ZQ280 (A) Usermanual
ZQ280 (A) Usermanual
ZQ280(A)
Vector Variable Frequency Drive
Solar Inverter
Safety Information and Precautions
This guide is packaged together with the product for ZQ280(A) Variable Frequency Drive. It
contains basic information for quick start of the drive. For safety and more information, please refer to
the ZQ280(A) VFD User's Manual, which can be downloaded on website: http://www.zest-electric.com
■ Electrical Safety
Extreme care must be taken at all times when working with the VFD or within the area of the VFD. The
voltages used in the VFD can cause severe electrical shock or burns and is potentially lethal. Only
authorized and qualified personnel should be allowed to work on VFD.
■ Machine/System Design and Safety of Personnel
Machine/system design, installation, commissioning startups and maintenance must be carried out by
personnel who have the necessary training and experience. They must read this safety information and
the contents of this manual. If incorrectly installed, the VFD may present a safety hazard.
The VFD uses high voltages and currents (including DC), carries a high level of stored electrical energy in
the DC bus capacitors even after power OFF. These high voltages are potentially lethal.
The VFD is NOT intended to be used for safety related applications/functions. The electronic “STOP
&START” control circuits within the VFD must not be relied upon for the safety of personnel. Such
control circuits do not isolate mains power voltages from the output of the VFD. The mains power
supply must be disconnected by an electrical safety isolation device before accessing the internal parts
of the VFD.
Safety risk assessments of the machine or process system which uses an VFD must be undertaken by the
user and or by their systems integrator/designer. In particular the safety assessment/design must take
into consideration the consequences of the VFD failing or tripping out during normal operation and
whether this leads to a safe stop position without damaging machine, adjacent equipment and machine
operators/users. This responsibility lies with the user or their machine/process system integrator.
The system integrator/designer must ensure the complete system is safe and designed according to
the relevant safety standards. ZEST Technology and Authorized Distributors can provide
recommendations related to the VFD to ensure long term safe operation.
■ Electrical Installation - Safety
Electrical shock risk is always present within an VFD including the output cable leading to the motor
terminals. Where dynamic brake resistors are fitted external to the VFD, care must be taken with regards
to live contact with the brake resistors, terminals which are at high DC voltage and potentially lethal.
Cables from the VFD to the dynamic brake resistors should be double insulated as DC voltages are
typically 300 VDC to 800 VDC.
Mains power supply isolation switch should be fitted to the VFD. The mains power supply must be
disconnected via the isolation switch before any cover of the VFD can be removed or before any
servicing work is undertaken stored charge in the DC bus capacitors of the PWM VFD is potentially lethal
after the AC supply has been disconnected. The AC supply must be isolated at least 10 minutes before any
work can be undertaken as the stored charge will have been discharged through the internal bleed resistor
fitted across the DC bus capacitors.
Whenever possible, it is good practice to check the DC bus voltage with a VDC meter before accessing
the VFD bridge. Where the VFD input is connected to the mains supply with a plug and socket, then
upon disconnecting the plug and socket, be aware that the plug pins may be exposed and internally
connected to the DC bus capacitors (via the internal bridge rectifier in reversed bias). Wait 10 minutes to
allow stored charge in the DC bus capacitors to be dissipated by the bleed resistors before commencing
work on the VFD.
1
Nameplate
ZEST Electric
Product Name Product:Variable Frequency Drive
VFD Model Model:ZQ280(A)T1D5
Application Motor Appli Motor: 1.5KW
Rated Input Rate Input:3PH AC 380-440V 50/60Hz
Rated Output Rate Output:3PH AC 380-440V 0-400Hz 4.1A
ZQ280(A) - T - 1D5
......
......
