0% found this document useful (0 votes)
16 views44 pages

OBH647G

Uploaded by

Tomás Arrebola
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views44 pages

OBH647G

Uploaded by

Tomás Arrebola
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Revision G:

• 10. TROUBLE SHOOTING has been modi-


fied.
OBH647 REVISED EDITION-F is void.

INDOOR UNIT
No. OBH647
SERVICE MANUAL REVISED EDITION-G

Models

MSZ-HJ25VA - E1 , E2 , ER1 , ER2

MSZ-HJ35VA - E1 , E2 , ER1 , ER2

MSZ-HJ50VA - E1 , E2 , ER1 , ER2

MSZ-HJ60VA - E1 , E2 , ER1

MSZ-HJ71VA - E1 , E2 , ER1

Outdoor unit service manual


MUZ-HJ·VA Series (OBH648)
MXZ-HJ•VA Series (OBH709)

CONTENTS
1. TECHNICAL CHANGES·······························3
2. PART NAMES AND FUNCTIONS···················4
3. SPECIFICATION·········································5
4. NOISE CRITERIA CURVES···························7
5. OUTLINES AND DIMENSIONS······················9
6. WIRING DIAGRAM···································· 10
7. REFRIGERANT SYSTEM DIAGRAM············ 12
MSZ-HJ25VA 8. SERVICE FUNCTIONS······························· 14
MSZ-HJ35VA 9. MICROPROCESSOR CONTROL················· 16
MSZ-HJ50VA 10. TROUBLESHOOTING································ 20
11. DISASSEMBLY INSTRUCTIONS·················· 34

PARTS CATALOG (OBB647)

1
Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.

<Preparation before the repair service>


Prepare the proper tools.
Prepare the proper protectors.
Provide adequate ventilation.
After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug.
Discharge the capacitor before the work involving the electric parts.

<Precautions during the repair service>


Do not perform the work involving the electric parts with wet hands.
Do not pour water into the electric parts.
Do not touch the refrigerant.
Do not touch the hot or cold areas in the refrigeration cycle.
When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.

Revision A:
• MSZ-HJ50V A- E1 has been added.

Revision B:
• MSZ-HJ25VA- ER1 , MSZ-HJ35VA- ER1 and MSZ-HJ50VA- ER1 have been added.

Revision C:
• MSZ-HJ60VA- E1 , ER1 and MSZ-HJ71VA- E1 , ER1 have been added.

Revision D:
• MSZ-HJ25/35/50/60/71VA- E2 and MSZ-HJ25/35/50VA- ER2 have been added.

Revision E:
• "How to check miswiring and serial signal error" has been corrected (10-6. D ).

Revision F:
• Description of the aircleaning filter have been changed.

Revision G:
• 10. TROUBLE SHOOTING has been modified.

2
OBH647G
1 TECHNICAL CHANGES
MSZ-HJ25VA - E1 , ER1

MSZ-HJ35VA - E1 , ER1

MSZ-HJ50VA - E1 , ER1

1. New model

MSZ-HJ60VA - E1 , ER1

MSZ-HJ71VA - E1 , ER1

1. New model

MSZ-HJ25VA - E1 MSZ-HJ25VA - E2
MSZ-HJ35VA - E1 MSZ-HJ35VA - E2
MSZ-HJ50VA - E1 MSZ-HJ50VA - E2
MSZ-HJ60VA - E1 MSZ-HJ60VA - E2
MSZ-HJ71VA - E1 MSZ-HJ71VA - E2
1. Optional air cleaning filter has been added.

MSZ-HJ25VA - ER1 MSZ-HJ25VA - ER2

MSZ-HJ35VA - ER1 MSZ-HJ35VA - ER2

MSZ-HJ50VA - ER1 MSZ-HJ50VA - ER2

1. Optional air cleaning filter has been added.

3
OBH647G
2 PART NAMES AND FUNCTIONS

MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA

Front panel

Air inlet
Air filter

Air cleaning filter


[Silver-ionized air purifier filter
(MSZ-HJ25/35VA- ER2 ),
option (MSZ-HJ25/35VA- E2 ,
MSZ-HJ50VA- E2 , ER2 )] Horizontal vane
Air outlet
Heat exchanger

Remote control
Remote controller receiving section
Operation indicator lamp

Emergency operation switch

MSZ-HJ60VA MSZ-HJ71VA

Air inlet
Front panel

Air filter

Air cleaning filter


(Silver-ionized air purifier filter,
option) (MSZ-HJ60/71VA- E2 )

Horizontal vane
Heat exchanger
Air outlet

Remote control
receiving section
Remote controller
Operation indicator lamp

Emergency operation switch

ACCESSORIES
Installation plate 1
Installation plate fixing screw 4 × 25 mm 5
Battery (AAA) for remote controller 2
Wireless remote controller 1
Felt tape (Used for left or left-rear piping) 1
4
OBH647G
3 SPECIFICATION

Indoor model MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA


Power supply Single phase 230 V, 50 Hz
Breaker Capacity A 10 12
Cooling 730 1,040 2,050
Power input 1 (Total) W
Heating 870 995 1,480
Electrical data

Running current 1 Cooling 3.7 4.9 9.0


A
(Total) Heating 4.2 4.8 6.6
Cooling 85 92 99
Power factor 1 (Total) %
Heating 90 97
Starting current 1 (Total) A 4.2 4.9 9.0
Model RC0J40-EF
Fan motor

Cooling 0.19 0.24 0.27


Current 1 A
Heating 0.20 0.22 0.34
Dimensions W × H × D mm 799 × 290 × 232
Weight kg 9
Air direction 5
Super High 571 654 772
Cooling

High 438 470 667


m3/h
Med. 328 341 547
Airflow

Low 227 380


Super High 598 619 861
Heating

High 451 667


m3/h
Med. 328 497
Low 208 364
Super High 43 45
Cooling

High 37 38 40
Special remarks

dB(A)
Med. 30 31 36
Sound level

Low 22 28
Super High 43 44 47
Heating

High 37 41
dB(A)
Med. 30 34
Low 23 27
Super High 1,080 1,200 1,120
Cooling

High 880 930 1,000


rpm
Med. 710 730 860
Fan speed

Low 550 660


Super High 1,120 1,150 1,220
Heating

High 900 1,000


rpm
Med. 710 800
Low 520 640
Fan speed regulator 4
Remote controller model MP13A ( E1 , ER1 ) / MS16B ( E2 , ER2 )

NOTE : Test conditions are based on ISO 5151.


Cooling : Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Heating : Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
1 Measured under rated operating frequency.

Specifications and rated conditions of main electric parts


Fuse (F11) T3.15AL250V
Horizontal vane motor (MV) 12 VDC
Varistor (NR11) S10K300E2K1 (ERZV10D471)
Terminal block (TB) 5P

5
OBH647G
Indoor model MSZ-HJ60VA MSZ-HJ71VA
Power supply Single phase 230 V, 50 Hz
Breaker Capacity A 16
Cooling 1,900 2,330
Power input 1 (Total) W
Heating 1,970 2,440
Electrical data

Running current 1 Cooling 8.4 10.3


A
(Total) Heating 8.7 10.8
Cooling 98
Power factor 1 (Total) %
Heating 98
Starting current 1 (Total) A 8.7 10.8
Model RC0J30-MD
Fan motor

Cooling 0.49
Current 1 A
Heating 0.49
Dimensions W × H × D mm 923 × 305 × 250
Weight kg 13
Air direction 5
Super High 1,192
Cooling

High 900
m3/h
Med. 729
Airflow

Low 555 598


Super High 1,192
Heating

High 957 981


m3/h
Med. 752 763
Low 565 619
Super High 50
Cooling

High 44
Special remarks

dB(A)
Med. 38
Sound level

Low 31 33
Super High 49
Heating

High 44
dB(A)
Med. 38
Low 31 33
Super High 1,250
Cooling

High 1,000
rpm
Med. 850
Fan speed

Low 690 730


Super High 1,250
Heating

High 1,050 1,070


rpm
Med. 870 880
Low 700 750
Fan speed regulator 4
Remote controller model MP14B ( E1 ) / MS16B ( E2 )

NOTE : Test conditions are based on ISO 5151.


