CE Test Report
CE Test Report
:XXXXXX Página 1 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
4 GENERAL REQUIREMENTS
4.1 General
This standard specifies requirements for the electrical
P
equipment of machines.
4.2 Selection of equipment
4.2.1 Electrical components/devices suitable for their
intended use and applied in accordance with P
supplier’s instructions.
4.2.2 In addition to the requirements of EN 60204-1.
depending upon the machine, its intended use and its
electrical equipment, the designer may select parts of
N/A
the electrical equipment of the machine that is in
compliance with relevant parts of the IEC 61439 series
(see also Annex F).
4.3 Electrical supply
4.3.1 Electrical equipment to be designed for correct 4.3.2
operation within the conditions of mains power supply P
- as stated below (cl. 4.3.2 or 4.3.3)
or as stated by the user N/A
or as stated by the supplier N/A
4.3.2 AC supplies
Supply Voltage: 198 – 242V~
P
Steady state voltage: 0,9 ... 1,1 of nominal voltage
Frequency:
0,99 ... 1,01 of nominal frequency continuously; P
0,98 ... 1,02 short time.
Harmonics: not exceeding 12 % of the total r.m.s. etc. P
Voltage unbalance: not exceeding 2% deviation. P
Voltage interruption: interrupted or at zero voltage for
not more than 3 ms at any random time in the supply
P
cycle with more than 1 s between successive
interruptions.
Voltage dips not exceeding 20 % of the rms voltage
of the supply for more than one cycle with more than P
1 s between successive dips.
4.3.3 DC supplies
Supply Voltage:
- other:0,85 to 1,15 of nominal voltage.
N/A
- battery-operated vehicles: 0,7 to 1,2 of nom. volt.
- from converting equipment: 0,9 to 1,1 of nom. volt.
Report No.:XXXXXX Página 2 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
Voltage interruption:
- other: not exceeding 5 ms N/A
- converting equipment: not exceeding 20 ms
Ripple (peak-to-peak): not exceed. 0,15 of nom. volt. N/A
4.3.4 Special supply systems; e.g. on board generators
limits acc. 4.3.2 /.3 exceeded, but equipment designed N/A
acc. exceeded limits.
4.4 Physical environment and operating conditions
4.4.1 Electrical equipment suitable for the physical
environment and operating conditions of its intended P
use.
4.4.2 Electromagnetic compatibility (EMC):
Electrical equipment shall not generate
electromagnetic disturbances above levels that are
appropriate for its intended operating environment P
and shall have a sufficient level of immunity to
electromagnetic disturbances so that it can function in
its intended environment
4.4.3 Electrical equipment shall be capable of operating ta: 40 °C
correctly in the intended ambient air temperature.
P
(Minimum requirement: air temperatures of +5 °C
and
+40 °C)
4.4.4 Electrical equipment shall be capable of operating
correctly when the relative humidity is up to 50 % at a P
maximum temperature of +40 °C
4.4.5 Electrical equipment shall be capable of operating
correctly at altitudes up to 1 000 m above mean sea P
level.
4.4.6 Electrical equipment shall be adequately protected
P
against the ingress of solids and liquids (see 11.3)
4.4.7 Electrical equipment shall withstand ionizing and non-
P
ionizing radiation.
4.4.8 Electrical equipment shall withstand vibration, shock
P
and bump.
4.5 Electrical equipment designed to withstand the
effects of transportation and storage within a P
temperature range of - 25 to + 55 °C.
4.6 Heavy or bulky electrical equipment of the machine
P
provided with suitable means for handling.
