STOP/RESET key function 0-1 1
1:Enabled in any case
Function Factory
Name Description Setting range
code default
F4 group: Auxiliary Operation 2 Parameters
Jog forward running frequency
F4.00
setting
Set jog forward and reverse frequency 0.00-50.00Hz 10.00Hz
Jog reverse running frequency
F4.01
setting
F4.02 Jog Accel time
Set the jog acceleration and deceleration time 0.1-999.9s Model setting
F4.03 Jog Decel time
F4.04 Accel Time 2 10.0s
0.1-999.9s
F4.05 Deccel Time 2 10.0s
0: invalid
1: When the inverter is running, the jog priority is
F4.06 Multi-function key (JOG KEY) the highest 0-3 1
2: Reverse rotation contrl
3: Forward and Reverse Switching

0.0-upper
F4.07 Jump frequency1 limited 0.00Hz
frequency
F4.08 Jump frequency range1 0.0-10.0Hz 0.00Hz
F4.09 Jump frequency2 By setting the jump frequency and range, the As F4.07 0.00Hz
inverter can avoid the mechanical resonance
F4.10 Jump frequency range2 point of the load. As F4.08 0.00Hz
F4.11 Jump frequency3 As F4.07 0.00Hz
F4.12 Jump frequency range3 As F4.08 0.00Hz
F4.13 Jump frequency4 As F4.07 0.00Hz
F4.14 Jump frequency range4 As F4.08 0.00Hz
F5 group: Digital Input and Output Parameters
0:Two-line control mode1
1:Two-line control mode2
F5.00 FWD/REV mode 0-3 0
2:Tree-line control mode1
3: Tree-line control mode2
Terminal run detection 0:Invalid when power on
F5.01 0-1 0
selection at power on 1:Valid when power on

0:Control end idle


1:Forword jog control
F5.02 Input X1 Function 2:Reverse jog control 0-26 3
3:Three-line control
4:Forword rotation contrl(FWD)
5:Reverse rotation contrl(REV)
6:Stop freely control
7:Externa Stop control
F5.03 Input X2 Function 8:External rest signal input(RST) 0-26 4
9:External failure open input
10:Frequency increase control(UP)
11:Frequency decelerase control(DOWN)
12:Multi-speed selection1
13:Multi-speed selection2
14:Multi-speed selection3
F5.04 Input X3 Function 15:Run command switch to terminal 0-26 12
16:Reserved
17:Stop DC brking
Function Factory
Name Description Setting range
code default
18:frequency source switch(F0.06)
19:Reserved
Input X4 Function 20:Reserved
F5.05 0-26 13
(Communication version is 485+) 21:Reserved
22:Count clearance signal(Fb.10 Count FUNC)
23:Count trigger signal(Fb.10 Count FUNC)
24:Timing clearance signal(Fb.10 Timing
FUNC)
Input X5 Function 25:Timing trigger signal(Fb.10 Timing function)
F5.06 0-26 8
(Communication version is 485-) 26:Acceleration or deceleration time selection
(Time 1 and Time 2 switch selection)

0:NO output
1:Inverter ready to run
2:Running indication signal
3:VFD zero-speed running
4:External fault stop
5:VFD fault
6:Frequency/speed arrival signal (FAR)
7:Frequency/speed level detection signal (FDT)
8:Upper limit arrival of output frequency
Programmable relay
F5.07 9:Lower limit arrival of output frequency 0-14 5
R output
10:VFD overload
11:Timer time is up(When the timing time
reaches the timing setting time of Fb.13, the relay
outputs)
12:Counter reaches the set value(When the
count value reaches the counter detection value
of Fb.12, the relay will output)
13:Counter reset signal (Reservedd)
14:Reservedd

