Transformer
Transformer
Transformers are an essential component in power distribution systems and are used to step up or step
down the voltage levels for efficient transmission and distribution of electricity.
1) Core: The core is typically made of laminated steel sheets and provides a low-reluctance path
for the magnetic flux generated by the transformer. It helps in reducing magnetic losses and
improving the efficiency of the transformer.
2) Windings: Transformers have two sets of windings: primary and secondary. The primary winding
is connected to the power source and carries the input voltage. The secondary winding is
connected to the load and delivers the output voltage. Windings are usually made of copper or
aluminum conductors and are insulated to prevent short circuits.
3) Insulation: Insulating materials such as paper, varnish, and oil are used to separate the windings
and to insulate them from the core. This prevents electrical breakdown and ensures safe
operation.
4) Tap changer: A tap changer is a device that allows the adjustment of the turns ratio between
the primary and secondary windings. It provides a means to vary the output voltage and
compensate for voltage fluctuations in the power system it is normally provided on HV side to
vary output voltage.
5) Cooling system: Transformers generate heat during operation, which needs to be dissipated to
prevent overheating. Cooling systems can be either natural (air cooling) or forced (using fans or
oil pumps). Some transformers also use cooling fins or radiators to increase heat dissipation.
6) Tank and insulating oil: The tank houses the core, windings, and other internal components of
the transformer. It is usually made of steel and provides mechanical protection and support.
Insulating oil is used to immerse the windings and the core, providing insulation and efficient
cooling.
7) Bushings: Bushings are insulating devices that provide a means to connect the transformer
windings to external circuits. They serve as the entry and exit points for the electrical
connections and ensure proper insulation between the transformer and the external system.
8) Conservator: The conservator is a reservoir connected to the transformer tank that
compensates for the expansion and contraction of the insulating oil due to temperature
variations. It helps maintain a constant oil level and allows for breathing space.
9) Breather: The breather is a device filled with desiccant material (silica gel) that removes
moisture from the air entering and leaving the conservator. It helps in preventing the moisture
content of the insulating oil from increasing.
10) Buchholz relay: This protective device is installed in oil-filled transformers and detects the
presence of gas made by insulation oil caused by heat or oil flow caused by internal faults. It
triggers an alarm or trips the transformer to prevent further damage.
1) When small fault occurs, it alarms.
2) When large fault occurs it shutdown transformer.
TYPES:
Transformers are classified into several types based on their construction, usage, and voltage levels.
Here are the common types of transformers:
Hermetically sealed transformers: when a transformer is sealed type, there is no possibility to oil
overflow.
Power Transformers: These transformers are used in power generation stations, substations, and
industrial applications to step up or step down the voltage levels for efficient power transmission.
Distribution Transformers: They are mainly used to step down high voltage from power lines to lower
voltage levels suitable for distribution to residential and commercial areas.
Instrument Transformers: These transformers are designed to measure high voltage and high current
levels accurately for protective relaying, metering, and control purposes. They include current
transformers (CTs) and potential transformers (PTs).
Current transformer:
In current transformer secondary side is always shorted. In order to reduce core losses.
Auto Transformers: An auto transformer has a single winding that serves as both the primary and
secondary winding. They are used for applications where a small voltage adjustment is required, such as
in voltage regulators.
Isolation Transformers: These transformers are used to provide electrical isolation between the input
and output circuits. They are commonly used in medical equipment and sensitive electronic devices to
protect against electrical noise and voltage spikes.
Step-Up and Step-Down Transformers: Step-up transformers increase the voltage level, while step-
down transformers decrease the voltage level. They are used to match the voltage requirements of
different electrical systems.
Three-Phase Transformers: These transformers are used in three-phase power systems to transfer
electrical power efficiently. They consist of three primary and three secondary windings.
TESTING OF TRANSFORMER:
To ensure transformer is working properly or if it needs maintenance the average life of transformer is
33.5 years. To check the health of transformer we go for some tests:
The purpose of this test is to detect the major faults of major insulation in transformer. Major insulation
includes:
INSULATION TESTING:
Firstly, disconnect the power supply and de-energize the transformer. We short all HV windings together
and then short all LV windings together. Note the temperature because high temperature affects the
resistance.