- isolate the electrical equipment from the supply and By plug/socket combination
have only one OFF (isolated) and only one ON N/A
position marked with "O" and "I"
- visible contact gap or a position indicator which
cannot indicate OFF (isolated) until all contacts are
N/A
actually open and the requirements for the isolating
function have been satisfied
- have an external operating means e.g. handle
N/A
(except power operated CB’s)
- coloured black or grey recommended
(If used as an emergency stop, red/yellow N/A
combination selected)
- be provided with a means permitting it to be locked
in the OFF position (padlocks). When so locked, N/A
remote as well as local closing shall be prevented
- disconnect all live conductors of its power supply
N/A
circuit
Requirements for plug/socket combination as a
disconnection device:
- Breaking capacity of the plug/socket combination:
sufficient to interrupt the current of the largest motor P
when stalled together with the sum of the normal
running currents of all other motors and/or loads.
- further see. cl. 13.4.5 a) to f)
5.3.4 The operating means (for example, a handle) of the
supply disconnecting device shall be external to the P
enclosure of the electrical equipment
5.3.5 Only the following circuits need not be disconnected
by the supply disconnecting device:
- lighting circuits for lighting needed during
N/A
maintenance or repair;
–socket outlets for the exclusive connection of repair or
N/A
maintenance tools and equipment;
– under voltage protection circuits that are only
provided for automatic tripping in the event of supply N/A
failure;
– circuits supplying equipment that should normally
N/A
remain energized for correct operation
– control circuits for interlocking N/A
Circuits not disconnected by the supply disconnecting
device have:
- permanent warning labels in accordance with cl. 16.1 N/A
- a statement is included in the maintenance manual N/A
- additionally one or more of the following is applied N/A
Report No.:XXXXXX Página 5 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
6.3.1 General
6.3.2 Prevention of the occurrence of a touch voltage
6.3.2.2 Protection by provision of:
- class II electrical devices or apparatus (double
insulation, reinforced insulation or by equivalent
insulation in accordance with IEC 61140) or
P
- switchgear and control gear assemblies having total
insulation in accordance with IEC 61439-1 or
- supplementary or reinforced insulation in
accordance with 413.2 of IEC 60364-4-41.
6.3.2.3 Protection by electrical separation.
For this type of protection, the requirements of 413.5 P
of IEC 60364-4-41 apply.
6.3.3 Protection by automatic disconnection of supply.
6.3.3 a) Use of overcurrent protective device for automatic
cut-off in the event of an insulation failure in a N/A
TN- System.
6.3.3 b) Use of residual current protective devices (RCD) for
automatic cut-off in the event of an insulation failure N/A
in a TN - or TT -System.
6.3.3 c) Use of earth fault detection device to initiate
N/A
automatic disconnection in an IT-System.
6.4 Protection by the use of PELV
6.4.1 a) PELV circuits shall satisfy all of the following
conditions:
-the nominal voltage does not exceed:
• 25 V a.c. r.m.s. or 60 V ripple-free d.c. when the
equipment is normally used in dry locations and when N/A
large area contact of live parts with the human body is
not expected; or 6 V a.c. r.m.s. or 15 V ripple-free d.c.
in all other cases;
6.4.1 b) one side of the circuit or one point of the source of the
supply of that circuit is connected to the protective N/A
bonding circuit
6.4.1 c) live parts of PELV circuits is electrically separated
N/A
from other live circuits
6.4.1 d) Conductors of each PELV circuit are physically
separated from those of any other circuit.
N/A
If this requirement is impracticable, the insulation
provisions of 13.1.3 are fulfilled;
Report No.:XXXXXX Página 8 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
7 PROTECTION OF EQUIPMENT
7.1 General
7.2 Overcurrent protection
7.2.1 General
7.2.2 Overcurrent protection
Unless otherwise specified by the user, the supplier of
the electrical equipment is not responsible for
With overcurrent protective
providing the supply conductors and the overcurrent P
device
protective device for the supply conductors to the
electrical equipment (see Annex B).
In the installation diagram data necessary for
selecting the overcurrent protective device are stated P
for each incoming feeder. (see 7.2.10 and 17.4)
7.2.3 Power circuits:
Devices for detection and interruption of overcurrent,
selected in accordance with 7.2.10, are applied to
P
each live conductor including circuits supplying
control circuit transformers.