Cooling : Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C
Heating : Indoor Dry-bulb temperature 20°C
Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C
1 Measured under rated operating frequency.

Specifications and rated conditions of main electric parts


Fuse (F11) T3.15AL250V
Horizontal vane motor (MV) 12 VDC
Varistor (NR11) S10K300E2K1 (ERZV10D471)
Terminal block (TB) 5P

6
OBH647G
4 NOISE CRITERIA CURVES
MSZ-HJ25VA MSZ-HJ35VA

FAN SPEED FUNCTION SPL(dB(A)) LINE FAN SPEED FUNCTION SPL(dB(A)) LINE
COOLING 43 COOLING 45
Super High Super High
HEATING 43 HEATING 44

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
NC-20 NC-20
NC-10 NC-10

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

MSZ-HJ50VA
FAN SPEED FUNCTION SPL(dB(A)) LINE Test conditions
Cooling : Dry-bulb temperature 27°C Wet-bulb temperature 19°C
COOLING 45 Heating : Dry-bulb temperature 20°C
Super High
HEATING 47

90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

INDOOR UNIT
80 WALL
1m
70
NC-70
0.8m

60
NC-60 MICROPHONE

50
NC-50

40
NC-40

30
NC-30

20
NC-20
NC-10

10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz

7
OBH647G
MSZ-HJ60VA MSZ-HJ71VA
FAN SPEED FUNCTION SPL(dB(A)) LINE FAN SPEED FUNCTION SPL(dB(A)) LINE
COOLING 50 COOLING 50
Super High Super High
HEATING 49 HEATING 49

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 20
NC-20 NC-20
NC-10 NC-10

10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

Test conditions
Cooling : Dry-bulb temperature 27°C Wet-bulb temperature 19°C
Heating : Dry-bulb temperature 20°C

INDOOR UNIT
WALL
1m

0.8m

MICROPHONE

8
OBH647G
5 OUTLINES AND DIMENSIONS
MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA Unit : mm
11×26 Oblong hole
11×20 Oblong hole
Installation plate

21.5
80.5 225 225 80.5
Indoor unit
799
785 7

206.5
207.5
249

248
41
46
167 157

42
3
61.5 338 340 59.5
Wall hole Ø65
5 232 Air in

Installation plate

Piping

290
69

57
100
14
7
41 42 Drain hose
103
49 630 120

(5

130

)
57 18
Air out 172
42
43
140

MSZ-HJ25/35VA
69 57 Insulation Ø35 O.D
Piping

Liquid line Ø7 - 0.39m (Flared connection Ø6.35)


80 Gas line Ø9.52 - 0.34m (Flared connection Ø9.52)
Drain hose Insulation Connected part Ø16 O.D active length 370
MSZ-HJ50VA
Insulation Ø37 O.D
Piping

Liquid line Ø7 - 0.39m (Flared connection Ø6.35)


Gas line Ø9.52 - 0.34m (Flared connection Ø12.7)
Drain hose InsulationØ29 Connected part Ø16 O.D active length 370

MSZ-HJ60VA MSZ-HJ71VA

MSZ-HJ60VA
Insulation Ø50 O.D
Piping

Liquid line Ø8 - 0.39m (Flared connection Ø6.35)


Gas line Ø12 - 0.34m (Flared connection Ø15.88)
Drain hose Insulation Connected part Ø16 O.D
MSZ-HJ71VA
Insulation Ø50 O.D
Piping

Liquid line Ø8 - 0.39m (Flared connection Ø9.52)


Gas line Ø12 - 0.34m (Flared connection Ø15.88)
Drain hose Insulation Connected part Ø16 O.D
9
OBH647G
6 WIRING DIAGRAM

MSZ-HJ25VA - E1 , ER1 MSZ-HJ35VA - E1 , ER1 MSZ-HJ50VA - E1 , ER1

MSZ-HJ25VA - E2 , ER2 MSZ-HJ35VA - E2 , ER2 MSZ-HJ50VA - E2 , ER2

10
OBH647G
MSZ-HJ60VA - E1 , ER1 MSZ-HJ71VA - E1 , ER1

MSZ-HJ60VA - E2 MSZ-HJ71VA - E2

11
OBH647G
7 REFRIGERANT SYSTEM DIAGRAM
MSZ-HJ25VA MSZ-HJ35VA Unit : mm

Refrigerant pipe ø9.52


(with heat insulator)

Indoor coil
Indoor thermistor
heat RT12
exchanger Flared connection

Indoor coil
thermistor
RT13

Room temperature
thermistor
RT11

Flared connection

Refrigerant pipe ø6.35


(with heat insulator)

Refrigerant flow in cooling


Refrigerant flow in heating

MSZ-HJ50VA

Refrigerant pipe ø12.7


(with heat insulator)

Indoor coil
Indoor thermistor
heat RT12
exchanger Flared connection

Indoor coil
thermistor
RT13

Room temperature
thermistor
RT11

Flared connection

Refrigerant pipe ø6.35


(with heat insulator)

Refrigerant flow in cooling


Refrigerant flow in heating

12
OBH647G
MSZ-HJ60VA MSZ-HJ71VA Unit : mm

Refrigerant pipe ø15.88


(with heat insulator)

Indoor coil
Indoor thermistor
heat RT12
exchanger Flared connection

Indoor coil
thermistor
RT13

Room temperature
thermistor
RT11

Flared connection

Refrigerant pipe ø6.35 (MSZ-HJ60VA)


ø9.52 (MSZ-HJ71VA)
(with heat insulator)
Refrigerant flow in cooling
Refrigerant flow in heating

13
OBH647G
8 SERVICE FUNCTIONS

MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA MSZ-HJ60VA MSZ-HJ71VA


8-1. TIMER SHORT MODE
For service, the following set time can be shortened by bridging the timer short mode point on the electronic control P.C.
board. (Refer to 10-7.)
Set time : 3-minute → 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by bridging the timer short mode point.)
NOTE: While the relay 52C is ON, the compressor starting time cannot be shortened.
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :

J1 J2

NOTE : For modification, take out the batteries


and press the OPERATE/STOP (ON/
OFF) (HJ·VA- E1 , ER1 ) / STOP/
OPERATE (OFF/ON) (HJ·VA- E2 , ER2 )
button 2 or 3 times at first.
After finish modification, put back the
batteries then press the RESET button.

The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.

Table 1
1 unit operation 2 units operation 3 units operation 4 units operation
No. 1 unit No modification Same as at left Same as at left Same as at left
No. 2 unit – Solder J1 Same as at left Same as at left
No. 3 unit – – Solder J2 Same as at left
No. 4 unit – – – Solder both J1 and J2
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote
controller for the indoor unit.
The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are
set.
The setting will be cancelled if the breaker is turned OFF, or the power supply is shut down.
Please conduct the above setting once again after the power has been restored.

14
OBH647G
8-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in
the same mode just before the shutoff of the main power.
Operation
If the main power has been cut, the operation settings remain.
After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to disable “AUTO RESTART FUNCTION”
Turn off the main power for the unit.
Cut the Jumper wire to JR77 on the indoor electronic control P.C. board. (Refer to 10-7.)

Indoor electronic

CN111
control P.C. board
CN151

CN112
JR77

CN110

CN10A

NOTE:
• The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
• If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
• If the unit has been turned OFF with the remote controller before power failure, the auto restart function does not work
as the power button of the remote controller is off.
• To prevent the breaker from tripping OFF due to the rush of starting current, systematize other home appliance not to
turn ON at the same time.
• When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.