F5.08 R output delay time The delay from the change of the state of relay R
0-999.9s 0.0s
F5.09 R turn off delay time to the change of the output
When the output frequency is within the positive
Frequency arrival
F5.10 and negative detection width of the set frequency, 0.00-15.00Hz 5.OOHz
detectionrange (FAR)
the terminal outputs a valid signal (low level)
0.00-Upper
F5.11 FDT level setting limited 10.00Hz
frequency
0.00~
F5.12 FDT lag 1.00Hz
30.00Hz
Set the frequency modification rate when the
UP/DOWN terminal sets the frequency. That is,
UF/DOWN terminal modification 0.10-
F5.13 the UP/DOWN terminal is short-circuited with 1.00Hz
rate 200.00Hz/s
COM for one second, the magnitude of the
frequency change.
F5.14 Reserved
Bit0 to Bit4 correspond to X1 to X5 respectively
0 is positive logic, i.e. terminal Xi is enabled when
it connects with common terminal and disabled if
Effective logic setting
F5.15 disconnected. 0-31 0
of input terminal (X1 - X5)
1 is negative logic, i.e. terminal Xi is disabled
when it connects with common terminal and
enabled when disconnected.
Function Factory
Name Description Setting range
code default
F5.16 X1 filter coefficient Used to set the sensitivity of the input terminals. If 0-9999 5
the digital input terminals are susceptible to
F5.17 X2 filter coefficient interference and cause malfunction, this 0-9999 5
parameter can be increased to increase the
F5.18 X3 filter coefficient resistance to 0-9999 5
interference. However, setting it too high will
F5.19 X4 filter coefficient result in a reduction in the sensitivity of the input 0-9999 5
terminals.
F5.20 X5 filter coefficient 1: represents the unit of 2MS scan time 0-9999 5
F6 group: Analog Input and Output Parameters
Lower limit voltage
F6.00 0.0%
of AVI input
Set AVI upper and lower limit voltage 0.00-100.0%
Upper limit voltage
F6.01 100.0%
of AVI input
Setting corresponding to AVI
F6.02 Set the setting corresponding to the AVI upper 0.0%
lower limit -100.0%-
and lower limits, which corresponds to the
Setting corresponding to AVI 100.0%
F6.03 percentage of the upper limit frequency [F0.09] 100.0%
upper limit
Lower limit current
F6.04 0.0%
of ACI input
Set ACI upper and lower limit current 0.00-100.0%
Upper limit current
F6.05 100.0%
of ACI input
Setting corresponding to ACI
F6.06 Set the setting corresponding to the ACI upper 0.0%
lower limit -100.0%-
and lower limits, which corresponds to the
Setting corresponding to ACI 100.0%
F6.07 percentage of the upper limit frequency [F0.09] 100.0%
lower limit
This parameter is used for filtering the input
Constant for filtering
signals of AVI, ACI and panel
F6.08 time of analog input 0.1-5.0s 0.1s
potentiometer to eliminate the effect of
signal
interference.
When analog input signal shows frequent
fluctuation around the set point, set F6.09 to
F6.09 Error limit of analog input 0.0-100.0% 0.0
restrain the frequency
fluctuation caused by this fluctuation.
0:Output frequency, 0-Max frequency
1:Given frequency, 0-Max frequency
2:Output current, 0-2 times rated current
F6.10 A01 output selection 0-5 0.0
3:Output voltage, 0-2 times rated voltage
4:AVI, 0-10V
5:ACI, 0-20mA
F6.11 AO function lower limit Set the upper and lower limit of the function 0.0
0.0-100.0%
F6.12 AO function upper limit selected by AO 100.0%
F6.13 AO output lower limit 0.0
Set AO output upper and lower limits 0.0-100.0%
F6.14 AO output upper limit 100.0%
F7 group:PLC、Multi-speed Parameters
F7.00 Multi-speed frequency 1 Set multi-speed 1 frequency 5.0Hz
F7.01 Multi-speed frequency 2 Set multi-speed 1 frequency lower limit 10.0Hz
F7.02 Multi-speed frequency 3 Set multi-speed 1 frequency frquecy 15.0Hz
F7.03 Multi-speed frequency 4 Set multi-speed 1 frequency - 20.0Hz
F7.04 Multi-speed frequency 5 Set multi-speed 1 frequency upper limit 25.0Hz
F7.05 Multi-speed frequency 6 Set multi-speed 1 frequency frequency 37.5.0Hz
F7.06 Multi-speed frequency 7 Set multi-speed 1 frequency 50.0Hz
0:Stop after single cycle
F7.07 PLC run mode selections 1:Continuous cycles 0-2 0
2: Keep final value after single cycle
Function Factory
Name Description Setting range
code default
F7.08 Stop save mode 0:No save 1:Save 0-1 0
F7.09 Power down save mode 0:No save 1:Save 0-1 0
F7.10 1st step running time T1 Set multi-speed 1 running time 10.0s
F7.11 2nd step running time T2 Set multi-speed 2 running time 10.0s
F7.12 3rd step running time T3 Set multi-speed 3 running time 10.0s
F7.13 4th step running time T4 Set multi-speed 4 running time 0.0-999.9s 10.0s
F7.14 5th step running time T5 Set multi-speed 5 running time 10.0s
F7.15 6th step running time T6 Set multi-speed 6 running time 10.0s
F7.16 7th step running time T7 Set multi-speed 7 running time 10.0s
F7.17 T1 run mode selections 0
F7.18 T2 run mode selections 0:Forward, Select acceleration time 1 0
F7.19 T3 run mode selections 1:Forward, Select acceleration time 2 0
F7.20 T4 run mode selections 2:Reverse, Select acceleration time 1 0-3 0
F7.21 T5 run mode selections 3:Reverse, Select acceleration time 2 0
F7.22 T6 run mode selections 0
F7.23 T7 run mode selections 0
Current running
F7.24
multi-speed(Reserved)
Current running time
F7.25
(Reserved)
0:No priority
F7.26 Multi-speed priority 1:Multi-speed priority, the priority is lower than 0-1 1
jog