1) H-XG
2) X-HG
3) HX-G
H=high voltage
X=low voltage
G=ground
If the resistance is in the range mentioned in the standards of NETA table 100.5, then the health of
transformer is in good condition. Otherwise, maintenance is needed.
These are just a few examples, and there are other vector group configurations as well, such as
Yz, Zz, and Zd, which are less common.
The vector group of a transformer is important for system operation and protection. It is used
to ensure that the transformers in a power system are properly interconnected and that the
phase angles between them are correct. By matching the vector group of transformers, it is
possible to parallel them and transfer power between them without phase shift issues or
circulating currents.
It's worth noting that the vector group is specific to three-phase transformers, as they are the
most common type used in power systems. Single-phase transformers do not have vector
groups.
Vector group test of transformer:
Following are the vector group testing given below:
1) Dyn11 2) Dyn 1 3) YNd1 4) YNd11
i) Dyn11:
Following test confirms if the transformer has Dyn 11 configuration:
ii) Dyn1
Following test confirms if the transformer has Dyn 1 configuration:
iii) YNd1
Following test confirms if the transformer has Dyn 1 configuration:
iv) YNd11
Following test confirms if the transformer has YNd11 configuration:
Standard:
- Ensure proper safety precautions are followed, such as using appropriate personal protective
equipment (PPE) and adhering to electrical safety guidelines.
- Verify the accuracy of the Megger device by performing a calibration check before the test.
- It's recommended to conduct the test at a standardized temperature, typically around 20°C
(68°F), or adjust the readings based on the measured temperature using a temperature
correction factor.
.
Expected Results:
1. The measured resistance values should generally match the manufacturer's specified values
or the baseline measurements within an acceptable tolerance.
2. Significant deviations in resistance values could indicate potential issues, such as winding
faults, poor connections, or deterioration of the winding conductors.
3. A significantly higher resistance value in one winding compared to others may indicate a
problem like a partial turn short or a broken conductor.
4. In a three-phase transformer, the resistance values of the three windings should be relatively
balanced. Significant imbalances could suggest an issue with one or more windings.
5. The resistance values should be within an acceptable range based on the transformer's
design, rating, and temperature.
If the resistance is getting low as the tap value gets lowers then it may a sign of better winding
resistance.
Signs for test:
To determine if there are signs to check the winding resistance of a transformer, you can look
for the following indicators:
1. Abnormal Temperature Rise: If the transformer exhibits unusually high operating
temperatures, it could be a sign of increased resistive losses due to issues like winding faults or
poor connections. Monitoring the winding resistance can help assess the potential cause of the
temperature rise.
2. Unexpected Load Imbalance: If there is an imbalance in the load distribution across the
transformer phases, it can indicate issues such as uneven winding resistance or faulty
connections. Monitoring the resistance values can help identify the cause of load imbalances.
3. Unexplained Voltage Drops: If there are significant voltage drops across the transformer
terminals during normal operation, it may indicate increased resistance in the windings.
Checking the resistance values can help determine if the windings are the source of the voltage
drop.
4. Previous Maintenance or Repair: If the transformer has undergone recent maintenance or
repair work on the windings or connections, it is advisable to check the winding resistance as a
part of post-maintenance testing. This ensures that the work was performed correctly and that
there are no lingering issues.
5. Periodic Maintenance Schedule: Including winding resistance testing as a part of routine
maintenance can help detect potential problems early on. Regularly monitoring the resistance
values can identify any changes or deviations over time, allowing for proactive maintenance
and preventing potential failures.
The connection diagram for short circuit test or impedance test on transformer is as
shown in the figure below. The LV side of transformer is short circuited and wattmeter (W),
voltmeter (V) and ammeter (A) are connected on the HV side of the transformer. Voltage is
applied to the HV side and increased from the zero to 20% of HV current ratings to get
readings.
The voltage applied for full load current is very small as compared to rated voltage. Hence,
core loss due to small applied voltage can be neglected. Thus, the wattmeter reading can
be taken as copper loss in the transformer.
Open circuit test or no-load test on a transformer is performed to determine 'no load loss
(core loss)' and 'no load current I0'. The circuit diagram for open circuit test is shown in
the figure below
Usually high voltage (HV) winding is kept open and the low voltage (LV) winding is
connected to its normal supply. A wattmeter (W), ammeter (A) and voltmeter (V) are
connected to the LV winding as shown in the figure. Now, applied voltage is slowly
increased from zero to normal rated value of the LV side with the help of a variac (variable
ratio auto transformer). When the applied voltage reaches to the rated value of the LV
winding, readings from all the three instruments are taken.
