MV-oil Immersed CT Type AGU and VT Type VKU
MV-oil Immersed CT Type AGU and VT Type VKU
AGU
CURRENT TRANSFORMERS
VKU
VOLTAGE TRANSFORMERS
12 to 52 kV - oil insulated
Performance
• Um: 12 to 52 kV
• All metering and protection classes
• AGU
- In: up to 6000 A
- Short circuit: up to 100 kA (Idyn: 250 kA peak)
- Secondary cores: up to 6
• VKU
- Secondary windings: up to 4
- Single or double pole insulated design
Main Features
• AGU
- Top core design - ensuring low primary winding losses
- Primary and/or secondary transformation ratio reconnection
- Low leakage reactance type
• VKU
- Secondary transformation ratio reconnection
- High thermal overload capability
- Ideal for capacitor bank discharge
• High quality paper-oil insulation
• High-precision measurement accuracy and protection classes with
superior transient response
• Standard ambient temperatures from -35 to +40 °C (extreme ranges
upon request)
• High quality porcelain or composite (silicone shed) insulator
• Extensive experience in seismically active regions
• Minimum oil design and PCB free - environment friendly
• Stainless steel bellows oil expansion system
• Sealing for life - every single transformer is vacuum tested with helium
• Non-corrosive hardware
• Maintenance free
• Explosion-safe design
Accessories
• Terminal for measuring dielectric dissipation factor (tgδ) (optional)
• Secondary winding protection (optional)
- fuses or Micro Circuit Breakers (MCB) for VKU
- surge arresters for AGU
• Oil level indicator (optional for VKU)
• Separate revenue metering secondary terminals sealing
• Internal overpressure indicator (optional)
Quality Assurance
Končar instrument transformers are designed in compliance with IEC, ANSI/IEEE, GOST, AS, IS, CAN, or any other relevant standard.
Product quality is assured through a certified quality standard, the ISO 9001, covering all aspects of design, production and testing.
Končar - Instrument transformers Inc. is ISO 14001 and OHSAS 18001 certified, ensuring environmental and occupational health and safety standards are met.
And most importantly, our tireless ambition to satisfy customers has sealed long lasting quality and reliability onto our product.
AGU VKU AGU VKU AGU VKU AG
VOLTAGE CURRENT VOLTAGE CURRE
TRANSFORMERS TRANSFORMERS TR
DESIGN
Dimensions
Type Maximum Total Terminal Total Oil Base Minimal
System Height Height Weight Weight Mounting Creepage
Voltage Distance
kV mm mm kg kg mm mm
AGU-24 24 1125 750 80 15 280x280 600
The given indicative values refer to our
AGU-36 36 1350 950 120 20 280x280 950 standard porcelain versions and vary
AGU-52 52 1800 1440 200 35 400x400 1300 depending on electrical, mechanical
VKU1-24;36 24;36 900 900 95 11 230x155 600;950 and environmental parameters speci-
fied in the customers’ inquiry.
VKU1-52 52 1375 1375 130 20 230x155 1300
The values are susceptible to change in
VKU-24;36 24;36 850 850 120 15 230x155 600;950
the course of technical developments.
VKU-52 52 1375 1375 240 25 400x400 1300