F8 group: PID Control, MPPT And PV Pump Parameters


F8.00 PID feedback trait selection 0:Positive trait 1:Negative trait 0-1 0
0:Keyboard number given
1:Keyboard Potentiometer given
F8.01 PID give signal source 0-3 0
2:AVI
3:ACI
F8.02 PID feedback signal source 0:AVI 1:ACI 0-1 0
PID range
lower limit
The given value when the PID given source is
F8.03 Keyboard number PID given - 0.5
Keyboard number setting
PID range
upper limit
PID instruction acceleration and
F8.04 0.0-100.0s 0.0
deceleration time
F8.05 PID control deviation limit 0.0-100.0% 0.0
PID control deviation limit
F8.06 0.0-6000.0s 0.0
keeping time
F8.07 PID deviatiom upper limit 0.0-100.0% 100.0
F8.08 PID deviatiom lower limit 0.0-100.0% 0.0
F8.09 Proportion gain 0.00-600.00 25.00
0:No
F8.10 Integral time Integral time 1.0
0.0-100.0s
0:No
Differential
F8.11 Differential coefficient 0.00
coefficient
0.00-10.00s
F8.12 PID output upper limit 0.0-100.0% 100.0
F8.13 PID output lower limit 0.0-100.0% 0.0
F8.14 PID output filter time 0.00-10.00 0.00
Function Factory
Name Description Setting range
code default
0:Run at the upper limit frequency
1:Run at the lower frequency limit
F8.15 Feedback fault action selection 2:Run according to the digital set frequency 0-4 2
3:Decelerate to stop
4:Free stop
PID feedback loss detection
F8.16 0.0-100.0% 0.0
value
F8.17 PID feedback loss detection time 0.0-100.0s 1.0
PID feedback over-limit detection
F8.18 0.0-100.0% 100.0
value
PID feedback over-limit detection
F8.19 0.0-100.0s 1.0
time
0:No sleep function
F8.20 PID sleep control 1:Internal wake-up 0-2 0
2:External input terminal control

0: Decelerate to stop
F8.21 Sleep shutdown mode 0-1 0
1: Free stop

0.00Hz-Max
F8.22 Sleep frequency 0.00
frequency

F8.23 Sleep pressure F8.25-100.0% 95.0%

F8.24 Sleep delay 0.0-6000.0s 0.0

F8.25 Wake-up pressure 0.0%-F8.23 80.0%

F8.26 Wake-up delay 0.0-60.0s 3.0

F8.27 PID range lower limit Since the display is 4 digital tubes, the displayed -3276.8 0.0
digits may not match the actual value, but it does -
F8.28 PID range upper limit not affect the final set value. 3276.8 0.1

0:Do not show decimal point


1:Display one decimal point
2:Display two decimal places
F8.29 Decimal point display settings 3:Display three decimal places 0-3 1
This parameter is only used to control the decimal
point display of F8.03, F8.25, F8.26, d0-11 and
d0-12;
Water shortage detection 0.00Hz-Max
F8.30 48.00Hz
frequency frequency
Water shortage detection
F8.31 0.0-F8.28 0.0
pressure

F8.32 Water shortage detection time 0-6500.0s 60.0s

F8.33 Water shortage restart time 0-6500.0s 600.0s

F8.34 Water shortage restart times 9999 6

F8.35 Reserved
Function Factory
Name Description Setting range
code default
0:Not enabled
F8.36 PV pump operation mode 1:PV pump operation mode 1 0-2 0
2:PV pump operation mode 2
If the bus voltage (d-03) is higher than the set
value of the MPPT high-point working voltage
MPPT low point operating (F8.38), it will run at the maximum frequency; if it 0-【F8.38】V
F8.37 Model setting
Voltage is lower than the MPPT high-point working
voltage (F8.38) set value, press ( Busbar
voltage/MPPT high-point working voltage) *Run at
the frequency obtained from the maximum
MPPT high point operating frequency, if the busbar voltage reaches the
【F8.37】-
F8.38 MPPT low-point working voltage (F8.37), it will Model setting
Voltage 1000/500V
run at the minimum running frequency (F8.40) of
the water outlet.
0:Not shield
F8.39 Water shortage fault shield 0-1 0
1:Shielded
0:Disabled
F8.40 Undervoltage restart enable 0-1 0
1:Enabled
The delay time is calculated from the beginning of
F8.41 Undervoltage restart delay 0.0s-360.0s 10.0s
the undervoltage
0:Not Enable
F8.42 Power-on self-start
1:Enable

PV pump lack of water detect If the frequency converter runs above the
F8.43 0.0-300.0% 0.0
Current Ratio minimum water output frequency (F8.40), and the
output current is less than the motor no-load
current (F9.11) * the water shortage detection
F8.44 PV pump Low limit frequemcy current of the Guangyou pump corresponds to 0.00-99.99Hz 0.00
the no-load current ratio (F8.39), after the
Guangyou After the water shortage detection time
PV pump lack of water detect of the water pump (F8.09), the inverter will report
F8.45 0.0-250.0s 0.0
time the water shortage fault ELT.

0:Disabled
F8.46 Swing frequency control 0-1 0
1:Enabled

0:Fixed amplitude
The reference value of amplitude is max.
frequency F0.08.
F8.47 Swing amplitude contro 0-1 0
1:Varied amplitude
The reference value of amplitude is specified
channel frequency.

Restart method of Swing 0:start to the state before stop


F8.48 0-1 0
frequency mode 1:just restart, no other requirement
The swing frequency amplitude is a percentage
F8.49 Swing frequency amplitude relative to the maximum output frequency 0.0-100% 0.00%
(F0.08).
Function Factory
Name Description Setting range
code default

This function code refers to the amplitude of rapid


decrease after the frequency reaches the upper
limit frequency of the swing frequency during the
wobble frequency process, and of course also
refers to the amplitude of the rapid rise after the
F8.50 Jump frequency amplitude 0.0-50.0% 0.00%
frequency reaches the lower limit frequency of the
wobble frequency. This value is a percentage
relative to the swing frequency amplitude (F8.49).
If it is set to 0.0%, there will be no sudden jump
frequency.

The running time from the lower limit frequency of


F8.51 Swing frequency rising time the swing frequency to the upper limit frequency 0.1-400.0s 5.0s
of the swing frequency.
The running time from the upper limit frequency
F8.52 Swing frequency rising time of the swing frequency to the lower limit 0.1-400.0s 5.0s
frequency of the swing frequency.
Swing frequency lower limit
F8.53 0.1-999.9s 5.0s
frequency delay Set the upper and lower frequency delay of the
Swing frequency upper limit swing frequency.
F8.54 0.1-999.9s 5.0s
frequency delay
F8.55 Reserved
F9 group: Motor Parameters
F9.00 Motor rated power Model setting
F9.01 Motor rated voltage 1-500V Model setting
F9.02 Motor rated current 0.01-99.99A Model setting
F9.03 Motor rated speed 0-60000Krpm Model setting
F9.04 Motor rated frequency 1-400.00hz 50.00Hz
Parameters self-adjustment 0:No operation
F9.05 0-1 0
selections 1:Static self-tuning
0.001-65.535
F9.06 Motor stator resistance Model setting
Ω
F9.07 Motor rotor resistance Model setting
F9.08 Motor rotor inductance Model setting
F9.09 Motor rotor mutual inductance Model setting
F9.10 Reserved

F9.11 Motor no-load current Model setting

FA group: Protect Parameters


0:Invalid
FA.00 Motor overload protection 0-1 0
1:Valid
The motor overload protection factor is the
Motor overload protection curve
FA.01 percentage of the rated current value of the motor 30%-110% 100%
coefficient
to the rated output current value of the inverter.
This power parameter specifies the allowable
150-280V
FA.02 Undervoltage protection level lower limit voltage of the DC bus when the 180/360V
300-480V
inverter is working normally.
0:disabled
FA.03 Overvoltage Stall Enable 0-1 1
1:enable
Function Factory
Name Description Setting range
code default
The overvoltage limit level defines the operating 350-380V
FA.04 Over-voltage limit level 375/660V
voltage for overvoltage stall protection 660-760V
The current limit level defines the current
threshold value of the automatic current limit
FA.05 Current limit level 30-200% 150%
action, and its set value is a percentage relative
to the rated current of the inverter.
Frequency drop rate at current
FA.06 0-99.99Hz/s 0
limit
0:invalid
1:Acceleration and deceleration are valid,
FA.07 Current limiting action selection constant speed is invalid 0-2 0
2:Valid for acceleration and deceleration, valid
for constant speed
The current threshold of the inverter overload pre-
FA.08 Overload pre-alarm level alarm action, and its set value is a percentage 50-150% 120%
relative to the rated current of the inverter.
The delay time between the inverter output
current continuously greater than the overload
FA.09 Overload pre-alarm delay 0.0-15.0s 5.0s
pre-alarm level amplitude (FA.08) and the output
of the overload pre-alarm signal.
Oscillation suppression In general, when the motor oscillates, increase
FA.10 0-200 30
coefficient the oscillation suppression coefficient.
Amplitude suppression Set the maximum adjustment amount for
FA.11 0-1000 20
coefficient oscillation suppression.
Oscillation suppression lower Below this frequency, oscillation suppression is
FA.12 0.0-FA.13 5.00Hz
limit frequency disabled.
Oscillation suppression upper Above this frequency, oscillation suppression is FA.12-
FA.13 50.00HZ
limit frequency disabled. 200.00Hz
Ones place: select in acceleration
0: invalid, 1: valid
Tens place: Select during deceleration
Cycle-by-cycle current limit
FA.14 0: invalid, 1: valid 000-111 011
selection
Hundreds place: select from constant speed
0: invalid, 1: valid
Thousands: Reservedd
FA.15 Cycle-by-cycle current limit level Inverter rated current. 80-200% 180
When the reset times are set to 0, there is no
automatic reset function, only manual reset.
FA.16 Malfunction auto-reset times 0-10 0
10 means that the number of times is unlimited,
that is, infinite times.
FA.17 Malfunction auto-reset interval 0.5-25.0s 3.0S
0:Not enabled
1:Overcurrent suppression enable
VF overcurrent, overvoltage
FA.18 2:Overvoltage Suppression enable 0-3 3
suppression selection
3:Overcurrent and overvoltage suppression
enable
FA.19 VF overcurrent suppression Kp 0-100 20
VF Double-speed overcurrent
FA.20 stall action current compensation 50-200 50
coefficient
FA.21 VF overvoltage suppression Kp 0-100 60
VF Overvoltage Stall Rise
FA.22 0-50 5
Maximum Frequency
Function Factory
Name Description Setting range
code default
VF Overvoltage Stall Regulator
FA.23 0-100 80
Kp
0:Report undervoltage fault, free stop
Power-off and under-voltage
FA.24 1:No undervoltage fault is reported, stop 0-1 0
shutdown mode
according to the set stop mode (F3.05)
FA.25 Reserved
0: Output phase loss protection is invalid
FA.26 Output phase loss enable
1: Output phase loss protection is valid
FB group: Display And Special Parameters
FB.00 Running monitoring parameters The default display item of the main monitoring 0
interface. The corresponding numbers are d 0-15
FB.01 Stop monitoring parameters group parameters. 1
It is used to correct the display error of the speed
FB.02 Motor speed display coefficient 0.01-99.99 1.00
scale and has no effect on the actual speed.
FB.03 Current Malfunction 0-9999 0
FB.04 Last malfunction 0-9999 0
FB.05 First two malfunction 0-9999 0
FB.06 Malfunction Bus Voltage 0-9999 0
FB.07 Malfunction out Current 0.0-999.9 0
FB.08 Malfunction given frequency 0.0-300.0 0
FB.09 Malfunction running frequency 0.0-300.0 0
Ones place: Count arrival processing
0:Single-week count, stop output,
1:Single-week count, continue to output
2:Cycle count, stop output
3:Cycle count, continue to output.
Tens: Reservedd
FB.10 Counting and Timing Modes 000-303 103
Hundreds place: timed arrival processing,
0:Single-week timing, stop output
1:One-week timing, continue to output,
2:Cycle timing, stop output
3:Cycle timing, continue to output.
Thousands: Reservedd
FB.11 Counter reset value setting 0-9999 1
FB.12 Counter detection value setting 0-9999 1
FB.13 Timing time setting 0-9999s 0
FB.14-
Reserved
FB19
FB.20 Software upgrade date (year)
Software upgrade date (month,
FB.21
day)
FB.22 Software version Model setting