5D5 5.5
7D5 7.5
2
Operating Panel
1. Appearance of Keyboard panel
3
2. Basic operation of panel
Display out frequency
after power on ESC SET SET
50.00 PRG
-d0- d-04 5.3
ESC ESC
Out Current
SET
-F0- F0.00
ESC
Automatic
return after SET
10.0
30 seconds -F6- F0.12
ESC/SET
20.2
ESC
-FB-
Use the RUN button to switch to display the units, tens, hundreds,
and thousands of the digital tube.
4
(2) Terminal start/stop: (set to terminal start/stop F0.02=1)
5
Installment and Wiring
Optional
S V M
T N W 220-240V AC
Single phase 220-240V AC (L N/R T) 380-440V AC
PE
Three phase 380-440 AC (R S T)
X1
X2
X3
X4(485+)
X5(485-)
GND
AO
Analog output
GND 0 to 10VDC
0V
+10V
0 to 10 V
1 to 5 kΩ AVI TC
0 to 20 mA Relay output:
ACI TB 250VAC, between 10mA and 3A
TA 24VDC, between 10mA and 2A
GND
P+、PB Connected with braking resistor According to the list of braking resistors,
choose an appropriate one.
6
Terminal Function Setting and Instruction
Frequency Setting
10V potentiometer power +10V, the maximum is 10mA
source
ACI 0-20mA analog input 0-20mA, input resistance: 100Ω
7
Function Parameter Specifications
Function Factory
Name Description Setting range
code default
F0 group-Basic running Parameters
0.00-
F0.00 VF Power The current power of the VFD. Model setting
99.99KW
0:V/F Control
F0.01 Control Mode 0-1 0
1:SVC mode
0:Keyboard command channel
F0.02 Running order channel selection 1:Terminal command channel 0-1/0-2 0
2:Communication command channel(Need RS48)
0:Digita setting (UP/DOWN terminals
requlate,Off electricity does not storage)
1:Digita setting 2(UP/DOWN terminals
requlate,Off electricity storage)
2:AVI analog setting(0~10V)
Frequency given source channel
F0.03 3:ACI analog setting(0~20mA) 0-7/0-8 4
A
4:Keybord potentiometer setting
5:Multi-speed setting
6:Simple PLC
7:PID control
8:Communication(Need RS48)
F00.12 Acceleration Time 1 Time for the inverter to accelerate to the 10.0s
maximum output frequency or decelerate to zero 0-999.9S
F00.13 Deceleration Time 1 frequency 10.0s
0:Foward direction
1:Reverse direction
2:Forbidden reverse operation
The forward and reverse selections are valid
F00.14 Running direction selection 0-2 0
when the run command comes from the panel.
No reverse rotation is prohibited No matter what
the source of the running command is, the
inverter will not reverse rotation
When a non-zero number is set, the password
F0.15 User password takes effect; after decryption, if 0000 is set, the 0000-9999 0
password function is canceled.
F0.16 Software version Current software version. 01.00-99.99 Model setting
0: No action
1: Restore factory default (not restoring motor
parameters)
F0.17 Parameter initialization 0-3 0
2: Clear malfunction records
3: Restore factory default (restoring motor
parameters)
F0.18-
Reserved
F0.19
0:Not Storage
F0.20 Digital setting stop hold 0-1 1
1:Storage
0.0-
F1.05 Self-setting voltage V1 25.0%
voltage V2
F2-Motor
F1.08 Self-setting frequency F3 rated 37.50Hz
frequency
F1.09 Self-setting voltage V3 Voltage is a percentage of the rated voltage of the V2-100% 75.0%
motor
0:Forbid
F1.10 AVR function 1:All Effective 0-2 0
2:Forbid only deceleration
F1.11 Brake ratio Braking resistor braking ratio 0-100% 90%
F1.12 Torque compensation gain · 0-150% 0%
F1.13 VF overexcitation gain 0-200% 84%
F1.14 Oscillation suppression ffunction 0-6 5
F2 group:Vector Control Parameters
F2.00 ASR Low speed Kp 1-100 20
F2.01 ASR Low speed Ki 1-10.00 0.50
F2.02 ASR High speed Kp 1-100 10
F2.03 ASR High speed Ki 1-10.00 1.0
Lower limit
ASR Low speed switch frequency -
F2.04 10.00Hz
frequency Max
frequency
Lower limit
ASR High speed switch frequency -
F2.05 30.00Hz
frequency Max
frequency
F2.06 Electric slip compensation gain 0.0-100.0% 0
F2.07 Reserved
F2.08 Reserved
F2.09 Reserved
F2.10 Current loop Kp 0-60000 2000
F2.11 Current loop Ki 0-60000 1300
F2.12 Reserved
F2.13 Reserved
F2.14 SVC motor slip compensation 0-200% 100%
F2.15 Reserved
F2.16 Reserved
F2.17 Reserved
F2.18 Reserved
Speed control (drive) torque
F2.19 0.0-200.0% 150.0%
upper limit digital setting
Function Factory
Name Description Setting range
code default
Maximum torque coefficient in
F2.20 50-200% 100%
field weakening region
Current loop M-axis proportional
F2.21 5-300 5
coefficient
Current loop M-axis integral
F2.22 0-65535 0
coefficient
Open loop vector velocity loop
F2.23 0-100 25
filter time constant
F2.24 Open loop vector torque boost 0-500 100
Lower limit
Open loop vector torque boost frequency -
F2.25 20.00Hz
cut-off frequency Max
frequency
F2.26 Torque given filter 0-31 28
Maximum field weakening
F2.27 0-110% 105%
voltage overmodulation factor
Magnetic flux observation
F2.28 0-100% 100%
compensation factor
F2.29 Flux observation filter coefficient 0-2000 300
T-axis current closed-loop
F2.30 0-500 0
coefficient
F2.31 Torque limit method 0-1 0
F2.32 Reserved
F2.33 Reserved
F3 group: Auxiliary Operation Parameters
0:Start frequency
F3.00 Start-up mode 0-1 0
1:DC breake+start frequency
F3.01 Start frequency Initial frequency of inverter start 0.50-20.00Hz 0.50hz
F3.02 Holding time of start frequency Start frequency run time 0.0-60.0s 0
Current value for applying DC braking:
When the rated current of the motor is less than
or equal to 80% of the rated current of the
inverter, it is a percentage base value relative to
F3.03 Start DC brking current the rated current of the motor: 0.0-100% 0.00%
When the rated current of the motor is greater
than 80% of the rated current of the inverter, it is
relative to 80% of the rated current of the inverter
as the percentage base value.
F3.04 Start DC brking time Duration of applying DC braking 0.0~100.0s 0.1s
0:Decelerate stop
F3.05 Stop mode 1:Decelerate stop + DC brking 0-2 0
2:Free stop
0.0-upper
Initial frequency for Stop DC When the frequency reaches the preset
F3.06 limited 0.00Hz
braking frequency, DC braking starts
frequency
Applying the same braking current value as DC
F3.07 Stop DC brking current 0.0-100% 0.00%
braking current
F3.08 Stop DC braking time Duration of applying DC braking 0.0-30.0% 0.0s
F3.09-
Reserved
F3.15
0:No status
F3.16 STOP/RESET key function 0-1 1
1:Enabled in any case
Function Factory
Name Description Setting range
code default
F4 group: Auxiliary Operation 2 Parameters
Jog forward running frequency
F4.00
setting
Set jog forward and reverse frequency 0.00-50.00Hz 10.00Hz
Jog reverse running frequency
F4.01
setting
F4.02 Jog Accel time
Set the jog acceleration and deceleration time 0.1-999.9s Model setting