15
OBH647G
9 MICROPROCESSOR CONTROL

MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA MSZ-HJ60VA MSZ-HJ71VA

WIRELESS REMOTE CONTROLLER


MSZ-HJ25/35/50VA- E1 , ER1

Signal transmitting section

Operation display section

OPERATE/STOP (ON/OFF) button

Fan speed control button Temperature buttons

ECONO COOL button

Operation select button Vane control button

Timer mode select button


Time set buttons

RESET button

MSZ-HJ60/71VA- E1 , ER1

Signal transmitting section

Operation display section

OPERATE/STOP (ON/OFF) button

Fan speed control button Temperature buttons

ECONO COOL button

Operation select button Vane control button

Timer mode select button


Time set buttons

RESET button

NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the
remote controller with beeps.

16
OBH647G
MSZ-HJ25/35/50VA- E2 , ER2 MSZ-HJ60/71VA- E2

Signal transmitting section

Operation display section

STOP/OPERATE (OFF/ON) button

Fan speed control button Temperature buttons

ECONO COOL button

Operation select button Vane control button

Timer mode select button


Time set buttons

RESET button

NOTE: Last setting will be stored after the unit is turned OFF with the remote controller. Indoor unit receives the signal of the
remote controller with beeps.
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
•The following indication applies regardless of shape of the indication.

Indication Operation state Room temperature

The unit is operating to About 2°C or more away Lighted


reach the set temperature. from set temperature
Blinking
The room temperature is Not lighted
About 1 to 2°C from set
approaching the set tem- temperature
perature.
Standby mode
(Only during multi system -
operation)
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.

1. Coil frost prevention


The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works. The indoor fan
operates at the set speed and the compressor stops. This mode continues until the temperature of indoor heat exchanger
rises.
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.

1. Coil frost prevention


Coil frost prevention works the same way as that in COOL mode. (9-1.1.)
17
OBH647G
9-3. HEAT ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.

1. Cold air prevention control


When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-
perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-
densing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor
heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
9-4. AUTO VANE OPERATION
1. Horizontal vane
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of
the motor are controlled by pulse signals (approximately 12 V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL button.

AUTO 1 2 3 4 5 SWING

(3) Positioning
To confirm the standard position, the vane moves until it touches the vane stopper. Then the vane is set to the selected
angle.
Confirmation of standard position is performed in the following cases:
(a) When the operation starts or finishes (including timer operation).
(b) When the test run starts.
(c) When standby mode (only during multi system operation) starts or finishes.

(4) VANE AUTO ( ) mode


In VANE AUTO mode, the microprocessor automatically determines the vane angle to make the optimum room tempera-
ture distribution.
In COOL and DRY operation In HEAT operation
Vane angle is fixed to Horizontal position. Vane angle is fixed to Angle 4.

Horizontal
position

(5) STOP (operation OFF) and ON TIMER standby


In the following cases, the horizontal vane returns to the closed position.
(a) When OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button is
pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When ON TIMER is ON standby.
(6) Dew prevention
During COOL or DRY operation with the vane angle at Angle 3 ~ 5 when the compressor cumulative operation time
exceeds 1 hour, the vane angle automatically changes to Angle 2 for dew prevention.
(7) SWING ( ) mode
By selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically.

18
OBH647G
(8) Cold air prevention in HEAT operation.
The horizontal vane position is set to Upward.
NOTE: When 2 or more indoor units are operated with multi outdoor unit, even if any indoor unit turns thermostat off,
this control does not work in the indoor unit.
(9) ECONO COOL ( ) operation (ECONOmical operation)
When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher.
Also the horizontal vane swings in various cycle.
SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher, the air
conditioner can keep comfort. As a result, energy can be saved.
ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is
pressed or change to other operation mode.

9-5. TIMER OPERATION (ON/OFF TIMER)


1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button to start
the air conditioner.
(2) Select the timer mode by pressing the button during operation.
Each time this button is pressed, the timer mode is changed in sequence:
(OFF TIMER) → (ON TIMER) → TIMER RELEASE
(3) Set the time of the timer using the button.
Each time this button is pressed, the set time increase or decrease by 1 hour to 12 hours.

2. To release the timer


Press the button until (OFF TIMER) and (ON TIMER) are not displayed.

NOTE :
• The OFF TIMER and the ON TIMER cannot be set at the same time.
• The displayed time is the time remaining and will decrease in 1-hour increments as time passes.
9-6. EMERGENCY/TEST OPERATION
In the case of test run operation or emergency operation, use the emergency operation switch on the right side of the
indoor unit. Emergency operation is available when the remote controller is missing or has failed, or when the batteries in
the remote controller are running down. The unit will start and OPERATION INDICATOR lamp will light up.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan runs at High
speed and the temperature control does not work.
After 30 minutes of test run operation, the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of
24°C. The fan speed shifts to Med.
The coil frost prevention works even in the test run or the emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode.
Emergency operation continues until the emergency operation switch is pressed once or twice or the unit receives any
signal from the remote controller. In the latter case, normal operation will start.

NOTE: Do not press the emergency operation switch during normal operation.
Operation mode COOL HEAT
Set temperature 24°C 24°C
Fan speed Med. Med.
Horizontal vane Auto Auto
The operation mode is indicated by the
Operation Indicator lamp as follows:

Operation Indicator lamp


Emergency operation switch
EMERGENCY COOL
↓ Lighted
Not lighted
EMERGENCY HEAT

STOP

9-7. 3-MINUTE TIME DELAY OPERATION


When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect
compressor from overload.

19
OBH647G
10 TROUBLESHOOTING

MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA MSZ-HJ60VA MSZ-HJ71VA


10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the P.C. board.
3) When removing the P.C. board, hold the edge of the board with care NOT to apply stress on the components.
4) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.

<Incorrect> <Correct>

Lead wiring Connector housing


3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is blinking ON and OFF to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is blinking ON and OFF before starting ser-
vice work.
2) Before servicing, verify that all connectors and terminals are connected properly.
3) When the electronic control P.C. board seems to be defective, check for disconnection of the copper foil pattern and
burnt or discolored components.
4) When troubleshooting, Refer to 10-2, 10-3 and 10-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
Remove the back lid and insert batteries. Press RESET button with a thin instrument, and
Then reattach the back lid. then use the remote controller.

Insert the minus pole of the


batteries first. Check if the polarity
of the batteries is correct.

NOTE: 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microprocessor when batteries are replaced.
This function is equipped to prevent the microprocessor from malfunctioning due to the voltage drop caused by the
battery replacement.
3. Do not use the leaking batteries.

20
OBH647G
10-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (10-4.) disappears, the memorized failure details can
be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
1. Flow chart of failure mode recall function for MSZ-HJ25/35/50- E1 , ER1 MSZ-HJ25/35/50- E2 , ER2
the indoor/outdoor unit
MSZ-HJ60/71- E1 , ER1 , E2

Operational procedure
The cause of abnormality cannot be found because the abnormality does not recur.

Setting up the failure mode recall function


Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators
on the LCD screen shown in the right figure are all displayed. Then release the but-
tons.

Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON)


(HJ·VA- E2 , ER2 ) button of the remote controller (the set temperature is displayed) with 1. Regardless of normal or abnormal condi-
the remote controller headed towards the indoor unit. 1 tion, a short beep is emitted once the signal
is received.
Does upper lamp of OPERATION INDICATOR
lamp on the indoor unit blink at the interval of 0.5 Indoor unit is normal.
seconds? But the outdoor unit might be abnormal because there are some abnor-
Blinks: Either indoor or outdoor unit is abnormal. No malities that cannot be recalled with this way.
Beep is emitted at the same timing as the Check if outdoor unit is abnormal according to the detailed outdoor unit
blinking of upper lamp of OPERATION (OFF)
failure mode recall function.
INDICATOR lamp. 2
Yes
Judgment of indoor/outdoor abnormality (Blinks)
Before blinking, does upper lamp of
OPERATION INDICATOR lamp stay ON for 3
seconds?
When it stays ON for 3 seconds (without beep): Yes
The outdoor unit is abnormal.
No
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by refer-
Check the blinking pattern, and identify the abnormal point by referring to the
ring to the outdoor unit failure recall mode table. (Refer to outdoor unit
indoor unit failure recall mode table. (Refer to 10-2.2)
service manual.)
Make sure to check at least 2 consecutive blinking cycles. 2
Make sure to check at least 2 consecutive blinking cycles. 3

Releasing the failure mode recall function


Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.