The ammeter reading gives the no load current I 0. As I0 itself is very small, the voltage drops
due to this current can be neglected.
The input power is indicated by the wattmeter (W). And as the other side of transformer is
open circuited, there is no output power. Hence, this input power only consists of core
losses and copper losses. As described above, no-load current is so small that these copper
losses can be neglected. Hence, now the input power is almost equal to the core losses.
Note:
core losses depend on voltage and winding losses depend on current.
3. Test Voltage: Reduced voltage (typically around 5-10% of rated voltage) is applied to the
primary winding.
4. Information Obtained: Copper losses and equivalent impedance referred to the primary side
are measured.
5. Focus: Assesses the transformer's performance under rated current conditions and the
impact of copper losses on its efficiency.
2. Load Condition: No load or minimal current flow in the secondary; the primary winding is
energized with DC.
The tan delta test, also known as the dielectric dissipation factor or power factor test, is a type
of insulation test performed on electrical equipment and materials. It is used to assess the
condition of the insulation by measuring the phase difference (angle) between the voltage
applied and the resulting current in the insulation.
When conducting a tan delta test, two types of tests are performed on the specimen:
1. Unearthed Specimen Test (UST):
In this test, the specimen (such as a cable or an insulating material) is not grounded. The test
measures the tan delta between the voltage applied to the specimen and the resulting current,
which helps in determining the insulation's quality.
2. Grounded Specimen Test (GST):
In this test, the specimen is grounded, and the tan delta is measured between the voltage
applied and the current flowing through the grounded specimen. This test is useful for
detecting defects or potential breakdowns in the insulation when it is connected to a grounding
system.
There are three measurable capacitances in transformer:
1) capacitance between HV windings and ground
2) capacitance between LV and HV windings
3) capacitance between LV winding and ground
The formula of tan delta is:
Tanδ = IR/IC
Where Ic is Capacitive current and IR is resistive current.
Reasons of power factor loss:
1) Aging of transformer
2) Dust
3) Moisture
Solution:
we can keep transformer windings in oven to absorb moisture so it may correct power factor
angle deviation.
Dielectric Response Analysis (DRA):
Dielectric Frequency Response (DFR), well-known as Frequency Domain Spectroscopy (FDS),
is now a days becoming more popular as effective tool for diagnosis of power transformer paper
insulation and estimation of moisture content in cellulose paper and oil.
Effects of water:
Water can produce number of factors produce in transformer:
1) Bubbling
2) Partial discharge inception voltage
3) Breakdown voltage
4) Accelerated aging of cellulose
1) Bubbling:
In a transformer bubbling is result of small water vapors of bubble coming out from the paper in
a transformer and floating up into the oil. They decrease the strength of dielectric strength of
the oil a breakdown may occur or partial discharge may happen.
2) Partial discharge:
Partial discharges can occur at lower voltages. Water decreases the PD inception voltage.
“Partial discharge in transformers refers to localized electrical discharges that occur within the
insulation system of the transformer.”
3) Breakdown voltage:
Water also decreases the breakdown voltage of oil. It depends on moisture in the oil and on
temperature change.
4) Accelerated Aging of cellulose:
Fourth effect of water is that it accelerates the aging of cellulose. Cellulose is one of the
insulating materials in transformer. Insulation paper is made up of cellulose. Water decreases
the mechanical strength of cellulose. A measure of mechanical strength is the degree of
polymerization value.
Cellulose tells us about the strength of cellulose molecules. Cellulose consists of glucose rings.
The high number of glucose rings means high number of polymerizations.
When cellulose is new polymerization value is 1200 and 200 value is considered it lost its
mechanical strength. hydrolysis and condensation decrease mechanical strength of paper
(cellulose).
Procedure:
1. Test Setup: Connect the equipment to the dielectric response analyzer and apply an
AC voltage signal across the insulation.
2. Measurement Acquisition: Measure the current and phase angle at each frequency
point during the frequency sweep.
3. Data Analysis: Analyze the measured data to calculate parameters such as
capacitance, power factor, and dielectric dissipation factor.
Expected Results: