Siprotec 7sd87 Profile
Siprotec 7sd87 Profile
www.siemens.com/siprotec
Description
The SIPROTEC 7SD87 differential protection device is suita-
ble for the selective protection of overhead lines and ca-
bles with singleended and multi-ended infeed of all
lengths with up to 6 ends. Transformers and compensa-
ting coils in the protection range are also possible. With its
modular structure, flexibility and the high-performance
DIGSI 5 engineering tool, the SIPROTEC 7SD87 device of-
fers future-oriented solutions for protection, control, auto-
mation, monitoring, and Power Quality – Basic. SIPROTEC 5 Device with Expansion Module
Main function Differential protection physical media, such as optical fiber, two-wire con-
Interoperability of SIPROTEC 4 and SI- nections, and communication networks
PROTEC 5 line protection devices
• Phasor Measurement Unit (PMU)
Tripping 1-pole and 3-pole, minimum tripping
time: 9 ms • Detection and recording of power-quality data in the
mediumvoltage and subordinate low-voltage power
Inputs and out- 12 predefined standard variants with system
puts 4/4 or 8/8 current/voltage transformers,
5 to 31 binary inputs, 8 to 46 binary Functions
outputs
DIGSI 5 permits all functions to be configured and com-
Hardware flexibi- Flexibly adjustable I/O quantity structure bined as required.
lity within the scope of the SIPROTEC 5
modular system • Minimum tripping time: 9 ms
Housing width 1/3 × 19 inches to 2/1 × 19 inches • Main protection function is differential protection
with adaptive algorithm for maximum sensitivity and
Applications stability even with the most different transformer er-
rors, current-transformer saturation, and capacitive
• Line protection for all voltage levels with 1-pole and
charging currents
3-pole tripping
• Directional backup protection and various additional
• Phase-selective protection of overhead lines and ca-
functions
bles with single-ended and multi-ended infeed of all
lengths with up to 6 line ends • Ground-fault detection using the pulse detection me-
thod
• Also used in switchgear with breaker-and-a-half layout
• Detection of ground faults of any type in compensa-
• Transformers and compensating coils in the protec-
ted or isolated electrical power systems using the
tion zone
following functions: 3I0>, V0>, transient ground fault,
• Detection of ground faults in isolated or arc-suppres- cos φ, sin φ, dir. detection of intermittent ground
sion-coilground power systems in star, ring, or faults, harmonic detection, and admittance measure-
meshed arrangement ment
• Serial protection communication with SIPROTEC 5 and • Detection of current-transformer saturation
SIPROTEC 4 devices over different distances and
Communicative and modular
• Fault locator plus for accurate fault location with in- • Virtual network partitioning (IEEE 802.1Q - VLAN)
homogenous line sections and targeted automatic
• Serial protection communication via optical fibers,
overhead-line section reclosing (AREC)
two-wire connections, and communication networks
• Arc protection (IEEE C37.94 and others), including automatic swit-
chover between ring and chain topology.
• Automatic frequency relief for underfrequency load
shedding, taking changed infeed conditions due to • Reliable data transmission via PRP and HSR redun-
decentralized power generation into consideration dancy protocols
• Power protection, configurable as active or reactive- • Extensive cybersecurity functionality, such as role-ba-
power protection sed access control (RBAC), logging of security-related
events, signed firmware, or authenticated IEEE
• Directional reactive-power undervoltage protection
802.1X network access
(QU protection)
• Simple, fast, and secure access to the device via a
• Detection of current and voltage signals up to the
standard Web browser to display all information and
50th harmonic with high accuracy for selected protec-
diagnostic data, vector diagrams, single-line and de-
tion functions (such as thermal overload protection)
vice display pages
and operational measured values
• Phasor Measurement Unit (PMU) for synchrophasor
• PQ – Basic: Voltage unbalance; voltage changes: over-
measured values and IEEE C37.118 protocol
voltage, dip, interruption; TDD, THD, and harmonics
• Time synchronization using IEEE 1588
• 1-pole automatic reclosing function with secondary
arc detection (SAD) • High-performance fault recording (buffer for a max.
record time of 80 s at 8 kHz or 320 s at 2 kHz)
• Point-on-wave switching
• Auxiliary functions for simple tests and commission-
• Control, synchrocheck, and switchgear interlocking
ing
protection
• Flexibly adjustable I/O quantity structure within the
• Graphical logic editor to create high-performance au-
scope of the SIPROTEC 5 modular system
tomation functions in the device
Benefits
• Single-line representation in the small or large display
• Safety due to powerful protection functions
• Fixed integrated electrical Ethernet RJ45 interface for
DIGSI 5 and IEC 61850 (reporting and GOOSE) • Purposeful and easy handling of devices and software
thanks to a user-friendly design
• Up to 4 optional, pluggable communication modules,
usable for different and redundant protocols (IEC • Cyber security in accordance with NERC CIP and BDEW
61850-8-1, IEC 61850-9-2 Client, IEC 60870-5-103, Whitepaper requirements
IEC 60870-5-104, Modbus TCP, DNP3 serial and TCP,
• Highest availability even under extreme environmen-
PROFINET IO, PROFINET IO S2 redundancy)
tal conditions by standard coating of the modules