Repair the failure parts.

Deleting the memorized abnormal condition


After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" men-
tioned above.
Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button of the
remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
Press the emergency operation switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2. Blinking pattern when the indoor unit is abnormal:

Blinking at 0.5- Blinking at 0.5-


2.5-second OFF second interval 2.5-second OFF second interval
ON
OFF
Beeps Beeps Beeps
Repeated cycle Repeated cycle Repeated cycle

3.Blinking pattern when the outdoor unit is abnormal:


Blinking at 0.5- Blinking at 0.5-
2.5-second OFF 3-second ON second interval 2.5-second OFF 3-second ON second interval
ON
OFF
No beep Beeps No beep Beeps
Repeated cycle Repeated cycle Repeated cycle

21
OBH647G
NOTE : Blinking patterns of this mode differ from the ones of
2. Indoor unit failure recall mode table TROUBLESHOOTING CHECK TABLE (10-4.).
Upper lamp of OP-
Abnormal point
ERATION INDICA- Condition Remedy
(Failure mode)
TOR lamp
Not lighted Normal — —
The room temperature thermistor short or
1-time blink every Room temperature Refer to the characteristics of the room temperature
open circuit is detected every 8 seconds dur-
0.5-second thermistor thermistor (10-7.).
ing operation.
2-time blink Indoor coil The indoor coil thermistor short or open circuit Refer to the characteristics of the main indoor coil ther-
2.5-second OFF thermistor is detected every 8 seconds during operation. mistor, the sub indoor coil thermistor (10-7.).
3-time blink The serial signal from outdoor unit is not re- Refer to 10-6. "How to check miswiring and serial
Serial signal
2.5-second OFF ceived for a maximum of 6 minutes. signal error".
The rotational frequency feedback signal is not
11-time blink
Indoor fan motor emitted for the 12 seconds after the indoor fan Refer to 10-6. "Check of indoor fan motor".
2.5-second OFF
motor is orperated.
It cannot properly read data in the nonvolatile
12-time blink Indoor control
memory of the indoor electronic control P.C. Replace the indoor electronic control P.C. board.
2.5-second OFF system
board.

22
OBH647G
10-3. INSTRUCTION OF TROUBLESHOOTING
*2 There is possibility that diesel explosion may occur due to the air mixied in the refrigerant circuit.
First, ensure that there are no leakage points on the valves, flare connections, etc. that allow the
air to flow into the refrigerant circuit, or no blockage points (e.g. clogged or closed valves) in the
refrigerant circuit that cause an increase in pressure.
If there is no abnormal point like above and the system operates cooling and heating modes nor-
mally, the indoor thermistor might have a problem, resulting in false detection.
Start Check both the indoor coil thermistor and the room temperature thermistor, and replace faulty
thermistor(s), if any.
(Do not start the operation again without repair to prevent hazards.)

Indoor unit operates. Indoor unit does


Indoor unit operates. OPERATION INDICATOR
Outdoor unit does not receive the
Outdoor unit does lamp on the indoor unit is
not operate. signal from remote
not operate normally. blinking on and off.
controller.

If blinking of OPERATION INDI-


CATOR lamp cannot be checked,
it can be checked with failure
Outdoor unit Outdoor unit Unit does not Indoor unit Indoor unit does mode recall function.
operates only does not operate nor- operates, when not operate, when
in Test Run operate even mal operation the emergency the emergency
operation. *1 in Test Run in COOL or operation switch operation switch
operation. *1 HEAT mode. is pressed. is pressed.

*1 "Test Run operation" means


the operation within 30 minutes
Check room Refer to "How Refer to Refer to 10-6. 1. Check indoor/out- after the emergency operation
temperature to check "Check of R.V. "Check of remote door connecting wire. switch is pressed.
thermistor. inverter/com- coil". controller and (Check if the power is
Refer to 10-7. pressor". indoor electronic supplied to the indoor
"Test point control P.C. unit.)
diagram and board". 2. Refer to 10-6. "Check
voltage". of indoor P.C. board
and indoor fan motor". Refer to outdoor unit service manual.

Upper lamp Upper lamp Upper lamp Upper lamp Upper lamp Upper lamp Upper lamp Upper lamp
Blink on and 2-time blink 3-time blink 4-time blink 5-time blink 6-time blink 7-time blink 14-time blink
off at 0.5-sec- Cause: Cause: Cause: Cause: Cause: Cause: or more
ond intervals Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Outdoor unit Cause:
Cause: • Trouble • Trouble of • Trouble • Outdoor • Trouble of • Trouble of Outdoor unit
Indoor/Outdoor of room indoor fan of indoor power sys- thermistor in outdoor con- • Other ab-
unit temperature motor unit control tem abnor- outdoor unit trol system normality
• Miswiring or / indoor coil system mality Indoor/Out-
trouble of thermistor door unit
serial signal • Trouble of
thermistors

*2
Refer to 10- Check room Refer to 10- Replace the Refer to Refer to Replace the • Check "Flow
6. "How to temperature 6. "Check indoor elec- "How to "Check of inverter P.C. chart of the
check mis- thermistor of indoor fan tronic control check outdoor ther- board or detailed
wiring and and indoor motor". P.C. board. inverter/com- mistors". the outdoor outdoor unit
serial signal coil thermis- pressor". electronic failure mode
error". tor. Refer to control P.C. recall func-
10-7."Test board. tion."
point diagram • Check
and voltage". thermistors.
Refer to
"Test point
diagram and
voltage" in
the service
manual of
indoor and
outdoor unit.
23
OBH647G
10-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after
the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp blinks.

OPERATION INDICATOR
Lighted
Blinking
Not lighted

Abnormal
No. Operation indicator lamp Symptom Condition Remedy
point

Upper lamp blinks.


0.5-second ON
Miswiring • Refer to 10-6. "How to check
1 or serial The serial signal from the outdoor unit is not miswiring and serial signal er-
signal received for 6 minutes. ror".
0.5-second OFF

Upper lamp blinks.


Indoor coil 2-time blink
thermistor • Refer to the characteristics of
The indoor coil or the room temperature ther- indoor coil thermistor, and the
2 mistor is short or open circuit. room temperature thermistor
Room tem-
perature (10-7.).
2.5-second OFF
thermistor
Upper lamp blinks.
3-time blink
Indoor fan The rotational frequency feedback signal is • Refer to 10-6. "Check of
3 motor not emitted during the indoor fan operation. indoor fan motor".
2.5-second OFF

Upper lamp blinks.


4-time blink
Indoor con- It cannot properly read data in the nonvolatile
4 memory of the indoor electronic control P.C. • Replace the indoor electronic
trol system control P.C. board.
board.
2.5-second OFF

Upper lamp blinks.


5-time blink Indoor unit and • Refer to "How to check of in-
Outdoor outdoor unit do It consecutively occurs 3 times that the com- verter/compressor".
5 power sys- not operate. pressor stops for overcurrent protection or Refer to outdoor unit service
tem start-up failure protection within 1 minute after manual
start-up.
2.5-second OFF • Check the stop valve.

Upper lamp blinks.


6-time blink
• Refer to "Check of outdoor
Outdoor The outdoor thermistors short or open circuit thermistor".
6 thermistors during the compressor operation. Refer to outdoor unit service
manual.
2.5-second OFF

Upper lamp blinks.


7-time blink • Replace the inverter P.C. board
Outdoor It cannot properly read data in the nonvolatile or the outdoor electronic con-
7 control sys- memory of the inverter P.C. board or the out- trol P.C. board.
tem door electronic control P.C. board. Refer to outdoor unit service
2.5-second OFF manual.

Upper lamp blinks. • Check the stop valve.