FB.23 Reserved

The default display items of the main monitoring


Stop and run auxiliary display
FB.24 interface. The corresponding numbers are group 0-15 4
(only valid for dual display)
d parameters.
Function Factory
Name Description Setting range
code default
FC group:Communication Control Function Parameter
0:1200 1:2400 2:4800
FC.00 Communication baud rate 0-5 3
3:9600 4:19200 5:38400
Data format: <data length, stop position>
0: No parity, <8,1>
FC.01 Modbus data format 1: odd parity, <8,1> 0-3 0
2: Even parity, <8,1>
3: no parity, <8,2>
It set communication address while VFD is
FC.02 485 communication address 1-247 1
Modbus communication slave machine.
Modbus communication overtime
FC.03 0.0-600.0s 10.0s
fault time
FC.04 Reserved
0:No checkout overtime fault
Modbus communication fault act
FC.05 1:Alarm 0-2 1
mode selections
2:Forced stop
d Group-Monitoring parameter group and fault record
Function Smallest
Name Set scope
code unit

d0.00 Output frequency 0.00-400.00Hz 0.01Hz

d0.01 Settings frequency 0.00-400.00Hz 0.01Hz

d0.02 Output voltage 0-999V 1V

d0.03 Bus voltage(V) 0-999V 1V

d0.04 Output current 0.0-999.9A 0.1A

d0.05 Motor rotation speed(RPM/min) 0-60000(RPM/min) 1

d0.06 Analog input AVI(V) 0.00-10.00V 0.01

d0.07 Analog input ACI(mA) 0.00-20.00mA 0.01

d0.08 Analog output AO1(V) 0.00~10.00V 0.01V

d0.09 Input and output terminal status 0-3FH 1H

d0.10 Radiator temperature1 0.0℃-+999.9℃ 0.1℃

d0.11 PID setting value PID range lower limit 0.01V


-
d0.12 PID feedback value PID range upper limit 0.01V

d0.13 Current count 0-9999 1

d0.14 Current timing value(S) 0~9999s 1s

Accumulated running time of the


d0.15 0~9999h 1h
machine(h)
Accumulated electrify time of the
d0.16 0~9999h 1h
machine(h)
U-phase current sampling offset
d0.17 0-4095
value
V-phase current sampling offset
d0.18 0-4095
value
W-phase current sampling offset
d0.19 0-4095
value
d0.20-
Reserved
d0.22
Fault code
Fault
Fault descriptions Possible reasons Troubleshooting
code
Abnormal supply voltage Check the power supply
Over voltage in
OU1(1) The driver is restarted with a Start after setting as DC braking,
Acc process
rotating motor or rotational
Over voltage in Too short Dec time Prolong the Dec time
OU1(2)
Dec process Abnormal of supply voltage Check the power supply
Over voltage in
OU1(3) Abnormal of supply voltage Check the power supply
constant-speed
Too short Acc time Prolong the Acc time
Hardware Over-current in VFD power is too small Select a higher power drive
OCC1(4)
Acc process V/F curve is not suitable Adjust V/F curve or torque boost
IGBT module damaged Contact suppliers for service
Too short Dec time Prolong the Dec time
Hardware Over-current in
OCC2(5) VFD power is too small Select a higher power drive
Dec process
IGBT module damaged Contact suppliers for service
Low grid voltage Check the power supply
Sudden change or abnormal of Check the load or reduce the
Hardware Over-current in
OCC3(6) load change of the load
constant speed
VFD power is too small Select a higher power drive
IGBT module damaged Contact suppliers for service
Too short Acc time Prolong the Acc time
Hardware Over-current in
OCS1(7) VFD power is too small Select a higher power drive
Acc process
V/F curve is not suitable Adjust V/F curve or torque boost
Hardware Over-current in Too short Dec time Prolong the Dec time
OCS2(8)
Dec process VFD power is too small Select a higher power drive
Low grid voltage Check the power supply
Hardware Over-current in Sudden change or abnormal of Check the load or reduce the
OCS3(9)
constant speed load change of the load
VFD power is too small Select a higher power drive
VFD output shorted or grounded Check motor wiring
Refer to overcurrent
VFD instantaneous overcurrent
countermeasures
EFO(10) Power module failure
The control board is abnormal or
Contact suppliers for service
has serious interference
Damaged power device Contact suppliers for service
Overvoltage during
OU(11) Abnormal input voltage Check the power supply voltage
shutdown
Check if the power supply voltage
Power supply voltage is too high
Over voltage in is too high
OU3(12)
constant-speed Sudden change or abnormal of Check the load or reduce the
load change of the load