F4.03 Jog Decel time
F4.04 Accel Time 2 10.0s
0.1-999.9s
F4.05 Deccel Time 2 10.0s
0: invalid
1: When the inverter is running, the jog priority is
F4.06 Multi-function key (JOG KEY) the highest 0-3 1
2: Reverse rotation contrl
3: Forward and Reverse Switching
0.0-upper
F4.07 Jump frequency1 limited 0.00Hz
frequency
F4.08 Jump frequency range1 0.0-10.0Hz 0.00Hz
F4.09 Jump frequency2 By setting the jump frequency and range, the As F4.07 0.00Hz
inverter can avoid the mechanical resonance
F4.10 Jump frequency range2 point of the load. As F4.08 0.00Hz
F4.11 Jump frequency3 As F4.07 0.00Hz
F4.12 Jump frequency range3 As F4.08 0.00Hz
F4.13 Jump frequency4 As F4.07 0.00Hz
F4.14 Jump frequency range4 As F4.08 0.00Hz
F5 group: Digital Input and Output Parameters
0:Two-line control mode1
1:Two-line control mode2
F5.00 FWD/REV mode 0-3 0
2:Tree-line control mode1
3: Tree-line control mode2
Terminal run detection 0:Invalid when power on
F5.01 0-1 0
selection at power on 1:Valid when power on
0:NO output
1:Inverter ready to run
2:Running indication signal
3:VFD zero-speed running
4:External fault stop
5:VFD fault
6:Frequency/speed arrival signal (FAR)
7:Frequency/speed level detection signal (FDT)
8:Upper limit arrival of output frequency
Programmable relay
F5.07 9:Lower limit arrival of output frequency 0-14 5
R output
10:VFD overload
11:Timer time is up(When the timing time
reaches the timing setting time of Fb.13, the relay
outputs)
12:Counter reaches the set value(When the
count value reaches the counter detection value
of Fb.12, the relay will output)
13:Counter reset signal (Reservedd)
14:Reservedd
F5.08 R output delay time The delay from the change of the state of relay R
0-999.9s 0.0s
F5.09 R turn off delay time to the change of the output
When the output frequency is within the positive
Frequency arrival
F5.10 and negative detection width of the set frequency, 0.00-15.00Hz 5.OOHz
detectionrange (FAR)
the terminal outputs a valid signal (low level)
0.00-Upper
F5.11 FDT level setting limited 10.00Hz
frequency
0.00~
F5.12 FDT lag 1.00Hz
30.00Hz
Set the frequency modification rate when the
UP/DOWN terminal sets the frequency. That is,
UF/DOWN terminal modification 0.10-
F5.13 the UP/DOWN terminal is short-circuited with 1.00Hz
rate 200.00Hz/s
COM for one second, the magnitude of the
frequency change.
F5.14 Reserved
Bit0 to Bit4 correspond to X1 to X5 respectively
0 is positive logic, i.e. terminal Xi is enabled when
it connects with common terminal and disabled if
Effective logic setting
F5.15 disconnected. 0-31 0
of input terminal (X1 - X5)
1 is negative logic, i.e. terminal Xi is disabled
when it connects with common terminal and
enabled when disconnected.
Function Factory
Name Description Setting range
code default
F5.16 X1 filter coefficient Used to set the sensitivity of the input terminals. If 0-9999 5
the digital input terminals are susceptible to
F5.17 X2 filter coefficient interference and cause malfunction, this 0-9999 5
parameter can be increased to increase the
F5.18 X3 filter coefficient resistance to 0-9999 5
interference. However, setting it too high will
F5.19 X4 filter coefficient result in a reduction in the sensitivity of the input 0-9999 5
terminals.