14-time blink or more • Check the 4-way valve.
• Confirm the abnormality in
An abnormality other than the above is de- detail using the failure mode
Other ab- tected. recall function for outdoor unit.
8 normality An abnormality of the indoor thermistors, the • Refer to "TEST POINT DIA-
*2 on 10-3 2.5-second OFF GRAM AND VOLTAGE" on the
defrost thermistor or ambient temperature service manual of indoor and
thermistor is detected. outdoor unit for the characteris-
tics of the thermistors. (Do not
start the operation again with-
out repair to prevent hazards.)

Outdoor Outdoor unit It cannot properly read data in the nonvolatile • Check the blinking pattern of
9 control sys- Upper lamp lights up the LED on the inverter P.C.
does not oper- memory of the inverter P.C. board or the out-
tem board or the outdoor electronic
ate door electronic control P.C. board. control P.C. board.

24
OBH647G
OPERATION INDICATOR

No. Abnormal Operation indicator lamp Symptom Condition Remedy


point
Upper lamp lights and lower lamp blinks.
The operation mode of the each indoor unit
MXZ type Outdoor unit
is differently set to COOL (includes DRY) and • Unify the operation mode.
Operation operates but
1 HEAT at the same time, the operation mode Refer to outdoor unit service
mode 2.5-second OFF indoor unit does
of the indoor unit that has operated at first has manual.
setting not operate.
the priority.

10-5. TROUBLESHOOTING CRITERION OF MAIN PARTS


MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA MSZ-HJ60VA MSZ-HJ71VA
Part name Check method and criterion Figure
Room temperature Measure the resistance with a tester.
thermistor (RT11)
Refer to 10-7. "Test point diagram and voltage", "2. Indoor electronic control
Indoor coil thermistor P.C. board", for the chart of thermistor.
(RT12, RT13)
Indoor fan motor (MF) Check 10-6. .
Measure the resistance between the terminals with a tester. SKY
(Part temperature 10 ~ 30°C) ROTOR
Color of the lead wire Normal SKY
RED
MSZ-HJ25/35/50VA RED - SKY 235 ~ 255 Ω
MSZ-HJ60/71VA RED - BLU 235 ~ 255 Ω SKY SKY

Vane motor (MV)


BLU
ROTOR
BLU
RED

BLU BLU

25
OBH647G
10-6. TROUBLESHOOTING FLOW

A Check of indoor fan motor

The indoor fan motor error has occurred, and the indoor fan does not operate.

Turn OFF the power supply. Pay enough attention to the high voltage on the fan motor connector CN211.

Turn ON the power supply, wait 5 seconds or more, and then press the
emergency operation switch.
Measure the supply voltage as follows within 12 seconds after the emer-
gency operation switch is pressed.
If more than 12 seconds passes, turn OFF the power supply and turn it
Is there any foreign matter that interferes
the rotation of the line flow fan? No ON again, then measure the voltage.
<Indoor power P.C. board>
1. Measure the voltage between CN211 (+) and (–).
Yes 2. Measure the voltage between CN211 (+) and (–).
<Indoor electronic control P.C. board>
3. Measure the voltage between CN10A (+) and GND (–).
Remove the foreign matter and
adjust the line flow fan. If more than 12 seconds passes after the emergency operation switch
is pressed, the voltage measured at 2. above goes 0 VDC although the
indoor P.C. board is normal.

Does the voltage between CN211


Is there 325 VDC (+) and (–) on the power P.C. board
between CN211 (+) rise to the range of 3 to 6 VDC within Replace the indoor fan motor.
Yes Yes
and (–) ? 12 seconds after the emergency
operation switch is pressed?
No
No

Does the voltage between CN10A


(+) and GND (–) on the indoor
Replace the indoor power electronic control P.C. board fall to Replace the indoor electronic
P.C. board. Yes 2 V or less within 12 seconds after No control P.C. board.
the emergency operation switch is
pressed?

The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.

Measure the voltage between CN211 Measure the voltage CN10A


Is it unchanged holding (+) and GND (–) on the indoor
(+) and (–) while the fan motor is
0 or 15 VDC? No electronic control P.C board when
rotating. (Changed) the fan motor is rotaring.
Yes
(Unchanged)

Replace the indoor fan motor.

Replace the indoor


Replace the indoor power P.C. Is it unchanged holding electronic control P.C.
board. Yes 0 or 5 VDC? No board.
(Unchanged) (Changed)

26
OBH647G
B Check of remote controller and indoor electronic control P.C. board

Check if the remote controller is exclusive for this air conditioner.

Press OPERATE/STOP (ON/OFF)


(HJ·VA- E1 , ER1 ) / STOP/OPERATE
(OFF/ON) (HJ·VA- E2 , ER2 ) button on
the remote controller.

Is LCD display on the remote controller 1 Look at the image of the signal transmitting section of
Replace the batteries. (Refer to 10-1.4.) the remote controller through the monitor of a digital
visible? No
(Not clear) camera or a camera phone. It is normal if the LED of
Yes the signal transmitting section lights up when the
OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/
Remove the batteries, then set them back OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button on the
and press RESET button. (Refer to 10-1.4.) remote controller is pressed. However, it may be difficult
Check if the unit operates with the remote to see the illuminated LED of the signal transmitting
controller. section with a smartphone camera.

2 If the inverter fluorescent light is turned on when the


Turn ON a radio to AM and press OPER- room is cool, the unit may have difficulty receiving the
Does the unit operate with the remote ATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / signal from the remote controller or may not be able to
controller? No STOP/OPERATE (OFF/ON) (HJ·VA- E2 , operate with it; if the inverter fluorescent light is turned
ER2 ) button on the remote controller. 1 on when the room is warm, the unit may be able to
Yes operate with the remote controller.

OK
Is noise heard from radio? Replace the remote controller.
No
Yes

Are there any fluorescent lights of


• Reinstall the unit away from lights.
inverter or rapid-start type within the
Yes • Attach a filter on receiving part.
range of 1 m? 2
No

Replace the indoor electronic control


P.C. board. (Including the receiver)

27
OBH647G
C Check of indoor P.C. board and indoor fan motor

Turn OFF the power supply.


Remove indoor fan motor connector CN211
from indoor power P.C. board and vane Measure the resistance of indoor fan
motor connector CN151 from the indoor Short circuit:
motor.
electronic control P.C. board and turn ON Replace the indoor fan motor.
Refer to 10-5.
the power supply.

Does the unit operate with the remote


controller? Measure the resistance of the vane Short circuit:
Does OPERATION INDICATOR lamp light motor coil. Replace the vane motor and the indoor
up by pressing the emergency operation Yes Refer to 10-5. electronic control P.C. board.
switch?
No

Replace the varistor (NR11)


and fuse (F11). 3

Yes
Is the varistor (NR11)
burnt and the fuse (F11)
blown? No
With a tester, check the
Turn OFF the power supply. Is electricity
Check both “parts side” and “pattern continuity between the Yes
Be sure to check both the fuse connector CN201 on the conducted? (The
side” of the indoor power P.C. board and the varistor in any case. resistance is 0 Ω .)
visually. indoor power P.C. board and
S2 on the terminal block. No
Is the fuse (F11) blown
only? No
Yes The thermal fuse connected
to the terminal block has
1. The fan motor connector's lead wire is red, failed.
whereas is black. Replace the terminal block
2. Connect "+" of the tester to fan motor Measure the resistance between assembly.
CN211 (+) and (-) of indoor fan
connector's lead wire, and “-” to lead wire, motor connector. 1, 2
otherwise the resistance cannot be measured
properly.
3. Please replace the fuse after removing the
indoor power P.C. board from the electrical
Is the resistance 1MΩ or more? Replace the fuse (F11) and the
box. indoor fan motor. 3
No
Yes

Replace the fuse (F11). 3

Replace the indoor


Measure the resistance of resistor (R111)/ Is the resistance of resistor (R111)/ power P.C. board, the
reactor (L111) on the indoor power P.C. indoor terminal P.C.
board. reactor (L111) approximately 4 Ω ? No board and the indoor fan
motor.