Abnormal input voltage Check the power supply voltage
LU(13) Undervoltage
Contactor does not pick up Contact suppliers for service
Ambient temperature is too high Improve the environment
Small space around the VFD Adjust space
OH(14) Overheat Air duct blocked Clean and unclog airways
Check the fan's power supply and
Cooling fan does not run
the fan itself
Fault
Fault descriptions Possible reasons Troubleshooting
code
Improper V/F curve or torque boost Adjust the V/F curve and torque
settings boost amount
The grid voltage is too low Check grid voltage
OL1(15) VFD overload The motor is blocked or the load
Check the load
suddenly changes too much
Motor overload protection factor Correctly set the motor overload
setting is incorrect protection factor
Improper V/F curve or torque boost Adjust the V/F curve and torque
settings boost amount
The grid voltage is too low Check grid voltage
OL2(16) Motor overload The motor is blocked or the load
Check the load
suddenly changes too much
Motor overload protection factor Correctly set the motor overload
setting is incorrect protection factor
BIAS(17) Current bias error Hardware malfunction Contact suppliers for service
VFD power is too small Select a higher power drive
Cycle-by-cycle current
CBC(18) Sudden change or abnormal of Check the load or reduce the
limit malfunction
load change of the load
Loose PID feedback line Check feedback connection
PID feedback is lower
FBL(19) The feedback amount is less than Adjust the detection input
than the lower limit
the disconnection detection value threshold

When the PID feedback amount is


greater than the feedback over- Check feedback connection
PID feedback exceeds value detection value, and the
FBH(20)
upper limit duration exceeds the PID feedback
over-value detection time, the Adjust the detection input
inverter will alarm fault FBH threshold
EPROM read / write
EEEP(21) EEPROM malfunction Contact suppliers for service
errors
Dual CPU communication
CE(22) CPU communication malfunction Contact suppliers for service
malfunction
Disconnect the external device
External device External device fault input terminal fault input terminal and clear the
EF(23)
malfunction is closed fault (pay attention to check the
cause)
EPA(24) Parameter setting error
Communication Check whether the communication line connection is abnormal and the
E485(25)
disconnection line sequence is correct.

Adjust the acceleration time, deceleration time, motor parameters do


SFOC(27) Software overcurrent
not match, re-parameter identification
ELH Water shortage malfunction
The wiring from the inverter to the
Troubleshoot wiring
motor is abnormal
The three-phase output of the Check whether the three-phase
SPO Output phase loss fault inverter is unbalanced winding of the motor is normal
Abnormal drive board Contact suppliers for service
Module Abnorma Contact suppliers for service
Warning code
Check whether the three-wire
VFD three-wire function setting is
EPA1 parameter setting error system setting of the inverter
incorrect
terminals is correct
Appendix Newsletter

1. Product parameter data

Parameter data is an important setting parameter of the inverter . The parameters are as follows:
Product Group F
parameter F0, F1, F2, F3, F4, F5, F6, F7, F8, F9, FA, FB, FC, FP
data (read and write)

The parameter data communication address is defined as follows:


1) When reading parameter data for communication, for the parameter data of F0~FP group, the high sixteen bits of
the communication address are directly 0 0-0D, and the low sixteen bits are directly the seria7l number of the
parameter in the function group, for example:
F0-16 function parameter, its communication address is 0010H, of which 00H represents the function parameter of the
F0 group, and 10H represents the hexadecimal data format of the serial number 16 of the parameter in the function
group
2) When writing parameter data for communication
For F0~FP group parameter data, for F0~FP group parameter data, the high sixteen bits of the communication address
are directly 0 0-0D, and the low sixteen bits are directly the serial number of the parameter in the function group, for
example:
--Write function parameter F0-16: When writing, its communication address is 0010H