F5.20 X5 filter coefficient 1: represents the unit of 2MS scan time 0-9999 5
F6 group: Analog Input and Output Parameters
Lower limit voltage
F6.00 0.0%
of AVI input
Set AVI upper and lower limit voltage 0.00-100.0%
Upper limit voltage
F6.01 100.0%
of AVI input
Setting corresponding to AVI
F6.02 Set the setting corresponding to the AVI upper 0.0%
lower limit -100.0%-
and lower limits, which corresponds to the
Setting corresponding to AVI 100.0%
F6.03 percentage of the upper limit frequency [F0.09] 100.0%
upper limit
Lower limit current
F6.04 0.0%
of ACI input
Set ACI upper and lower limit current 0.00-100.0%
Upper limit current
F6.05 100.0%
of ACI input
Setting corresponding to ACI
F6.06 Set the setting corresponding to the ACI upper 0.0%
lower limit -100.0%-
and lower limits, which corresponds to the
Setting corresponding to ACI 100.0%
F6.07 percentage of the upper limit frequency [F0.09] 100.0%
lower limit
This parameter is used for filtering the input
Constant for filtering
signals of AVI, ACI and panel
F6.08 time of analog input 0.1-5.0s 0.1s
potentiometer to eliminate the effect of
signal
interference.
When analog input signal shows frequent
fluctuation around the set point, set F6.09 to
F6.09 Error limit of analog input 0.0-100.0% 0.0
restrain the frequency
fluctuation caused by this fluctuation.
0:Output frequency, 0-Max frequency
1:Given frequency, 0-Max frequency
2:Output current, 0-2 times rated current
F6.10 A01 output selection 0-5 0.0
3:Output voltage, 0-2 times rated voltage
4:AVI, 0-10V
5:ACI, 0-20mA
F6.11 AO function lower limit Set the upper and lower limit of the function 0.0
0.0-100.0%
F6.12 AO function upper limit selected by AO 100.0%
F6.13 AO output lower limit 0.0
Set AO output upper and lower limits 0.0-100.0%
F6.14 AO output upper limit 100.0%
F7 group:PLC、Multi-speed Parameters
F7.00 Multi-speed frequency 1 Set multi-speed 1 frequency 5.0Hz
F7.01 Multi-speed frequency 2 Set multi-speed 1 frequency lower limit 10.0Hz
F7.02 Multi-speed frequency 3 Set multi-speed 1 frequency frquecy 15.0Hz
F7.03 Multi-speed frequency 4 Set multi-speed 1 frequency - 20.0Hz
F7.04 Multi-speed frequency 5 Set multi-speed 1 frequency upper limit 25.0Hz
F7.05 Multi-speed frequency 6 Set multi-speed 1 frequency frequency 37.5.0Hz
F7.06 Multi-speed frequency 7 Set multi-speed 1 frequency 50.0Hz
0:Stop after single cycle
F7.07 PLC run mode selections 1:Continuous cycles 0-2 0
2: Keep final value after single cycle
Function Factory
Name Description Setting range
code default
F7.08 Stop save mode 0:No save 1:Save 0-1 0
F7.09 Power down save mode 0:No save 1:Save 0-1 0
F7.10 1st step running time T1 Set multi-speed 1 running time 10.0s
F7.11 2nd step running time T2 Set multi-speed 2 running time 10.0s
F7.12 3rd step running time T3 Set multi-speed 3 running time 10.0s
F7.13 4th step running time T4 Set multi-speed 4 running time 0.0-999.9s 10.0s
F7.14 5th step running time T5 Set multi-speed 5 running time 10.0s
F7.15 6th step running time T6 Set multi-speed 6 running time 10.0s
F7.16 7th step running time T7 Set multi-speed 7 running time 10.0s
F7.17 T1 run mode selections 0
F7.18 T2 run mode selections 0:Forward, Select acceleration time 1 0
F7.19 T3 run mode selections 1:Forward, Select acceleration time 2 0
F7.20 T4 run mode selections 2:Reverse, Select acceleration time 1 0-3 0
F7.21 T5 run mode selections 3:Reverse, Select acceleration time 2 0
F7.22 T6 run mode selections 0
F7.23 T7 run mode selections 0
Current running
F7.24
multi-speed(Reserved)
Current running time
F7.25
(Reserved)
0:No priority
F7.26 Multi-speed priority 1:Multi-speed priority, the priority is lower than 0-1 1
jog
0: Decelerate to stop
F8.21 Sleep shutdown mode 0-1 0
1: Free stop
0.00Hz-Max
F8.22 Sleep frequency 0.00
frequency
F8.27 PID range lower limit Since the display is 4 digital tubes, the displayed -3276.8 0.0
digits may not match the actual value, but it does -
F8.28 PID range upper limit not affect the final set value. 3276.8 0.1
F8.35 Reserved
Function Factory
Name Description Setting range
code default
0:Not enabled
F8.36 PV pump operation mode 1:PV pump operation mode 1 0-2 0
2:PV pump operation mode 2
If the bus voltage (d-03) is higher than the set
value of the MPPT high-point working voltage
MPPT low point operating (F8.38), it will run at the maximum frequency; if it 0-【F8.38】V
F8.37 Model setting
Voltage is lower than the MPPT high-point working
voltage (F8.38) set value, press ( Busbar
voltage/MPPT high-point working voltage) *Run at
the frequency obtained from the maximum
MPPT high point operating frequency, if the busbar voltage reaches the
【F8.37】-
F8.38 MPPT low-point working voltage (F8.37), it will Model setting
Voltage 1000/500V
run at the minimum running frequency (F8.40) of
the water outlet.
0:Not shield
F8.39 Water shortage fault shield 0-1 0
1:Shielded
0:Disabled
F8.40 Undervoltage restart enable 0-1 0
1:Enabled
The delay time is calculated from the beginning of
F8.41 Undervoltage restart delay 0.0s-360.0s 10.0s
the undervoltage
0:Not Enable
F8.42 Power-on self-start
1:Enable
PV pump lack of water detect If the frequency converter runs above the
F8.43 0.0-300.0% 0.0
Current Ratio minimum water output frequency (F8.40), and the
output current is less than the motor no-load
current (F9.11) * the water shortage detection
F8.44 PV pump Low limit frequemcy current of the Guangyou pump corresponds to 0.00-99.99Hz 0.00
the no-load current ratio (F8.39), after the
Guangyou After the water shortage detection time
PV pump lack of water detect of the water pump (F8.09), the inverter will report
F8.45 0.0-250.0s 0.0
time the water shortage fault ELT.
0:Disabled
F8.46 Swing frequency control 0-1 0
1:Enabled
0:Fixed amplitude
The reference value of amplitude is max.
frequency F0.08.
F8.47 Swing amplitude contro 0-1 0
1:Varied amplitude
The reference value of amplitude is specified
channel frequency.
FB.23 Reserved
Parameter data is an important setting parameter of the inverter . The parameters are as follows:
Product Group F
parameter F0, F1, F2, F3, F4, F5, F6, F7, F8, F9, FA, FB, FC, FP
data (read and write)
Control parameter
Control parameters are divided into control command, digital output terminal control, analog output AO1 control,
analog output AO2 control, high-speed pulse (FMP) output control
Control commands
When F0-02 (command source) is selected as 2: communication control, the host computer can control the related
commands such as start and stop of the inverter through this communication address. The control commands are
defined as follows :
Communication settings
The communication setting value is mainly used for the given data when the frequency source, torque upper limit
source, V/F separation voltage source, PID given source, PID feedback source, etc. are selected as communication
given in the product. Its communication address is 1000H. When the host computer sets the communication address
value, its data range is -10000~10000, corresponding to the relative given value -100.00%~100.00
The product series inverter provides RS485 communication interface and supports Modbus-RTU slave
communication protocol. Users can realize centralized control through computer or PLC, set inverter running
commands, modify or read parameters, read inverter working status and fault information, etc. through this
communication protocol. The serial communication protocol defines the content and format of information transmitted
in serial communication. These include: host polling (or broadcast) format; host encoding method, including:
parameters required for action, transmission data and error checking, etc. The response of the slave also adopts the
same structure, including: action confirmation, return data and error checking, etc. If the slave has an error in receiving
the information, or cannot complete the action required by the master, it will organize a fault message as a response
and feed it back to the master .