Yes

Is there approximately 5 VDC between


5 V (+) and GND (-) of the indoor
electronic control P.C. board? Is there Replace the indoor fan motor.
Indoor electronic control approximately 9 V to 13 VDC between Yes
P.C. board 12 V (+) and GND (-) of the indoor
electronic control P.C. board?
No
GND
Is the connector CN10A on
CN10A the indoor electronic control Connect the connector CN10A or repair
P.C. board or lead wires Yes disconnection.
disconnected?
No
12 VDC 5 VDC

Indoor power P.C. board Indoor power P.C. board Replace the indoor electronic control P.C. board.

R111

CN211

CN211
L111
MSZ-HJ25/35/50VA MSZ-HJ60/71VA

28
OBH647G
D How to check miswiring and serial signal error
Turn OFF the power supply.
MUZ-HJ type
Is there rated voltage in the
Check the power supply.
power supply? No
Yes
MSZ-HJ25/35/50- E1 , ER1
1. Turn ON the power supply.
2. Press the emergency operation switch.

No Has the relay 52C been turned on 3 minuets later ?


[The relay will be turned on in 3 to 7 seconds by
bridging the timer short mode point (Refer to 10-7.).]
Initializing the determination of the power Yes
receiving system
The microprocessor may have mistaken the
unit as a model receiving power from the
outdoor unit. Follow the procedure below to Has the miswiring or the serial error
start the determination of the power receiv- been indicated? No
ing system all over again.
1. Hold down the emergency operation Yes Indication of miswiring
switch for 30 seconds. (Do not release the Indication of serial signal error
switch even though a buzzer beeps once OPERATION
in about 5 seconds. Keep holding down INDICATOR lamp
the switch until a buzzer beeps again for Continuous blinks
1 second after 30 seconds. Figure 1)
Is there any miswiring, poor
2. Turn off the power supply.
contact, or wire disconnec- MSZ-HJ25/35/50- E2 , ER2
3. Wait for about 30 seconds. Correct them.
4. Turn on the power supply.
tion of the indoor/outdoor Yes MSZ-HJ60/71- E1 , ER1
connecting wire?
5. Press the emergency operation switch. MSZ-HJ60/71- E2
6. The relay 52C will be turned on in 3 min- No
utes.
A
Figure 1
Buzzer 0.5-second 1-second
ON Turn OFF the power supply. Make sure again that the
indoor/outdoor connecting wire is correctly connected.
With the indoor/outdoor connecting wire connected, bridge
OFF between S2 and S3 on the outdoor terminal block. 1
Beeps Beeps Beeps <Preparation of the remote controller>
While pressing both OPERATION SELECT button and
Emergency B TOO COOL button on the remote controller at the same
operation switch time, press RESET button.
First, release RESET button.
ON Hold down the other two buttons for another 3 seconds.
Make sure that the indicators on the LCD screen shown in
OFF the right figure are all displayed. Then release the buttons.
5-second (Setting up the failure mode recall function)

ON 30-second OFF Aim the remote controller at the indoor unit, and press
OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/ 1 Make sure that the wiring is correct. If the pro-
OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button. The relay 52C cedure is performed without correcting miswir-
will be turned on, and the outdoor unit will be energized. ing, it may lead to damage to the P.C. board.

Is the rated supply voltage applied Is there any problem in the Replace
between the S1 and S2 on the indoor/outdoor connecting wire, the indoor/
A such as the damage of the wire, outdoor con-
outdoor terminal block? (Check of intermediate connection, poor
No necting wire.
supply voltage) contact with the terminal block? Yes
• Turn OFF inverter-controlled lighting Yes
No
equipment.
• Turn OFF the power supply and then Is there approximately 250 VDC – 370
turn ON again. VDC between DB61 (+) and DB61 Replace the
• Press the emergency operation switch. inverter P.C.
(–) on the inverter P.C. board in the board in the
outdoor unit? (Voltage check of the No outdoor unit. 2
inverter P.C. board in the outdoor unit)
After the relay • Reinstall ei- 2 Be careful of 140
52C is turned on ther the unit Yes
or the light VDC – 280 VDC
3 minutes later, is
miswiring or the away from residual charge in
serial signal error No each other. the capacitor on the
indicated? • Attach a filter Does the LED on the inverter P.C. main inverter circuit.
on remote board in the outdoor unit repeat
Yes control "3.6-second-OFF and 0.8-second-
receiving ON quick blinking" for 3 minutes Replace the
section of after the outdoor unit is energized? inverter P.C.
B the indoor (Check the blinking pattern within 3 board in the
unit. No
minutes after LED is turned on. Af- outdoor unit. 2
ter 3 minutes, LED will blink 6 times
whether the inverter P.C. board in
the outdoor unit is normal or not.)
Yes
Replace the indoor electronic control
P.C. board. 3
3 Be sure to release the failure-mode recall function after checking.

29
OBH647G
MXZ type

Turn ON the breaker.


LED indication for communication status

Communication status is indicated by the LED.


Is there rated voltage
Unit status Check the power supply
between outdoor
Blinking: normal communication terminal block S1 and S2? No and correct the problem.
Lighted: abnormal communication or not connected
Not lighted: The outdoor P.C. board is abnormal. Yes
NOTE: "Lighted" and "Not lighted" in the table below
does not indicate abnormal. Replace the indoor *1 Turn OFF the breaker before
Press the emergency electronic control replacing the indoor electronic
operation switch once. P.C. board. *1
MXZ-2HJ40VA control P.C. board.
Outdoor display P.C. board Refer to indoor unit service manual.
LED1 LED2
Does the OPERATION Is there rated
INDICATOR lamp light voltage between Check the indoor/outdoor
up? <Confirmation of outdoor terminal connecting wire and
LED 1 LED 2 No No correct the problem.
Unit A Unit B the power to the indoor block S1 and S2?
status status unit>
Yes A
If the trouble sometimes occurs,
possible causes are as follows:
Is serial signal error
MXZ-3HJ50VA A • Poor connection of the indoor/
indicated 6 minutes
Outdoor control P.C. board No outdoor connecting wire
later?
Check for intermediate connection of
LED3 LED2 LED1 Yes the indoor/outdoor connecting wire,
loose connection to the terminal block,
and cut wire inside the cable.
Blinking Is there any miswiring, If any of them is found, correct the
poor contact, or wire problem(s).
Pattern LED 3 LED 2 LED 1 disconnection of the Check the indoor/outdoor
• Effects of the inverter lighting
Unit B Unit A indoor/outdoor connecting wire and on the indoor unit
1 Lighted Yes
status status connecting wire? correct the problem. If the trouble occurs or does not occur
2 Not lighted Unit D Unit C depending on whether the light is on
status status or off, distance the lighting from the
No indoor unit or apply the glass filter on
the receiving part of the indoor unit.
• Noise on the indoor/outdoor
Turn OFF the breaker. connecting wire
Pass the indoor/outdoor connecting
wire through a different route if the
Remove the indoor/out- existing wiring is arranged as below:
door connecting wire from
the outdoor terminal block • The indoor/outdoor connecting wire
connected with the indoor runs near the power supply cable of
unit on which miswiring or other equipment.
the serial signal error is • The indoor/outdoor connecting wire
indicated. Short-circuit is detoured and run long.
between S2 and S3 of the
outdoor terminal block .

Turn ON the breaker. *2 The LED indicates the status of serial communication.
Check the communication status.

Does the LED on the


outdoor display P.C. Replace the indoor
board or the outdoor control Yes electronic control
P.C. board. *1 *4
P.C. board repeat quick
BLINKING and OFF? *2
No (Lighted or
not lighted)
*1 Turn OFF the breaker before replacing the indoor electronic control
Replace the inverter P.C. P.C. board.
board or the outdoor control Refer to indoor unit service manual.
P.C. board. *3 *4 *3 Turn OFF the breaker before replacing the inverter P.C. board.
Be careful of residual voltage of smoothing capacitor.
*4 Remove the short-circuit between outdoor terminal block
S2 and S3. Connect the indoor/outdoor connecting wire.

30
OBH647G
E Electromagnetic noise enters into TV sets or radios

Is the unit earthed? Earth the unit.