Cross section area of neutral conductor is at least
equal to the phase conductor. No overcurrent P
protective/ disconnecting device is required.
IT-Systems: no neutral conductor is used. TN systems
Or, when it is used, the measures detailed in 431.2.2 N/A
of IEC 60364-4-43 are applied.
7.2.4 Control circuits
Report No.:XXXXXX Página 9 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
8 EQUIPOTENTIAL BONDING
8.1 General P
8.2 Protective bonding circuit
8.2.1 Where the conductance of structural parts of the
electrical equipment or of the machine is less than that
of the smallest protective conductor connected to the P
exposed conductive parts, a supplementary bonding
conductor is provided.
In IT distribution systems, the machine structure is
part of the protective bonding circuit and insulation N/A
monitoring is provided.
Exposed conductive parts of equipment in
accordance with 6.3.2.3 (Protection by electrical
separation) are not connected to the protective
bonding circuit. N/A
(For this type of protection, the requirements of 413.5
of IEC 60364-4-41 apply.)
8.2.2 Protective conductors
Protective conductors shall be identified in accordance with 13.2.2. P
Copper conductors are preferred. P
8.2.3 Continuity of the protective bonding circuit
Parts that are mounted so that they do not constitute a
hazard because cannot be touched on large surfaces or
grasped with the hand and they are small in size (less
than approximately 50 mm × 50 mm) or they are P
located so that either contact with live parts, or an
insulation failure is unlikely need not be connected to
the protective bonding circuit
Where a part is removed the protective bonding
P
circuit for the remaining parts isn’t interrupted.
Report No.:XXXXXX Página 12 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
13 WIRING PRACTICES
13.1 Connections and routing
13.1.1 All connections are secured against accidental
P
loosening.
The means of connection are suitable for the cross-
sectional areas and nature of the conductors being P
terminated.
No connection of two or more conductors to one
P
terminal, unless the terminal is designed for it.
No soldered connections to terminals unless they are
P
suitable for it.
Terminals on terminal blocks are plainly marked or
P
labelled corresponding with the diagrams.
Installations of flexible conduits and cables are such
N/A
that liquids drain away from the fittings.
Report No.:XXXXXX Página 26 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict
17 TECHNICAL DOCUMENTATION
17.1 Documentation in agreed language provided. P
17.2 Information related to the electrical equipment P
18 VERFICATION
18.1 The extent of verification will be given in the dedicated product standard for a particular
machine. Where there is no dedicated product standard for the machine, the verifications
shall always include the items a), b) and f) and may include one or more of the items c) to
e):
a) verification that the electrical equipment complies with its technical documentation;
b) in case of protection against indirect contact by automatic disconnection, conditions P
for protection by automatic disconnection shall be verified according to 18.2;
c) insulation resistance test (see 18.3);
d) voltage test (see 18.4);
e) protection against residual voltage (see 18.5);
f) functional tests (see 18.6).
18.2 Verification of conditions for protection by automatic disconnection of supply
18.2.1 The conditions for automatic disconnection of supply
(see 6. 3.3) shall be verified by tests. Test 1 verifies P
the continuity of the protective bonding circuit.
18.2.2 Test 1: Verification of the continuity of the protective bonding circuit
The resistance of each protective bonding circuit
between the PE terminal and relevant points that are
<0.05 Ω P
part of each protective bonding circuit is measured
with a current between at least 0,2 A.
And the resistance measured is in the expected range
according to the length, the cross sectional area and
P
the material of the related protective bonding
conductor.
18.2.3 Test 2: Fault loop impedance verification and suitability of the associated overcurrent
N/A
protective device.
Report No.:XXXXXX Página 31 de 42
EN 60204-1:2018
Clause Test - Requirement Result-Remark Verdict