2. Product non-parametric data

d monitoring parameters, inverter fault


Product Status data (read only)
description, inverter running status
nonparametric
data Control parameter (write Control commands , communication
only) settings
Data status
Status data is divided into monitoring parameters, inverter fault description, and inverter running status monitoring
parameters. The function codes in this table are inconsistent with those in the parameter table. Please follow this table
when communicating. The addresses are defined as follows: (function codes are discontinuous)
Function code Name Address
d0.00 Output frequency 7000H
d0.01 Setting frequency 7001H
d0.03 Bus voltage(V) 7002H
d0.02 Output voltage 7003H
d0.04 Output current 7004H
Reserved 7005H-7006H
d0.09 Input and output terminal status 7007H
Reserved 7008H
d0.06 AVI voltage 7009H
d0.07 ACI current 700AH
Reserved 700BH-700EH
d0.11 PID given 700FH
d0.12 PID feedback 7010H
Reserved 7011H-7017H
d0.05 Motor rotation speed(RPM/min) 7018H
d0.16 Accumulated electrify time of the machine(h) 7019H
d0.15 Reserved 701BH-7021H
d0.10 Radiator temperature1 7022H
Inverter fault description
When reading the fault description of the inverter, the communication address is fixed at 8000H. The host computer can
obtain the current fault code of the inverter by reading the address data. For the description of the fault code, see the
definition in the "function parameter table" parameter.
Inverter running status
When reading the running status of the inverter by communication, the communication address is fixed at 3000H, and
the host computer can obtain the current running status information of the inverter by reading the address data, which
is defined as follows:

Inverter running status communication Read Status Word Definition


address
1 : Forward operation 2 : Reverse operation
3000H
3 : Stop

Control parameter
Control parameters are divided into control command, digital output terminal control, analog output AO1 control,
analog output AO2 control, high-speed pulse (FMP) output control

Control commands
When F0-02 (command source) is selected as 2: communication control, the host computer can control the related
commands such as start and stop of the inverter through this communication address. The control commands are
defined as follows :

Inverter running status communication


address Read Status Word Definition

1 : Forward operation 2 : Reverse operation


3 : Forward jog 4 : Reverse jog
2000H
5 : Free stop 6 : Decelerate to stop
7 : Fault reset

Communication settings
The communication setting value is mainly used for the given data when the frequency source, torque upper limit
source, V/F separation voltage source, PID given source, PID feedback source, etc. are selected as communication
given in the product. Its communication address is 1000H. When the host computer sets the communication address
value, its data range is -10000~10000, corresponding to the relative given value -100.00%~100.00

3. Modbus communication protocol

The product series inverter provides RS485 communication interface and supports Modbus-RTU slave
communication protocol. Users can realize centralized control through computer or PLC, set inverter running
commands, modify or read parameters, read inverter working status and fault information, etc. through this
communication protocol. The serial communication protocol defines the content and format of information transmitted
in serial communication. These include: host polling (or broadcast) format; host encoding method, including:
parameters required for action, transmission data and error checking, etc. The response of the slave also adopts the
same structure, including: action confirmation, return data and error checking, etc. If the slave has an error in receiving
the information, or cannot complete the action required by the master, it will organize a fault message as a response
and feed it back to the master .
4. Communication data structure

The Modbus-RTU protocol communication data format of the product series inverter is as follows, the inverter only
supports the reading or writing of Word-type parameters, and the corresponding communication read operation
command is 0x03 ; 10 , support byte or bit read and write operations :
Example 1: Read parameter d - 01 (set frequency) , query d- 01 to set the frequency parameter, and receive a return
value of 0 Hz

Modbus Function Parameter Parameter High word Word count CRC CRC
low
address code number high Number low count low order high

0x 01 0x03 0x70 0x01 0x00 0x01 0x81 0xF7


Answer:
CRC CRC
Modbus address Function code Number of bytes Data high Data low
Low order high
0x01 0x03 0x20 0x00 0x00 0xB8 0x 44
Example 2: Write the parameter F 0 -08 (maximum frequency of the inverter) to 20.0 0Hz , and the return setting value
is set successfully
Modbus Function code Parameter Parameter High word Word count CRC CRC
address number high Number low count low low order high

0x01 0x06 0x00 0x08 0x07 0XD0 0x81 0xF7

Answer:

Modbus Function Parameter Parameter High word word count CRC CRC
address code number high number low count low low order high

0x01 0x06 0x00 0x08 0x07 0XD0 0x81 0xF7


Example 3: Reset the parameter to the factory value , set 1 in F0-17 , and restore the parameter to the factory value

Modbus Function Parameter Parameter High word word count CRC CRC
address code number high number low count low low order high

0x01 0x06 0x00 0x11 0x00 0X01 0x81 0xF7


Answer:
High CRC
Modbus Function Parameter Parameter Word count CRC
address code number high Number low word low low high
count order
0x01 0x06 0x00 0x0A 0x07 0XD0 0x81 0xF7
Data frame field description :
Frame header
START Idles greater than 35 character transfer times
Slave address
ADR Communication address range: 1 to 247;

Command 03: Read slave parameters; 06: Write slave parameters ;


code CMD 10 : Write a group of parameters continuously
Parameter The parameter address inside the inverter , expressed in hexadecimal; it is divided into parameter
address H
type and non-parameter type (such as running state parameters, running commands, etc.)
Parameter parameters, etc., see the address definition for details. When transmitting, the high byte comes first
address L
and the low byte follows.
Number of The number of parameters to be read in the frame, if it is 1, it means to read 1 parameter. When
parameters H
transmitting, the high byte comes first and the low byte follows. When the command code is 0 3 , this
Number of
parameters L protocol can only rewrite one parameter at a time, and there is no such field.
Data H The data to be answered, or the data to be written, is transmitted with the high byte in front and the
Data L low byte in the back.
CRC Detection value: CRC16 check value. When transmitting, the low byte comes first and the high byte
CHK low
follows.
CRC
CHK high For the calculation method, please refer to the description of CRC check in this section.