No
Yes

Is the distance between the antennas


Extend the distance between the antennas and
and the indoor unit within 3 m, or is the
the indoor unit, and/or the antennas and the
distance between the antennas and the Yes outdoor unit.
outdoor unit within 3 m?
No

Is the distance between the TV sets or


Extend the distance between the TV sets and/or
radios and the indoor unit within 1 m, or
radios and the indoor unit, or the TV sets or
is the distance between the TV sets or Yes radios and the outdoor unit.
radios and the outdoor unit within 3 m?
No

Are the antennas damaged?


Is the coaxial cable damaged? Replace or repair the antenna.
Is there any poor contact in the anten- Yes Replace or repair the coaxial cable.
na wiring?
No

Is the indoor/outdoor connecting wire Extend the distance between the indoor/outdoor
of the air conditioner and the wiring of connecting wire of the air conditioner and the wir-
the antennas close? Yes ing of the antennas.
No

Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength
or the installation condition (combination of specific conditions such as antennas or wiring).
Check the following before asking for service.
1. Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ;
indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric field intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifier such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic
noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/
OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button on the remote controller for power ON, and check for the electromag-
netic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the
electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) (HJ·VA- E1 , ER1 ) / STOP/OPERATE (OFF/ON) (HJ·VA- E2 , ER2 ) button on the
remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In
this situation, check for the electromagnetic noise.

31
OBH647G
10-7. TEST POINT DIAGRAM AND VOLTAGE
MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA
1. Indoor power P.C. board
Connector to
Fuse (F11) Terminal block
T3.15AL250V (CN201) Varistor (NR11) Resistor (R111)

Connector to
Indoor fan motor
(CN211)
(+)0 or 15 VDC
(+)3-6 VDC
15 VDC
(-) GND
(High voltage DC)
325 VDC

12V
5V
GND

Indoor terminal block 12 VDC GND 5 VDC


connecting (TAB1) Connector to indoor electronic
Indoor terminal block control P.C. board (CN20A)
connecting (TAB2)
2. Indoor electronic control P.C. board
Room temperature thermistor RT11 (CN111)
To disable "Auto restart function",
cut the Jumper wire to JR77.
(Refer to 8-3.)

Connector to
Vane motor Indoor coil
(CN151) thermistor
RT12, RT13 Room temperature thermistor (RT11)
(CN112) Indoor coil thermistor (RT12, RT13)
Timer short
mode point
(Refer to
8-1.)
Resistance (kΩ)

GND

5V DC

Emergency operation 12V DC Connector to indoor power Temperature (°C)


switch (E.O. SW) (SW1) P.C. board (CN10A)
32
OBH647G
MSZ-HJ60VA MSZ-HJ71VA
1. Indoor power P.C. board
12 VDC Connector to indoor electronic 5 VDC Indoor terminal block Indoor terminal block
control P.C. board (CN20A) connecting (TAB2) connecting (TAB1)

12V

Connector to
Terminal block

5V
(CN201)

GND

Fuse (F11)
T3.15AL250V
Varistor (NR11)

GND Connector to Indoor fan


motor (CN211)
Reactor (L111)
325 VDC
(+)0 or 15 VDC
(-) GND
(+)3-6 VDC
(High voltage DC)
15 VDC

2. Indoor electronic control P.C. board


Room temperature thermistor RT11 (CN111)
To disable "Auto restart function",cut the
Jumper wire to JR77. (Refer to 8-3.)

Connector to
Vane motor Indoor coil
(CN151) thermistor
RT12, RT13 Room temperature thermistor (RT11)
(CN112) Indoor coil thermistor (RT12, RT13)
Timer short
mode point
(Refer to
8-1.)
Resistance (kΩ)

GND

5V DC

Emergency operation 12V DC Connector to indoor power Temperature (°C)


switch (E.O. SW) (SW1) P.C. board (CN10A)
33
OBH647G
11 DISASSEMBLY INSTRUCTIONS

<"Terminal with locking mechanism" Detaching points>


The terminal which has the locking mechanism can be detached as shown below.
There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Sleeve

Slide the sleeve. Hold the sleeve, and


Pull the terminal while pull out the terminal
Locking lever pushing the locking slowly.
lever.
Connector

11-1. MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA


: Indicates the visible parts in the photos/figures.
: Indicates the invisible parts in the photos/figures.
NOTE: Turn OFF the power supply before disassembly.

OPERATING PROCEDURE PHOTOS


1. Removing the panel Photo 1
(1) Remove the screw caps on the panel and remove the Front panel
screws of the panel. Horizontal vane
(2) Pull the panel slightly toward you, and then remove the
panel by pushing it upward.

Screws of the panel

34
OBH647G
OPERATING PROCEDURE PHOTOS
2. Removing the indoor power P.C. board and the Photo 2
electrical box Earth wire
(1) Remove the panel. (Refer to section 1.) Remove the right
corner box.
(2) Disconnect the following connectors:
<Indoor electronic control P.C. board>
Screw of the
CN151 (Vane motor) electrical cover
CN112 (Indoor coil thermistor)
CN10A (To the indoor power P.C. board) Screw of the
V.A. clamp
(3) Unhook the catch on the left side of the control P.C. Vane motor
board holder. Pull the control P.C. board holder as if connector CN151
opening the door at 90 degrees. Remove the control P.C.
board holder from the axial rod on the electrical box. Indoor coil ther-
(4) Remove the screw of the V.A. clamp. mistor connec-
(5) Remove the V.A. clamp and the indoor/outdoor connect- tor CN112
ing wire.
Connector CN10A
(6) Remove the earth wire connected to the indoor heat
(To indoor power
exchanger from the electrical box.
P.C. board)
(7) Remove the screw of the electrical cover and remove the
electrical cover. Indoor electronic control Control P.C. board holder
(8) Disconnect the following connectors: P.C. board
<Indoor power P.C. board>
CN211 (Indoor fan motor) Photo 3
CN201, TAB1, TAB2 (Terminal block)
TAB2 (Terminal block)
CN20A (To the indoor electronic control P.C. board) Electrical box
TAB1 (Terminal block)
(9) Remove the upper catch of the electrical box, and pull Terminal block
out the electrical box. connector CN201
To attach the electrical box, pass the wires connecting
Indoor fan motor
the indoor power P.C. board and the indoor electronic connector CN211
control P.C. board through A. Pass the lead wires of the
fan motor through B as shown in the Photo 3.
Connector CN20A
(To indoor elec-
tronic P.C. board)
Power P.C. board

35
OBH647G
OPERATING PROCEDURE PHOTOS
3. Removing the indoor electronic control P.C. Photo 4
board Control P.C. board holder (Inside)
(1) Remove the panel. (Refer to section 1.) Remove the right
corner box. Catch
(2) Disconnect the following connectors: Indoor electronic
<Indoor electronic control P.C. board> control P.C. board
CN151 (Vane motor)
CN112 (Indoor coil thermistor)
CN10A (To the indoor power P.C. board)

(3) Unhook the catch on the left side of the control P.C.
board holder. Pull the control P.C. board holder as if
opening the door at 90 degrees. Remove the control P.C.
board holder from the axial rod on the electrical box.
(4) Remove the room temperature thermistor from the back
side of the control P.C. board holder.
(5) Unhook the catches of the control P.C. board holder, and
open the control P.C. board holder.
(6) Remove the indoor electronic control P.C. board from the Catch
control P.C. board holder.

Control P.C. board holder (Back side)

Room temperature thermistor

4. Removing the vane motor


(1) Remove the panel. (Refer to section 1.) Remove the Photo 5
corner box.
(2) Remove the control P.C. board holder and the electrical
box. (Refer to section 2.)
(3) Pull out the drain hose from the nozzle assembly and
remove the nozzle assembly.
(4) Remove the screws of the vane motor and remove the
vane motor.
(5) Disconnect the connector from the vane motor.