4. Communication data structure
The Modbus-RTU protocol communication data format of the product series inverter is as follows, the inverter only
supports the reading or writing of Word-type parameters, and the corresponding communication read operation
command is 0x03 ; 10 , support byte or bit read and write operations :
Example 1: Read parameter d - 01 (set frequency) , query d- 01 to set the frequency parameter, and receive a return
value of 0 Hz
Modbus Function Parameter Parameter High word Word count CRC CRC
low
address code number high Number low count low order high
Answer:
Modbus Function Parameter Parameter High word word count CRC CRC
address code number high number low count low low order high
Modbus Function Parameter Parameter High word word count CRC CRC
address code number high number low count low low order high
The rule is represented by the parameter group number and label as the parameter address:
High byte: 00~0F (group F), 70 ( group d ) Low byte: 00~FF
For example: to access parameter F3-12, the access address of the parameter is represented as 0x030C;
Note: FP group: parameters can neither be read nor changed;
Group d : can only be read, parameters cannot be changed.
Some parameters cannot be changed when the inverter is in the running state; some parameters cannot be changed
regardless of the state of the inverter; when changing the parameters, pay attention to the range, unit and related
descriptions of the parameters .
parameter group number Communication access address
F0~FC group 0x0000~0x0EFF
d0 group 0x7000~0x70FF
Communication settings:
The communication setting value is the percentage of the relative value,
10000 corresponds to 100.00%, -10000 corresponds to -100.00%;
parameter address Parameter Description
Communication setting value (decimal)
1000H
–10000 to 10000
Control command input to inverter: (write only)
Command word address Command function
0001: Forward running 0002: Reverse operation
0003: Forward jog 0004: reverse jog
2000H
0005: Free stop 0006: Decelerate to stop
0007: Fault reset
Read drive status: (read only)
Status word address Status word function
1 : Forward operation 2 : Reverse operation
3000H
3 : Stop
Inverter fault description:
Fault address Inverter fault information
000B: Motor overload
0000: No fault
000E: Over temperature fault
0002: Acceleration overcurrent
000F: External input failure
0003: Deceleration overcurrent
0010: Communication failure
0004: Constant speed overcurrent
0012: Current paranoid error
0005: Acceleration overvoltage
8000H 0013: PID feedback overrun
0006: Deceleration overvoltage
0014: PID feedback value is low
0007: Constant speed overvoltage
0015: Parameter setting failure
0008: Software deceleration
001F: PID feedback lost during operation
overcurrent 0009: Undervoltage fault
0070: EEPROM fault
000A: Inverter overload
The rest not listed are reserved
6. FC group communication parameter description
Factory default 3
This parameter is used to set the data transmission rate between the host computer and the inverter. Note that the
baud rate set by the host computer and the inverter must be the same, otherwise, the communication cannot be carried
out. The higher the baud rate, the faster the communication speed .
Factory
Data Format default 6
The data format set by the host computer and the inverter must be consistent, otherwise, the
communication cannot be carried out.
Factory default 1
FC-02 local address Predetermined
1~247
area
The local address is unique, which is the basis for realizing point-to-point communication between the host computer
and the inverter.
Factory default 1 0.0 s
FC-03 Communication timeout Predetermined
0.0 s ~ 600.0 s
area
When this parameter is set to a valid value, if the interval between one communication and the next communication
exceeds the communication timeout time, the system will report a communication failure error. Normally, it is set to
invalid. If this parameter is set in a continuous communication system, the communication status can be monitored.
Factory default 1
Communication error 0: no operation
FC-05
handling Predetermined area 1: Alarm
2: Fault stop
Appendix: Braking resistor selection
30
Anhui Zest Electric Co.,Ltd
E-mail:[email protected]