END 3.5 characters

5.Parameter parameter address marking rules

The rule is represented by the parameter group number and label as the parameter address:
High byte: 00~0F (group F), 70 ( group d ) Low byte: 00~FF
For example: to access parameter F3-12, the access address of the parameter is represented as 0x030C;
Note: FP group: parameters can neither be read nor changed;
Group d : can only be read, parameters cannot be changed.
Some parameters cannot be changed when the inverter is in the running state; some parameters cannot be changed
regardless of the state of the inverter; when changing the parameters, pay attention to the range, unit and related
descriptions of the parameters .
parameter group number Communication access address
F0~FC group 0x0000~0x0EFF
d0 group 0x7000~0x70FF
Communication settings:
The communication setting value is the percentage of the relative value,
10000 corresponds to 100.00%, -10000 corresponds to -100.00%;
parameter address Parameter Description
Communication setting value (decimal)
1000H
–10000 to 10000
Control command input to inverter: (write only)
Command word address Command function
0001: Forward running 0002: Reverse operation
0003: Forward jog 0004: reverse jog
2000H
0005: Free stop 0006: Decelerate to stop
0007: Fault reset
Read drive status: (read only)
Status word address Status word function
1 : Forward operation 2 : Reverse operation
3000H
3 : Stop
Inverter fault description:
Fault address Inverter fault information
000B: Motor overload
0000: No fault
000E: Over temperature fault
0002: Acceleration overcurrent
000F: External input failure
0003: Deceleration overcurrent
0010: Communication failure
0004: Constant speed overcurrent
0012: Current paranoid error
0005: Acceleration overvoltage
8000H 0013: PID feedback overrun
0006: Deceleration overvoltage
0014: PID feedback value is low
0007: Constant speed overvoltage
0015: Parameter setting failure
0008: Software deceleration
001F: PID feedback lost during operation
overcurrent 0009: Undervoltage fault
0070: EEPROM fault
000A: Inverter overload
The rest not listed are reserved
6. FC group communication parameter description

Factory default 3

Baud rate 0:1200


FC-00 (Ones place: Modbus 1:2400
Predetermined 2:4800
baud rate) area 3:9600
4:19200
5:38400

This parameter is used to set the data transmission rate between the host computer and the inverter. Note that the
baud rate set by the host computer and the inverter must be the same, otherwise, the communication cannot be carried
out. The higher the baud rate, the faster the communication speed .
Factory
Data Format default 6

Data format: <Data length, stop position >


0: no parity, < 8,N,1>
1: odd parity, < 9,O,1>
FC-01
Predetermined 2: Even parity, < 9,E,1>
area 3: no parity, < 8,N,1>
4: Even parity, < 8,E,1>
5: odd parity, < 8,O,1>
6: no parity, < 8,N,2>

The data format set by the host computer and the inverter must be consistent, otherwise, the
communication cannot be carried out.

Factory default 1
FC-02 local address Predetermined
1~247
area
The local address is unique, which is the basis for realizing point-to-point communication between the host computer
and the inverter.
Factory default 1 0.0 s
FC-03 Communication timeout Predetermined
0.0 s ~ 600.0 s
area
When this parameter is set to a valid value, if the interval between one communication and the next communication
exceeds the communication timeout time, the system will report a communication failure error. Normally, it is set to
invalid. If this parameter is set in a continuous communication system, the communication status can be monitored.
Factory default 1
Communication error 0: no operation
FC-05
handling Predetermined area 1: Alarm
2: Fault stop
Appendix: Braking resistor selection

Braking resistor selection

Braking Braking resistor


Type Power Power supply resistor
power resistance
ZQ280AS0D4 0.4KW 100 W 250 Ω
ZQ280AS0D7 0.75KW Single phase 100 W 200 Ω
ZQ280AS1D5 1.5KW AC 300 W 100 Ω
ZQ280AS2D2 2.2KW 200V-240V 300 W 100 Ω
ZQ280AS4D 4.0KW 50Hz/60Hz 1000 W 75 Ω
ZQ280AS5D5 5.5KW 1000 W 75 Ω
ZQ280AT0D7 0.75KW 100 W 750 Ω
ZQ280AT1D5 1.5KW Three phase 300 W 400 Ω
ZQ280AT2D2 2.2KW AC 300 W 250 Ω
ZQ280AT4D 4.0KW 380V-440V 500 W 150 Ω
50Hz/60Hz
ZQ280AT5D5 5.5KW 800 W 100 Ω
ZQ280AT7D5 7.5KW 1000 W 75 Ω

30