Screws of the
vane motor

36
OBH647G
OPERATING PROCEDURE PHOTOS
5. Removing the indoor fan motor, the indoor coil Photo 6
thermistor and the line flow fan
(1) Remove the panel. (Refer to section 1.) Remove the
corner box.
(2) Remove the control P.C. board holder, the electrical box
and the nozzle assembly. (Refer to section 2.)
(3) Remove the screws fixing the motor bed.
(4) Disengage the hooks of the water cover and remove
the water cover.
(5) Disconnect the earth wire from the motor band.
(6) Remove the indoor coil thermistor from the motor band.
(7) Loosen the screw fixing the line flow fan.
(8) Remove the motor bed together with the indoor fan
motor and the motor band.
(9) Disconnect the lead wire of the fan motor from the
motor band.
(10) Disengage the hooks of the motor band and remove
the motor band. Pull out the indoor fan motor.
(11) Remove the indoor coil thermistor from the heat
exchanger.
Install the indoor coil thermistor in its former position
when assembling it.
(12) Remove the screws fixing the left side of the heat
exchanger. Screw of the line flow fan
(13) Lift the heat exchanger, and pull out the line flow fan
to the lower-left.
Photo 7 Earth wire
When attaching the line flow fan, screw the line flow fan
so 4 mm gap is provided between the right end of the Motor band
line flow fan and the right wall of the air passage of the
box (Figure 1).

Figure 1
Indoor coil
thermistor

4 mm
Water cover Screws of
the motor bed
Photo 8
Photo: MSZ-HJ50VA

Screws of the left


side of the heat
exchanger

37
OBH647G
11-2. MSZ-HJ60VA MSZ-HJ71VA
NOTE: Turn OFF the power supply before disassembly.

OPERATING PROCEDURE PHOTOS


1. Removing the panel Photo 1
(1) Remove the screw caps on the panel and remove the
Front panel
screws of the panel.
(2) Pull the panel slightly toward you, and then remove the
panel by pushing it upward.

Screws of the panel

38
OBH647G
OPERATING PROCEDURE PHOTOS
2. Removing the indoor power P.C. board and the Photo 2
electrical box Water cover
(1) Remove the panel. (Refer to section 1.) Remove the
right corner box.
Screws of the earth plate
(2) Disconnect the following connectors:
<Indoor electronic control P.C. board> Screw of the
electrical cover
CN151 (Vane motor)
CN112 (Indoor coil thermistor)
CN10A (To the indoor power P.C. board)
Screw of the
(3) Unhook the catch on the left side of the control P.C. V.A. clamp
board holder. Pull the control P.C. board holder as if
opening the door at 90 degrees. Remove the control P.C. Indoor coil ther-
board holder from the axial rod on the electrical box. mistor
(4) Remove the screw of the V.A. clamp. Indoor coil ther-
(5) Remove the V.A. clamp and the indoor/outdoor con- mistor connec-
necting wire. tor CN112
(6) Remove the screws of the earth plate. (Photo 2)
(7) Remove the indoor coil thermistor from the water cover. Connector
CN10A
(8) Disengage the hooks of the water cover and remove
(To indoor power
the water cover. P.C. board)
(9) Remove the screw of the electrical cover and remove Indoor electronic
the electrical cover. control P.C. board Control P.C. board holder
(10) Disconnect the CN211 (Indoor fan motor) from the Vane motor
indoor power P.C. board. connector (CN151)
(11) Remove the upper catch of the electrical box, and pull Photo 3
out the electrical box.
To attach the electrical box, pass the wires connecting
TAB2 (Terminal block) TAB1 (Terminal block)
the indoor power P.C. board and the indoor electronic
control P.C. board through A. Pass the lead wires of the
Terminal block
fan motor through B as shown in the Photo 3. connector CN201
(12) Disconnect the following connectors and tabs.
<Indoor power P.C. board>
CN201, TAB1, TAB2 (Terminal block) Connector CN20A
(To indoor elec-
CN20A (To the indoor electronic control P.C. board)
tronic P.C. board)

Indoor fan motor


connector CN211
Electrical box

39
OBH647G
OPERATING PROCEDURE PHOTOS
3. Removing the indoor electronic control P.C. Photo 4
board Control P.C. board holder (Inside)
(1) Remove the panel. (Refer to section 1.) Remove the right Catch
corner box.
(2) Disconnect the following connectors: Indoor electronic
<Indoor electronic control P.C. board> control P.C. board
CN151 (Vane motor)
CN112 (Indoor coil thermistor)
CN10A (To the indoor power P.C. board)

(3) Unhook the catch on the left side of the control P.C.
board holder. Pull the control P.C. board holder as if
opening the door at 90 degrees. Remove the control P.C.
board holder from the axial rod on the electrical box.
(4) Remove the room temperature thermistor from the back
side of the control P.C. board holder.
Catch
(5) Unhook the catches of the control P.C. board holder, and
open the control P.C. board holder.
(6) Remove the indoor electronic control P.C. board from the
control P.C. board holder.
Control P.C. board holder (Back side)

Room temperature thermistor

4. Removing the vane motor


(1) Remove the panel. (Refer to section 1.) Remove the Photo 5
corner box.
(2) Remove the control P.C. board holder, water cover and
the electrical box. (Refer to section 2.)
(3) Pull out the drain hose from the nozzle assembly and
remove the nozzle assembly.
(4) Remove the screws of the vane motor and remove the
vane motor.
(5) Disconnect the connector from the vane motor.

Screws of the vane motor

40
OBH647G
OPERATING PROCEDURE PHOTOS
5. Removing the indoor fan motor, the indoor coil Photo 6
thermistor and the line flow fan
(1) Remove the panel. (Refer to section 1.) Remove the
corner box.
(2) Remove the control P.C. board holder, the water cover,
the electrical box and the nozzle assembly. (Refer to
section 2.)
(3) Remove the screws fixing the motor bed.
(4) Loosen the screw fixing the line flow fan.
(5) Remove the motor bed together with the indoor fan
motor and the motor band.
(6) Disconnect the lead wire of the fan motor from the
motor band.
(7) Disengage the hooks of the motor band and remove
the motor band. Pull out the indoor fan motor.
(8) Remove the indoor coil thermistor from the heat
exchanger.
Install the indoor coil thermistor in its former position
when assembling it.
(9) Remove the screws fixing the left side and upper right
side of the heat exchanger.
Screw of the line flow fan
(10) Lift the heat exchanger, and pull out the line flow fan
to the lower-left. Photo 7
When attaching the line flow fan, screw the line flow fan
so 4 mm gap is provided between the right end of the
Screws of the
line flow fan and the right wall of the air passage of the motor bed
box (Figure 1).

Figure 1

4 mm

Photo 8
Screw of the upper right side of the heat exchanger

Photo 9

Screws
of the left
side of
the heat
exchanger

41
OBH647G
Fixing the indoor coil thermistor

There are 2 forms of parts for fixing the indoor coil thermistor.
When fixing the indoor coil thermistor
to the clip-shape/holder-shape part, the
Clip shape Holder shape lead wire should point down.

About the
same length

Position and procedure for mounting the clip-shape part

1. Set the indoor coil 2. Check the (marked) 3. Mount the


thermistor in the center of mounting position. clip-shape part.
the clip-shape part.

NOTE:
Take care to avoid loss and accidental falling of the clip-shape part inside the unit.
Mount the clip-shape part on the marked position.
Do not pull the lead wire when removing the indoor coil thermistor.

42
OBH647G
43
OBH647G
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

© Copyright 2012 MITSUBISHI ELECTRIC CORPORATION


Issued: Oct. 2020. No. OBH647 REVISED EDITION-G
Issued: Apr. 2018. No. OBH647 REVISED EDITION-F
Issued: Jul. 2016. No. OBH647 REVISED EDITION-E
Issued: Dec. 2015. No. OBH647 REVISED EDITION-D
Issued: Oct. 2014. No. OBH647 REVISED EDITION-C
Issued: Dec. 2013. No. OBH647 REVISED EDITION-B
Issued: Mar. 2013. No. OBH647 REVISED EDITION-A
Published: Dec. 2012. No. OBH647
Made in Japan Specifications are subject to change without notice.

You might also like